HomeMy WebLinkAboutSubmittal - CTV Chiller - SLC Rock Road Jail CTV Chiller Repl 4-14-2020
Prepared For:
Salas O’Brien
Date: April 14, 2020
Customer P.O. Number:
Customer Project Number:
Sold To:
St. Lucie County
Job Number:
Job Name:
SLC - Rock Road Jail Chiller Repl
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Centrifugal Water Chiller
Chris Cowling
Trane U.S. Inc.
6965 Vista Parkway North, Suite 11
West Palm Beach, FL 33411
Phone: (561) 683-1521
Cell: (561) 683-1521
Fax: (561) 697-8714
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
between submittal generation and equipment release, the product
performance and submittal data will need to be verified. It is the
customer’s responsibility to obtain such verification.
Please Note:
Please review submittal for accuracy before ordering.
Submittal
J:\Jobs\46\55879\2\Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Repl 4-14-2020.doc
Table Of Contents
Product Summary ........................................................................................................................... 1
Centrifugal Water Chiller (Item A1)
Tag Data .................................................................................................................................................. 3
Product Data ............................................................................................................................................ 3
Performance Data .................................................................................................................................... 5
Product Data Report-CH-2 ....................................................................................................................... 6
Mechanical Specifications ........................................................................................................................ 8
Unit Dimensions ..................................................................................................................................... 13
Weight, Clearance & Rigging Diagram ................................................................................................... 18
Accessory .............................................................................................................................................. 20
Field Wiring ............................................................................................................................................ 22
Field Installed Options - Part/Order Number Summary
Centrifugal Water Chiller ........................................................................................................................ 25
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 3 of 25
Tag Data - Centrifugal Water Chiller (Qty: 1)
Item Tag(s) Qty Description Model Number
A1 CVHE450 1 Centrifugal Chiller ( CTV ) CVHE0450
Product Data - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
Standard ship cycle CVHE, CVHF & CVHG
Centrifugal liquid chiller with 3 stage compressor
Compressor size: 450 nominal tons
Adaptiview controls
Incoming line hertz: 60
Compressor motor hertz: 60.
Incoming line voltage: 460 volt
Compressor motor voltage: 460 volt 3 phase
Startup Included - Trane Service must start equipment for warranty to be honored
Compressor motor power: 233 kW
Motor frame size: 440E
Compressor impeller cutback: 230
Standard cooling
Evaporator shell size: 050 short barrel
Evaporator bundle size: 580 nominal tons
Evaporator tubes: 0.75 inch (19.1 mm) dia. internally enhanced copper
Evaporator tube wall: .025 inch (0.6 mm) thick
Evaporator fluid type: Water
Evaporator waterbox type: Non-marine
Evaporator waterbox construction: Standard
Evaporator water box passes: Two pass
Evaporator waterbox pressure: 150 psig (1034 kPa)
Evaporator waterbox connection: Victaulic
Evap waterbox arrangement: in LH end - out LH end
Thermal dispersion flow switch (IFM) - Field Installed (Fld)
Condenser shell size: 050 short barrel
Condenser bundle size: 500 nominal tons
Condenser tube: 0.75 inch (19.1 mm) internally enhanced copper
Condenser tube wall: .028 inch (0.7 mm) thick (thicker tube wall option)
Condenser shell construction: Standard
Condenser fluid type: Water
Condenser waterbox type: non-marine
Condenser waterbox construction: Standard
Condenser water box passes: Two pass
Condenser waterbox pressure: 150 psig (1034 kPa)
Condenser waterbox connection: Victaulic
Condenser waterbox arrangement: in LH end - out LH end
Standard tube sheet construction
Thermal dispersion flow switch (IFM) - Field Installed (Fld)
Orifice size: 400 nominal tons
Agency listing: U.L. listed unit (United States requirement)
Factory performance test: Standard air run and vibration test
Selection tolerance: AHRI Standard tolerance
Brass logo with customer specified engraving
No unit insulation package (field installed insulation by field insulator)
AHRI Certified
Complies with ASHRAE 90.1 - 2016
Generic BAS
BACnet interface
R514 Refrigerant
Trane Supplied Refrigerant
Low Voltage Wye-Delta Starters
Starter type: Unit Mounted Wye-Delta
Starter maximum RLA: 346 Amps
Starter power connection: Circuit Breaker High-Interrupt
Starter power connection maximum RLA: 296 Amps
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 4 of 25
Starter option: Surge protector/lightning arrestor
Factory Start-up
10 year Parts, Labor, & Refrigerant warranty
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 5 of 25
Performance Data - Centrifugal Water Chiller
Tags CVHE450
Primary cooling capacity (tons) 300.00
Primary power (kW) 166.30
Primary RLA (Incoming line) (A) 246.40
Minimum circuit ampacity (A) 306.00
Maximum overcurrent protection (A) 500.00
Compressor motor RLA (A) 237.70
Motor locked rotor amps (A) 1661.00
Actual motor voltage full load (V) 460.0
Actual motor frequency (Hz) 60.0
Primary efficiency (kW/ton) 0.5542
NPLV (kW/ton) 0.4937
Evaporator entering fluid temp (F) 54.00
Evaporator leaving fluid temp (F) 42.00
Evaporator fluid flow rate (gpm) 597.10
Evaporator pressure drop (ft H2O) 6.66
Evaporator fouling factor (hr-sq ft-deg F/ Btu) 0.000100
Evaporator fluid concentration (%) 0.00
Condenser entering fluid temp (F) 85.00
Condenser leaving fluid temp (F) 95.00
Condenser fluid flow rate (gpm) 841.90
Condenser pressure drop (ft H2O) 11.12
Condenser fouling factor (hr-sq ft-deg F/ Btu) 0.000250
Condenser fluid concentration (%) 0.00
Refrigerant charge (lb) 550.0
Shipping weight (lb) 17144.0
Operating weight (lb) 19067.0
Unit center of gravity X (in) 28.000
Unit center of gravity Y (in) 45.000
Unit center of gravity Z (in) 57.000
Left Front isolator load (lb) 4599.0
Left Rear isolator load (lb) 3621.0
Right Front isolator load (lb) 5980.0
Right Rear isolator load (lb) 4867.0
Chiller heat rejected to ambient (MBh) 2.83
Evaporator maximum fluid flow rate (gpm) 1848.40
Evaporator pressure drop maximum flow (ft H2O) 50.91
Evaporator minimum fluid flow rate (gpm) 336.10
Evaporator pressure drop minimum flow (ft H2O) 2.10
Condenser maximum fluid flow rate (gpm) 1688.90
Condenser pressure drop maximum flow (ft H2O) 37.51
Condenser minimum fluid flow rate (gpm) 460.60
Condenser pressure drop minimum flow (ft H2O) 3.74
Compressor Weight (lb) 5418.0
Motor Weight (lb) 1732.0
Starter Weight (lb) 557.0
Suction Elbow Weight (lb) 280.0
Economizer Weight (lb) 635.0
Evaporator Weight (lb) 4025.0
Evaporator Waterboxes Weight (lb) 630.0
Condenser Weight (lb) 2454.0
Condenser Waterboxes Weight (lb) 399.0
Miscellaneous Weight (lb) 1013.0
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 6 of 25
Centrifugal Chiller
Job Information
Tag CH-2 Model Number CVHE0450
1 Quantity
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages
Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified
units may be found in the AHRI Directory at www.ahridirectory.org.
ASHRAE 90.1 - 2007 Complies
ASHRAE 90.1 - 2007 Add. M Complies
ASHRAE 90.1-2010 Complies
ASHRAE 90.1-2013 Complies
ASHRAE 90.1 - 2016 Complies
Unit Information
Compressor size 450 CVHE Model
Impeller size 230 Orifice size 400
Motor size 233 Refrigerant R-514A
60. Hz Motor frequency 460. V Motor voltage
60. Hz Incoming line frequency 460. V Incoming line voltage
Evap shell size 050S Cond shell size 050S
580 Evap bundle size Cond bundle size 500
Evap tube type TECU TECU Cond tube type
Evap tube thickness 0.025" Cond tube thickness 0.028"
Cond passes Evap passes Two pass evap water box Two pass cond water box
Design Information
300.0 tons Refrigeration capacity Refrigerant charge 550 lb
Total power 166.3 kW 17144 lb Shipping weight
0.5542 kW /ton Refrigeration Efficiency 19067 lb Operating weight
0.4937 kW /ton NPLV.IP No Free cooling option
W ye-delta starter type No Green Seal certification Unit Mounted WyeD
Application type Standard cooling 2.84 MBh Heat rejection capacity
Evaporator Information
Entering fluid evap 54.00 F Evap fluid type water
42.00 F Leaving fluid evap N/A Evap fluid concentration
Flow evap 597.1 gpm Fluid pressure drop evap 6.66 ft H2O
Min flow evap 336.1 gpm 2.10 ft H2O Fluid pressure drop evap min flow
Maximum flow evap 1848 gpm 50.9 ft H2O Fluid pressure drop evap max flow
1.990 gpm / ton Flow evap/refrigeration capacity Evap water box type non-marine
Evap fouling factor 0.000100 hr-sq ft-deg F/ Btu Evap water box pressure 150 psig
Condenser Information
85.00 F Entering fluid cond Cond fluid type water
95.00 F Leaving fluid cond N/A Cond fluid concentration
Flow cond 841.9 gpm Fluid pressure drop cond 11.1 ft H2O
Selection code revision level M0C1E111C111S00 55218 Page 1 of 2
4/14/2020
Product Version 31.8.0.0
Report Date Data generation date 4/9/2020
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 7 of 25
Centrifugal Chiller
Job Information
Tag CH-2 Model Number CVHE0450
1 Quantity
Min flow cond 460.6 gpm Minimum fluid pressure drop cond 3.74 ft H2O
Maximum flow cond 1689 gpm Maximum fluid pressure drop cond 37.5 ft H2O
Flow cond/refrigeration capacity 2.806 gpm / ton Cond water box type non-marine
Cond fouling factor 0.000250 hr-sq ft-deg F/ Btu Cond water box pressure 150 psig
Electrical Information
237.70 A Compressor motor RLA 1661 A Motor LRA
306 A Min circuit ampacity 246.4 A Primary RLA (Incoming line)
500 A 0.90 Un-corrected power factor Max overcurrent protection
Information for LEED Projects
300.0 tons Total power 166.3 kW Refrigeration capacity
Refrigerant charge 550.0 lb 0.4937 kW /ton NPLV.IP
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4) due to the R-514A refrige rant GWP
being <2.
Trane recognizes and respects the U.S. Green Building Council® mandate that a default 2% Refrigerant Leakage Rate (Lr) be used by all
manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there is no industry standard. Trane
has exhaustively documented a leak rate of less than 0.5% for CenTraVac™ chillers (models CVHE, CVHF, CVHG, CVHL, CVHS, CVHM, CDHF,
CDHG, CVHH and CDHH) and utilizes an average design refrigerant charge of less than 2 lb./ton. The overall environmental performance of the
CenTraVac chiller is verified in its product-specific Type III Environmental Product Declaration (EPD) in accordance with ISO 14025, further
demonstrating Trane’ s commitment to safeguarding the environment.
Note:
The U.S. Green Building Council’ s LEED ® green building program is the preeminent program for the design, construction, maintenance and operations of high-performance green
buildings. It provides independent, third -party verification that a building project meets the highest green building and performance measures.
Selection code revision level M0C1E111C111S00 55218 Page 2 of 2
4/14/2020
Product Version 31.8.0.0
Report Date Data generation date 4/9/2020
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 8 of 25
Mechanical Specifications - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
Compressor-Motor
Direct drive multiple-stage compressor, multi-stage capacity control guide vanes. Shrouded aluminum alloy impellers
dynamically balanced. Motor-compressor assembly balanced to .15 in./sec (.0038m/sec) maximum vibration measured
on motor and bearing housings. Refrigerant cooled, hermetically sealed, two-pole, squirrel cage induction motor. Two
pressure lubricated bearings support the rotating assembly. A direct drive submerged oil pump motor, 3/4 hp (.560 kW)
115V/50/60/1 provides filtered and temperature controlled oil to compressor bearings.
Evaporator-Condenser
Shells are carbon steel plate. Evaporator includes rupture disk per BSR/ASHRAE 15 Safety Code. Carbon steel tube
sheets are drilled, reamed and grooved to accommodate tubes. Tubes are individually replaceable externally finned
seamless copper. Tubes are mechanically expanded into tube sheets. Eliminators are installed over entire length of the
evaporator tube bundle. A multiple orifice control system maintains proper refrigerant flow. Condenser baffle prevents
direct impingement of compressor discharge gas upon the tubes. Refrigerant side of the assembled unit is tested at both
pressure(30.00 psi leak test) and vacuum. Water side is hydrostatically tested at one and one-half times design working
pressure, but not less than 225.00 psi.
Trane reserves the right to implement chiller technology enhancements that will reduce the chiller's refrigerant charge,
with no impact on chiller performance. Changes may be reflected in the chiller's nameplate refrigerant charge and the
quantity of refrigerant charge shipped to the jobsite, depending upon the final date of equipment manufacture.
Water Boxes
Drains and vents - Water boxes typically have 3/4-inch NPTI vents and drain connections provided. Evaporators have 2
vents and 2 drains, condensers have 1 vent and 1 drain. If grooved connections are offered, the design is based on
Style 77.
Non-marine water boxes have water connections that extend out from the end.
Economizer
A flash economizer with no moving parts provides power saving capability.
Purge System
The EarthWise(TM) purge includes a 1/4 hp 115V/60/1, 100V/50/1 air cooled condensing unit, purge tank, drier
elements, and a 1/20 hp (.037 kW) 115V/60/1, 110V/50/1 pump-out compressor. The purge is designed with an
activated carbon filtration system that includes an autoregeneration feature which results in automatic high-efficiency
removal of noncondensibles from the chiller without manual carbon maintenance. The purge meets Green Seal GS-31
with a leak rate less than 1.0% of the charge per year and also meets ASHRAE 147 with a leak rate of less than one unit
mass of refrigerant per unit of air.
AdaptiView Control Panel:
The Tracer(tm) AdaptiView is a microprocessor-based chiller control system that provides complete stand alone system
control and monitoring for the water cooled CenTraVac (TM). It is a factory mounted package including a full
complement of controls to safely and efficiently operate the CenTraVac chiller, including oil management, purge
operation, interface to the starter, and comprehensive motor protection including three phase solid state motor overload.
Inlet and outlet water (fluid) temperature sensors are located in the evaporator and condenser waterbox connections as
standard.
The display is a touch sensitive 12 1/8" diagonal color liquid crystal display (LCD) that uses color graphics and animation
to ensure ease of use. The touch sensitive interface allows the operator to view the chiller graphically and receive a
status indication via subsystem animations. The operator can navigate easily between the primary chiller subsystems
including: compressor, evaporator, condenser, and motor. For each subsystem, you can view status and detailed
operating parameters. In addition, alarms, reports, trending, and settings can all be accessed quickly from the main
screen. The display is mounted on a flexible "arm" that allows extensive height and viewing angle variations.
The panel supports an extensive list of languages including the default English. The data can be set to be viewed in inch
pounds IP or metric units SI. For remote starters - Class 1 control panel voltage (30-115 V) are clearly labeled in the
control panel. Class 2 input voltage (30V max) is also labeled in the control panel.
Operating Data including:
*operating hours
*number of starts
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 9 of 25
*chilled water setpoint
*evaporator and condenser water flow status
*evaporator entering and leaving water temperatures
*evaporator saturated refrigerant temperatures
*evaporator approach temperature
*evaporator refrigerant pressure
*condenser entering and leaving water temperatures
*condenser saturated refrigerant temperatures
*condenser approach temperature
*condenser refrigerant pressure
*oil differential pressure
*oil tank temperature
*purge mode
*purge average daily pump-out time
*% RLA per phase for motor
*RLA per phase
*volts per phase
*power factor
*kw
*kwh
*frequency
The AdaptiView also contains the following dedicated reports:
Evaporator, Condenser, Compressor, Motor, Purge, and ASHRAE. Each report is comprised of a detailed listing of
operational data relative to that chiller subsystem.
Control functions including:
*leaving chilled water temperature
*percent demand limit
*chiller water reset (based on return water temperature
*front panel control type
*setpoint source
*differential to start
*differential to stop
Status data including:
*waiting to start
*running
*run limit
*run inhibit (adaptive)
*auto
*free cooling (option)
*preparing to shutdown
*shutting down (post lube)
*stopped
Safeties including:
Automatic safety shutdown for:
*Low chilled water temperature,
*low evaporator refrigerant temperature
*high condenser refrigerant pressure
*evaporator and condenser flow status
*low evaporator/condenser differential refrigerant pressure
*low oil pressure
*oil pressure overdue
*high or low oil temperature
*high bearing oil temperature (requires enhanced protection option)
*high motor current
*high motor temperature
*starter function faults
*critical temperature and pressure sensor faults
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 10 of 25
The devices are of a latching trip out type requiring manual reset. Non-latching safety trip outs for operating conditions
external to the chiller automatically permits unit to resume normal operation when condition is corrected.
Advanced motor protection monitors 3-phase current to provide latching trip out protection from adverse effects of
phase loss, phase unbalance, phase reversal, loss of phase reversal protection, and electrical distribution faults
(momentary power loss) by instantaneous trip out of motor.
Surge protection - Detects surge and limits chiller loading through inlet vane modulation. Head relief through lowering
cooling tower water temperature can be requested. If not corrected within 7 minutes, chiller is shut down.
Enhanced Adaptive Control(TM) - Built in intelligence to keep the chiller on line (safely making maximum tons) while
simultaneously preventing chiller damage/failure. During any chiller limiting mode of operation, the control panel
enunciates the condition via a relay output.
Trending:
The controller provides 10 standard graphs for trending multiple parameters, The operator can add an additional 6
custom graphs if desired. On any one custom graph, the operator can choose to trend up to 10 unique parameters from
a more comprehensive list. Two Y axes are available for any graph to facilitate readability.
Diagnostics:
AdaptiView includes comprehensive diagnostic monitoring. All active diagnostics are available, and up to 20 historic
diagnostics are communicated to the operator via the 12 1/8" LCD display with graphic navigation system. Each
diagnostic is time and date stamped.
Service Tool:
A PC-based service tool called Tracer TU, connected to the chiller via USB port, is available for additional cost and
displays the last 100 diagnostics, indicating the time, date of occurrence, and system parameters at the time of the
diagnostic. The service tool provides advanced troubleshooting and access to sophisticated configuration settings not
needed during operation of the chiller.
Security:
The AdaptiView can be set to prevent unauthorized access to the chiller settings. The operator can choose to secure the
operating settings with a password. Data and reports can still be accessed once the settings are locked out.
The memory for the AdaptiView is non-volatile type, so if power is lost, operating settings are retained. A life time battery
is standard, which is used only to support the clock function for the chiller.
Chilled and Condenser water pump relays:
Chilled water and condenser water pump relays are provided and it is recommended that they be used for pump control.
Hardwire BAS Interface provides:
Chilled Water Setpoint input - Provides for setpoint adjustment of control point from multiple sources
Current Limit Setpoint input - provides for setpoint adjustment of control point from multiple sources
Percent RLA Output - provides % RLA output
Condenser Pressure Output - A hardwire output signal of condenser pressure, or differential pressure between the
evaporator and condenser is provided.
Operating Status:
The following hardwire binary outputs are available:
Compressor running relay
Alarm relay - manual reset
Alarm relay - auto reset
Limit warning relay
Purge alarm relay
Head relief request relay
Maximum capacity relay
Evaporator Proof of Flow - Thermal Dispersion
A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion
controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the
ship with components box. Follow the installation instructions in the chiller installation manual. Reference specific IFM
Installation manual (PART-SVN223*-EN) notes shipped with your rupture guard /contact local Trane sales office
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 11 of 25
Condenser Proof of Flow - Thermal Dispersion
A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion
controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the
ship with components box. Follow the installation instructions in the chiller installation manual. Reference specific IFM
Installation manual (PART-SVN223*-EN) notes shipped with your rupture guard /contact local Trane sales office
Paint
All CenTraVac(TM) painted surfaces are coated with a primer and an air-dry beige primer-finisher prior to shipment.
Isolation
All units ship with neoprene isolator pads as standard, except when spring isolators are chosen. Enough pads are
provided to cover the area under the chiller supports.
Shipment
All units are of hermetic design, leak tested, charged to 5.00 psi and shipped as a single factory assembled package.
Full oil charge shipped in oil sump. Refrigerant shipped to jobsite from refrigerant manufacturer. The entire chiller is
shrink wrapped for protection.
Unit Mounted Starter
Wye Delta-Reduced Voltage, NEMA 1A (vented) enclosure with a gasket. Starter factory mounted and completely
prewired to compressor motor and control panel. Factory run testing assures proper circuitry and operational reliability.
The Wye Delta starter is a reduced voltage starter and therefore draws ~ 33% of locked rotor amps (LRA), and the motor
acceleration time is 5-12 seconds typically.
The starter is designed and tested in accordance with UL 1995
Features include:
115 volt control power transformer to power chiller unit controller, purge and oil system. Therefore, with line power, no
other power is needed for auxiliary equipment on the chiller.
Environmental specification: Operation from sea level to 6000 ft (1829 m). Operating ambient temperature range 32.0 F
to 104.0 F. Non-operating ambient temperature range -40.0 F to 158.0 F. Relative humidity, non-condensing 5% to 95%
through the ambient temperature range. Voltage utilization ±10 %
Top of starter includes access area for a wiring entrance area. Bottom entry for line power is not available.
Terminal block connection is standard. Circuit breakers may be included as an option. See the following submittal
pages for disconnect ratings and lug information on these optional disconnects if offered.
Starter installer responsibilities
The following are considered functions normally required of the equipment installer for unit mounted starters.
Remove access area panel for line side wiring. The upper right quadrant of the starter provides recommended access to
starter/disconnect lugs. The starter can accommodate top line power entry only.
Provide and install field wiring to line side lugs of starter.
Required Installer Responsibilities
The following are considered functions normally required of the equipment installer./n
Install unit on a foundation with flat support surfaces level within 1/16" and of sufficient length to support concentrated
loading. (Spring isolators should be considered whenever chiller installation is planned for an upper story location.)
Place isolation pads or optional spring type isolators provided by the chiller manufacturer under the unit. When spring
isolators are chosen, no pads are provided.
Install unit per applicable Trane Installation Manual.
Complete all water and electrical connections.
Where specified, provide and install valves in water piping upstream and downstream of the evaporator and condenser
water boxes as means of isolating shells for maintenance and to balance and trim system.
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 12 of 25
Furnish and install a flow switch with timer or equivalent device in both the chilled water and condenser water piping
properly interlocked to insure that unit can operate only when water flow is established.
Furnish and install taps for thermometers and pressure gauges in water piping adjacent to inlet and outlet connections
of both evaporator and condenser.
Furnish and install drain valves to each water box.
Install vent cocks on each water box.
Furnish and install strainers upstream of chiller evaporator and condenser bundles to protect tubes from potential
damage caused by debris in the circulating water. Note: Failure to install strainers in all water piping entering the chiller
could result in tube plugging conditions that could damage unit components. If the circulating pumps are immediately
upstream of the chiller bundles, then the strainer can be installed immediately ahead of the pumps. If the circulating
pumps are downstream of the chiller bundles, then the strainers should be installed immediately ahead of the chiller
bundles.
Furnish sufficient refrigerant 25.0 lb per machine and dry nitrogen 50.0 lb per machine for pressure testing under
manufacturer's supervision.
Start-up unit under supervision of a qualified Trane field engineer.
Where specified, insulate evaporator and any other portions of machine required to prevent sweating under normal
operating conditions.
Water connection piping must not transfer forces to the chiller. Because of cumulative tolerances in manufacture and
field installation, prepiping of water connections closer than 36" is not recommended. Any problems associated with
prepiping of water connections closer than 36" to the chiller are the responsibility of the installing contractor.
Furnish and install vent lines for rupture disk and purge venting to atmosphere per ASHRAE 15 and unit installation
manual. If RuptureGuard-Relief Valve option is ordered, remove factory rupture disk and install RuptureGuard-Relief
Valve per the IOM manual. In some chiller configurations the RuptureGuard may not bolt directly to the chiller flange.
Locally sourced and approved piping may be required between the chiller and the RuptureGuard.
Field Disassembly
With chillers that may require field disassembly (for example due to clearance concerns during unit installation)
reference the Disassembly and Reassembly manual and your Trane Sales representative prior to the order being
placed. Caution: if certain components are removed in the field, for example the economizer, the necessary
components (gaskets, seals, etc.) are not provided as standard.
Leak-Tight Warranty
The CenTraVac chiller features a 5-year limited Leak-Tight Warranty which is valid for the lesser of 60 months from
initial start-up or 66 months from date of shipment. The limited Leak-Tight Warranty covers models CVHE/F/L, CVHS,
CVHM and CDHF chillers installed in the United States or Canada. The Company's obligations and liabilities under this
warranty are limited to furnishing replacement refrigerant; no other parts or labor are covered under this limited
warranty. No liability whatever shall attach to the Company until appropriate actions have been taken (acceptable to
Company) to eliminate the source of the leak, and then said liability shall be limited to furnishing the replacement
refrigerant.
If the chiller is placed under a comprehensive Trane service and maintenance agreement (Trane Select Agreement or
better) prior to the expiration of the standard Leak-Tight Warranty, the protection against refrigerant loss shall continue
under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without
interruption.
If a 10-Year Parts, Labor and Refrigerant Warranty was purchased for the chiller and the chiller is placed under a Trane
Select Agreement (or better) prior to the expiration of the 10-Year Parts, Labor and Refrigerant Warranty, the protection
against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select
Agreement remains in effect without interruption
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 13 of 25
Unit Dimensions - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2".COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.EVAPORATORCOOLING COND8"8"VICTAULICVICTAULICIN REAR OUT FRONTIN BOTTOM OUT TOPCUSTOMER NOTES:FLOW DIRECTIONCONN TYPECONN DIASHELL TYPETOP VIEWLEFT SIDE VIEWFRONT VIEWRIGHT SIDE VIEWGRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 14 of 25
Unit Dimensions - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
7 3/4"25 3/16"61 5/8"1 5/8"135 7/8"UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2".COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.EVAPORATORCOOLING COND8"8"VICTAULICVICTAULIC Unit MountedWye-delta StarterPurge IN REAR OUT FRONTIN BOTTOM OUT TOPCVHE 450 Nominal tons500 Ton short shell evap.500 Ton short shell cond.Without additional condenserCUSTOMER NOTES:TOP VIEWEvaporatorCondenserEconomizerCompressorFLOW DIRECTIONCONN TYPECONN DIASHELL TYPEAdaptiView Control Paneltouch screen is field installed(See accessory drawing for details)RuptureDisk 3" NPTGRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 15 of 25
Unit Dimensions - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
20 3/4"96 5/8"7 15/16"10 1/2"7 5/16"12 3/4"135"UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2".COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.EVAPORATORCOOLING COND8"8"VICTAULICVICTAULICIN REAR OUT FRONTIN BOTTOM OUT TOPCVHE 450 Nominal tons500 Ton short shell evap.500 Ton short shell cond.Without additional condenserCUSTOMER NOTES:FRONT VIEWFLOW DIRECTIONCONN TYPECONN DIASHELL TYPEGRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 16 of 25
Unit Dimensions - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
44 1/2"30"15 3/8"45 1/4"44 13/16"48 1/4"27 5/8"8 7/8"62"21 1/2"UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2".COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.EVAPORATORCOOLING COND8"8"VICTAULICVICTAULICIN REAR OUT FRONTIN BOTTOM OUT TOPCVHE 450 Nominal tons500 Ton short shell evap.500 Ton short shell cond.Without additional condenserCUSTOMER NOTES:LEFT SIDE VIEWFLOW DIRECTIONCONN TYPECONN DIASHELL TYPEGRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 17 of 25
Unit Dimensions - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
98 11/16"16 1/8"78"14 1/2"17 3/8"UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2".COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.EVAPORATORCOOLING COND8"8"VICTAULICVICTAULICIN REAR OUT FRONTIN BOTTOM OUT TOPCVHE 450 Nominal tons500 Ton short shell evap.500 Ton short shell cond.Without additional condenserCUSTOMER NOTES:RIGHT SIDE VIEWFLOW DIRECTIONCONN TYPECONN DIASHELL TYPEGRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 18 of 25
Weight, Clearance & Rigging Diagram - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
WEIGHTS AND CENTER OF GRAVITY
LEFT FRONT
LEFT REAR
RIGHT FRONT
RIGHT REAR
LEFT MIDDLE
RIGHT MIDDLE
LOCATION ISOLATOR LOAD*VENDOR P/N TRANE P/N ISOLATOR COLOR
SHIPPING OPERATING
SPRING ISOLATOR SELECTION
WEIGHTS
19067.0 lb17144.0 lb
4599.0 lb
3621.0 lb
4867.0 lb
5980.0 lb
N/A
N/A
UNIT CENTER OF GRAVITY
CG X (DIMENSION FROM FRONT TO REAR)
CG Y (HEIGHT DIMENSION FROM FLOOR)
CG Z (DIMENSION FROM RIGHT TO LEFT)
RIGHT FRONT ISOLATOR MOUNTING HOLE
X
Y
Z
COMPONENT WEIGHT*
NAMEPLATE PRODUCT DESCRIPTION:
COMPRESSOR WEIGHT
MOTOR WEIGHT
STARTER WEIGHT
SUCTION ELBOW WEIGHT
ECONOMIZER WEIGHT
EVAPORATOR WEIGHT
EVAPORATOR WATERBOXES WEIGHT
CONDENSER WEIGHT
CONDENSER WATERBOXES WEIGHT
HEAT RECOVERY CONDENSER WEIGHT
HEAT RECOVERY CONDENSER WATERBOXES WEIGHT
AUXILIARY CONDENSER WEIGHT
AUXILIARY CONDENSER WATERBOXES WEIGHT
MISCELLANEOUS WEIGHT
57.000 in
28.000 in
45.000 in
CVHE
TECU
500
460
TECU 233
050S
450
228
580
050S
MODL
EVTM
CDBS
VOLT
CDTM CPKW
EVSZ
ORSZ
NTON
CPIM
EVBS
CDSZ400
PTON 300.00 tons
BOTTOM OF THIS HOLE IS 0,0,0 POINT
FOR CENTER OF GRAVITY DIMENSIONS
5418.0 lb
1732.0 lb
557.0 lb
280.0 lb
635.0 lb
4025.0 lb
630.0 lb
2454.0 lb
399.0 lb
N/A
N/A
N/A
N/A
1013.0 lb
*ALL PUBLISHED WEIGHTS ACCURATE TO +/- 10 %
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 19 of 25
Weight, Clearance & Rigging Diagram - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
DIMENSION INCLUDES TUBESHEETS
FRONT OF UNIT
SEE HOLE DETAIL
REFERENCED TUBE PULL IS GOOD FOR
BOTH EVAPORATOR AND CONDENSER
TUBE PULL CLEARANCE DIMENSION TO
RIGHT HAND TUBE PULL SHOWN, APPLY
LEFT END FOR LEFT HAND TUBE PULL.
CLEARANCE SPACE
DIMENSION INCLUDES TUBESHEETS
FRONT OF UNIT
SEE HOLE DETAIL
REFERENCED TUBE PULL IS GOOD FOR
BOTH EVAPORATOR AND CONDENSER
TUBE PULL CLEARANCE DIMENSION TO
RIGHT HAND TUBE PULL SHOWN, APPLY
LEFT END FOR LEFT HAND TUBE PULL.
CLEARANCE SPACE
HOLE DETAIL TYP
2" TYP
(51mm)
1 3/16" TYP (30mm)
EVAPORATOR
TUBESHEET
2 5/8" TYP (67mm)
5" TYP (127mm)
135"
62"
141"
34 1/4"
44 1/2"
320 1/2"
4
MAXIMUM OPERATING
MAXIMUM SHIPPING
FOLLOW NEC SECTION 110 AND OTHER APPLICABLE LOCAL CODES
FOR CLEARANCES IN FRONT OF ELECTRICAL ENCLOSURES.
7
1. HEAVY OBJECTS!
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS SHOWN. EACH OF
THE CABLES (CHAINS OR SLINGS) USED TO LIFT THE UNIT MUST BE
CAPABLE OF SUPPORTING THE ENTIRE WEIGHT OF THE UNIT. LIFTING
CABLES (CHAINS OR SLINGS) MAY NOT BE OF THE SAME LENGTH. ADJUST
AS NECESSARY FOR EVEN UNIT LIFT. OTHER LIFTING ARRANGEMENTS
MAY CAUSE EQUIPMENT OR PROPERTY-ONLY DAMAGE. FAILURE TO
PROPERLY LIFT UNIT MAY RESULT IN DEATH OR SERIOUS INJURY.
SEE DETAILS BELOW.
2. IMPROPER UNIT LIFT!
TEST LIFT UNIT APPROXIMATELY 24 INCHES TO VERIFY PROPER CENTER
OF GRAVITY LIFT POINT. TO AVOID DROPPING OF UNIT, REPOSITION LIFTING
POINT IF UNIT IS NOT LEVEL. FAILURE TO PROPERLY LIFT UNIT COULD
RESULT IN DEATH OR SERIOUS INJURY OR POSSIBLE EQUIPMENT OR
PROPERTY-ONLY DAMAGE.
3. ATTACH SAFETY CHAIN OR CABLE AS SHOWN WITHOUT TENSION, NOT AS
A LIFTING CHAIN OR CABLE, BUT TO PREVENT THE UNIT FROM ROLLING.
4. DO NOT FORKLIFT THE UNIT TO MOVE OR LIFT.
5. LIFTING HOLES PROVIDED ON CHILLER TO ATTACH CABLES (CHAINS OR SLINGS).
6. 36" (900 MM) RECOMMENDED CLEARANCE ABOVE HIGHEST POINT OF COMPRESSOR.
OR CABLES
SAFETY CHAINS
8. SPECIFIC SHIPPING AND OPERATING WEIGHTS OF THE SUBMITTED
CHILLER ARE PROVIDED IF THE CENTRIFUGAL CHILLER SELECTION
WAS ENTERED IN TOPSS. DETAILED LOAD POINT AND SPRING
ISOLATOR APPLICATION WEIGHTS ARE AVAILABLE FROM "CENTRAVAC
ISOLATOR SELECTION REPORT" AVAILABLE FROM THE REPORT GENERATOR
OF THE TRANE TOPSS CHILLER SELECTION PROGRAM. CONTACT
YOUR LOCAL TRANE SALES ENGINEER IF THIS DATA IS REQUIRED.
(SEE NOTE 8 ABOVE)
17144.0 lb
19067.0 lb
X .88 (22mm)
DIA HOLES FOR
ANCHORING UNIT
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 20 of 25
Accessory - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
7 1/2"
16"
20"
6 5/8"
7/8" DIA HOLE
1 1/8" DIA HOLE
26 1/8"
32 3/4"
6 HOLES FOR CONTROL WIRING CONDUITS
6 3/4"
5 XTYPICAL HOME
POSITION
REF-BOTTOM FRONT
OF PANEL DOOR
NOTE: DISPLAY CAN MOVE TO AN
INFINITE NUMBER OF POSITIONS.
TOP VIEW
AVAILABLE
LOWEST POSITION
ADAPTIVIEW CONTROL PANEL
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 21 of 25
Accessory - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
MAX DOOR SWING
145° & 38 1/4" [972mm]
MAX D OOR SWING145° & 38 1/4" [972mm]
60"
33 3/8"
38"MAX D OOR SW
ING145°
&
38
1/4"
[972mm
]
16 5/16"13 7/16"
6 5/16"
29 7/16"
ELECTRICAL ENTRANCE 7" x 14" TOP
ALLOW MIN. FRONT WORKING SPACE CLEARANCE PER NEC ARTICLE 110
REQUIREMENTS FOR ELECTRICAL
INSTALLATIONS.
CBIC = CIRCUIT BREAKER HIGH INTERRUPT CAPACITY
4DP 296 65,000 65,000 (2) 2/0-250 OR (1) 2/0-500
WYE-DELTA STARTERS
CBIC 25"
POWER FACTOR CORRECTION CAPACITORS, WHEN SELECTED, ARE NOT
INCLUDED IN THE UL SHORT CIRCUIT RATING OF THE STARTER.
DOOR SWINGS TO THE LEFT FOR A MAX OF 145 DEGREES & 38 1/4"
UNIT MOUNTED WYE-DELTA STARTER
THE NON-FUSED DISCONNECT OR CIRCUIT BREAKER IS DESIGNED FOR USE AS A SERVICE DISCONNECT ONLY.
TOP
FRONT
CONNECTION
PANEL
AIC AMPS
BREAKERSIZE
MAX
CONN RATINGS (RMS SYMETRICAL AMPS)
SHORT CIRCUIT CURRENT LINE CONNECTION LUGS
LENGTH
INTERNAL WIRE
VIEW
ELEVATION
RLA
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 22 of 25
Field Wiring - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
CONDENSER REFRIGERENT PRESSURE OUTPUT
PERCENT RLA COMPRESSOR OUTPUT
EXTERNAL CURRENT LIMIT SETPOINT
EXTERNAL CHILLED WATER SETPOINT
CHILLED WATER RESET INPUT OR
2-10V OUTPUT (2 WIRES)
2-10V INPUT (2 WIRES)9
1010
10
10
9
9
8
8
8
8
8
8
8
PURGE REMOTE ALARM
MAXIMUM CAPACITY RELAY
REMOTE ALARM RELAY (LATCHING)
HEAD RELIEF REQUEST RELAY
LIMIT WARNING INDICATOR
COMPRESSOR RUNNING RELAY
REMOTE ALARM RELAY (NON-LATCHING)
REQUIRED. CONTACTS ARE NO/NC RATINGS - 2.88 INDUCTIVE 1/3 H.P.(.25 kW) AT 115 VAC.
2 OR 3 WIRES(N.O. &/OR N.C.), 115 VAC CIRCUIT, SEPARATE 115 VAC POWER SUPPLY IS8
MOUNTED
(SEE NAMEPLATE)
STARTER
UNIT
VOLTAGE
LINE
TRACER OR OTHER TRANE REMOTE
DEVICE (COMMUNICATIONS INTERFACE)
SHIELDED PAIR. 30 VOLT OR LESS CIRCUIT. MAX
LENGTH 1500 FT. BELDON TYPE 8760 RECOMMENDED. (2 WIRES)
12
12
LOW VOLTAGE (30V MAX)
DO NOT RUN WITH HIGHER
VOLTAGE CIRCUITS
ARE N.O. CONTACT RATING - 2.88 INDUCTIVE 1/3 H.P.(.25 kW) AT 115 VAC OPTIONAL.
2 WIRES, 115 VAC CIRCUIT, SEPARATE POWER SUPPLY IS REQUIRED. MINIMUM
CONTACT RATING AT 115 VAC - 2.88 INDUCTIVE 1/3 H.P.(.25 kW) AT 115 VAC REQUIRED.
2 WIRES, 115 VAC CIRCUIT, SEPARATE POWER SUPPLY IS REQUIRED. CONTACTS
ALL CUSTOMER CONTROL CIRCUIT WIRING MUST HAVE A MINIMUM RATING OF 150 VOLTS.
EVAPORATOR AND CONDENSER FLOW SWITCHES ARE REQUIRED. THEY MUST BE
INSTALLED AND WIRED TO THE TRANE PANEL BY THE INSTALLING CONTRACTOR.
CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURES HAVE BEEN COMPLETED.
* CONNECTION DIAGRAMS ARE AVAILABLE AT THE WEBPAGE SHOWN IN THE MECHANICAL SPECIFICATIONS SECTION OF THIS SUBMITTAL.
DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY OTHERS. CHECK SALES ORDER TO DETERMINE IF WIRING IS REQUIRED FOR SPECIFIC OPTIONS.
THE UNIT CONTROL PANEL (ADAPTIVIEW) SUPPLIES A CONTACT
SHOWN BELOW. MAXIMUM FUSE SIZE PER DEVICE - 15 AMPS.
OUTPUT TO CONTROL THE CUSTOMER SUPPLIED DEVICES
CHILLED WATER PUMP STARTER
CONDENSER WATER PUMP STARTER
CHILLED
WATER PUMP
PUMP
WATER
COND
COND
6
7
PURCHASE OF SWITCHES FROM TRANE IS OPTIONAL.
1.
2.
REQUIRED
5.
3.
6
7
NOTES:
EMERGENCY STOP NORMAL/TRIP (CONTACT)
EXTERNAL AUTO/STOP (CONTACT)
115 VOLTS
CONTROL VOLTAGE
FRONT ELEVATION
EVAP
PANEL
CONTROL
LEAVING
CONDENSER
WATER
LEAVING
CHILLED
WATER
REMOTE DISCONNECTS AND FOLLOW LOCK OUT
FAILURE TO DO THE ABOVE BEFORE SERVICING
COULD RESULT IN DEATH OR SERIOUS INJURY.
HAZARDOUS VOLTAGE!
AND TAG PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR CAPACITORS HAVE
DISCHARGED STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
DISCONNECT ALL ELECTRIC POWER INCLUDING
WARNING
DAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CAUTION
FAILURE TO DO SO MAY CAUSE
OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
COUNTRIES APPLICABLE NATIONAL AND/OR LOCAL REQUIREMENTS SHALL APPLY.
(NEC), STATE AND LOCAL REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER
ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE4.
5-LEAD JACKETED CABLE
DETECTION SENSORS
REQUIRED COND WATER FLOW
5-LEAD JACKETED CABLE
DETECTION SENSORS
OPTIONAL EVAP WATER FLOW
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 23 of 25
Field Wiring - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
(SEE UNIT NAMEPLATE)
LINE VOLTAGE
CUSTOMER SUPPLIED
L1GND L3L2
L1G L2 L3
2Q1 OR 2S1 DISCONNECT
OR 2X3 TERMINAL BLOCK
PUMP MOTOR; 1PH 3/4 HP, 11.7 FULL LOAD AMPS AT 115VAC. 14 AWG MAX WIRE SIZE.
TWISTED, SHIELDED PAIR, 30VDC, MAX LENGTH 1500 FT
24VDC, 12MA RESISTIVE LOAD, 14 AWG MAX WIRE SIZE
(BELDEN TYPE 8760 RECOMMENDED)
CIRCUIT PROTECTED AT 20A, 115VAC 1PH, 10 AWG MAX WIRE SIZE
CONTACT RATING; 2.88A INDUCTIVE, 1/3 HP, 0.25KW AT 115VAC. 14 AWG MAX WIRE SIZE.
* TAPPED CONTROL CONDUCTORS
5S1*, 5S2*, 3B* AND 4B*
5S3 THRU 5S8
WB4
ALL REMAINING LLID TERMINALS
9A* AND 10A*
1A*
SUPPLY AND MOTOR LEADS
WIRE NO OR DEVICE
4000VA AT 115VAC, 8 AWG MAX WIRE SIZE
SEE NAMEPLATE; MINIMUM CIRCUIT AMPACITY
FIELD WIRING CIRCUIT SELECTION INFORMATION
AND START-UP PROCEDURES HAVE BEEN COMPLETED.
DO NOT ROUTE LOW VOLTAGE (30V) WITH CONTROL VOLTAGE (115V) AND DO NOT POWER UNIT UNTIL CHECK-OUT
DASHED LINES INDICATE FIELD WIRING BY OTHERS. WIRE NUMBERS SHOWN ARE RECOMMENDED BY TRANE.
2.
1.
NOTES:
2A* AND GRN/YEL 4000VA AT 115VAC, 8 AWG MAX WIRE SIZE (WITHOUT OPTIONAL CPTR)
2A* AND GRN/YEL CIRCUIT PROTECTED AT 20A, 115VAC 1PH, 10 AWG MAX WIRE SIZE (WITH OPTIONAL CPTR)
DEVICE PREFIX CODE
= MAIN UNIT CONTROL PANEL DEVICE
= REMOTE MOUNTED DEVICE
= UNIT MOUNTED DEVICE
1
2
4
= CUSTOMER PROVIDED DEVICE5
AND TAG PROCEDURES BEFORE SERVICING.
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
FAILURE TO DO THE ABOVE BEFORE SERVICING
COULD RESULT IN DEATH OR SERIOUS INJURY.
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
VARIABLE SPEED DRIVE, REFER TO DRIVE
DISCHARGED STORED VOLTAGE. UNITS WITH
INSURE THAT ALL MOTOR CAPACITORS HAVE
USE COPPER CONDUCTORS ONLY!
CAUTION
HAZARDOUS VOLTAGE!
REMOTE DISCONNECTS AND FOLLOW LOCK OUT
DISCONNECT ALL ELECTRIC POWER INCLUDING
WARNING
TRANE SUPPLIED
UNIT MOUNTED
LOW VOLTAGE
WYE-DELTA
STARTER PANEL
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 24 of 25
Field Wiring - Centrifugal Water Chiller
Item: A1 Qty: 1 Tag(s): CVHE450
NH
5K1
5K2
1A5 J2-6
1A5 J2-3
1A5 J2-4
1A5 J2-1
EVAPORATOR WATER
CONDENSER WATER
1A13 J2-1
1A13 J2-2
1A13 J2-3
1A13 J2-4
5S3
5S4
EXTERNAL AUTO STOP
(REMOVE JUMPER 1W2 IF USED)1W2
1W3EMERGENCY STOP
(REMOVE JUMPER 1W3 IF USED)
PUMP RELAY OPTIONAL
PUMP RELAY REQUIRED
GND
GRN/YEL
115VAC 15A
CUSTOMER PROVIDED POWER
MAIN UNIT CONTROL PANEL
TERMINAL CONNECTIONS
1X1-G
EN1
WB16
FACTORY CONNECTED
IN CONTROL PANEL
1A22
ETHERNET
1A2-J4
POWER
CUSTOMER TO CONNECT
ETHERNET AND POWER CABLES TO
4A2 ADAPTIVIEW DISPLAY MONITOR
(DEFAULT)
OPTIONAL
OPTIONAL
OPTIONAL
1A9 J2-1
1A9 J2-4
1A9 J2-3
1A9 J2-6
1A8 J2-10
1A8 J2-12
1A8 J2-6
1A8 J2-4
1A5 J2-12
CHILLER MAXIMUM
CAPACITY
CHILLER RUNNING
CHILLER HEAD
RELIEF REQUEST
5H10
OPTIONAL
5H11
CHILLER LIMIT
WARNING
INDICATOR
5H7
OPTIONAL
5H6
OPTIONAL
(ALTERNATE)
TO ANY ALTERNATE ALARM OR STATUS
DEFAULT OUTPUTS MAY BE REPROGRAMMED
CHILLER ALARM INDICATOR
1A9 J2-9
1A9 J2-7
1A8 J2-1
1A8 J2-7
1A8 J2-9
1A8 J2-3
OPTIONAL
5H15
CHILLER MAR
CHILLER MMR
PURGE ALARM
(LATCHING)
ALARM INDICATOR
(DEFAULT)
5H2
OPTIONAL
5H4
5H1
OUTPUT LISTED BELOW
(NON-LATCHING)
INDICATOR
ALARM INDICATOR
(DEFAULT)
(DEFAULT)
INDICATOR
(DEFAULT)
INDICATOR
(DEFAULT)
INDICATOR
(DEFAULT)
CONDENSER REFRIGERANT PRESSURE
OR EVAPORATOR/CONDENSER
DIFFERENTIAL PRESSURE OUTPUT
CURRENT LIMIT SETPOINT
EXTERNAL CHILLED
2-10VDC OR 4-20MA
2-10VDC EXTERNAL
1A16 J2-3
1A16 J2-6
1A16 J2-5
1A15 J2-6
1A16 J2-2
%%% RLA COMPRESSOR OUTPUT
2-10VDC
2-10VDC
(GENERIC BAS)1A15 J2-3
1A15 J2-4
1A15 J2-1
WATER SETPOINTAND TAG PROCEDURES BEFORE SERVICING.
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
FAILURE TO DO THE ABOVE BEFORE SERVICING
COULD RESULT IN DEATH OR SERIOUS INJURY.
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
VARIABLE SPEED DRIVE, REFER TO DRIVE
DISCHARGED STORED VOLTAGE. UNITS WITH
INSURE THAT ALL MOTOR CAPACITORS HAVE
USE COPPER CONDUCTORS ONLY!
CAUTION
HAZARDOUS VOLTAGE!
REMOTE DISCONNECTS AND FOLLOW LOCK OUT
DISCONNECT ALL ELECTRIC POWER INCLUDING
WARNING
1K26-4
1X1-5
PUMP INTERLOCK
EVAPORATOR WATER
OPTIONAL
AUX
5S13
4
BY CUSTOMER
TO BE INSTALLED
4R17
EVAPORATORGRY
BLK
BRN
BLU
WHT
WB11
DETECTION SENSORWATER FLOW4R172
3
1
5
GRY
BLK
BRN
BLU
WHT1K26-17
1K26-18
1K26-19
1K26-20
1K26-21
4
1K27-4
1X1-6
PUMP INTERLOCK
CONDENSER WATER
REQUIRED
AUX
5S14
1K27-21
1K27-20
1K27-19
1K27-18
1K27-17 WHT
BLU
BRN
BLK
GRY
5
4
1
3
2 4R18
WATER FLOWDETECTION SENSORWB12
WHT
BLU
BRN
BLK
GRY CONDENSER4R18
TO BE INSTALLED
BY CUSTOMER
4
58A 5W
59A 5T
1K26 EVAPORATOR AND/OR 1K27
CONDENSER WATER FLOW
DETECTION CONTROLLERS: ALL
COMPONENTS ARE SUPPLIED BY
TRANE. THE CONTROLLERS ARE
FACTORY INSALLED IN THE MAIN
UNIT CONTROL PANEL. 4R17
EVAPORATOR AND/OR 4R18
CONDENSER WATER FLOW
DETECTION SENSORS ARE
CUSTOMER INSTALLED AND WIRED
TO THE CONTROLLERS WITH
SUPPLIED WB11 AND/OR WB12
JACKETED CABLES. THE USE OF
SEPARATE WATER PUMP CONTROL
RELAYS WITH AUX INTERLOCK
CONTACTS WIRED AS SHOWN ARE
REQUIRED.
4
ETHERNET 1
1A27EN2
BACNET OVER ETHERNET
4
4
SLC - Rock Road Jail Chiller Repl March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 25 of 25
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
material for the job.
Product Family - Centrifugal Water Chiller
Item Tag(s) Qty Description Model Number
A1 CVHE450 1 Centrifugal Chiller ( CTV ) CVHE0450
Field Installed Option Description Part/Ordering Number
Thermal dispersion flow switch (IFM) - Field Installed
Thermal dispersion flow switch (IFM) - Field Installed