EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P9290.02.08 -R24
1111 West Newport Center Drive FL1654-R26
Deerfield Beach, FL 33442 Date of Issuance: OZ/11/Z008
(954) 233-1230 Revision 24: 10/14/2019
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 61h Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: Polyglass SBS and APP Modified Bitumen Roof Systems
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions ofthe Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). MEMO )etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle,
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEM0I etc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 5, plus an 81 -page Appendix.
Prepared by:
�5 g
Robert J.M. Nieminen, P -E.
a-aT OE ;fit
•iyEs`c. •- The facsimile sea[ appearing was authorized by Robert
Fiorido Registrotion No. 59166, Fiorido DCA ANE1983 %"a,,,v,'�``s Nieminen, P.E. on 10124(2019. This dues not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. MEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distri'outing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
CO2018, NEMO ETC, LLC
ONEMOletc.
ROOFING SYSTEms EVALUATION:
NEMO ETC, LLC Evaluation Report P9290.02.08-1124
Certifimte of Authorization #32455 6Y" EDITION (2017) F13C NON-HVHZ EVALUATION FL1654-R26
Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Revision 24: 10/14/2019
Page 2 of 5
Product Category;
Roofing
Sub -Category:
Modified Bitumen
Roof Systems
Compliance Statement: Polyglass SSS and APP Modified Bitumen Roof
Systems, as produced by Polyglass USA,
Inc., have demonstrated compliance with the following sections of the bth Edition (2017) Florida Building Code
through testing in accordance with the fallowing
Standards. Compliance is subject to the Installation Requirements
and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Pro ertv
Standard
Year
1504.3.1
Wind
FM 4474
2011
1504-3.1
Wind
UL 1897
2012
1504.7
Impact
FM 4470
2012
1507.10.2
Physicals
ASTM 04897
2001
1507.11.2
Physicals
ASTM 06162
200S
1507.11.2
Physicals
ASTM D6163
2008
1507.11.2
Physicals
ASTM D6164
2011
1507.11.2
Physicals
ASTM 06222
2011
1507.11.2
Physicals
ASTM D6509
2009
3. REFERENCES:
Entity
Exam
Reference
Date
Enti
Exam
Reference
Date
ERD [TST6049)
Physicals
P10490.10.08-2
10/30/2008
FM (TST1867)
FM 4470
3006115
OS/D2/2001
ERD (TST6049)
FM 447014474
P13760.09.09
09/10/2009
FM (TST1867)
FM 4470
3012321
07/29/2002
ERD I75T6049)
EM 4470/4474
P1377C.09.09
09/1012009
FM (757186%)
FM 4473
3014592
08/05/2003
ERD IT5TOD49)
FM 4470/4474
P3DS40.11.09-111
11/30/2009
FM (7871867)
FM 4470
3014751
08/27/2003
ERD (TST6D49)
FM 4470/4474
P30550.12.09
12/0212009
FM (T5T1867)
FM 4470
3607170
01/13/2004
ERD (TST50491
Physicals
P33960.12.10
1Z/3012010
FM (TST1867)
FM 4470
3019317
06/30/2004
ERD MT6049)
FM 447014474
P33970.03.11
03/1312011
FM (TM867)
FM 4470
3020703
07/30/2004
ERD (TST6049)
Physicals
P37590.03.13 -3A
03/0e/2013
FM (TST1867)
FM 4470/4474
3018332
01/31/2006
ERD MT60491
FM 447014474
P39680.03.13
03/04/2013
FM(TST1867)
FM 4470/4474
3023368
03/20/2005
ERD MT60491
Physicals
P37590.03.13 -1-R1
06/28/2013
FM (TST1867)
FM 4170/4474
3024594
05/2312005
ERD (TST60491
Physicals
P37590.03.13 -2-R1
37/01/2013
FM 6TST1867j
FM 4470/4474
3023458
07/18/2006
ERD MT60491
Physicals
P37590-07.13-2
07/01/2013
FM (TST1867)
FM 4470/4474
3030668
09/12/2007
ERD (T5T60491
Physicals
P37590.03.13 -5-R1
07/01/2013
FM ITST1367)
FM 4470/4474.
3032172
06/1212009
ERD (TST6049)
Physicals
P37590.07.13-1
D7/0212C13
FM ITST1867j
FM 4470/4474
3049631
04/21/2014
ERB(TST604%
FM 4470/4474
P4153008A3
08/06/2013
FM ITST1867)
FM 4470/4474
3057029
02/02/2017
ERD (TSTG0491
Physicals
P45940,09.13
09/04/2013
NEMC (TST6D49)
Criticality
4S-PLYG-1e-001.4618
06/23/2018
ERD (TST6049y
Physicals
P44373 10.13
10/04/2013
NEMC (TST6049)
FM 4474
4L-PLYG-18-0030818
08/21/2015
ERD (TSTG049y
Physicals
P39520.09,14-2
09111/2014
NEMC ITST6049)
Criticality
45 PLYG-18001.10.18
10103/2018
ERD (TST6049i
FM 4470/4474
506166 11.14
11/10/2014
NEMC (TST6049)
ASTM D4897
45-PLYG-1E-002.1118-2
11/16/2018
ERB (TST6049)
Physicals
P454405C..03.15-1
03/31/2015
NEMC (TST6049)
ASTM 36164
4E-PLYG-1E-002.11.18.8
11/28/2018
ERD (7876044)
Physicals
SC5170.05.15
05/08/2015
NEMC (7876049)
FM 4474
4L-PLYG38-003.11.18
11/2812018
ERD MT6049)
FM 4474
SCSO85,05.25
05/19/201.5
NEMA (TST60491
FM 4474
4L-PLYG-1"03.01.19
01/11/2019
ERD (TS76049)
Physicals
5[5170.12.15
12/29/2015
NEMC ITSTS0491
ASTM D6163
45-PLYG-184 2.0219-A
01/2412019
ERD (TST6049)
FM 4470/4474
SC9455.15
04101/2016
NEMA (TST6049)
ASTM D6162
45-PLYGAS-M2.01.19-11
01/25/2019
ERB (TST6049)
FM 4470/4474
PLYG-SC8905.05-16-1
05117/2016
NEMC (TS76049)
FM 4474
4L-PLYG-1&003.0419-A
04/08/2019
ERD (TST6049)
FM 4470/4474
PLYG-5[8905.05.16-2
05/17/2016
NEMA (T576049)
ASTM D6222
45-PLYG-18-002,05.19-C
05/20/2019
ERD(T5T60491
FM 4470/4474
PLYG-5c10a19.07.1G-R1
04/230016
IN
ASTM D5222
45 PLYG-18-002.n5.19-0
05/20/2019
ERB (TST60491
UL 1897
PLYG-SC32025.10-16
10/12/2016
NEMC (TST60491
ASTM D6163
45-PLYG-18-002.05.19-11
05/20/2019
ERD IT5T6049)
FM 4470/4474
PLYG-SC11475.16
11117f2016
NEMO (T5T50491
ASTM D6164
45-PLYG-28 205.19-N
05/31/2019
ERD{TMI)49)
FM 4470/4474
PLYG-SC13235.01.17
01/17/2017
NEMD(TST60491
Criticality
45-PLUG-1s-o07,.05.19.A
07/17/2019
ERD MT6049)
FM 447014474
PLYG-5013920-05.17
05/3012017
NEMD(TST6049(
ASTM 06164
45-PLYG-18.002.09.19-1
09/06/2019
ERD (TST--1294)
FM 4470/4474
PLUG-ai-13945D517-1
05/30/2017
NEMD (TST6049)
ASTM D6164
45-PLYe-18-m2.09.194
09/06/2019
ERD 175 7 312 9 4)
FM 4470/4474
PLYG-CTL13945.0517-3
05/30/2017
PRI (15?5878)
Physicals
PUSA-062-02-01
12/D4/2007
ERD (TST6049)
FM 4470/4474
PLYG-5013945,05.17
05/30/2017
PRI (TS75878)
PhYSIL.is
PUSA-061-02-02
01/28/2008
ERB ITST60491
FM 4470/4474
PLYG-801576009.17
09/1112017
FRI (TST58781
Physicals
PUSA-064-02-02
02/27/2008
FM(TST1867)
FM 4470
ZW7A7.AM
08/04/1994
PRI(TST5878)
Physicals
PUSA-062-02-02
12/04/2008
FM (TST1867)
FM 4470
0D3A3-AM
04/04/1997
PRI (TSTS8781
TAS 114
PUSA-188-02-01
02/08/2017
FM (TS71867)
FM 4470
2DOAO.AM
12/23/1998
PRI (TST58781
TAS 114
PUSA-188-02-02
02/08/2017
FM (7571867)
FM 4470
2DSA9.AM
06/2212999
PRI (7875878)
TAS 114
PUSA-188-02-03
02/08/2017
FM (7ST1867)
FM 4470
3006546
01/04/2000
PRI (TSTS978)
TA5 114
PUSA-202-02-01
05/17/2017
FM (T5T1867)
FM 4470
3001334
01/25/2000
PRI (7875878)
TA5114
PUSA-202-02-02
05/1712017
NEMO ETC, LLC Evaluation Report P9290.02.08-1124
Certifimte of Authorization #32455 6Y" EDITION (2017) F13C NON-HVHZ EVALUATION FL1654-R26
Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Revision 24: 10/14/2019
Page 2 of 5
Entity Exann Reference Date Entity Exam
FM (TSf1867) FM 4470 3001334 0245/2000 M -D {CER1592j HVHZ
rm ii5T1867) FM 4470 3000857 0111212040 M -D {CEBiS92} Prop. for Rev.
FM fTST18G7) FM 4470 3004091 01112/2000 UL (4UA9625i Quality Cantrul
tONEMOjetc.
Reference Date
Various WAs Various
10-0823 10/12/2010
Service Confirm C9113/20H
4. PRODucr DESCRIPTION:
This Evaluation Report covers Polyglass Modified Bitumen Roof Systems installed in accordance with Polyglass USA,
Inc. published installation instructions and the Limitations / Conditions of Use herein. The following Polyglass
membranes make up the subject 5vstems.
TABLE 1; ROLL -GOODS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS
Type
Product
Specification
Reference Grade
Type
Base Sheet/ Base Ply
Elastavert
ASTM 04897
N/A
N/A
Polyglass G2 Base ASTM D4601 N/A
II
Polyflex SA Base ASTM 04641 N/A
II
Elastobase SA ASTM D4601 N/A
ASTM D6163, Table 2 5
II
1
Polyglass Base ASTM D6509 N/A
N/A
SBS Membranes
Elastoshield HT
ASTM D6162
_
S
III
Elastoshield HT G ASTM D6162 G
III
Elastoshield HT G FR ASTM D6162 G
III
Elastobase ASTM D6163 5
1
Elastoflex V ASTM D6163 S
1
Elastoflex SA V ASTM D6163 5
1
Elastoflex SA V FR ASTM D6163 5
1
Elastoflex SA V Plus ASTM D6163 S
I
Elastoflex SA V Plus FR ASTM 06163 S
I
Elastobase P ASTM D6154 S
1
Elastoflex SA Base HD ASTM D6164 5
1
_ Elastoflex 56 ASTM D6164 S
I
Elastoflex S6 HP ASTM D6164 5
It
Elastoflex V G ASTM D6163 IS
1
Elastoflex V G FR ASTM D6163 G
I
Elastoflex 56 G ASTM D6164 G
i
Elastoflex 56 G FR ASTM D6264 G
I
PDlyfresko G SBS ASTM D6164 G
I
Polyfresko G 5135 FR ASTM D6164 G
I
Elastoshield TS G ASTM D6164 G
I
Flastoshield T5 G FR ASTM D6164 G
I
Elastoflex SA P ASTM D6164 G
I
Elastoflex SA P FR ASTM D6164 G
I
Polyreflect ASTM D6164 S
I
NEMO ETC, LLC Evaluation Report P9290.02.08-1124
Certificote ofAutha0zation 1132455 Sr" EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R26
Polyglass Modified Bitumen Roof Systems; (954) Z33-1330 Revision 24: 10/14/2019
Page 3 of 5
5. MIMITATIONS:
S.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Niernmen, P.E. are, in any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings ofthis product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with
FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2643.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall
be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of
the roof deck shall be documented through proper codified and/or FBC Approval documentation.
5-6 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure for the
selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16.
Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated
pressure criteria. Commonly used methods are ANSI/SPRI WDl, FM Loss Prevention Data Sheet 1-29, Roofing
Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk*
carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3
enhancements.
5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly
shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is
permitted for these systems.
5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing
deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing and analysis shall be in accordance with ANSI/SARI FM -1 or Testing Application
Standard TAS 105.
5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the existing
deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface
conditions exist that bring system performance into question, field uplift testing in accordance with ANSI/SPRI IA -1,
ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on
mock-ups of the proposed new roof assembly.
NFMO ETC, LLC Evaluation Report P9290.02.0a-RZ4
ccrrifjwte ofAvthorizotion 02455 GT" EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-RZ6
Polyglass Modified Bitumen Roof systems; (9541233-1330 Revision 24: 10/14/2019
Page 4 of 5
'N /
NEMO I etc.
TABLE 1(CONTINUED). ROLL -GOODS FOR POLYGLASS MODIFIED BITDMEN_ ROOF SYSTEMS
Specification
Type Product
Reference Grade Type
Polyflex
ASTM D6222
5 I
Polyflex G
ASTM D6222
G
Palyflex G FR
ASTM D6222
G I
Pclyfresko G
ASTM D6222
G I
Polyfresko G FR
ASTM D6222
G
Polybond
ASTM D6222
S I
APP Membranes
Polybond G
ASTM D6222
G I
Polyflex SA P
ASTM D6222
G i
Polyflex SA P FR
ASTM D5222
G I
Polyfresko G SA
ASTM D6222
G I
PDlyfresko G SA FR
ASTM D6222
G
Polykocl
A5TM D6222
5 1
5. MIMITATIONS:
S.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Niernmen, P.E. are, in any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings ofthis product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with
FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2643.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall
be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of
the roof deck shall be documented through proper codified and/or FBC Approval documentation.
5-6 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure for the
selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16.
Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated
pressure criteria. Commonly used methods are ANSI/SPRI WDl, FM Loss Prevention Data Sheet 1-29, Roofing
Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk*
carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3
enhancements.
5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly
shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is
permitted for these systems.
5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing
deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing and analysis shall be in accordance with ANSI/SARI FM -1 or Testing Application
Standard TAS 105.
5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the existing
deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface
conditions exist that bring system performance into question, field uplift testing in accordance with ANSI/SPRI IA -1,
ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on
mock-ups of the proposed new roof assembly.
NFMO ETC, LLC Evaluation Report P9290.02.0a-RZ4
ccrrifjwte ofAvthorizotion 02455 GT" EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-RZ6
Polyglass Modified Bitumen Roof systems; (9541233-1330 Revision 24: 10/14/2019
Page 4 of 5
NMEMO I etC.
5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall
be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having
Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Lass Prevention Data
Sheet 1-52 or Testing Application Standard TAS 124.
5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC
Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES -1 or Roofing Application Standard RAS 111,
except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3).
5.13 All products in the roof assembly shat! have quality assurance in accordance with FAC Rule 61G20-3. For non-
Polyglass components listed within wind uplift rated assemblies in Appendix 1, refer to the Product Approval of the
component manufacturer.
■
6.1 Polyglass Modified Bitumen Roof Systems shall be installed in accordance with Polyglass USA, Inc. published
installation instructions, subject to the Limitations / Conditions of Use noted herein.
6.2 System attachment requ'rements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design
Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate
passing pressure divided by 2 (the 2 to 1 margin of safety per FBG 1504.9 has already been applied). Refer to FBC
1609 for determination of design wind loads.
REQUIREMENTS:7. BUILDING PERMIT
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANdA'auRiNG PLANTS:
Contact the noted CA agency for information on product locations covered for F.A.C. Rule 61G20-3 QA requirements
UL LLC— QUA9625; (314) 578-3406, k.chancellor@us.ul.com
- THE 81 -PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
NEMO ETC, ILC Evaluation Report P9290.02.09-RZ4
Certifi-tr afAuth.6- ion #32455 6' EDITION {2017} FBC NON-HVHZ EVALUATION FL1654-1126
Polyglass Modified Bitumen Roof Systems; (9541233-1330 Revision Z4: 10/14/2019
Page 5 of 5
ONEMOjetc.
APPENDIX
TABLE
1: ArrAcmMENT REQUIREMENTS FOR
DECK
WIND Uplui ftsimi
APPLICATION
TYPE
DESCRIPTION
PAGE
1A
Wood
New or Rerouf (Tear -Off)
A-1
Bonded Insulation,. Bonded Roof Cover
5
1B
Wood
New or Reroof (TearOff)A-2
Mech. Attached Anchor Sheet, Sanded Insulation, Banded Roof Cover
5-10
1C
Wood
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Banded Insulation, Bonded Roof Cover
11-12
1D
Wood
New, Reroof (Tear -Off) or Recover
3
Mech. Attached Base insulation, Bonded Top Insulation, Bonded Roof Cover
13
1E
Wood
New, Reraof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
13-16
1F
Wood
New, Reroof (Tear -Off) or Recover
D
Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
17-20
1G
Wood
New or Reraof (TearOff)E
Non -Insulated, Mech. Attached Base Sheet (nails), Bonded Roof Cover
21-25
1H
Wood
New, Reroof (Tear -Off) or Recover
E
Non -insulated, M2CI1. Attached Base Sheet (screws & plates), Bonded Roof Cover
26-32
11
Wood
New or Reroof (Tear -off)
F
Non -Insulated, Bonded Roof Cover
33
2A
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Tap Insulation, Bonded Roof Cover
34-36
ZB
Steel or Structural concrete
New, Reroof (Tear -Oft) or Recover
C
Mech. Attached insulation, Bonded Roof Cover
37-43
2C
Steel or Structural concrete
New, Reroof (Tear -Off} or Recover
D-1
Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
44-45
2D
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
0-2
Insulated, Mech. Attached Velociflex, Bonded Roof Cover
46-47
3A
Structural concrete
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
48-58
33
Structural concrete
New or Reroof (Tear -Oft}
F
Non -Insulated, Bonded Roof Cover
58
4A
Lightweight concrete
New or Reroof (TearOff)A-1
Bonded Insulation, Bonded Roof Cover
59-62
4B
Lightweight concrete
New or Rereof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Banded Roof Cover
63
4C
Lightweight concrete
New or Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
64-68
5A
Cementitious wood fiber
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
69
5B
Cementitious wood fiber
Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Raof cover
70-71
5C
Cementitious wood fiber
Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
72
SO
Cementitious wood fiber
Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
72
5E
Cementitious wood fiber
Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
72
6A
Existing gypsum
Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
73-75
66
Existing gypsum
Reraof {Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
76
6C
Existing gypsum
Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
76
6D
Existing gypsum
Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
76
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
77-81
7B
Various
Recover
F
Nan -Insulated, Bonded Base Sheet, Bonded Roof Cover
Si
The following notes api to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof cum currents. Roof decks and structural members shall he in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:
.' Wood: Minimum 0.75 -inch penetration.
➢ Steel: Minimum 0.75 -inch penetration and engage the top flute of the steel deck.
➢ Structural concrete: Minimum 1 -inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
Ni ETC, ILC Evaluation Report P9290.02.08 -R24 for F1.1654-11ZB
Certificate of Authorization #32455 1 EDITION (2317) FBC NON-HVHZ EVALUATION Revision 24: 10/14/2C19
02018 NEMD ETC, LLC Pulyglass Modified Bitumen Roof Systems; (954) 233-1334 Appendix 1, Page 1 of 81
NNEMD1 etc.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate,polystyrene, wood fiberboard, perlite,gypsum-based roofboard or mineral -wool roof board that meets the OA requirements
of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1and, for foam plastic, FOC Chapter 26, when installed with the roof cover.
4. Minimum 200 psi, minimum 2 -inch thick lightweight insulating concrete may be substituted far rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet
fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shat{ be ofeclual or greater configuration to the steel and concrete deck listings. Roof decks and structural
members shall be in accordance with FSC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval
documentation.
5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturers published instructions.
D Hot asphalt (HA):
Full coverage at 25-30 lbs%square.
> Dow INSTA STIR Quik Set Insulation Adhesive (p -IS):
Continuous D,75 to 1 -inch wide ribbons, 12 -inch o.c.
➢ Millennium one Step Foamable Adhesive (M-DSFA):
Continuous 0.25 to D.5 -inch wide ribbons, 12 -inch o.c.
➢ Millennium PG -1 Pump Grade Adhesive (M -PG 1):
Continuous 0.25 to 0.5 -inch wide ribbons, 12 -inch o.c.
➢ OMG OlyBone 500 (OB5e0):
Continuous 0.75 to 1 -inch wide ribbons, 12 -inch o.c. (PaceCart or SpotShot). Note: Olyeond Green may he used where Ofyiiond500 is referenced.
9 Olyeond Classic (OB Classic};
Full coverage at 1 gal/square.
ICP Adhesive & Sealants Polyset CR -20:
Continuous 2.5 -3.5 -inch wide ribbons, 12 -inch o.c-
9 Note: When multiple layera(5J ofinsulation and/or coverboard are installed in ribbon -applied adhesive, boardjoints shall be staggered.
i Nate: The maximum edge distance from the adhesive
ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are flat -stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations maybe substituted with the fallowing Maximum
Design Pressure (MDPii limitations. In no case shall these values
he used to'increase'the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the
thinner board listed below may be used as a drop-in for the
equivalent thicker material listed in the table!
➢ Millennium One Step Foamable Adhesive (M-OSFA(:
MPP -157.5 psf (Mon. 0.5 -inch thick)
D Millennium PG -1 Pump Grade Adhesive (M -PGI):
MDP -157.5 psf {Men. 0.5 -inch thick)
➢ OMG OlyBond 500 (08500):
MPP -45.0 psf (Min. 0.5 -inch thick Multi -Max FA -3)
➢ OMG Olyllond 500 (06500}:
MDP -187.5 psf (Min. 0.5 -inch thick 150 95+ GLI
? OMG OlyBond 500 (06500):
MDP -315.0 psf (Min. 0.5 -inch thick El 3)
➢ OMG OlyBond 500 (08500):
MDP -487.5 psf (Min. 0.5 -inch thick ACFaam II)
➢ ICP Adhesives & Sealants Polyset CR -20:
MDP -117.5 psf (Min. 1.0 -inch thick)
8. Bonded polyisocyanurate insulation hoards shall be maximum 4 x 4 ft.
9-. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with F3C
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI W01, FM Loss Prevention
Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2..10.1 of FM Loss Prevention Data
Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For fully bonded assemblies, the maximum design pressure far the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX -1 at Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shalt be examined for compatibility and band performance with the selected adhesive, and the existing
roof system (far recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI W1, ASTM E907,FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application.
NEMO ETC, LLC
Certificate of Authorization #32455
02018 NEMO ETC, LLC
6' EDITION (2017) FBC NDN-HVHZ EVALUATION
Polyglass Modified Bitumen Roof Systems; (954) 233-1330
Evaluation Report P9290.02.08-RZ4 for FL -1654-R26
Revision 24:1011412019
Appendix 1, Page 2 of 61
NMEMO I etc.
14. Lightweight Insulating Concrete (LWC) shall he cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. Unless otherwise noted, for systems where specific LWC is net referenced, the minimum design mix shall be 300 psi. In all cases, the minimum topcoat
thickness is 2 -inches. For LWC over structural concrete, refererce is made to FBC Section 1917.4.1, Point 1. For "pre-existent" LWC references, listings were established through testing over lightweight concrete cast
using only foaming agent (ASTM C896), water and Portland cement (ASTM 01501, with no proprietary additives, in accordance with procedures adapted by Miami -Dade BCCO (FBC CER1592). Unless otherwise noted,
use of these listings in new construction or re -roof (tear off) applications is at the discretion of the Designer or Record and Authority Having Jurisdiction.
15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications
REFERENCE
PoLYGLAss ROOF COVERS
LAYER rAATERIAL
APPLICATION
BP -AA
Base Ply One or more plies Polyglass G2 Base, FBCApproved ASTM D4601, Type II
Base and PI sheets,
{ Y
PI One of more lies Pol lass PI. IV, Pol [ass PI VI, FBC Approved ASTM D2178, T
y p Yg y Yg y pp Type IV or VI
Hot Asphalt at 20-40
Asphalt -Applied(
Note: Asphalt -applied sheets or insulation shall not be applied to paly flim surfaced membranes.
lbs/square
Base Ply One ply Elastobase (sand/sand(, Elastoflex V, Elastoflex S6, Elastoflex 56 HP, Elastoshield HT
SBS-CA1
Elastoshield HT G, Elastoshield HT G FR, Etastofiex V G, Elastoflex V G FR, Elastoflex SG, Elastofex S6 HP, Elastoflex 56 G, Elastoflex
PG350 at 1.5-2.0
Cap Pry 56 G FR, Elastoshield TS G, Elastoshield TS G FR, Palyfresko G SBS (sand -backed), Palyfresko G SBS FR (sand -backed)
go[/square
Base Ply One ply Elastabase (sand/sand), Elastoflex V, Elastoflex 55, Elastoflex 56 HP
SBS-CA2
Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex SG HP, Elastoflex 56 G, Elastoflex
Polyplus 35 at 1.5-2.0
Ca p6
Cap y 55 G FR, Elastoshield TS G, Elastoshield T5 G FR, Polyfresko G SBS (sand -backed), Palyfresko G 565 FR (sand -backed)
gal/square
Base Ply or Ply One or more plies Elastobase (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex 56, Elastoflex
SBS
56 HP, Elastoshield HT
-AA
Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex 56, Elastoflex S6 HP, Elastoflex 56G,
Hot Asphalt at 20-40
(565, Asphalt -Applied)
Cap Ply
Elastoflex 56 G FR, Elastoshield TS G, Elastoshield TS G FR, Palyfresko G SBS (sand-backedl, Polyfresko G SBS FR (sand -backed)
lbs/square
Note: I Asphalt -applied sheets or insulation shall not be applied to poly -film surfaced membranes.
Base Ply or Ply One or more plies Elastobase (sand/poly), Elastobase (poly/poly), Elastoflex V, Elastoflex 56, Elastoflex S6 HP, Elastushield HT
SBS -TA
Elastoshield HT G, Elastoshield HT FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex 56, Elastaflex56 HP, Elastoflex 56
(SBS, Torch -Applied)
Cap Fly G, Elastoflex 56 G FR, Elastoshieid T5 G, Elastoshield T5 G FR, Palyfresko G SBS (poly -film backed), Polyfresko G SB5 FR (poly -film
Torch -Applied
backed)
SBS -SA -H
Base Ply Elastabasp SA
Self -adhering (followed
Isar, Se16Adhering. Hy6.dd Syne,.)
by torch -applied sheet}
Base Ply One or more plies Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Flastoflex SA V Plus FR, Elastoflex SA Base HD
SBS -SA
Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyrefled
(585, Self -Adhering)
Note: Unless otherwise noted, permissible membrane substratesforSIRS-SA ore fimited to the SBS -SA Base Ply options herein,
Self -Adhering
Elastobase (poly/sond) or Elastabase (poly/poly). _
APP-CA1
Cap Ply Polyflex G FR
PG350 at 1.5-2.0
_
gal/square
APP -TA
Base Ply or Ply Cne or more plies Polyglass Base, Palyflex, Polybond
(APP, Torch -Applied)
Cap Ply I Polyflex, Polyflex G, Pulyflex G FR, Polybond, Polybond G, Palyfresko G, Polyfreska G FR
Torch -Applied
APP -SA -H
Base Ply Polyflex SA Base
Self -adhering (followed
(APP, self -Adhering. Hybridsg1r 1
by torch -applied sheet)
APP
Cap Ply Polyflex SA P, Polyflex SA P FR, Palyfresko G SA., Polyfresko G SA FR, Pclykoal
-SA
{APP, Setf-Adhering)
Note: Unless otherwise noted, permissible membrane substrates forAPP-SA are limited to the SHS -SA Base Ply options herein,
Self -Adhering
Elastobase (poly%sand) or Elastobase {poly%poly),
NEMO ETC, LLC Evaluation Report P9290.02.08 -R24 for FL1654-R26
Certificate of Authorization #32455 bra EDITION (2017) FBC NON-HVHZ EVALUATION Revision 24: 10/14/2019
02018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 3 of 81
ONEMO etc.
TABLE IE: WOOD DECKS ..
SYSTENITYPEC: M ECHAN ICALLY ATTACHED INSULATION, BONDED ROOF COVER
System Top Insulation Layer Roof Cover (Note 151 MDP
Deck [iJdte 1) Base Insulation Layer
Nu
Type Fasten Attach Base Ply Ply Cap Ply (P5f)
Min. 0.5 -inch Structodek High Density
Min. 19/32- (Optional) One or mare Fiberboard Roof Insulation or min.
(Optional if (Optional if axing
W-49 layers, any combination, 0.25 -inch Dens Deck, Dens Deck Prime
Dekfast Hex (aka, Dekfast PLT -H -Z-718) with Dekfast
1 per1.33 using AA Ply) AA Base) BP -AA,
SBS -AA, 585 -
inch plywood loose laid or SECUROCK Gypsum -Fiber Roof
012 DP
R' BP -AA, SBS- 505 -AA, SBS -TA
TA,APP-TA -82.5
Board
AA or APP TA
SILT-ADNFRING BASE PLY:
)Optional) One or more
Dekfast 014 with Dekfast Hex )aka, Dekfast PLT -H-2-
50
M. 15/3b
layers, any
Min. 1.5 -inch Polytherm, ACFoam 11,
7/8), OMG #lA HD with OG 3"Galvalume Steel
M
1 per 2.67
(Optional] SBS-
56S -SA, APP -
inch
inch plywood
combination,
H -Shield or Polytherm
Plates or Trufast HD with Trufast 3 -inch Insulation
ftr
585 -SA
SA, SBS -TA, APP-
SA, 565 -TA,
-30,0
loose laid
Plates
TA
APP -TA
(Optional) One or more
Dekfast Hex )aka, Dekfast PLT -H-2-7/8) with Dekfast
W -51
Min. 1S/32-
layers, any combination,
Min, 0,25 -inch Dens Deck. Prime or
#14, OMG 3" Round Metal Plate with OMG Hp,
1 2 ft:
SBS
)Optional) Ses-
SRS -SA, APP -
inch plywood
loose laid
SECUROCK Gypsum -Fiber Roof Board
OMG Flat Bottom Plate (Accutrac) with Roofgrip 414
per
-SA
SA, SBS -TA, APP-
SA, 56.9 -TA,
-30.0
or Trufast 3" Metal Insulation Plate with Trufast HD.
TA
APP -TA
Polygrip #14 with Polygrip Hex Plate or Dekfast #14
(Optional far recover)
with Dekfast Hex (aka, Dekfast PLT -H-2-7/8) or
Min.
One or more layers, any
Min. 0.25 -inch SECUROCK Gypsum-
Dekfast Galvalume Steel 3" Round (aka, Dekfast PI -T-
W -5Z
inch plywood
plywood
combination, min. 1-
Fiber Roof Board optionally rimed
0 Y p
R-3 or OMG #14 Rootgrip
) 8 P with OMG 3 in, Round
1 per 2 ftp
SBS -SA
None
565 -SA
-45.0
inch, loose laid
with POLYBRITE 745 or WD3000
Metal Plate, OMG 3 in. Ribbed Galvalume Plate
(Flat) or Accutrac Flat Bottom Plate or Trufast 914
HD Fasteners with Trufast 3" Metal Insulation Plate
(Optional far recover)
Polygrip #14 with Polygrip Hex Plate or Dekfast #14
Min. 15/32-
One or more layers, any
Min. 0.25 -inch Dens Deck Prime
with Dekfast Hex (aka, Dekfast PLT -H-2-7/8) or OMG
W-53
Inch plywood
combination, min. 1-
optionally primed with POLYBR17E 745
014 Roofgrip with OMG 3 in. Round Metal Plate or
1 per 2ft2
Sli
None
S35 -SA
-45.0
inch, loose laid
or WB3000
Accutrac Flat Bottom plate or Trufast 014 HD
Fasteners with Trufast 3" Metal Insulation Plate
O tional far recover
( P )
Polygnp #14 with Polygrip Hex Plate or Dekfast DF-
(Optional when
Mein.. 15132-
One or more la
yn. any
Min. 0.25 -inch SECUROCK Gypsum-
014 with Dekfast Hex (aka, Dekfast PLT -H-2-7/8) or
1per 1.78
u5ingtorch-
SBS -SA, APP-
W-54
Inch plywood
combination, in. 1-
Fiber Roof Board optionally primed
OMG 014 Roofgrip with OMG 3 in, Round Metal
ft,
5B5 -SA
SA, SBS -TA or
-45.0
inch, loose laid
with POLYBRITE 745 or W83000
Plate or Accutrac Fiat Bottom Plate or Trufast H14
applied Cap Ply]
APP -TA
HD Fasteners with Trufast 3" Metal Insulation Plate
585 -TA, APA -TA
Min. 15/32-
(Optional for recover)
One or more layers, an
Min. 0.25 -inch Dens Deck Prime
OMG 914 Roof r> with OMG 3 in.. Round Metal
g p
(Optional when
SRS -SA, APP-
inch
Y y
combination, min: i-
optionally primed with POLYBRITE 745
Plate or Trufast p14 HD Fasteners with Trufast 3"
1 per 1.78
ftg
SBS -5A
using torch -
SA, SBS -TA or
X5.0
plywood
or WB3000
Metal Insulation Plate
applied Cap Piy}
APP -TA
inch, loose laid
SBS -TA, APP TA
(Optional) One or more
Min., 0.25 -inch Dens Deck Prime,
Dekfast 014 with Dekfast Hex (aka, Dekfast PLT -H -2-
W-56
Min. 15,/32-
layers an combination,
y y
DEKcell FA Glass Mat Roof Board or
7/8), 0 M 914 HO with OMG 3" Gall Steel
1 per 1 ft a
SBS -SA
(Optional) 5BS-
SBS -TA, APP TA
-60.0
inch plywood
loose laid
SECUROCK Gypsum -Fiber Roof Board
Plates or Trufast HD with Trufast 3 -inch Insulation
TA, APP -TA
Plates
NEMO ETC, LLC Evaluation Report P9290.02.D8-R24 for 71-16541
Certificate of Authorization #32455 6- EDITION (2017) FDC NON-HVHZ EVALUATION Revision 24: 10/1412019
®2018 NEMO ETC, LEC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 14 of 81
NEW I etc.
Certificate of Authorization #32455
353 Christian Street, Unit #13
Oxford, CT 06478
(203) 262-9245
ENGINEER EVALUATE TEST CONSULT CERTIFY
REPORTEVALUATION
Hunter Panels Evaluation Report C32980.10.11 -R6
15 Franklin Street FE5968-R10
Portland, 04101 Date of Issuance: 10/18/2011
(717) 245-7070 00 Revision 6: 02/05/2019
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: H -Shield Roof Insulations
LABELING. Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named products) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). NEMO I etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 3.
Prepared by:_
--
t ?. t
^
s
Robert J.M, Nieminen, P.E.
,
The facimilie seal appearing was authorized by Robert
Florida Registration No. 59165, Florida DCAANE1983
,.,
Nieminen, P.E. on 02/05/2019. This does notserve as an
electronically signed document
CERTIFICATION of INDEPENDENCE:
1. NEMO Ietc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. MEMO I etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO I etc. nor Robert Nieminen, P.E. are, in anyway, the Designer of Record for any project
on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically
for that purpose.
MEMO j etc.
ROOFING COMPONENT EVALUATION:
Product Category: Roofing
Sub -Category: Insulation
Compliance Statement: H -Shield Roof Insulations, as produced by Hunter Panels, have demonstrated compliance
with the following sections of the 6" Edition (2017) Florida Building Code through testing in accordance with the
following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use
set forth herein.
Section
2603.3
T1508.2
1520.1
Property
Flame Spread
Physical Properties
Physical Properties
Standard
ASTM E841
ASTM C1289
TAS 110
Year
2013
2013
2000
Entity
Examination
Reference
Date
ERD (TST6049)
ASTM C1289 & TAS 110
C31640.04.10
04/06/2010
ERD (TST6049)
ASTM C1289 & TAS 110 (FL)
C42950.09.13-1A-Rl
03/04/2014
ERD (TST6049)
ASTM C1289 & TAS 110 (PA)
C42950.03.14
03/26/2014
ERD (TST6049)
ASTM C1299 & TAS 110 (FL)
C42950,02.14 -1A -R2
04/16/2014
ERD (TST6049)
ASTM C1289 (IL)
C46470.10.14 -1A-1
10/03/2014
ERD (TST6049)
ASTM C1289 (IL)
C46470.10.14 -1A-2
10/03/2014
ERD (TST6049)
TAS 110 (IL)
C46470.10.14 -1A -3A
10/03/2014
ERD (TST6049)
ASTM C1289 (UT)
046470.01.15-1
01/08/2015
ERD (TST6049)
TAS 110 (UT)
C46470.01.15-2
01/08/2015
FM Approvals (TST1867)
ASTM E84
3018331
08/30/2004
ITS(TST1585)
ASTM E84
100114954SAT-001 B
06/08/2010
ICC -ES (EVL2396)
2015 1BC/IRC Compliance
ESR -3174
12/01/2017
Miami -Dade (CER 1592)
HVHZ Compliance
14-0505.08
11/06/2014
R&D Services (IAS TL -566)
ASTM C1289 (TX)
RD18149
02/26/2018
R&D Services (IAS TL -566)
ASTM C1299 (NY)
RD18229
04/02/2018
UL, LLC (CER 9626)
UL1256
TJ3X.R18846
07/03/2013
UL, LLC (QUA9625)
Quality Control
Service Confirmation
02/04/2019
FL, IL, NY, PA, TX, UT
The following insulations are mechanically attached or adhered to Approved substrates using fasteners, stress
plates and adhesives, as outlined in the Roof System Product Approval.
Product
PRODUCTSTABLE 1: SUMMARY OF HUNTER INSULATION
ASTM C1289 Dimensional Offering
Plants
Type T
Class
Grade Thick (in)
Dimensions (ft)
Non-HVHZ (C3289)
HVHZ
(TAS 110)
H -Shield F
1
1
2 or 3 1 to 4
4x4 or 4x8
FL, IL, NY, PA, UT
FL, IL, PA, UT
H -Shield
II
1
2 or 3 1 to 4.5
4x4 or 4x8
FL, IL, NY, PA, TX, UT
FL, IL, PA, UT
H -Shield (Tapered)
II
1
2 or 3 0.5 to 4.5
4x4
FL, IL, NY, PA, TX, UT
FL, IL, PA, UT
H -Shield CG
II
2
2 ar 3 0.5 to 4.5
4x4 or 4x8
FL, IL, NY, PA, TX, UT
FL, IL, PA, UT
1 Numerical ratings as determined by ASTM E84 are not intended to reflect hazards presented by these materials under actual fire
conditions.
NEMO ETC, LLC Evaluation Report C32980.10.11 -R6
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ & HVHZ EVALUATION FL5968-R10
H -Shield Roof Insulation Revision 6: 02/05/2019
Page 2 of 3
*NEMO I etc.
' Plants
ft) Non-HVHZ (C1289)
HVHZ
(TAS 110)
ASTM C1289
FL, IL, PA, UT
Dimensional Offering
Product
FL, NY, PA, TX, UT
FL, PA
4x8 FL, IL, NY, UT
48 FL
FL, IL, UT
FL
IL
N/A
Type
Class
Grade
Thick (in)
Dimensions I
H -Shield CG (Tapered)
II
2
2 or3
0.5 to 4.5
4x4
H -Shield Premier
II
2
2 or 3
1
4x8
H -Shield HD or HD90
II
4
1
0.5
4x3
H -Shield HD Composite CG
IV
N/A
2
2 to 4
nominal 4x4 of
H -Shield WF
IV
N/A
N/A
1.5 to 3.5
nominal 4x4 or
H -Shield NB (OSB)
V
N/A
N/A
1.5 to 4
nominal 4x!
H -Shield NB (plywood)
V
N/A
N/A
1.5 to 4
nominal 4xE
Cool -Vent (OSB)
V
N/AN/A
2.5 to 5
48Cool-Vent
(plywood)
V
N/A
N/A
2.5 to 5
4xg
Cool -Vent II (05B)
V
N/A
N/A
2.5 to 6
4x8
Cool -Vent Il (plywood)
V
N/A
N/A
2.5 to 6
4x8
*NEMO I etc.
' Plants
ft) Non-HVHZ (C1289)
HVHZ
(TAS 110)
FL, IL, NY, PA, TX, UT
FL, IL, PA, UT
UT
UT
FL, NY, PA, TX, UT
FL, PA
4x8 FL, IL, NY, UT
48 FL
FL, IL, UT
FL
IL
N/A
IL
FL, IL, NY, PA, UT
FL, IL, NY, PA, UT
aILPA,
IL
IL
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 H -Shield NB, Cool -Vent and Cool -Vent fl with OSB as the top surface are not for use in FBC HVHZ jurisdictions.
5.3 Refer to roof system Product Approval (for uplift resistance) and an approved Roofing Materials Directory (for fire
ratings; e.g., UL T1BX.R18845) for use and installation of H -Shield Roof Insulation_ If H -Shield Roof Insulation is not
listed in the roof system Product Approval, a request may be made to the Authority Having Jurisdiction for local -
approval provided that NFPA 276 or UL1256 internal fire; ASTM E108, UL790 or Testing Application Standard TAS
114, Appendix A external fire and/or FM 4474, UL1897 or Testing Application Standard TAS 114 wind uplift data,
as applicable, is provided specifically with the subject roof cover.
5.4 All products in the roof assembly shall have quality assurance in accordance with the F.A.C. Rule 61G20-3.
6.1 H -Shield Roof Insulation shall be installed in accordance with Hunter Panels' published installation instructions,
coupled with attachment requirements set forth in the roof system Product Approval documentation and approved
Roofing Materials Directory (for fire ratings).
6.2 The maximum board size for bonded applications is 4 x 4 ft.
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer
to Table 1 for products and locations having qualified under ASTM C1289-13 and TAS 110.
UL, LLC—QUA9625; (847) 664-3281
- END OF EVALUATION REPORT -