HomeMy WebLinkAboutSealed Engineering8559 US 1, Port St. Lucie, FL 34952
Conforms to the requirements of the 6th Edition (2017)
of the Florida Building Code sections 1604, 1609, 3105, H
V(ult) = 160 mph
Exposure category = C
Risk category = II
John J. Orlando PE LLC
165 Old Ridge Road
Macon, GA 31211 478 731 5394
jjorlando@cox.net
Florida registration # 0044089
job 0320GM
sheet 1 of 2
Complies to
NEC 2014
UNDERWRITERSLABORATORIESULINC.LISTEDELECTRIC SIGN
®®
EXISTING WALL
OR SURFACE
120V PRIMARY
ELECTRICAL CIRCUIT
RACEWAY
DIMENSION
7" x 7"
SECONDARY
12V LED SUPPLY LEADS
.040 ALUMINUM
RETURNS
1" TRIMCAP
LED'S
TYPICAL SECTION VIEW
SCALE - NTS
POWER
SUPPLY
FASTENER OPTIONS AS SHOWN ON
MOUNTING DETAIL
TWELVE (12) EVENLY SPACED PLACES
MOUNTING DETAIL
3/8" THREADED
GALVANIZED STEEL ROD
INTO A BLOCKING MEMBER
PLACED BEHIND FRAMING
MEMBER.
3/8" GALVANIZED LAG
BOLTS WITH AT LEAST 5"
OF EMBEDMENT INTO
FRAMING MEMBERS.
3/8" X 6" LONG TOGGLE
BOLTS LIBERTY BRAND
ITEM NO. 38600TM
OR EQUIVALENT
HILTI 3/8" X 3"
KWIK BOLT TZ SS 304
ITEM NUMBER 387523
OR EQUIVALENT
THRU-BOLT MOUNTING
HANGER BOLTS
REVERSE TOGGLE BOLT MOUNTING
MASONRY EXPANSION BOLT MOUNTINGThis item has been electronically signed and sealed by
John J. Orlando, PE using a Digital Signature and date.
Printed copies of this document are not considered signed and
sealed and the signature must be veried on any electronic copies.
Job name Best Value Jewelry & Pawn
Job#0420GM
Sign company:GloMaster Signs
Installation location:8559 US 1, Port St. Lucie, FL 34952
Section 1609.6.4 of Florida Building Code 2017 applies.
Application of wind pressures using the alternative all heights method for components and cladding
Type of structure:raceway mounted LED channel letters
Occupancy Category:II
Ultimate design wind speed, figure C, FBC 2017, section 1609:160 mph
W ind stagnation pressure (qz) per 1609.6.3 FBC 2017 65.5 psf
Net Pressure Coeficient (Cnet) from Table 1609.6.2 (1)
Components and cladding not in areas of discontinuity - walls and parapets -1.09
W ind Pressure -71.4 psf
W ind load applied between wall and structure, pulling structure away from wall
Load carried by tension in fasteners connecting structure to wall
- maximum height of structure to be attached 1.75 ft
- maximum width of structure to be attached 27.00 ft
- fill factor 0.80
- projected area of each component to be attached 37.8 ft^2
- wind load -2699 lbs
- design limit tension load per fastener to 250 lbs
- even number of fasteners minimum of 2 =-12
- number of fasteners practically required due to structure shape 12
- weight of structure is approximately 189 lbs
- design limit shear load per fastener to 125 lbs
- average shear load per fastener =15.8 lbs
Mounting surface construction is:to be determined
Use methods:1 through 4
Method 1 - Liberty brand toggle bolts
- use 3/8" x 6" long toggle bolts, item no. 38600TM
- ultimate tested shear load in hollow CMU = 3000 lbs
- ultimate tested pull out load in hollow CMU = 1800 lbs
- design pull out load = 250 lbs
NOTE: . Design assumes that fasteners are installed according to manufacturer's
instructions, using correct size drill.
Method 2 - Lag bolts into framing members.
-use 3/8" galvanized lag bolts with at least 5" of embedment into framing members.
- allowable pull out load =436 pounds
- allowable tension load =680 pounds
Method 3 - Through bolts into a blocking member.
- use threaded steel rod into a blocking member placed behind framing member.
- ultimate tension load #10/24 rod =100 pounds ultimate shear load =50 pounds
- ultimate tension load 1/4" rod =270 pounds ultimate shear load =200 pounds
- ultimate tension load 3/8" rod =680 pounds ultimate shear load =510 pounds
- ultimate tension load 1/2" rod =1260 pounds ultimate shear load =940 pounds
Method 4 - Hilti 3/8" x 3" Kwik Bolt TZ SS 304, Item number 387523
- ultimate tension load = 1520 lbs
- allowable shear load = 1685 lbs
NOTE: . Design assumes that fasteners are installed according to manufacturer's
instructions, using correct size drill.
https://www.hilti.com/medias/sys_master/documents/hac/9233455513630/Technical-information-ASSET-DOC-LOC-1543424.pdf
References:
ASCE 7-10
The 6th Edition (2017) of the Florida Building Code
sheet:2 of 2
John J. Orlando PE LLC 0044089
165 Old Ridge Road
Macon, GA 31211
(478) 731-5394
jjorlando@cox.net
This item has been electronically signed and sealed by
John J. Orlando, PE using a Digital Signature and date.
Printed copies of this document are not considered signed and
sealed and the signature must be veried on any electronic copies.