C2182-2
9.9.17
Page 2 of 3
Manufacturer: Metal Sales Manufacturing Corporation
Product Name: 5V-Crimp
Panel Description: 24" wide coverage with (5) 1/2" high ribs
Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or
Galvalume coated steel (ASTM A792) or painted steel (ASTM A755).
Deck Description: Min. 19/32" plywood or min. ¾" thick wood plank (min SG of 0.42)
for new and existing constructions. Designed by others and installed
as per FBC 2017.
Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c.
(Minimum) in the field and edges. Designed as per FBC 2017.
Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1
Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2.
Requires applied lap sealant for roof slopes less than 3:12.
Design Uplift Pressure: 84.5 psf @ fastener spacing of 24" o.c.
(Factor of Safety = 2) 131.3 psf @ fastener spacing of 18" o.c.
149.6 psf @ fastener spacing of 12" o.c.
Fastener Pattern:
Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener
shall be of sufficient length to penetrate through the deck a minimum
of 3/8".
At panel ends 6 fasteners per panel width. (4 located adjacent to ribs and 2 between
ribs)
At intermediate 4 fasteners per panel width. (4 located adjacent to ribs)
Test Standards: Roof assembly tested in accordance with TAS 125-03 ‘Standard
Requirements for Metal Roofing Systems’.
Code Compliance: The product described herein has demonstrated compliance with FBC
2017 Section 1507.4
Product Limitations: Design wind loads shall be determined for each project in accordance
with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress
design. The maximum fastener spacing listed herein shall not be
exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Fire classification is not within scope of this
Evaluation Report. Refer to FBC 2017 Section 1505 and current
FL 14645.2-R3
C2182-2
9.9.17
Page 3 of 3
approved roofing materials directory or ASTM E108/UL790 report
from an accredited laboratory for fire ratings of this product.
Supporting Documents: TAS 125 Test Reports
Farabaugh Engineering and Testing Inc
Project No. T235-07, Reporting Date 7/12/07
Project No. T172-08, Reporting Date 4/29/08