HomeMy WebLinkAboutengineeringForensic Engineering Consultants, Inc.
INSULATION BOARD ATTACHMENT CALCULATIONS
Project Name Body Talk & Sports Bar FEC Report No.: CIS-IB-20.002
Project Address 8259 US-1
Port St. Lucie, FL - 34952
Deck Substrate Steel with LWC, Insulated Max. Roof Height 13.0 Feet
Configuration Low Slope Roof Area (Approx.) 2117 Sq.Ft.
Category II Max_ Roof Width 29.0 Feet
Exposure Condition C Perimeter Width 3.0 Feet
Building Type Enclosed Parapet Height 0.0 Feet
Base Wind Speed 170 mph Corner Zones 3' x 3' Each
Slope V 0.0 Slope H 12.0 Slope Angle' 0.00
Uplift Pressures qZ - 0.00256 KZ Kt Kd V2 P = qz( GCp- O GC 1
q= KZ Kt Kd V GCp GCp;
53.721 0.850 1.005 0.85 170 -1.00 0.18 Field
-1.80 0.18 Perimeter
-2.80 0.18 Corner
Field P1 A -63.39 psf Pt asd -38.03 psf
Perimeter P2 u1t.-106.37 psf P2 asd -63.82 psf
Corner P3 A-160.09 psf P3 asd -96.05 psf
Proposed System CertainTeed Flintlastic Modified Bitumen Roof Systems
Product Approval No. FL2533-R23 (Page 26 of 67) System No. S-52
System Design Pressure -60 psf
Insulation Board Dimensions 4' x 8' x 0.5" (min. Thickness) Insulation Board Area 32 Sq.Ft.
Fasteners Approved Screws and Insulation Plates
Min. Fasteners per Board 18
Min_ Characteristic Resistance Force-106.67 Ibf-271.75 Ibf (MCRF from TAS-105 Tests)
No. of Fasteners Required NF = (Ins. Board Area x Pi) / MCRF
Field Perimeter Corner
Fastener Requirement 11.41 19.15 28.82
RECOMMENDED INSULATION BOARD ATTACHMENT PATTERN
Field Use 18 Fasteners per 4' x 8' board
Perimeter Use 20 Fasteners per 4' x 8' board
Corner Use 29 Fasteners per 4' x 8' board
These calculations have been done in accordance with ASCE 7-10, based on the information provided by the
contractor. The roof system should be installed in accordance with the FBC & manufacturer's recommendations.
Ensure that roof system meets drainage & fire rating requirements of the Florida Building Code, before installation.
Sincerely
Forensic Engineering Consultants, Inc.
R. N. Sailappan, P.E.
Principal Engineer
Florida Registration No. 46696
Forensic Engineering Consultants, Inca (CA #8265), P.O. Box 970034, Boca Raton, FL - 33497 Ph (561) 901 8490 Fax (561) 218 3830
Forensic Engineering Consultants, IncX
INSULATION BOARD ATTACHMENT CALCULATIONS
Project Name
Body Talk & Sports Bar FEC Report No.: CIS-I13-20.002
Project Address
8259 US-1
Port St. Lucie, FL - 34952
Deck Substrate
Steel with LWC, Insulated Max. Roof Height 13.0 Feet
Configuration
Low Slope Roof Area (Approx.) 2117 Sq.Ft.
Category
II Max. Roof Width 29.0 Feet
Exposure Condition
C Perimeter Width 3.0 Feet
Building Type
Enclosed Parapet Height 0.0 Feet
Base Wind Speed
170 mph Corner Zones 3' x 3' Each
Slope V
0.0 Slope H 12.0 Slope Angle° 0.00
Uplift Pressures
qz = 0.00256 Kz Kzt Kd V2 P = qz (GCP - GCP;)
qz Kz
Kt Kd V GCp GCpi
53.721 0.850
1.005 0.85 170 -1.00 0.18 Field
-1.80 0.18 Perimeter
-2.80 0.18 Corner
Field P1 A.
-63.39 psf P1 asd -38.03 psf
Perimeter P2 ult.
-106.37 psf P2 asd -63.82 psf
Corner P3 ult.
-160.09 psf P3 asd -96.05 psf
Proposed System
CertainTeed Flintlastic Modified Bitumen Roof Systems
Product Approval No.
FL2533-R23 (Page 26 of 67) System No. S-52
System Design Pressure
-60 psf
Insulation Board Dimensions 4' x 8' x 0.5" (min. Thickness) Insulation Board Area 32 Sq.Ft.
Fasteners
Approved Screws and Insulation Plates
Min. Fasteners per Board 18
Min. Characteristic Resistance Force-106.67 lbf-271.75 Ibf (MCRF from TAS-105 Tests)
No. of Fasteners Required NF = (Ins. Board Area x P;) / MCRF
Field Perimeter Corner
Fastener Requirement
11.41 %15 28.82
RECOMMENDED INSULATION BOARD ATTACHMENT PATTERN
Field Use 18 Fasteners per 4' x 8' board
Perimeter Use 20 Fasteners per 4' x 8' board
Corner Use 29 Fasteners per 4' x 8' board
These calculations have been done in accordance with ASCE 7-10, based on the information provided by the
contractor. The roof system should be installed in accordance with the FBC & manufacturer's recommendations.
Ensure that roof system meets drainage & fire rating requirements of the Florida Building Code, before installation.
Sincerely
Forensic Engineering Consultants, Inc.
R. N. Sailappan, P.E.
Principal Engineer
Florida Registration No. 46696
Forensic Engineering Consultants, Inc. (CA #8265), P.O. Box 970034, Boca Raton, FL - 33497 Ph (561) 901 8490 Fax (561) 218 3830
1
TESTING APPLICATION STANDARD (TAS) No. 105-11
APPENDIX TAS 105-A
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION:
Job Name:
Job Address:
Job Site Contact:
Body Talk Sports Bar
8259 S. US Highwav #1
Port _St. Lucie, FL34952
Nicotera Roofing - 561-707-0771
TESTING AGENCY/EQUIPMENT INFORMATION:
Note: The undersigned acknowledges that all testing has been conducted and
results have been reported in compliance with TAS 105 Appendix T105-A
Testing Agency:
Address:
Telephone:
Fax:
Email:
Representative Name
Title:
Cleary Inspection Services, Inc.
1017 North "H" Street
Lake Worth, FL 33460
(561) 722 - 9881
(561) 582 - 8039
clearyinspections@kcwand.com
Katherine I. Cleary
Inspector
Test Apparatus: COMTEN MODEL # DFG2W2000, SERIAL # 21806036
BUILDING/ROOF SYSTEM INFORMATION:
Roof Area Height: Height:
Roof Area Dimensions: Length:
Width:
Total roof area:
Perimeter width:
Perimeter area:
Corner area:
Parapet Height:
FASTENER INSTALLATION INFORMATION:
Is the fastener a self driller?
Tool: Rigid 18v
Fastener type:
Fastener Manufacturer:
Approx.
13 ft.
73 ft.
29 ft.
2117 ft.Z
3 ft.
540 ft.Z
36 ft.2
N/A ft.
Yes
0-1800 rpm's
#14
OMG
TEST INFORMATION:
Test Date:
Number of Test Conducted
*Note the Location of all tests on 'Building Information', attached.
3/4/2020
10
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Steel
Body Talk Sports Bar
8259 S. US Highway #1
Port St. Lucie, FL 34952
Cleary Inspection Service, Inc.
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
SAMPLE NO.
PLAN IDENTIFIER
MTIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
TI
330
x
2
T2
285
X
3
T3
295
X
4
T4
300
X
5
T5
295
X
6
T6
285
X
7
T7
320
X
8
T8
225
X
9
T9
300
X
10
T10
275
X
STATISTICAL ANALYSIS:
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
Sincerely,
Cleary Inspections Service, Inc.
Katherine . leary
Miami -Dade Lab Certification No. 16.0211.02
n= 10
t' = 2.262
F= 291 lbf
SF-- 26.91lbf
1" 271.751bf
R.N. Sailappan, P.E. 111-01
Florida Registration No. 46696
2
Cleary Inspection Service, Inc.
Telephone (561) 722-9881
Fax (561) 582-8039
Email: kc@kcwand.com
Notes-
1. Use of the results herein to determine the required number of
fasteners for insulation attachment or an acceptable anchor or base
sheet fastener spacing, as outlined in TAS 117, shall utilize the
minimum characteristic resistance for (F') determined in compliance
with Section 9 of TAS 105. No margin of safety shall be applied to
field withdrawal resistance test results determined in compliance with
TAS 105.
2. A safety factor of 2 to 1 shall be applied to all results of laboratory
testing.
3. The following pages shall be completed for each roof area and
included with all Field Withdrawal Resistance Test Recording Sheets.
Body Talk Sports Bar
8259 S. US Highway #1
Port St. Lucie, FL
Test Date: 3/4/20
Roof Area Building and Parapet Heights
(If no parapet exists "N/A")
N/A
13'
Ground
Level
Page 3
t I ! l
Cleary Inspection Service, Inc.
Tel. (561) 722-988, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
7259S.
lk Sports Bar
8S Highway #1
Pucie, FL 34952
Test Date: 3/4/20
> Z
29'
T1®
T8
T9
T7
T6
73' 73'
T5
T4
T3
T2
T1
29'
NOT DRAWN TO SCALE
Drawings & measurements are approximate representation of field layout
Page 4
c+c�,rv�►---�,--,E
CERTIFICATE OF CALIBRATION
TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AND PERFORMED 1N ACCORDANCE WITH IS010012-2003
THIS DEVICE IS CERTIFIED TO BE WITHIN +/- 0.5% OF FULL SCALE READING AT EACH TEST POINT AT
THE TIME OF SHIPMENT
CERTIFICATE NUMBER: 26589 CALIBRATION DATE: 12/9/2019
PART AND CUSTOMER INFORMATION
MODEL #: DFG2000
I
SERIAL #: 21806036
CUSTOMER: CLEARY INSPECTION SERVICE INC.
CUSTOMER #: CLE33460
!`ei �Qo�rnnaT,
APPLIED
EXPECTED
VALUE
VALUE
(LB)
(LB)
0.00
100.00
400.00
600.00
800.00
1000.00
1200.00
1400.00
1600.00
1800.00
2000.00
0.00
400.00
800.00
1200.00
1600.00
I
2000.00
CALIBRATION EQUIPMENT USED
SERIAL #1: 11706016
CAL EQUIP COMTEN INDUSTRIES load cell CNR EA, S/N
CNR EA 11706016 was calibrated at ComTen Industries
following to ASTM E-74. The uncertainty is 2
CAL DATE: Lbf. Report No: 20300
6/12/2017
RUN 1
(LB)
0.000
397-000
798.000
1201.000
1604.000
2005.000
SERIAL #2:
FULL
AVERAGE SCALE
(LB) ERROR
0.000
0.000%
397-000
-0.150%
798.000
-0.100%
1201-000
0.050%
1604.000
0.200%
2005.000
0.250%
THIS EQUIPMENT IS CERTIFIED TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNO
CONDITIONS
ITEMPERATURE 73°F
RELATIVE HUMIDITY: 27 %
AS FOUND NOTES: ( * Indicates that the part was out of tolerance)
VALIDATION
CALIBRATION
PERFORMED
BY: MG
LOGY.
i
Calibration not valid without CERTIFIED stamp and initials
6405-49th Street North, Pinellas Park, FL 33781-5724 * 727-520-1200 * FAX 727-520-0299
E-Mail: sales@com-ten.com * Web: www.Com-ten.com