HomeMy WebLinkAboutAmazon DVB1 submittal
Prepared For:
Amazon
Date: March 17, 2020
Customer P.O. Number:
Customer Project Number:
Sold To:
Job Number:
Job Name:
Amazon MEP Structural Design Amazon DVB1
7440 Commercial Circle
FORT PIERCE, FL 34951
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Air-Cooled Scroll
1 Performance Climate Changer (CSAA)
Jose Perez
Trane U.S. Inc.
2884 Corporate Way
Miramar, FL 33025
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
between submittal generation and equipment release, the product
performance and submittal data will need to be verified. It is the
customer’s responsibility to obtain such verification.
Submittal
J:\JOBS\44\175353\3\Amazon DVB1 submittal.doc
Table Of Contents
Product Summary ........................................................................................................................... 1
Air-Cooled Scroll (Item A1)
Tag Data .................................................................................................................................................. 3
Product Data ............................................................................................................................................ 3
Performance Data .................................................................................................................................... 3
Product Data Report-CGAM-130pump .................................................................................................... 5
Mechanical Specifications ........................................................................................................................ 7
Unit Dimensions ..................................................................................................................................... 10
Weight, Clearance & Rigging Diagram ................................................................................................... 16
Accessory .............................................................................................................................................. 19
Field Wiring ............................................................................................................................................ 23
Performance Climate Changer (CSAA) (Item B1)
Tag Data ................................................................................................................................................ 26
Product Data .......................................................................................................................................... 26
Performance Data .................................................................................................................................. 27
Mechanical Specifications ...................................................................................................................... 30
As-Built ................................................................................................................................................... 34
Fan Curve .............................................................................................................................................. 43
Accessory .............................................................................................................................................. 45
Field Wiring ............................................................................................................................................ 53
Field Installed Options - Part/Order Number Summary
Performance Climate Changer (CSAA) .................................................................................................. 54
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 3 of 54
Tag Data - Air-Cooled Scroll (Qty: 1)
Item Tag(s) Qty Description Model Number
A1 CGAM-130p
ump
1 20-130 Ton Air-Cooled
(CGAM)
CGAM130F2**2AXB2A1B1A1AXXA1D1A4XXX8B1B1
A3A1D1X-L-X
Product Data - Air-Cooled Scroll
Item: A1 Qty: 1 Tag(s): CGAM -130pump
Air-Cooled Scroll Packaged Chiller
Startup Included - Trane Service must start equipment for warranty to be honored
130 nominal tons
60 hertz
460 volt 3 phases
High efficiency/performance
Full factory refrigerant charge (HFC-410A)
With factory installed freeze protection
Refrigerant isolation valves (discharge valve)
UL listed to US and Canadian safety standard
ASHRAE 90.1 all versions up to 2016
AHRI certified
Factory installed flow switch - set point 60 cm/sec
Phase reversal protection
Std cooling (40 to 65F/4.44 to 18C)
Grooved pipe connection
Factory insulation 1.25" - high humidity/low evaporator temperature
Performance based on water
High ambient (up to 125F/up to 52C)
Lanced aluminum fins
Across the line starter/direct on line
Single point connection main line unit power-ancillary items require other power
Circuit breaker-high fault rated control panel
Enclosure type UL 1995 rated for outdoor applications
BACnet interface
Dual high head pump
Pump flow ctrl by var speed drive
With buffer storage tank
High A short circuit rating
Elastomeric isolators
With water strainer factory installed
Super quiet
Architectural louvered panels
2nd-5th year compressor parts
1st year labor warranty
Performance Data - Air-Cooled Scroll
Tags CGAM-130pump
Refrigeration capacity (tons) 126.06
Total chiller power (kW) 146.77
Cooling efficiency (EER (Btu/W -h)) 10.306
NPLV.IP (EER (Btu/W -h)) 16.553
IPLV.IP (EER (Btu/W -h)) 16.554
Sound power level (dBA) 95
Sound pressure level (dBA) 67
Refrigerant R410A
Refrigerant charge circuit 1 (lb) 112.0
Refrigerant charge circuit 2 (lb) 112.0
Oil charge circuit 1 (gal) 5.81
Oil charge circuit 2 (gal) 5.81
Entering fluid evap (F) 53.98
Leaving fluid evap (F) 44.00
Flow evap (gpm) 301.81
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 4 of 54
Tags CGAM-130pump
Min flow evap (gpm) 146.90
Min flow PD evap+strainer (ft H2O) 5.99
Evap fluid freeze point (F) 32.00
Fluid pressure drop evap (ft H2O) 14.77
Total PD evap+strainer (ft H2O) 20.92
Evap fouling factor (hr-sq ft-deg F/ Btu) 0.000100
Saturated evap temp circuit 1 (F) 37.64
Saturated evap temp circuit 2 (F) 37.63
Ambient air temperature (F) 95.00
Altitude (ft) 0.00
Saturated cond temp circuit 1 (F) 123.54
Saturated cond temp circuit 2 (F) 123.54
Compressor power input (kW) 134.35
RLA - compressor 1A (A) 33.00
LRA - compressor 1A (A) 215.00
RLA - compressor 1B (A) 33.00
LRA - compressor 1B (A) 215.00
RLA - compressor 1C (A) 41.90
LRA - compressor 1C (A) 260.00
RLA - compressor 2A (A) 41.90
LRA - compressor 2A (A) 260.00
RLA - compressor 2B (A) 33.00
LRA - compressor 2B (A) 215.00
RLA - compressor 2C (A) 33.00
LRA - compressor 2C (A) 215.00
Total airflow (cfm) 91332
Number of fans ( ) 10
Fan power (kW) 12.22
Total fan FLA (A) 33.00
Pump size (kW) 11.33
Pump nominal current (A) 21.00
Expansion tank volume (gal) 6.30
Buffer tank volume (gal) 201.00
Avail head pressure at water connection (ft H2O) 76.98
Total PD pump+evap+strainer (ft H2O) 26.76
Single point power MCA (A) 285.10
Single point power MOP (A) 300.00
Short circuit current rating (A) 65000.00
Number of compressors ( ) 6
Number of circuits ( ) 2
Refrigeration capacity steps ( ) 6
Shipping weight (lb) 9721.9
Operating weight (lb) 11622.8
Length (in) 202
Width (in) 89
Height (in) 92
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 5 of 54
20-130 Ton Air-Cooled
Job Information
High efficiency Unit type Unit nominal tonnage 130 tons
1 Quantity Model Number CGAM-130pump Tag
CGAM 130
233 TOPSS version number
General Information
Sound attenuator package Super quiet IPLV.IP 16.55 EER (Btu/W-h)
Refrigerant R410A NPLV.IP 16.55 EER (Btu/W-h)
Refrigeration capacity 126.1 tons Sound power level 95 dBA
Full load refrigeration efficiency 10.31 EER (Btu/W-h) 67 dBA Sound pressure level *
Note: * At 30 feet in free field.
Evaporator Information
Evaporator application Std cooling Fouling factor 0.000100 hr-sq ft-deg F/ Btu
Entering temperature 53.98 F Saturated temperature-ckt 1 37.6 F
Leaving temperature 44.00 F Saturated temperature-ckt 2 37.6 F
Fluid flow rate 301.8 gpm Minimum flow rate 146.9 gpm
Pressure drop 14.8 ft H2O Pressure drop at min flow rate 5.99 ft H2O
Total PD evap+strainer 20.9 ft H2O Flow switch set point Flow switch set point 60 cm/sec
Evap fluid type Water With freeze protection Freeze protection (factory inst)
Evap fluid freeze point 32.00 F
Condenser Information
Unit application High ambient Total fan FLA 33.00 A
Ambient air temperature 95.0 F 91332 cfm Total airflow
Elevation 0.000 ft Fin material Lanced aluminum
Number of fans 10.00 Each Saturated temperature-ckt 1 123.5 F
Fan power 12.22 kW Saturated temperature-ckt 2 123.5 F
Number of compressors 6 RLA LRA
Compressor Information
Number of circuits 2 Compressor A 33.00 A 215.00 A
Refrigeration capacity steps 6 Compressor B 33.00 A 215.00 A
Compressor power input 134.4 kW Compressor C 41.90 A 260.00 A
Compressor D 41.90 A 260.00 A
Compressor E 33.00 A 215.00 A
Compressor F 33.00 A 215.00 A
Electrical Information
MOP MCA Unit voltage 460. volt 3 phases
Unit hertz 60. hertz Single point power 285 A 300 A
Incoming power line connection Single point Short circuit High
Starter type Across the line Short circuit current rating 65000 A
Total power input 146.8 kW
Note: Unit power includes: compressors, condenser fans, and control kW
3/17/2020
Page 1 of 2 233
Data generation date 3/17/2020 TOPSS version number
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 6 of 54
20-130 Ton Air-Cooled
Job Information
High efficiency Unit type Unit nominal tonnage 130 tons
1 Quantity Model Number CGAM-130pump Tag
CGAM 130
233 TOPSS version number
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program which is based on
AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI directory at www.ahridirectory.org.
Pump Package Information
Pump type Dual high head 15.196 hp Pump size
77.0 ft H2O Avail head pressure at water
connection
21.00 A Pump nominal current
6.30 gal Expansion tank volume Total PD pump+evap+strainer 26.8 ft H2O
Buffer tank With buffer storage tank Pump flow control Var speed drive
201.00 gal Buffer tank volume
Physical Information
202 in Length Water connection (inlet) 4.000 in
89 in Width 112.0 lb Refrigerant charge circuit 1
92 in Height Refrigerant charge circuit 2 112.0 lb
11623 lb Operating weight Oil charge circuit 1 5.81 gal
9722 lb Shipping weight Oil charge circuit 2 5.81 gal
Note: This information includes the pump and buffer tank.
Information for LEED Projects
ASHRAE 90.1/CSA compliance ASHRAE all to 2016 IPLV 16.55 EER (Btu/W-h)
112.0 lb Refrigerant charge circuit 1 Rated refrigeration capacity
(AHRI)
126.1 tons
112.0 lb Refrigerant charge circuit 2 Rated cooling efficiency 10.31 EER (Btu/W-h)
Note: This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 and CANS/CSA C743 for all versions (which are based on
AHRI standard rating conditions) and, therefore, also meets the LEED "Minimum Energy Performance" prerequisite in the Energy and
Atmosphere section.
The LEED Green Building Rating Systemâ„¢, developed by the U.S. Green Building Council, provides independent, third-party verification that a building project meets green
building and performance measures.
3/17/2020
Page 2 of 2 233
Data generation date 3/17/2020 TOPSS version number
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 26 of 54
Tag Data - Performance Climate Changer (CSAA) (Qty: 1)
Item Tag(s) Qty Description Model Number
B1 AHU-whse 1 Performance Climate Changer (CSAA) CSAA080UB
Product Data - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse
Unit level options
Outdoor unit
Unit size 80
No
6in. integral base frame
UL listed unit
Single metal handle - ganged latches
142.63 Unit length
Field Provided (mtrs, lights, controls)
No seismic certification required
Controls and VFD/starter
Supply fan field provided VFD
Return/exhaust fan no NEMA
Energy wheel field provided starter or no wheel
CDQ field provided starter or no wheel
Warranty
Standard warranty only
Pipe cabinet section
No pipe cabinet
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
Air mixing section (Pos #1)
Air mixing section
Mixing box w/filter
Door- right side
Back damper - parallel blade
Front full face opening
Left side - High velocity parallel
2in. filter frame
Pleated media - run set (Fld)
Coil section (Pos #2)
Horizontal coil
Medium
Door- right side
Stainless steel drain pan
Left side - drain connection
Left side - coil supply
Service panel opposite connection side
Unit coil height
Cooling coil
Chilled water
Single use coil
Type "UU" coil
4 rows
84 fins per foot nominal fin spacing
Aluminum fins
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 27 of 54
Delta flo H (Hi efficient)
.016" (0.406 mm) copper tubes
1/2in. tube diameter (12.7 mm)
Galvanized steel coil casing
Turbulators
Fan section (Pos #3)
Fan section
Supply fan
Door- right side
Outward swing
24.5in. dd plenum, full width, M press
Higher efficiency
4 Fan quantity
Plenum fan
Right side drive
NEMA premium compliant ODP
Voltage 460/3
NEMA motor hps only
10 max applied hp
1800 RPM
Inverter balance with shaft grounding
Side rectangular discharge
Field provided VFD
Performance Data - Performance Climate Changer (CSAA)
Tags AHU-whse
Unit level options
Position
Length (in) 142.631
Width (in) 140.500
Height (in) 107.500
Rigging weight (lb) 7400.8
Installed weight (lb) 8081.7
Roof curb weight (lb) 401.2
Actual airflow (cfm) 40000
Unit elevation (ft) 0.00
Shipping split 1 weight (lb) 3965.1
Shipping split 2 weight (lb) 3715.4
Fan section
Position #3
Section length (in) 61.478
Section weight (lb) 3715.4
Fan airflow (cfm) 40000
Elevation (ft) 0.00
Overall ESP (in H2O) 2.000
Total static pressure (in H2O) 3.895
Maximum TSP @ 60 Hz (in H2O) 3.895
Fan pressure drop (in H2O) 2.319
Speed (rpm) 1752
Total brake horsepower (hp) 37.084
Unit static efficiency (%) 66.24
Motor hertz (Hz) 60
Discharge 1 side - airflow (cfm) 40000
Discharge 1 side - face velocity (ft/min) 1596
Discharge 1 side - pressure drop (in H2O) 0.319
Discharge 1 side - area (sq ft) 25.06
Coil section
Position #2
Section length (in) 27.028
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 28 of 54
Tags AHU-whse
Section weight (lb) 1748.2
Coil performance airflow (cfm) 40000
Unit airflow (cfm) 40000
Coil face area (sq ft) 78.75
Coil face velocity (ft/min) 508
Air pressure drop (in H2O) 0.447
Coil section pressure drop (in H2O) 0.447
Coil rigging weight (lb) 730.4
Coil installed weight (lb) 1010.1
Top or single coil dry weight (lb) 365.2
Middle or bottom coil dry weight (lb) 365.2
Leaving dry bulb (F) 60.84
Leaving wet bulb (F) 59.44
Entering dry bulb (F) 80.40
Entering wet bulb (F) 70.80
Fluid type Water
Coil fluid percentage (%) 100.00
Entering fluid temperature (F) 44.00
Leaving fluid temperature (F) 54.00
Fluid temperature rise (F) 10.00
Standard fluid flow rate (gpm) 308.71
Fluid pressure drop (ft H2O) 17.74
Fluid velocity (ft/s) 3.78
Fluid volume (gal) 33.45
Sensible capacity (MBh) 866.93
Total capacity (MBh) 1549.07
Air mixing section
Position #1
Section length (in) 54.000
Section weight (lb) 2216.9
Opening 1 back - airflow (cfm) 40000
Opening 1 front - airflow (cfm) 40000
Opening 1 left - airflow (cfm) 20000
Opening 1 back - area (sq ft) 30.83
Opening 1 front - area (sq ft) 92.42
Opening 1 left - area (sq ft) 18.45
Opening 1 back - face velocity (ft/min) 1297
Opening 1 left - face velocity (ft/min) 1084
Opening 1 back - pressure drop (in H2O) 0.273
Opening 1 left - pressure drop (in H2O) 0.083
Opening 1 back total pressure drop (in H2O) 0.273
Opening 1 left side total pressure drop (in H2O) 0.083
Back hood pressure drop (in H2O) 0.220
Back hood area (sq ft) 54.54
Back inlet type Unducted
Left side inlet type Ducted
Greatest entry PD (in H2O) 0.493
Filter condition Mid-life
Filter airflow (cfm) 40000
Filter area (sq ft) 85.56
Filter face velocity (ft/min) 468
Filter pressure drop (in H2O) 0.636
Total mixing section pressure drop (in H2O) 1.130
Front total pressure drop (in H2O) 0.000
Back total pressure drop (in H2O) 0.493
Top total pressure drop (in H2O) 0.000
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 29 of 54
Tags AHU-whse
Bottom total pressure drop (in H2O) 0.000
Right side total pressure drop (in H2O) 0.000
Left side total pressure drop (in H2O) 0.083
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 30 of 54
Mechanical Specifications - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse
GENERAL
Outdoor air handling units will be shipped with all openings covered to protect unit interior from in-transit debris.
Installing contractor is responsible for long term storage in accordance with the Installation, Operation, and Maintenance
manual (CLCH-SVX07B-EN).
Unit shall be UL and C-UL Listed.
Supply fans within the scope of AHRI Standard 430 shall be certified in accordance with AHRI Standard 430.
Unit sound performance data shall be provided using AHRI Standard 260 test methods and reported as sound power.
Trane, in providing this program and data, does not certify or warrant NC levels. These levels are affected by factors
specific to each application and/or installation and therefore unable to be predicted or certified by Trane. Refer to
product data for specific fan footnote references.
Unit Construction
Outdoor unit roofs shall incorporate a standing seam on the exterior to ensure a rigid roof construction and prevent
water infiltration . Roof assembly shall overhang all walls by 1.5 -inch minimum to prevent sheeting from roof to side
panels . Rain gutters shall also be provided over all doors shorter than total unit height to direct rain away from the door
assembly. Outdoor roofs shall be sloped, not less than 0.125 inches per foot, for water drainage. Where outdoor units
are shipped in multiple sections, provide standing-seam joiners at each split with adhesive, hardware, and cover strips
for field joining by the installing contractor.
All unit panels shall be 2" solid, double-wall construction to facilitate cleaning of unit interior. Unit panels shall be
provided with a mid-span, no-through-metal, internal thermal break. Casing thermal performance shall be such that
under 55°F supply air temperature and design conditions on the exterior of the unit of 81°F dry bulb and 73°F wet bulb,
condensation shall not form on the casing exterior.
All outdoor AHU interior casing panels will be made of galvanized steel.
Unit Paint
External surface of unit casing will be coated with water-based polyurethane paint. Color to be standard "Slate Gray".
Factory-painted units will be able to withstand a salt spray test in accordance with ASTM B117 for a minimum of 500
consecutive hours and shall meet the following requirements following the salt-spray test:
- Mean scribe creepage rating of at least 6 per ASTM D1654 procedure A
- Blister size no larger than #6 per ASTM D714
- Blister density no greater than Medium per ASTM D714
- No onset of red rust
Casing Deflection
The casing shall not exceed 0.0042 inch deflection per inch of panel span at 1.00 times design static pressure.
Maximum design static shall not exceed +8 inches w.g. in all positive pressure sections and -8 inches w.g. in all negative
pressure sections.
Floor Construction
The unit floor shall be of sufficient strength to support a 300.0 lb load during maintenance activities and shall deflect no
more than 0.0042 inch per inch of panel span.
Unit base
Manufacturer to provide a full perimeter integral base frame for either ceiling suspension of units or to support and raise
all sections of the unit for proper trapping. Indoor unit base frame will either be bolted construction or welded
construction. All outdoor unit base frames shall be welded construction. For indoor units, refer to schedule for base
height and construction type. Contractor will be responsible for providing a housekeep ing pad when unit base frame is
not of sufficient height to properly trap unit. Unit base frames not constructed of galvanized steel shall be chemically
cleaned and coated with both a rust-inhibiting primer and finished coat of rust-inhibiting enamel. Unit base height to be
included in total height required for proper trap height.
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 31 of 54
Insulation
Panel insulation shall provide a minimum thermal resistance (R) value of 13 ft²-h-ºF/Btu throughout the entire unit.
Insulation shall completely fill the panel cavities in all directions so that no voids exist and settling of insulation is
prevented. Panel insulation shall comply with NFPA 90A.
Drain Pan
In sections provided with a drain pan, the drain pan shall be designed in accordance with ASHRAE 62.1. To address
indoor air quality (IAQ) the drain pan shall be sloped in two planes promoting positive drainage to eliminate stagnant
water conditions. Drain pan shall be insulated, and of double wall construction. The outlet shall be the lowest point on
the pan, and shall be of sufficient diameter to preclude drain pan overflow under normally expected operating
conditions. All drain pans connections shall have a threaded connection, extending a minimum of 2-1/2" beyond the unit
base, and shall be made from the same material as the drain pan. Drain pan located under a cooling coil shall be of
sufficient size to collect all condensate produced from the coil.
Refer to Product Data for specific information on which sections are supplied with a drain pan, the drain pan materi al
and connection location.
Access Door Construction
Access doors shall be 2" double wall construction. Interior and exterior door panels shall be of the same construction as
the interior and exterior wall panels respectively. All doors shall be provided with a thermal break construction of door
panel and door frame. Gasketing shall be provided around the full perimeter of the doors to prevent air leakage. Surface
mounted handles shall be provided to allow quick access to the interior of the functional section and to prevent through
cabinet penetrations that could likely weaken the casing leakage and thermal performance. Handle hardware shall be
designed to prevent unintended closure. Access doors shall be hinged and removable for quick easy access. Hinges
shall be interchangeable with the door handle hardware to allow for alternating door swing in the field to minimize
access interference due to unforeseen job site obstructions. Door handle hardware shall be adjustable and visually
indicate locking position of door latch external to the section. Door hinges shall be galvanized.
All doors shall be a minimum of 60" high when sufficient height is available or the maximum height allowed by the unit
height.
Door handles shall be provided for each latching point of the door necessary to maintain the specified air leakage
integrity of the unit. Optionally for indoor AHUs and as standard on outdoor AHUs, outward swing doors are provided
with a single handle linked to multiple latching points. An optional shatterpro of window shall be provided in access doors
where indicated on the plans. Window shall either be single pane, or thermal dual pane, as defined on schedule.
Window shall be capable of withstanding unit operating pressures and shall be safe for viewing UV -C lamps.
Refer to Product Data for specific information on which sections are supplied with an access door, the door location, a
single handle and a window.
Factory-supplied Curb
Outdoor AHU will be provided with a factory-supplied roof curb. Curb will be shipped to jobsite disassembled.
Contractor will be responsible for assembly and mounting to roof structure per the Roof Curb Manual. Units with
factory-supplied external piping cabinet(s), the factory-supplied curb will include a curb section for the pipe cabinet(s).
Refer to the Roof Curb Detail drawing and Product Data section of submittal for height of factory -supplied roof curb(s).
MIXING SECTION
A mixing section shall be provided to support the damper assembly for outdoor, return, and/or exhaust ai r.
Dampers
Dampers shall modulate the volume of outdoor, return, or exhaust air. The dampers shall be of double -skin airfoil design
with metal, compressible jamb seals and flexible blade-edge seals on all blades. The blades shall rotate on
stainless-steel sleeve bearings. The dampers shall be rated for a maximum leakage rate of 3 cfm/ft² at 1 in. w.g.
complying with ASHRAE 90.1 maximum damper leakage. All leakage testing and pressure ratings shall be based on
AMCA Standard 500-D. Dampers may be arranged in a parallel or opposed-blade configuration.
Inlet Hoods
Inlet hoods are provided on the outside air openings and equipped with high performance moisture eliminators to
minimize water carryover from the outside into the unit casing. Eliminators also perform the function of a bird screen to
prevent nesting.
Refer to the unit As-Built and Product Data section for specific information on which sections are supplied with inlet
hood.
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 32 of 54
Dampers
Dampers shall modulate the volume of outdoor, return, or exhaust air. The dampers shall be of double-skin airfoil design
with metal, compressible jamb seals and flexible blade-edge seals on all blades. The blades shall rotate on
stainless-steel sleeve bearings. The dampers shall be rated for a maximum leakage rate of 3 cfm/ft² at 1 in. w.g.
complying with ASHRAE 90.1 maximum damper leakage. All leakage testing and pressure ratings shall be based on
AMCA Standard 500-D. Dampers may be arranged in a parallel or opposed-blade configuration.
Title 24
The following specifications apply only to units with outside air and return air dampers, with actuators. The 5 year
warranty applies only to these items.
This unit contains Economizer that meets or exceeds all mandatory requirements prescribed by Title 24, including but
not limited to:
- 5 yr parts only warranty
- Successfully tested to 60,000 Actuations
- Less than 10 cfm/sq.ft. of damper leakage at 1" WG per AMCA 500L
Filters
Mixing sections shall be provided with a filter rack as indicated in the Product Dat a and As-Built sections of the submittal.
2-inch pleated media filters made with 100% synthetic fibers that are continuously laminated to a supported steel -wire
grid with water repellent adhesive shall be provided. Filters shall be capable of operating up to 625 fpm face velocity
without loss of filter efficiency and holding capacity. The filters shall have a MERV 8 rating when tested in accordance
with the ANSI/ASHRAE Standard 52.2.
COIL SECTION WITH FACTORY INSTALLED COIL
The coil section shall be provided complete with coil and coil holding frame. The coils shall be installed such that
headers and return bends are enclosed by unit casings. If two or more cooling coils are stacked in the unit, an
intermediate drain pan shall be installed between each coil and be of the same material as the primary drain pan. Like
the primary drain pan, the intermediate drain pan shall be designed being of sufficient size to collect all condensation
produced from the coil and sloped to promote positive drainage to eliminate stagnant water conditions. The
intermediate pan shall begin at the leading face of the water -producing device and be of sufficient length extending
downstream to prevent condensate from passing through the air stream of the lower coil. Intermediate d rain pan shall
include downspouts to direct condensate to the primary drain pan. The outlet shall be located at the lowest point of the
pan and shall be sufficient diameter to preclude drain pan overflow under any normally expected operating condition.
Coil with Inspection
The coil section shall include an inspection section complete with a double-wall, removable door downstream of the coil
for inspection, cleaning, and maintenance. Interior and exterior door panels shall be of the same construction as t he
interior and exterior wall panels, respectively. All doors shall be provided with a thermal break construction of door
panel and door frame.
In lieu of a door, an easily removable service panel shall be provided in sections as specified, to facilitate access to unit
for periodic servicing, or for removal and replacement of coils. Removal of service panel will not impact the structural
integrity of the unit.
Casing penetrations supplied for hydronic drain and vents. Piping contractor shall provide exte nded piping.
Water Coils (UP, WP, UW, UU, UA, 3W, 3U, W, 5W, 5A, WD, 5D, D1, D2, P, or TT)
The coils shall have aluminum fins and seamless copper tubes. Copper fins may be applied to coils with 5/8 -inch tubes.
Fins shall have collars drawn, belled, and firmly bonded to tubes by mechanical expansion of the tubes. The coil casing
may be galvanized or stainless steel. Refer to the Product Data section of the submittal for the coil casing material.
The coils shall be proof-tested to 300 psig and leak-tested under water to 200 psig. Coils containing water or ethylene
glycol are certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification
Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the
Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Propylene glycol and calcium
chloride, or mixtures thereof, are outside the scope of AHRI Standard 410 and, therefore, do not require AHRI 410 rating
or certification.
Coil connections are constructed of cast iron with female connections, steel block with female connections or steel pipe
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 33 of 54
with male connections. Type P or TT coil connections do not extend out of unit casing. All other water coil types have
connections that extend out beyond unit casing. Headers on downstream coil bank of staggered coil sections do not
extend beyond the unit casing and must be completed by the on-site piping contractor.
Tubes are 1/2" [13 mm] OD 0.016" [0.406 mm] thick copper.
DIRECT-DRIVE PLENUM FAN SECTION
The fan type shall be provided as required for stable operation and optimum energy efficiency. The fan shall be a
single-width, single-inlet, multiblade-type direct-drive plenum fan. Motor bearing life of the direct-drive plenum fan shall
be not less than L-10 250,000 hrs. Refer to the Product Data section for fan quantity and number of blades selected
within each unit. Fans shall be certified as complying with AHRI Standard 430 for airflow per formance. Fans shall be
tested and rated in-accordance with AHRI Standard 260 for sound performance.
Fans that are selected with inverter balancing shall first be dynamically balanced at design RPM. The fans then will be
checked in the factory from 25% to 100% of design RPM to insure they are operating within vibration tolerance
specifications, and that there are no resonant frequency issues throughout this operating range. Inverter balancing that
requires lockout frequencies inputted into a variable frequency drive to in order to bypass resonant frequencies shall not
be acceptable. If supplied in this manner by the unit manufacturer, the contractor will be responsible for rebalancing in
the field after unit installation. Fans selected with inverter balancing shall have a maintenance free grounding assembly
installed on the fan motor to discharge both static and induced shaft currents to ground.
On units supplied with plenum or motorized impeller fans, expanded metal door guard(s) shall be supplied on the
access door(s) to the fan and those downstream access door(s) where unintended access to the plenum or motorized
impeller fan could occur. Door guard is intended to deter unauthorized entry and incidental contact with rotating
components. Refer to the Product Data section for fans with access door guard(s).
Motor Frame
The motor shall be mounted integral to the isolated fan assembly and furnished by the unit manufacturer. The motor is
mounted inside the unit casing on an adjustable base to permit adjustmen t of drive belt tension (not applicable for direct
drive plenum fans). The motor shall meet or exceed all NEMA Standards Publication MG 1 requirements and comply
with NEMA Premium efficiency levels when applicable except for fractional horsepower motors which are not covered
by the NEMA classification. The motor shall be T-frame, squirrel cage with size, type, and electrical characteristics as
shown on the equipment schedule. Refer to the Product Data section for selected fan motors within each unit.
Two-Inch Spring Isolators
Direct-drive fan and motor assemblies shall be internally isolated from the unit casing with 2-inch (50.8 mm) deflection
spring isolators. The isolation system shall be designed to resist loads produced by external forces, such as
earthquakes, and conform to the current IBC seismic requirements.
Lifting Instructions
The air handling units must be rigged, lifted, and installed in strict accordance with the Installation, Operation, and
Maintenance manual (CLCH-SVX07G-EN). The units are also to be installed in strict accordance with the specifications.
Units may be shipped fully assembled or disassembled to the minimum functional section size in accordance with
shipping and job site requirements.
Outdoor units shall be shipped on 6" integral base frame for the purpose of mounting units on a roof curb or
field-supplied pier support system. Refer to the Product Data section for type of the base frame provided (for roof curb
or pier-mount).
All units will be shipped with an integral base frame designed with the necessary number of lift points for safe
installation. All lifting lugs are to be utilized during lift. The lift points will be designed to accept standard rigging d evices
and be removable after installation. Units shipped in sections will have a minimum of four points of lift.
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 34 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE Unit size: 80Product group: Outdoor unitIntegral base frame: 6in. integral base framePaint: Slate grayJob Name: Actual airflow: 40000 cfmSales Office: Unit Casing: 2in Double Wall Foam Proposal Number: Rigging/Installed Weight: 7400.8 lb/ 8081.7 lbPerformance Climate ChangerAir Handlers9 5/844 45 1/813 34 1/420"10"23"7 1/4126 140 1/21234566 15 7/879 1/245 1/8761 1/2Ship Split3715 lbs81 1/8Ship Split3965 lbs142 5/8107 1/21 2 3 4 5 67 Opening left82.000 x 44.000Plenum fan - 24.5in. ddplenum, full width, M pressSupply fan 10 hp 460/3NoneCooling coil - 4 Coil typeUUDamper left-parallel blade88.000 x 34.250Damper back-parallelblade40.000 x 123.000Hood backFlat filters - Doors20 width x 61 height 10 width x 61 height 23 width x 97 height For maneuvering purposes, include 1.125 inches to each ship split length for overlapping panel flange. Flange will not add to overall installed unit length shown.
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 35 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 80
Product group: Outdoor unit
Integral base frame: 6in. integral base frame
Paint: Slate gray
Job Name:
Actual airflow: 40000 cfm
Sales Office:
Unit Casing: 2in Double Wall Foam
Proposal Number:
Rigging/Installed Weight: 7400.8 lb/ 8081.7 lb
Performance Climate Changer
Air Handlers
Pos #
3
2
1
Module
Fan section
Coil section
Air mixing section
Length
61 1/2
27 1/8
54
Weight
3715.41
1748.25
2216.85
Installed Unit Weight 7680.51 lbs
3 2 1
140 1/2Basic Overall Plan View: Top - Measurements in inches
S2 S1
6
3 2 1
142 5/8 111 1/8For maneuvering purposes, include 1.125 inches to each ship split length for overlapping panel flange. Flange will not add to overall installed unit length shown.
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 36 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 80
Product group: Outdoor unit
Integral base frame: 6in. integral base frame
Paint: Slate gray
Job Name:
Actual airflow: 40000 cfm
Sales Office:
Unit Casing: 2in Double Wall Foam
Proposal Number:
Rigging/Installed Weight: 7400.8 lb/ 8081.7 lb
Performance Climate Changer
Air Handlers
3 2 1
61 1/2 27 1/8 54 140 1/2Right Side of Unit Detailed Plan View: Top - Measurements in inches
3 2 1
30 1/8
61 1/2
27 1/8 54
3.563" dia elec. conn.(NEMA)
135 1/2
140 1/2Left Side of Unit Detailed Plan View: Bottom - Measurements in inches
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 37 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 80
Product group: Outdoor unit
Integral base frame: 6in. integral base frame
Paint: Slate gray
Job Name:
Actual airflow: 40000 cfm
Sales Office:
Unit Casing: 2in Double Wall Foam
Proposal Number:
Rigging/Installed Weight: 7400.8 lb/ 8081.7 lb
Performance Climate Changer
Air Handlers
321
44 34 1/482 88 8
7 1/2
13
61 1/227 1/8
54
1.5" N.P.T.E
6 1/86
13 1/4
15 3/4107 1/2Detailed Elevation View: Left - Measurements in inches
6 7 5/87 3/4
15 7/860 1/297 1/479 1/23 2 1
3 3 3/8 2 1/8
54
20"
10"
23"45 1/8142 5/8 111 1/8
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 38 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 80
Product group: Outdoor unit
Integral base frame: 6in. integral base frame
Paint: Slate gray
Job Name:
Actual airflow: 40000 cfm
Sales Office:
Unit Casing: 2in Double Wall Foam
Proposal Number:
Rigging/Installed Weight: 7400.8 lb/ 8081.7 lb
Performance Climate Changer
Air Handlers
1 143 1/2126 3 5/879 1/21 1/2
7 1/4
140 1/2
6
15 7/8107 1/2Detailed Elevation View: Back - Measurements in inches 111 1/83 143 1/23 5/86
Detailed Elevation View: Front - Measurements in inches
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 39 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE Unit size: 80Product group: Outdoor unitIntegral base frame: 6in. integral base framePaint: Slate grayJob Name: Actual airflow: 40000 cfmSales Office: Unit Casing: 2in Double Wall Foam Proposal Number: Rigging/Installed Weight: 7400.8 lb/ 8081.7 lbPerformance Climate ChangerAir Handlers107 1/232161 1/227 1/854 142 5/8111 1/8NPTI : National Pipe Thread Internal ConnectionNPTE : National Pipe Thread External Connection
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 40 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE Unit size: 80Product group: Outdoor unitIntegral base frame: 6in. integral base framePaint: Slate grayJob Name: Actual airflow: 40000 cfmSales Office: Unit Casing: 2in Double Wall Foam Proposal Number: Rigging/Installed Weight: 7400.8 lb/ 8081.7 lbPerformance Climate ChangerAir Handlers3219 1/45 61 1/227 1/854 2.5" (NPTE) Return2.5" (NPTE) Supply3/8" (NPTI) Vent3/8" drain (NPTI)31 1/234 5/878 3/481 7/8107 1/2142 5/8111 1/8Coil connection view: Left - Measurements in inchesNPTI : National Pipe Thread Internal ConnectionNPTE : National Pipe Thread External Connection
Amazon MEP Structural Design Amazon DVB1 March 17, 2020
FLD = Furnished by Trane U.S. Inc. / Installed by
Others
Equipment Submittal Page 41 of 54
As-Built - Performance Climate Changer (CSAA)
Item: B1 Qty: 1 Tag(s): AHU-whse OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE Unit size: 80Product group: Outdoor unitIntegral base frame: 6in. integral base framePaint: Slate grayJob Name: Actual airflow: 40000 cfmSales Office: Unit Casing: 2in Double Wall Foam Proposal Number: Rigging/Installed Weight: 7400.8 lb/ 8081.7 lbPerformance Climate ChangerAir Handlers32193 156 156 11 7/856 Basic Service Clearance - Plan - Measurements in inches