HomeMy WebLinkAboutSnapNrack System ManualHE structural ENGINEERS April 12, 2018 SnapNrack 775 Fiero Lane, Ste. 200 San Luis Obispo, CA 93401 TEL: (877) 732-2860 Attn.: SnapNrack - Engineering Department Subject: Report # 2017-03227.03 — Engineering Certification and Span Tables for the SnapNrack Ultra Rail Flush -Mount Solar Photovoltaic Racking System PZSE, Inc. —Structural Engineers has reviewed the SnapNrack Ultra Rail Flush -Mount Racking System, a proprietary mounting system intended for rooftop installation of solar photovoltaic (PV) panels, and has provided the attached span tables. This review included the complete system including the 6005-T5 aluminum rail, attachment devices, splice elements, and PV Panels. All information, data, and analysis contained within are based on, and comply with, the following building codes and typical specifications: Building Codes: 1. ASCE/SEI 7-10, Minimum Design Loads for Buildings and Other Structures, by American Society of Civil Engineers 2. 2015 International Building Code, by International Code Council, Inc. 3. 2015 International Residential Code, by International Code Council, Inc. 4. AC428, Acceptance Criteria for Modular Framing Systems Used to Support Photovoltaic (PV) Panels, November 1, 2012 by [CC -ES 5. Aluminum Design Manual 2015, by The Aluminum Association, Inc. 6. ANSI/AWC NDS-2015, National Design Specification for Wood Construction, by the American Wood Council Design Criteria: Risk Category II; Seismic Design Category = A- E Wind Loads: Basic Wind Speed (ultimate) per ASCE 7-10 = 110 mph to 190 mph. Includes roof pitches from 0° to 90% up to 60 feet mean roof height, and exposure categories B, C, & D. Parapets, roof overhangs, and topographic wind speed adjustment have not been considered. See Appendix A for conversion to Service -level wind speeds per ASCE 7-05. Snow Loads: Ground Snow Load = 0 to 120 (psf). Spans are based on the sloped roof snow load (Ps) corresponding to each ground snow load. See Appendix B to adjust span tables for non -reducible snow loads. PV Modules: All solar PV modules with metal frames. Modules up to 5'-6" long (66 inches long) are referred to as "60-Cell", and modules up to 6'-6" long (78 inches long) are referred to as "72-Cell". Length is measured perpendicular to the rail, regardless of panel orientation. If you have any questions on the above, do not hesitate to call. Prepared by: PZSE, Inc. —Structural Engineers Roseville, CA 8150 Sierra College Boulevard, Suite 150, Roseville, CA 95661 T 916.961.3960 F 916.961.3965 W www.pzse.com 1/106 Experience I Integrity I Empowerment HE tNGINERS E Table of Contents Item.................................................................................................................................................... Page # Description and Limitations of the Ultra Rail Flush -Mount System........................................................................................3 Span Tables for Ultra Rail Flush -Mount, 60-Cell Modules with Attachment Bin 1 ................................................................. 6 Span Tables for Ultra Rail Flush -Mount, 60-Cell Modules with Attachment Bin 2 ...............................................................12 Span Tables for Ultra Rail Flush -Mount, 60-Cell Modules with Attachment Bin 3 ...............................................................18 Span Tables for Ultra Rail Flush -Mount, 60-Cell Modules with Attachment Bin 4 ...............................................................24 Span Tables for Ultra Rail Flush -Mount, 60-Cell Modules with Attachment Bin 5 ...............................................................30 Span Tables for Ultra Rail Flush -Mount, 60-Cell Modules with Attachment Bin 6 ...............................................................36 Span Tables for Ultra Rail Flush -Mount, 72-Cell Modules with Attachment Bin 1 ...............................................................42 Span Tables for Ultra Rail Flush -Mount, 72-Cell Modules with Attachment Bin 2 ...............................................................48 Span Tables for Ultra Rail Flush -Mount, 72-Cell Modules with Attachment Bin 3 ...............................................................54 Span Tables for Ultra Rail Flush -Mount, 72-Cell Modules with Attachment Bin 4 ...............................................................60 Span Tables for Ultra Rail Flush -Mount, 72-Cell Modules with Attachment Bin 5 ...............................................................66 Span Tables for Ultra Rail Flush -Mount, 72-Cell Modules with Attachment Bin 6 ...............................................................72 Appendix A: ASCE 7-10 to ASCE 7-05 Wind Conversion.......................................................................................................78 Appendix B: Snow Load Conversion.....................................................................................................................................79 AppendixC: Structural Details..............................................................................................................................................80 8150 Sierra College Boulevard, Suite 150, Roseville, CA 95661 T 916.961.3960 F 916.961.3965 w www.pzse.com 2/106 Experience I Integrity I Empowerment He structural ENGINEERS Flush -Mount System Geometry Limitations: Flush -Mounted PV modules are designed per the Components and Cladding provisions of ASCE 7. Flush -Mounted PV modules shall be oriented parallel to the plane of the roof surface, and shall be located between 2" to 10" clear from the surface of the roof to the PV module. The maximum cantilever length of the rail is L/3, where "L" is the maximum rail span after adjustments, provided there is at least 1 module length between maximum cantilevers. The modules shall be centered between the rails with consideration of industry standard tolerance. Installations utilizing the Tile Replacement or Tile Hook attachment devices are permitted to have panels offset from the centerline of the rails. Components and Cladding Roof Zones: The Edge Zones of the roof shall be determined based on the building's dimensions. The Edge Zone, "a", is the smaller of 10% of the least horizontal dimension, or 40% of the building height, and "a" shall not be taken as less than 3 feet (ASCE 7-10 figures 30A-1 & 30.4-2). For buildings exceeding a least horizontal dimension of 60 feet, further analysis may be required to determine proper Edge Zones. Edge and Corner Zone spacings (Zone 2 & 3, respectively) apply only to mounts located in those Zones, not to all the mounts supporting the module. For the 45-90 degree roof pitch range, mount spacings shall be determined utilizing roof zones 1, 2, & 3. CORNER ZONE L SEE DETAIL FOR MOUNT LOCATION RIDGE GABLE EDGEZONE INTERIOR ZONE Q7 INTERIOR ZONE Q HATCHED AREA INDICATES 'a' DISTANCE a = 0.1 x (LHD) OR MINIMUM OF 3W 'e OR 3`-0' MIN " �0 r',V_1 I� Figure 1: Roof Edge and Corner Zones 01 `w CORNERZONE SEE DETAIL FOR MOUNT LOCATION 8150 Sierra College Boulevard, Suite 150, Roseville, CA 95661 T 916.961.3960 F 916.961.3965 W www.pzse.com 3/106 Experience I Integrity I Empowerment HE structural ENGINEERS Attachment to Roof: The attached span tables include consideration of the attachment device capacity, based on UL 2703 load testing performed by SnapNrack. Tested load values are developed with 5/16" 0 lag screws with an effective embedment of 2- 1/2" into a Douglas Fir substrate, with a reference withdrawal (uplift or pullout) load capacity of 532 lb, and a reference shear (side or lateral) load capacity of 270 lb for resisting short-term wind or seismic loads. Reference values are the base values, before any adjustment is made per the NDS. Installations into alternate substrates or which use alternate fasteners shall be permitted; provided that the fastener has tested or code -derived allowable load capacities, and meets one of the following two criteria: A) The allowable load values for the alternate fastener shall meet or exceed the allowable values noted above for the 5/16" 0 lag screws in Douglas Fir; or B) the span length identified in the "span tables" shall be reduced according to the more restrictive of the following two formulas: Rail Span = Table Span a Alternate Reference Withdrawl Capacity 532 lb Or Rail Span =Table Span . Alternate Reference Shear Capacity 270 lb These formulas shall not be used to increase the allowable span beyond the spans listed in the span tables. Attachment Devices: The span tables have been grouped into 6 separate sets of attachment devices called 'Bins", which are presented below. To use this table, find the attachment device to be used in the list below, then read across to determine which bin the attachment is in. The spans may then be determined from the table with the corresponding Bin number. Structural details for the system and attachments may be found in Appendix C. Note: Side load direction is parallel to rafter. Maximum Reaction Loads Attachment Device Name: Bin No. Down Up Side Standard Base Seam Clamp with L-Foot 1 235 235 212 Wide Base Seam Clamp with L-Foot Universal Tile Hook Flat Tile Hook 2 394 318 417 Hanger Bolt Clamp Flashed L-Foot (92 Deg) 3 1469 309 251 Tile Replacement 4 1333 445 93 All Purpose L-Foot (90 Deg) Umbrella Comp Kit Corrugated Straddle Block with L Foot Metal Roof Base with L-Foot 5 788 405 236 Metal Roof Base with 7in Standoff 5-1/2in Standoff on 4-Hole Base 7in HD Standoff on 6-Hole Base 5-1/2in, 7in, or 8-1/2" Standoff on 1-Hole Base 8-1/2in Standoff on 4-Hole Base 6 788 445 163 Table 1: Allowable load Capacities of SnapNrack Flush -Mount Attachment Devices. 8150 Sierra College Boulevard, Suite 150, Roseville, CA 95661 T 916.961.3960 F 916.961.3965 W www.pzse.com 4/106 Experience I Integrity I Empowerment HE structural ENGINEERS Design Responsibility: These tables are intended to be used under the responsible charge of a registered design professional where required by the authority having jurisdiction. In all cases, these tables should be used under the direction of a design professional with sufficient structural engineering knowledge and experience to be able to: • Evaluate whether these tables are applicable to the project, and Understand and determine the appropriate values for all input parameters of these tables. This letter certifies that the SnapNrack Ultra Rail Flush -Mount Racking System, when installed according to the limitations of this letter and the attached span tables, is in compliance with the above codes and loading criteria. This certification excludes evaluation of the building structure to support the loads imposed on the building by the array; including, but not limited to: strength and deflection of structural framing members, fastening and/or strength of roofing materials, and/or the effects of snow accumulation on the roof. This requires additional knowledge of the building and is outside the scope of the certification of this racking system. If you have any questions on the above, do not hesitate to call. Prepared by: PZSE, Inc. —Structural Engineers Roseville, CA 8150 Sierra College Boulevard, Suite 150, Roseville, CA 95661 T 916.961.3960 F 916.961.3965 w www.pzse.com 5/106 Experience I Integrity I Empowerment 0 Industry leading Wire Management Solutions An install experience unlike any other Mounts available for all roof types Compatible with all Series 100 Module Clamps & Accessories Start Installing Ultra Rail Today The SnapNrack Ultra. Rail is a sleek, lightweight rail solution :for mounting solar modules on the roof. Key f C-.1`aa- _• Ultra Rail, UR-40 Rail S Wind (mph) Quality. Innovative. Superior. SnapNra.ck Solar Mounting Solutions are engineered to optimize material use and labor resources and improve overall in;sta.11ation• quality and safety. 877-732-2860 www.snapnrack.com contact@snapnrack.com © 2018 by SnapNrack Solar Mounting Solutions, All rights reserved SnapNrack Umbrella Sealing Technology Featuring New Innovative Flashing O Smaller 9"x12" size allows for easier insertion under shingles © Alignment markers make it easy to locate pilot holes © Rounded corners make for easier Insertion & eliminate corner points from folding up • Innovative Flashing Elevates Protection. New flashing uses a fully formed raised cone to prevent any potential water from getting into penetration. Feel secure as the flashing is one piece and doesn't rely on multiple parts sealing together. • Mechanical Design Creates a Lifelong Seal. Patented Umbrella technology utilizes unique Umbrella Washer to seal lag bolt, L Foot, and flashing and prevent any potential roof leaks. Technology passes UL 2582 Wind Driven Rain Test without a rubber seal, however rubber gasket is included for extra peace of mind. • Single Fastener Eliminates Extra Steps. Utilize one lag bolt with Umbrella Washer to secure the entire mount assembly and flashing. No longer necessary to attach a base, then a flashing, then a mount as all are secured in one step. • Single Tool Installation. SnapNrack was the first in the industry to develop a complete system that only requires a single tool. That tradition is continued as a Yz" socket is still the only tool necessary to secure the mount as well as all other parts of the system. Note: Flashing shown in yellow for illustration purposes only Industry Leading Spans for a Light Rail Solution This table was prepared in compliance with applicable engineering codes and standards. Values are based on the following: • ASCE 7-10 • Chapter 30 Wind Loads & Chapter 7 Snow Loads • Roof Slope: 7 - 27 deg • Roof Height: 0 - 30 ft • Exposure: B • Roof Zone: 1 • Module Orientation: Portrait • Module Type: 60 Cell Modules • Roof Type: Comp System Span Key Ultra Rail, UR-40 Rail System Spans Wind (mph) -- Visit SnapNrack.com for detailed span tables and certifications. Single Lag jSecu MounttoRoo h ! / Raised Cone Flashing Pre -assembled Ultra R: L Foot & Clamp Certifications SnapNrack Ultra Rail system has been evaluated by Underwriters Laboratories (UL) and Listed to UL/ANSI Standard 2703 for Mechanical Loading and Fire. Additionally it is listed to UL 2582 for wind -driven rain. SnapNrack- Solar Mounting Solutions 877-732-2860 www.snapnrack.com contact@snapnrack.com @ 2018 by SnapNrack Solar Mounting Solutions. All rights reserved SNAPNRACK UR-40 ULTRA FOOT FOR UMBRELLA FLASHING COMP MOUNTING s%i6"0 UMBRELLA LAG SCREW MUST EMBED A MIN. OF 2%" INTO THE ROOF STRUCTURAL MEMBER. FOR LEVELING DETAILS, PLEASE SEE SNAPNRACK DETAIL DRAWING-UR40-D01, L FOOT LEVELING" FLASHING SHOULD EMEND TO END OF DOWNSLOPE SHINGLE COURSE UR-40 RAIL ASSEMBLY, REFER TO-UR40-D04" LAG SCREW, TYP. 2%" MIN. EMBEDMENT INTO WOOD MEMBER SNAPNRACK UMBRELLA FLASHING MUST SLIP BENEATH THE UPSLOPE SHINGLE COURSE ROOF ROOFING, TYP. DECKING, TYP. WOOD RAFTER SHOWN, SIMILAR AT OTHER STRUCTURAL MEMBERTYPES REVISION: g 1312017 NEW OEfAR MA BRELLA GASKET AND UMBRELLA CONE) CONE ON TO SHIELD WATER U'�' INSTALLED SECTION VIEW STRUCTURAL MEMBER (RAFTER) DETAIL A BSMtwSa� LLB DESIGNER: M.AffenLrdngef SCALE: DNS PART NUMBER: DESCRIPTION: REV n�,U\\VII IIfV111' W DRAFTER: M.Affentranger UR40-PEN-DOI FOR UMBRELLA FLASHING ] UP-00 PENETRATION DETAIL, ULTRA FOOT /► Solar f�aUnhng Solutions M APPROVED BY: G.McPheeters DATE: 11/13/2017 os SNAPNRACK UR-40 PENETRATION DETAIL FOR COMP FLASHED L-FOOT ON BASE s�i6.0 LAG SCREW MUST EMBED A MINIMUM OF 2%" INTO THE ROOF STRUCTURAL MEMBER. FOR LEVELING DETAILS, PLEASE SEE SNAPNRACK DETAIL DRAWING-UR40-D01, L-FOOT LEVELING" FLASHING SHOULD EXTEND TO END OF DOWNSLOPE SHINGLE COURSE SNAPNRACK COMP FLASHING MUST SLIP UNDER THE UPSLOPE SHINGLE COURSE UR-40 RAIL, TYP. L-FOOTTO BASE ATTACHMENT DOWMSLOPE FROM ROOF PENETRATION SNAPNRACK ULTRA FOOT ASSEMBLY, 92" L FOOT SHOWN, TYP. FLASHING SHIELDS ENTIRE ROOF PENTRATION �s/s°0 TAG SCREW S.S. TILE ROOFING, TYP. DECKING, TYP. WOOD RAFTER SHOWN, SIMILAR AT OTHER STRUCTURAL MEMBER TYPES REVISION: A 11M=7 NEW DE ML MA SNAPNRACK ULTRA FOOT ASSEMBLY (92") 2s/' MIN. EMBEDMENT INTO WOOD MEMBER SNAPNRACK COMP FLASHING FOR L-FOOT BASE IMPORTANT: APPLY SEALANT AROUND LAG HOLE, BETWEEN THE D SHINGLE, AND ON THE BETWEEN BEFORE MOUNTING TO ROOF INSTALLED VIEW �TAWSM�vu�SouM LLB m DESIGNER: G.MTPhee[eR SCALE: DNS PART NUMBER: DESCRIPTION: REV IIII�\VII IW✓1' '" DRAFTER: M.Affentmnger UR40-PEN-D02 UR-40 PENETRATION DETAIL, FLASHED L-FOOT Q Solar Mo nting Solutions APPROVED BY: G.MCPheeters DATE' 11J30J2017 os