NOA No.: 19-0620.03
Expiration Date: 08/05/24
Approval Date: 08/01/19
Page 1 of 3
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
Drexel Metals, Inc.
1234 Gardiner Lane
Louisville, KY 40213
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of constr uction materials. The
documentation submitted has been reviewed and accepted by Miami-Dade County RER -Product Control Section to be
used in Miami-Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(in Miami-Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have this
product or material tested for quality assurance purpo ses. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: MetShield HT Underlayment
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami-Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews NOA 16-0322.06 consists of pages 1 through 3.
The submitted documentation was reviewed by Freddy Semino
NOA No.: 19-0620.03
Expiration Date: 08/05/24
Approval Date: 08/01/19
Page 2 of 3
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub-Category: Underlayment
Material: SBS
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
Product
Dimensions Test
Specification
Product
Description
MetShield HT
3’ x 66’ rolls ASTM D 1970 Self-adhering reinforced membrane for use as
an underlayment in sloped roof assemblies.
MANUFACTURING LOCATION
1. Terrell, TX
EVIDENCE SUBMITTED
Test Agency Test Identifier Test Name/Report Date
Momentum Technologies, Inc. EX08H2A ASTM D 1970 07/22/03
PRI Construction Materials CCW-021-02-01 ASTM D 1970 11/20/14
Technologies
APPROVED ASSEMBLIES:
Deck Type 1: Wood, non-insulated
Deck Description: 19/32" or greater plywood or wood plank
System E (1): Anchor sheet mechanically fastened to deck, membrane adhered.
Base Sheet: One or more plies of ASTM D 226 Type II or ASTM D 2626 with a minimum 4” side lap and 6”
end lap mechanically fastened to deck with approved nails and tin caps 6"o.c. at the laps and two
staggered rows 12"o.c. the field of the roll.
Membrane: One or more plies of MetShield HT underlayment with a minimum 4” side lap and 6” end lap.
Surfacing: Approved Roof Assemblies. See Limitation #3.
NOA No.: 19-0620.03
Expiration Date: 08/05/24
Approval Date: 08/01/19
Page 3 of 3
LIMITATIONS:
1. Fire classification is not part of this acceptance.
2. This acceptance is for prepared roofing applications. Minimum deck requirements shall be in compliance with
applicable building code. MetShield HT underlayment shall be installed in strict compliance with applicable
Building Code.
3. MetShield HT underlayment may be used in asphaltic shingles, wood shakes and shingles, non-structural metal
panels, metal shakes and shingles, and quarry slate roof assemblies. MetShield HT underlayment shall not be used
as roof tile underlayment.
4. MetShield HT underlayment shall not be applied over an existing roof membrane as a recover, but may be applied
over a roofing Base/Anchor sheet underlayment.
5. MetShield HT underlayment shall not be left exposed as a temporary roof for longer than 180 days of application.
6. Refer to Prepared Roofing system Product Control Notice of Acceptance for listed approval of this product with
specific prepared roofing products.
7. MetShield HT underlayment may be used with any approved roof covering Notice of Acceptance listing MetShield
HT underlayment as a component part of an assembly in the Notice of Acceptance. If MetShield HT underlayment
is not listed, a request may be made to the Authority Having Jurisdiction (AHJ) or the Miami-Dade County Product
Control Section for approval provided that appropriate documentation is provided to detail compatibility of the
products, wind uplift resistance, and fire testing results.
8. MetShield HT underlayment shall be applied to a smooth, clean and dry surface with dec k free of irregularities.
All nails in the deck shall be carefully checked for protruding heads. Re -fasten any loose decking panels. Sweep
the deck thoroughly to remove any dust and debris prior to application.
9. When applying the membrane in the valley, start at the low point and work to the high point, rolling the membrane
from the center outward in both directions. For ridge applications, center the membrane and roll from the center
outward in both directions.
10. Roll or broom the entire membrane surface so as to have 100% contact with the surface, giving special attention to
overlap areas.
11. Flash vent pipes, stacks, chimneys and penetrations in compliance with Roof Assembly current Product Control
Notice of Acceptance and applicable Building Code.
12. All protrusions or drains shall be initially taped with a 6" piece of underlayment. The flashing tape shall be
pressed in place and formed around the protrusion to ensure a tight fit. A second layer of MetShield HT
underlayment shall be applied over the underlayment.
13. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61G20-3 of the Florida Administrative Code.
14. All membranes or packaging shall bear the imprint or identifiable marking o f the manufacturer's name or logo, city
and state of manufacturing facility, and the following statement: "Miami-Dade County Product Control Approved"
or the Miami-Dade County Product Control Seal as shown below.
END OF THIS ACCEPTANCE