HomeMy WebLinkAboutSerge EngineeringCONTRACTOR: Master Craft Aluminum Products
DESIGN CRITERIA:
Applicable Codes, Regulations, and Standards
1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural
Design, Chapter 20 Aluminum, and Chapter 23 Wood.
2. AA ASM 35 and AA ADMl Specifications for Aluminum Structures, Part I -A of
the Aluminum Design Manual prepared by The Aluminum Association. and the
AAF Guide to Aluminum Construction in High Wind Areas.
3. ASCE 7-10.
Loading Criteria
1. Live Load: 10 PSF per 6th Edition (2017) Florida Building Code, Appendix I
Section 105.1
2. Dead Load: 2 PSF
3. Wind Load:
3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk
Category 1.
3.2. Basic Wind Speed, Figure 1609.3(3), State of Florida Debris Region & Basic
Wind Speed, Section 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind
Speed: V- =150 MPH, VASD =116 MPH
3.3. Exposure Category, Section 1609.4.3: Exposure C
3.4. Screen Enclosure Section 2002.4
4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1 -
Screen Room: Non -Habitable, Unconditioned
Roof Type
1. Roof Type: MONOSLOPE
2. Roof Material: 3" x 48" x 0.024" composite panel Elite 2000, 1.04 density foam,
Florida Product Approval Number FL 7561-R4.
Foundation Design
Existing concrete. No additional concrete footing or slab is required to resist the
loads imposed by the proposed construction if the existing slab is a minimum 4"
thick with an 8" x 8" thickened slab edge and in sound condition, free from
structural cracking, spalling, or other deterioration.
Specifications
The following specifications are applicable to this project:
1. All work shall be in accordance with the 6th Edition (2017) Florida Building Code,
and any other applicable local codes and regulations.
2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no
manufacturer substitution is acceptable without the specific written, signed and
sealed authorization of Florida Aluminum Engineering, Inc.
3. Screen material shall be 18/14 screen unless approved by Florida Aluminum
Engineering, Inc.
4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better
zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated
stainless steel series "400".
5. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from
ends and 24" center to center or #12 screws 6" from ends and 12" center to center.
6. Where concrete specifications are required, whether in the screen enclosure scope
or not, by one or more regulatory agency, the following specifications are
applicable:
a. Concrete shall conform to ASTM C94 for the following components:
i. Portland Cement Type I,- ASTM C 150
ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33
iii. Air entraining +/- 1% - ASTM C 260
iv.Water reducing agent - ASTM C 494
v. Clean Potable water
vi. Other admixtures not permitted
b. Metal accessories shall conform to:
i. Reinforcing Bars - ASTM A615, grade 60
ii. Welded wire fabric - ASTM A185
c. Concrete shunp at discharge chute not less than 3" or more than 5". Water
added after batching is not permitted.
d. Prepare and place concrete per American Concrete Institute Manual of
Standard Practice, Parts 1, 2, and 3 including hot weather recommendations.
e. Moist cure or polyethylene curing permitted.
f Prior to placing concrete, treat the entire subsurface area for termites in
compliance with the FBC.
g. Concrete shall be placed over a polyethylene vapor barrier.
h. All aluminum components embedded within concrete shall be coated with a
bituminous paint or epoxy.
7. All flashing and weatherproofing shall be provided by the contractor.
8. Door location shall be determined by contractor in the field.
9. Use of these plans acknowledges and accepts a limit of liability not to exceed
design and engineering fee.
WIND SPEED AND EXPOSURE HAVE
BEEN DETERMINED USING THE ADVANCED
TECHNOLOGY COUNCIL'S WEBSITE
AND GOOGLE EARTH.
1X3
X N
ih
3X3X0.090
2XDJ
lI DJ -i
0) N
I ;•� A-2
N 2XDJ
3X3X0.090
X N
3X3XO.090
A-3
F
L2'-11" 11'-5"
14'-6" 4
A-3
Co 0
O) 0
3"X48"X0.024"
1.0# DENSITY FOAM S-3
COMPOSITE PANELPr A-3
IVOJ O CO CO �O
�n o 0 0 0 =
iT X X C X X ��
i I
M M A-.�
2X3 2X3 2X3
1X3 1X3 1X3
B
A-2
7 5'-4J"
2'-6"
1X3
2X 7S: ¢ w
IDGE
U')U
N
N o a
BEAM o
W
LL
wa
U)
H Q
M
o i
o
N J UJ
m
-
X a
M 00
Z
At
2X3
ND
BEAM
F
L2'-11" 11'-5"
14'-6" 4
A-3
Co 0
O) 0
3"X48"X0.024"
1.0# DENSITY FOAM S-3
COMPOSITE PANELPr A-3
IVOJ O CO CO �O
�n o 0 0 0 =
iT X X C X X ��
i I
M M A-.�
2X3 2X3 2X3
1X3 1X3 1X3
B
A-2
7 5'-4J"
2'-6"
1X3
X
X
N
3X3XO.090
LL
N
X
o i
N
3X3X0.090
-
00
I
d'
i
ro
I
d-
8' -OJ"
� LLI
W
W p_
Z
3
W Z v
Z QZ
O d Ln
N Q w
W J
W
O =
d.
2 CU
Z Z
(D "
Z
J GLL^M
Q LLI W g M M
Q W ZM` ,
D Z ate~
OWLL
w
N Z)
W Z
LU
D Q
Q �U
it
w
� o N D- Lr)
0"O W N W M
LZ OLJL
DRAWN BY
TP
DATE DRAWN
03/26/20
REVISION
SHEET NO:
A- 1
M
O
Z
c�
Z
U
0
z
2
VA
LL
o i
N
0. LU
-
Z
At
00
I
d'
i
ro
I
d-
8' -OJ"
� LLI
W
W p_
Z
3
W Z v
Z QZ
O d Ln
N Q w
W J
W
O =
d.
2 CU
Z Z
(D "
Z
J GLL^M
Q LLI W g M M
Q W ZM` ,
D Z ate~
OWLL
w
N Z)
W Z
LU
D Q
Q �U
it
w
� o N D- Lr)
0"O W N W M
LZ OLJL
DRAWN BY
TP
DATE DRAWN
03/26/20
REVISION
SHEET NO:
A- 1
M
O
Z
c�
Z
U
0
z
2
ALUMINUM MEMBERS DBUNSIONS
l""
HOLLOW SECTIONS
2 x 2: 2" x 2" x 0.046"
2x3: 2"x3"x0.050"
2 x 4: 2" x 4" x 0.050"
LL
2 x 5: 2" x 5" x 0.050"
O
OPEN BACK SECTIONS
w -�
ui Q
Z
Q �•
1x2: 1"x2"x0.040"
1x3: 1"x3"x0.045"
SNAP SECTIONS
.•'���!/�,��
• • • •'
2 4 Snap: 2" 4" 0.049"
��0,`,,�,
x x x
itttt
SELF MATING (SMB)
2 x 4 SMB: 2" x 4" x 0.044"x 0.100"
�
2 x 5 SMB: 2" x 5" x 0.050"x 0.100"
W W
2 x 6 SMB: 2" x 6" x 0.050" x 0.120"
LL d
z
2 x 7 SMB: 2" x 7" x 0.057"x 0.120"
2 x 8 SMB: 2" x 8" x 0.072"x 0.124"
2 x 9 SMB: 2" x 9" x 0.072" x 0.124"
LD
W Z
2 x 10 SMB: 2" x 10" x 0.092" x 0.398"
J
O
¢ Z
MINIMUM FASTENER EDGE DISTANCE: 1/2"
Z
d uj
MINIMUM FASTENER SPACING: 3/4"
0
(,n Q W
CONCRETE SCREW ANCHOR:
w 2 J
SIMPSON TITEN HD OR EQUIVALENT
�- 0
SHEET METAL SCREWS (SMS):
_
ITW / BUILDEX OR EQUIVALENT
p F—
U
z z
.t to c
5 z WmPz �1
Q
LWLI 2
Q W
oz$ o
J W LL
LL
cn
W Z
w
Q
J
Q W
U
CC
ui0OW_
CLLO
O I- rn F b
W N R' M
CL
m-°IJi
DRAWN BY
TP
DATE DRAWN
03/26/20
REVISION
z _
© -
a _
SHEET NO:
A-2-
3
MUPRIGHT,'��ICHAIR RAIL MEMBER1x 3" OB W/ 1/4" CONCRETE2" x 2" x 3" x 118" ALUM ANGLEEACH SIDE OF UPRIGHT
SCREW ANCHOR 6" FROMW/ 3/8"DIA. x 3" CONCRETEUPRIGHT & AT 24ANCHORS ON EACH SIDE 2" x 2" x 1/8ANGLE/(MIN. 2 3/4" EMI(3) #12 x 3/4" SMS SCREWS(4) #10 x 5/8" EACH SIDE3 x UPRIGHTCCHAIR RAIL TO UPRIGHT DETAIL
A_2SCALE: NTS
B3" x 3"POST TO DECK CONNECTION DETAILSSCALE: NTS1/8" x 2" x 2" EXTRUDEDANGLE 5052 H-32 ALLOY#12 x 3/4" SMS
NTO DJ
I
21/4°MINCONC
ANCHOR EMBEDMENTSLABFOOTINGSEE PLANw�ATTACH 1" x 3" WITHCAULKINGSIDEVIEW�,,;�(4) #10 x 1 1/2" INTO
'`,SCREW BOSS (1) 318" DIA. CONCRETESCREWANCHORS2 1/4"CONC. EMBEDUPRIGHTPRE-HUNGDOORJAMB2"x2"OR2"X3"HOLLOWSECTION GIRT 1x 3" BASE PLATE
ANCHORED TO CONC W/ 114"CONCRETE SCREWANCHOR1x3"(MIN. 1 1/4" EMBED)6"MAXEACHSIDEOFPOSTAND 24" O.C. MAXFRONT VIEW
C'�1X3 TO HOST STRUCTURE DETAILUPRIGHT TO CONCRETEPRE-HUNG
A-2 SCALE; NTS A_2DOOR LOCATION DETAIL
SCALE:NTS
#14 x 4 7/8" SMS W/
3" COMPOSITE
1 1/2" DIA. NEOPRENE PANEL
FACED WASHER 6" O.C. #14 SMSx 1" MIN. LONGER
\\� �.
r
THAN PANEL W/ 1 1/2" DIA.
OPRENE FACED WASHER
,\\' V ,•'�
�
•b %G/�2 r
ALONG LENGTH
♦♦ �,.�
i 1
} � ,
ro
U-•. ..+
V+
�E�SLLEND BEAMS
� Q � �
0
3" x 0.062" ALUM
W
W ¢ t`
RECEIVING CHANNEL
W! #10 x 3/4" TOP AND a �•
EXISTING HOST WALL � N •: V �
BOTTOM AS END CAP
�
Z
1¢— v
2" x 3" FLAT TOP RAIL - NO
I
� •••'• • •
//
• • ..
ANGLE REQUIRED UNLESS � f � � J PANEL
/ //I
Q�0 ,,\\\
SPLICED OR CORNER - 1 Q 2" x 3" FLAT i
ATTACH w/ (4) #10 x 4" LG
2" x 3" FLAT
,F,f
"�
END BEAM
i
C
� O
UPRIGHT --__1 11 „ � 2" x 3" FLAT
W
3 ;Ili LL TOP RAIL W/ � Id � W
'
!i^;
LLJ C
(4) #10 x 4" SMS
Z4111
INTO POST
2" 3" FLAT
L
3
x
F
TOP RAIL w!
(4) #10 x 4" SMS
W Z z
C
INTO POST
CONCRETE'
J li ?
° y '
2x2 x1/8
" "
x
(2) 1/4" 3" QUICKSET
Z LL
2"x 2"x 3" LG
ALUM ANGLE
��•;
ANCHORS INTO WALL
Z z
2" x 2" x 3" LG x 1/8" ANGLE
W/ (3) #12 x 3/4"
WOOD:
VG., z
x 1/8" ANGLE
SMS INTO BEAM
(2) 1!4" x 3" LAG SCREWS
Z IL
N Q w
...__ _ _ ...
INTO WALL
W (.l g
(4) #10 x 314" (4) #10 x 314"
71 F
L1. O J
BEAM 3" COMPOSITE
SMS INTO SMS INTO i
1 1/2" DIA. NEOPRENE WASHER
ROOF PANEL
a
TOP SCREW ONLY
SCREW BOSSES SCREW BOSSES
(2)INTOTOPRAIL (2)INTOTOPRAIL
CL a
c
CFL
2" x 7" SMB ,
l
(2) INTO POST (2) INTO POST
I I I I
CONNECTION AT CORNER CONNECTION AT SPLICE
c
G V C
=Z; c
r���
-• �`j ._ 2�� x 3��
S-1 BEAM TO HOST STRUCTURE ATTACHMENT DETAIL
z
S X 3 TOP RAIL CONNECTION TO 3 X 3 UPRIGHT
A_3
SCALE: NTS
Z
SCALE: NTS
s
�
....FLAT,...
J ♦Y �LL r� LL
Q
W
W Z m es Z
� 1 >
O Z LL
1 1/8" x 21/8" x 1 1/8" x 0.050"
#14 SMS x 1" MIN. LONGER
�
CONCRETE:
ALUM RECEIVING CHANNEL W/
THAN PANEL W! 1 1/2" DIA.
(3) 114" DIA. x 3" OUICKSET
(2) #12 x 3/4" SMS EACH FLANGE
NEOPRENE FACED WASHER
ANCHORS INTO WALL
& (1) 3/8"THRU BOLT
, @ 12" O.C. ALONG LENGTH
WOOD:
'
OZ$ o
i
' UPRIGHT OF ALL END BEAMS
(3) 1/4" DIA. x 3" LAG SCREWS
J W LL C
1 112" x 21/8" x 1 1/2" x 7" x 0.062" INTO WALL STUDS
3" x 0.062" EXTRUDED
ALUM RECEIVING CHANNEL STAGGERED
LL
3
�
RECEIVER CHANNEL W/
FLASHING
a
(2) #12 x 3!4" @ 12" O.C.
S -Z BEAM TO HOST STRUCTURE ATTACHMENT DETAIL
S'3 RIDGE BEAM
A_3
EACH SIDE OF RIDGE BEAM
A_3 SCALE: NTS
z
EXISTING HOST WALL
#14 x 3/4" SMS @ 6" O.C.
TOP AND BOTTOM W/
2" x 7" SMB
RIDGE
C
LL
C
x
3
z
c
LL
N W c
W Z LL
Lu
LL
Q
Q C
Q W C
U
rV
N z
of �
—Wi0NCL
O w Qw m
Z
a mr°
u-
DRAWN BY
TP
DATE DRAWN
03/26/20
REVISION
z -
© -
4 -
SHEET NO:
A-3
BEAM 3" COMPOSITE
1 1/2" DIA. NEOPRENE WASHER
ROOF PANEL
TOP SCREW ONLY
I
2" x 7" SMB ,
a M
s
if
-• �`j ._ 2�� x 3��
V. t
®
s
�
....FLAT,...
i
1 1/8" x 21/8" x 1 1/8" x 0.050"
#14 SMS x 1" MIN. LONGER
�
CONCRETE:
ALUM RECEIVING CHANNEL W/
THAN PANEL W! 1 1/2" DIA.
(3) 114" DIA. x 3" OUICKSET
(2) #12 x 3/4" SMS EACH FLANGE
NEOPRENE FACED WASHER
ANCHORS INTO WALL
& (1) 3/8"THRU BOLT
, @ 12" O.C. ALONG LENGTH
WOOD:
'
i
' UPRIGHT OF ALL END BEAMS
(3) 1/4" DIA. x 3" LAG SCREWS
1 112" x 21/8" x 1 1/2" x 7" x 0.062" INTO WALL STUDS
ALUM RECEIVING CHANNEL STAGGERED
�
W! (6) #14 x 3/4" SMS EACH
SIDE INTO BEAM
S -Z BEAM TO HOST STRUCTURE ATTACHMENT DETAIL
S'3 RIDGE BEAM
A_3
TO ROOF PANEL CONNECTION
SCALE: NTS
A_3 SCALE: NTS