HomeMy WebLinkAboutProject Informationwrightsoft' Project Summary
Entire House
Quick Calcs, Inc.
• 317 St Ude Lam, Fort Pierce, FL 34946 Plnre: 772-466-6799 Email: qurkcelcs@aol.cem
For.
Notes:
Design Information
Weather. Fort Pierce, FL, US
Winter Design Conditions
Outside db
Inside db
Design TD
Heating Summary
Job:
Date:
By:
DEC 17 919
ST. Lucie County, Permitting
Summer Design Conditions
42 OF Outsidedb
70 OF Insidedb
28 OF Design TO
Daily range
Relative humidity
Moisture difference
Structure
23023
Btuh
Ducts
6600
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Humidification
0
Btuh
Piping
0
Btuh
Equipmentload
29623
Btuh
Infiltration
Method
Simplified
Construction quality
Fireplaces
Average
0
He gg
Co gg
Area (ft)
215tin1
2151
Volume (ft)
19428
19428
Airchanges/hour
0.32
0.16
EquivAVF(clim)
104
52
Heating Equipment Summary
Make Carrier
Trade CARRIER
Model CH14NBO4200GOA0
AHRI ref 9162733
Efficiency
8.2 HSPF
Heating input
Heating output
41000
Btuh @ 47-F
Temperature rise
28
OF
Actual airflow
1333
cirn
Airflowfactor
0.045
cfmBtuh
Static pressure
0.50
in H2O
Space thermostat
Capacity balance point = 34 OF
Backup:
Input=BkW, Output= 28100 Btuh, 100AFUE
Calculations
90 OF
75 OF
15 M OF
50 %
61 grAb
Sensible Cooling Equipment Load Sizing
Structure
23303
Btuh
Ducts
8115
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data
in
Rate/swing multiplier
Equipment load
0.95
Btuh
sensible
29847
Latent Cooling Equipment Load Sizing
Structure
3364
Btuh
Ducts
2591
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Equipment latent load
5955
Btuh
Equipment Total Load (Sen+Lat)
35802
Btuh
Req. total capacity at 0.70 SHR
3.6
ton
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Cond CH14NBO4200GOA0
Coil FX4DNF049L
AHRI ref 9162733
Efficiency 12.0 EER,14.5
SEER
Sensible cooling
28000
Btuh
Latent cooling
12000
Btuh
Total cooling
40000
Btuh
Actual airflow
1333
cBn
Air flow factor
0.042
cfmBtuh
Static pressure
0.50
in H2O
Load sensible heat ratio
0.84
to meet all
of Manual J 8tholue c®f',
_ -r k wrightsofv-
Rigk-Sute0Uriversa1201919.0.01 RSU06101
ACCk sHams -2169 Model-8301 Castelle Coutnp Cale=MJ8 Frart Door faces: NW
2019-Oct-2810111:46
Page 1
1 wrilghtsoftRight-J@ Worksheet Job:
Entire House Date:
Quick Calcs, Inc. By:
317 St Lutle Lane, Fort Pierce, FL 34946 Phone: 772-466-6799 Email: qudmalcs@aol.mm
1
2
3
4
5
Room name
Eposed yell
Room height
Room dimensions
Room area
Entre House
201.0 It
9.0 ft
2151.0 ft'
SunroomBedroom 4
34.0 It
8.0 ft heaVccol
1.0 x 164.0 ft
164.0 ft'
Ty
Construction
number
U-value
(BtuhMz°F)
Or
HTM
(Bluhtn
Area (M
or perimeter (fl)
Load
(Btuh)
Area ("
or perimeter (f0
Load
(Btuh)
Heat
Cod
Gros
NIPB
Heat
Cool
Gross
N/PIS
Heat
Cool
6
11
V
13A4acs
4A5-2om -
4A5-20m
j1D0 _,
13A-4ors
11D0 _
-13A44A5.22cm " ..
13A4ocs
4A5-2om
4A5-2om
11DO
1(BB..30ad-
22A- I ..._,.._....._..�a........._......,_....-._...
6.143
0.770
0.770
_,_0.390
0.143
0.390
-Re-
ne
ne
_ne_
se
se
400
, I2156
21.56
„_,.10.92
4.00
10.92
21.56
'2156
_,..-.,1 .
4.00
21.55
21.56
10.92
=0.90
2769
....�-
--" 2.19
36.90
36.90
10.34
2.19
10.34
31
800.
_"-..1 .34
219
36.90
36.90
10.34
=,60
0.00
,.....,.-.v.
534
� 60
75
--19
396
19
'"-'"-990'-
01
0
__.__.,19
1520
1294
1617
---210
1508
_210 09
, - 1310
223
1741
194
323
210
:=„-1927
5566
.._._.._.,.
831
2214
2767
--199
824
'-- 104
30
- 0
_ _ _ 0
-774
"0
0
_„____0
37
19
-"`" 298
647
0
-_„-._„_ O
147
210
"" 162
1107
0
0
G
' - D
w
"
377
19
56
19
80
199
1
0.770
0.770
0.143
0.770
0.770
0.390
.�d0.032
0.989
sw
sw
nw
nw
nw
nw
-
4 1144
14
._-_-_„20
478
9
15
19
=2151
2151
..,..._-..-_._
�235
14
'.,��20
435
0
0
19
201
�,-...._.
_199
Z278
_211
951
332
553
199
_ 3442
0
,,,ram..
�0
__,-_0
,0
_._0
0
_0
0
,_„_„,;0
w
112
0
0
0
7�w:-164
164
112
0
0
0
448
0
0
0
245
0
0
0
�262
0
-_ 0
C..._,_.:
F
,...._w,161
34
=J-47
942
6
c)AEDexalrsion
1500
-75
F_melopelos4gain
19834
17669
2837
1981
12
a) Infiltration
b) Roomventlation
3188
0
854
0
489
0
131
0
13
Intemalgains Omlpants@ 230
Applianossrolher
6
1380
3400
1
230
0
Subtotal (lines6 to 13)
23023
23303
3327
2342
14
15
Leseaemalload
Less transfer
Redistribution
Subtotal
Ductloads
29%
35%
0
0
0
23023
6600
0
0
0
23303
8115
29%
35%
0
0
0
3327
954
0
0
0
2342
815
Total room load
Airrequired(dm)
29623
1333
31418
1333
4281
193
3157
134
Calculations approved bVACCA to meet all requirements of Manual J 8th Ed
AC-rk- wrigtiesosie- 2019-Od-2810:01A6
C Right-Sute®Uriversal 201919.0.01 RSU08101 Page 1
...aHomes-2169 Model- 8301 Castelle Coutnp Calc=MJ8 FrortDoorfaces:NW
�s wrightsoft• Right-J®Worksheet Job:
Entire House Date:
eY:
Quick Calcs, Inc.
317 St Lucie Lam, Fort Pierce, FL 34946 Plow 772-466-6799 Email: quckcalos@aol.com
1
Room name
Bedroom
Rath
2
F)posedwall
12.0 ft
9.0 It
3
Room height
8.0 ft heall000l
8.0 ft heah'mol
4
Room dimensions
1.0 x 174.0 ft
1.0 x 75.0 ft
5
Room area
174.0 ft'
75.0 ft
Ty
Constvdlon
U-value
Or
HTM
Area (ft0
Load
Area (M
Load
number
(BtuhNV-'F)
(BWh/"
or perimeter (ft)
(Btuh)
or perimeter (ft)
(BWh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
WP/S
Heat
Cool
6
13,4-0ots
0.143
ne
"� 400'
2.19
"" 0
0'
«0
0
^0'�
0�^"
6
'0
4A5-2om ''
0,770
ne
21.56
36.90
'0
r 0
- 0
0
`',D
4 0
< 0
I0
4AS-2om
A170
ne
r 2156
36.90
-0
0
0
,; 01
'0
o
0
.0
..�-,; _0,390
wpe_
._;_1R.92
.-,_.,t0,34
,_„_�;,_.0
.:. ;,N, o
0
-0
-,0
,
0
.a0
..0
11
W
LD
134400s
0.143
se
4.00
2.19
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
W
11DO
13A-4ocs
0.390
�70143
se
sw
1092
"" Ib0
10.34
2.19
0
0
0
0
"0
""' 0
4A5-tom
0.770
5w
,2156
19.31
0
0
0
0
0
0
0
0
4A5-20m
0770
sw
2156
19.31
0
0
0
0
0
0
0.
- 0
4A5-2om
0:770
sN
2156
28.30
0
0
0
0
0',
0
0
�0
4A5-20m
0770
sm
.2156
30.64
0"
0
0
0
0
0
0
`^ 0
_sx_
„�„,10.92
i,„.10.34
,.«..a,..._0
z....__.., Q
...,.-......_,..0
_m__„_;�;,0
<.,.„._._....;0
-....«.,w..0
.�..._.,,.-.0
_,,,d._,__-0
..11D0
.._...r,..0.390
0.143
13A-4ocs
nw
4.00
2.19
96
81
324
177
72
63
252
138
4A5-tom
0.770
nw
21.56
36.90
0
0
0
0
9
0
194
332
4A5-20m
0.770
nw
21.56
36.90
15
0
323
553
0
0
0
0
C_,,;.,,...
16030ad�,.�.r-
__,�.; 60-2
- .
�,„„�0
=kb
=74
:.;,.J74
�e�:,,,,156
,„.::wa.27,8
' _75
==75
'_ „67
_ -;1200
F
22A-tpl
0.989
-
27.69
0.00
174
12
332
0
75
9
249
0
.,m
.....a.....___,,....._....
>_.-..,,...
.«„
__
..,^.,._,a.[
......_::...,ram....-.x
:...,.,
...�3z. �`.,.,
c...<
,.-r..>•.• ..n
.w
...,^m-m
�
e.,�...-�e.n.
... r
�.�.
-.n..mssmr-m..
a+.��w.e
r«�..s
.�.s-.
..�yw
77
....-.-..�mn;w�w-....e-
-..e,-,-..n..^.
w...,,.
�w.,..ow
.�n...ww,....,
w...�--xr.m
v.nw-,..,.-.-........,.��.
x
r.......-.w...w
nr-.+m.. e-..+
......,...�....a..
..«...- ....w.
nv
,...... «vwm
..�..,....
-k....
�.......-.
.�
_�...
..,.._.,.f: .,
:..ter.-.>.
�
�--
r....
6
c)AED exalrsion
165
112
En<elopelossrgain
1136
1175
763
702
12
a) Infiltration
173
46
130
35
b) Room ventilation
0
0
0
0
13
Internal gains: O=pants@ 230
1
230
0
0
Appliancesfother
0
0
Subtotal (lines 6 to 13)
1309
1451
892
736
Lesse#emalload
0
0
0
0
Lesstransfer
0
0
0
0
Redistibuton
6
11
21
36
14
Subtotal
1315
1462
913
772
15
Ductloads
29%
35%
377
509
29%
35%
262
269
Total room load
1692
1971
1175
1041
Air required(om)
76
84
53
44
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
A-pp- 2019-0G2810:01:46
& "^ Right-Sute®Uriversa1201919.0.01RSU08101 Paget
...s Homes-2169Model-8301 Castelle Coutnp CaIc=MJ8 FrortDoorfaces NW
wrightsoft° Right-J®Worksheet Job:
Entire House Date:
sy:
Quick Calcs, Inc.
317 St Lude Lane, Fort Pierce, FL 34946 Phone: 772-466-6799 Email: qud(calos@aDLoam
1
2
3
4
5
Room name
E:Vocedvall
Room height
Room dimensions
Room area
Closet
4.0 It
8.0 ft heaYbool
5.0 x 4.0 ft
20.0 W
AH
0 ft
8.0 ft heatf000l
4.0 x 4.0 It
16.0 ft
Ty
Construrton
number
U-value
(Btuhltl-*n
Or
HTM
(BWhM
Area (W)
or perimeter (f)
Load
(Btuh)
Area (ft)
or perimeter (10
Load
(Bluh)
Heat
cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
iYA-5 s
4A5-2om-
4A5-2om.
13AAocs
11D0
13A;4 s
4A5-20m
4A5-20m
4A8-2am
4AS2om
11D0-,-
13AAors
4A5-2om
4A5-2om
11D0_
" 0.143
0.770
0.770
.,_..a,„0.390
0.143
0.390
0.143
0770
0.770
0.770
0.770
0.390
ne
ne
ne
une..:_,.10,92
se
se
sw
sa
sv
av
w
_sw„
nw
nw
nw
400
21.56
21.56
4.00
10.92
400
21.56
21.56
21:66
24.56
-„_10,92
4.00
21.56
21.56
10.92
219
36.90
36.90
t0.3q
2.19
10.34
219-
1931
1931
2830
30.61
10.34
2.19
36.90
36.90
10.34
, 0
0
0
' 0
0
0
0
0
.-0
,' 10
0
0
--0
0
0'
_„_-0
0
0
--0
0
- 0
_ ' 0
0
0
- 0
0
0
..:...........s.0
0
0
.0
0
0
„....„;:...._0
0
0
--0
0
0
..,;. ---m0
0
0
0
0
0
;,a,„._._0
0
0
"-6
0
.0
; 0
0
0
G
D
IW
L-D
W^
0
0
0
0
G.
____,_-0
32
0
0
0
0
0
0
'.. • 0
0
0
0
0
'6
" o
0
0
0'
0
0
, -0
0
_ '0
0
0
0
0
0
0
.0
0
'0
0
0
0
• 0
0
-_0
0
0
0
0
0
0
0
_ 0
0
--0
0
0
0
0
W
0.143
0.770
0.770
0.390
32
0
0
0
128
0
0
0
70
0
0
0
-0
0
0
0
0
D
_
,C_-_,_�
F
_
168�30ad a
22A-tpl
_,
=6.032
_- 0.989
_mv
=
6.90
27.69
=7,60
0.00
_..__20
20
- 10
4
=18
111
.._-..,_32
0
, -, f6
16
;i6
0
��]4.
0
-s26
0
-
--.-...�_,......<_...-..........
-_
._..._.
-..�.�
.._s.„,.,
.�._..�..,-•
--T
.. .,.s..�--"--.._..-ram..,-....«...e......
.8-_
6
c)AED exarrson
4
-1
Errvelope loss/gam
257
98
14
25
12
a) Infiltration
b) Rcomventilaton
58
0
15
0
0
0
0
0
13
Internal gains: O=pant3@ 230
Applianoes'other
0
0
0
0
0
0
Subtotal(lines6to13)
314
114
14
25
14
15
LesseAemalload
Lesstransfer
Redistribufion
Subtotal
Duct loads
29%
35%
0
0
6
320
92
0
0
10
124
43
29%
35%
0
0
-14
0
0
0
0
-25
0
0
Total room load
Air required(dm)
412
19
167
7
0
0
0
0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-rid- wrightsoR- Ri9KS v2019-Oa-281091:46
sHomes-2169Matlel-8301 CastelleCoutrLpCalc=MJB FmrtDoorfams:NW Page
wrightsofr Right-M Worksheet Job:
Entire House Date:
Quick Calcs, Inc. sv.
317 St LLue Lane, Fort Pierce, FL 34946 Phone: 772-466-6799 Email: gdd<ralcs@aol.00m
1
2
3
4
5
Room name
Elposedvell
Room height
Room dimensions
Room area
Hall
0 it
8.0 it heat000l
1.0 x 58.0 it
58.0 ft2
Bedroom 2
33.0 it
8.0 1t heaV000l
13.0 x 12.0 it
156.0 11
Ty
construction
number
U-value
(BtAnk-F7
Or
HTM
(Btuhdl)
Area (fF)
or perimeter (it)
Load
(Btuh)
Area (it)
or perimeter (f0
Load
(Bi
Heat
Cool
Gross
N/P/5
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
w
4AS-2orn
4A5-20rh
J1D0._..
13AA s
11DO
0143
0.770
0.770
._w..0.390
0.143
0.390
-ne
ne
ne
_.ne_
se
se
400
' 2156
21.56
_1092.
4.00
10.92
219
'36.90
36.90
10,34
2.19
10.34
0
0
0
0
0
0
0-'
0-
0
0
0
0
o
0'
0
_„.._..,,_.0
0
0
a
0
0
,.�,,;�.,„,,.0
0
0
0-
0
0
.,....-:0
64
0
0'
0
0
0
0
0
0
0.
256
0
. 0
0
'0
0
140
0
.„,..,
w
"
W-'"
64
0
13A-4ors'
4A5-26m
4A5-tom
4A5w2om
4A5-2om
13A-4=
4A5-2om
4A5-tom
11 DO
j61336ad__.,_,_�,
22A_fpl
0143
0.770
0,770
`0.770
0.770
0.390
0.143
0.770
0,770
0,390
_,.�0.989
0.989
svi
w2156
w
w'2156
w,
„,sK,
nw
nw
nw
nw
400
2156
2156
r_..10.92
4.00
21.56
21.56
10.92
219
1931
19.31
28.30
30.64
....._10.34.,._„.._._..0
2.19
36.90
36.90
10.34
0
0
0
t0
0
0
0
0
0
0
0
0
0
0
.,,,„,,,",__0
0
0
0
0
0
0
0
`, �0
0-
,_,,,,,..�-.._;0
0
0
0
- 0
0
0
0
6
0.„...�.,..,...0
0
0
0
0
104~89-
0
0
15
0
96
0
0
0
.,,_, 156
1.56
0
0
7'
0
-.�.,,,,._...;,0
96
0
0
0
7350
0
0
` 323
0
._„..„�.0
384
0
0
0
0
0
425
6
-___.:0.
210
0
0
0
Noj1DO-
Iw
0 .,,,-_
FA
-
' 27.69
27.69
,�0.00
0.00
,�
______.58
58
^�
_.�.,,,,_58
0
`_0
„,.52
0
______.
^,,,_„93
0
„1
33
'IQO
914
250
0
6
c)AEDexanaon
.3
186
Envelope loss(gam
52
90
2374
1405
12
a) Infiltration
b) Roomwntilaton
0
0
0
0
475
0
127
0
13
Internal gains O=pants@ 230
Applianoesfother
0
0
0
1
230
0
Subtotal(lines6 to 13)
52
90
2849
1762
14
15
Lessodemalload
Lesstransfer
R�shibufion
Subtotal
Dudloads
29%
35%
0
0
-52
0
0
0
0
-90
0
0
29%
35%
0
0
12
2861
820
0
0
21
1784
621
Total room load
Air required(dm)
0
0
0
0
36821
1661
2405
102
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed
. -'j-!- ,`w`!, rsg!! �K- 2019-Od-2810:01:46
AeZA RitelleG urtrLp Calc=MJ8 Front RSUaces, Page4
...s Homes-2169 Model-8301 Castelle Coutnp Cale=MJ6 Front Door faces:IJVJ
wrightsoft' Right-J® Worksheet Job:
Entire House Date:
s>r
Quick Calcs, Inc.
317St Lucie Law,For(Pierce, FL 34946 Prnre:772-466-6799 Email: quckcalm@aol.mm
1
2
3
4
5
Room name
FVosedwall
Room height
Roan dimensions
Room area
Family Room
17.0 it
10.0 it heaV000l
17.0 x 23.0 ft
391.0 W
LhAng Room
9.0 8
10.0 it heaVmol
1.0 x 115.0 it
115.0 ft'
Ty
Construction
number
U-value
(Btui-A-9
Or
HTM
(Btuh/ft')
Area (ftj
or perimeter (it)
Load
(Btuh)
Area (ftV)
or perimeter (it)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heal
Cool
6
11
-106
0
0
--„j9
0
0
12W45 s °
4A5-20m
4A5-2om
11DO-
13A4or_s
11D0.�^
-6143
0.770
0.770
0.390
0.143
0.390
-Fe-
ne
ne
-ne_
se
se
sv
sw
sw
sw
sw
_sw.
nw
nw
nw
nw
4 06
2156
2156
____19.92.
4.00
10.92
T 46)
2156
2156
^ 12156
21.56
10.92
4.00
21.56
21.56
10.92
'219
36.90
36.90
-.1024
2.19
10.34
2.19
19.31
19.31
28.30
30.64
-10.34
2.19
36.90
36.90
10.34
- 1T0
0
45
�19
" 423
0
' 970
_210
0
0
=231
0
1660
,_,. 199
0
0
--0
0
0
___o
0
0
0
0
' 0
0
--0
'0
0
_ _ 0
- 6
0
- 0
D
W
0
0
_a
0
0
0
0
,.,., , .0
0
0
W
G
-If 3A-0as-"'�^'
4AS-2om
4A5-2om
4A5-2om
'4A5'2om
-11D0-
13A4os
4A5-2om
4A5-2om
11D0
0143
0770
0.770
0.770
0.770
-0.390
0.143
0.770
0.770
0.390
0
0
0
0
0
__--..,.;0
0
0
0
0
0
0
0
0
0
--0
0
0
0
0
-0
0.
0
0
0-
-'''--0
0
0
0
0
: 6
- 0.
0
0'
0
^ �,�0-
0
0
0
0
""' 90
0
- 7
30
0
-0
0
0
0
0
-'T 53
0
7
15
0
_,_,.'_0
0
0
0
0
211
0
155
647
0
0
116
= -0
139
$49
. 0
'0
_
W
G
0
0
0
0
0
0
0
0
C ;
F
-160:30ic'r '
22A-V
=0,632
0.989
.�
-
��0.90
27.69
=(30
0.00
._.4^-,391
391
_,� 391
17
_-„ R50
471
,„..-._626
0
-=115
115
Z 115
9
� 103
249
=1 l
0
61
o)AED exwrson
-115
594
Emelopeloss(gain
2425
2602
1366
1871
12
a) Infiltration
b) Roonnentlation
306
0
82
0
162
0
43
0
13
Internal gains Occupants@ 230
Applianoe.Uother
0
0
900
1
230
0
Subiotal(linestlto13)
2731
3584
1528
2145
14
16
Lessextemalload
Lesstransfer
Redistribullon
Subtotal
Dudloads
29%
35%
0
0
6
2737
785
0
0
11
3595
1252
29%
35%
0
0
15
1542
442
0
0
25
2170
756
Total room load
Airrequired((fm)
3522
158
4847
205
1984
89
2926
124
Calculations approved bvACCA to meet all reouirements of Manual J 8th Ed
�}t wrYgt�tLsolrt- 2019-Oct-2810:01:46
AC15P, Right-SuteOUriwrwl201919.0.01RSU08101 Page
...a Homes-2169 Model- 6301 Castelle Coutnp Cale =MJ8 Frort Doorfaces: NW
wrightsoft• Right -A) Worksheet Job:
Entire House Date:
Quick Calcs, Inc. By.
317 St Lucie Lane, Fort Pierce, FL 34946 P1nre: 772-466-6799 Email: qurkals@aol.ocm
1
2
3
4
5
Room name
FVosed MI
Room height
Room dimensions
Room area
Foyer
7.0 ft
10.0 it heatloaol
1.0 x 82.0 ft
82.0 ft
Dining Room
11.0 it
10.0 ft heaVcool
1.0 x 130.0 ft
130.0 ft'
Ty
Construcfion
number
U-value
(BtuWM F)
Or
HTM
(MUM)
Area (ftl
or perimeter (M
Load
(Btuh)
Area (ft�
or perimeter (M
Load
(Btuh)
Heat
Cool
Gross
WP/S
Heat
Cool
Gros;
N/P/S
Heat
Cool
6
11
.
13A�las
4AS-2cm
4A5-2om
J100
13A-4=
11D0
13A-069"`
4A5-2om
4A5-20m
4A5-2om ^
4A5-2om
11D0-,_.--_-._....0.390
13A4=
4A5-2om
4A5-2om
11D0,
J) la'd. ~
0.143
0.770
0.770
-0.390
0.143
0.390
6143
0.770
0.770
0.770
0.770
rie
ne
ne
-ne_
se
se
sw
SN.
six
w
ex
_W-
nw
m
nw
nw
400
2156
2156
1092
4.00
10.92
- 400
2156
2156
21.56
2156
,r,1092
4.00
21.56
21.56
10.92
219
36.90
36.90
10,34
2.19
10.34
219-
19.31
19.31
28.30
30.64
_10.34
2.19
36.90
36.90
10.34
0.00
0.00
0
0
0
0
0
'0'
0
0
10
0
-0
0
,:. -0
__,__,_,_0
40
0
""'-60'-
129
0
10
293
,223
0
0
0
0
- 194
194
0
0
�0
0
0
0
0
0
0
0
-110
0
7
30
0
_,",_„__0
0
0
0
,,,�^_0
�130
130
0
0
o
0
0
0
0
__0
0
0
0
0
0
;_0
0
0
G
_
W
10
0
60
6,
0
0
14;
20
0
0
0
0_
22
0
44
116
0
0
417
_-„^211
0
0
0
0
`130
0
0
0
W
` fO
6
0
' 0
5
-�20
0
0
0
0
87
7
-73
0
7
' 15
0
---0
0
0
0
�� 0
111
11
-M
0
155
' 647
0
159
0
139
'849
1 0
__0
0
0
0
0
_ 200
0
-47
W
0.143
0.770
0.770
0.390
-0
0
0
0
0
305
05
F ..
_-- -.0� 89
_1
�y2069
�7.69
82
82
6
c)AEDexarrson
310
588
Envelope loss/gain
1033
1250
1515
1944
12
a) Infiltafion
b) Room venfilafion
126
0
34
0
198
0
53
0
13
Intemal gains Ocapants@ 230
ApplianoeJother
0
0
0
0
0
0
Subtotal (lines6 to 13)
1159
1284
1713
1997
14
15
Less odemal load
Lemtransrer
Redistribution
Subtotal
Ductloads
29%
35%
0
0
0
1159
332
'0
0
0
1284
447
29%
35%
0
0
0
1713
491
0
0
0
1997
695
Total room load
Airrequired(CIM)
1491
67
1731
73
2203
99
2692
114
Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed
-fir- =Lanma:m- 2019-Oct-2810:0146
^LcA Riga-SuteOUdversa1201919.0.01 RSU08101 Page 6
...s1-fomes-2169Model-8301 Castelle Coutrp Calc=MJB FrontDoorfaces: NW
I wrightsoft• Right-JO Worksheet Job:
Entire House Date:
By
Quick Calcs, Inc.
317 St Lude Law, Fort Pleroe, FL 34946 Phone: 772-466-6799 Email: qutktalcs@aoLoom
1
2
3
4
5
Room name
6¢ostivall
Room height
Room dimensions
Roomarea
Nook
10.0 ft
8.0 ft heaVcool
10.0 x 6.0 ft
60.0 ft2
Mohan
0 ft
10.0 ft heaV=l
1.0 x 158.0 ft
158.0 ft2
Ty
Conslructon
number
U-value
(BluhAM-T)
Or
HTM
(Bbi"I
Ala (ft�
or perimeter (ft)
Load
(BWh)
Area (ft0
or perimeter (ft)
Load
(BWh)
Heat
Cool
Gross
N/P/S
Heat
Cod
Gros
N/P/S
Heat
Cool
6
11
13A4as
4A5-2om.
4A5-2om
11D0
13A4oas
11D9
0343
0.770
0.770
-_0.390
0.143
0.390
0143
0.770
0.770
0.770
0.770
^�0.390
0.143
0.770
0.770
0.3
ne
ne
ne
_ne
se
se
-sw
sN
sN
sw
sv
_W-
nw
nw
nw
400
2156
21.56
>✓1092
4.00
10.92
400
21.56
2156
2156
2156
^10.92
4.00
21.56
21.56
-�092
� 096
27.69
219
36.90
36.90
,�10.34
2.19
10.34
- 80
0
30
60
0
0
0
0
0
200
0
647
0
109
0
1107
0
0
0
0
00
-0
0
0
p-0
0
-'-0
0
0
"�_ 0
0
0
- -�0
0
0
0
0
0
W
-0
0
0
0
0
0
0
0
0
.
W
13A74acs
4A5-2om
4AS20m
4A5-2om
4A520m
,11130,._;
13A-0as
4A5-2om
4A5-2om
__ �
16B-30ad___,___„"
22A4p1
-fib
19,31
19.31
2830
3064
__1034
219
36.90
36.90
10.34
_-=7.60
0.00
- 0
0
0
0
0
__._p
0
0
0
� 0
:.„„......._..,60
60
-. 0
0
0
0
0,
_--L_0
0
0
0
0
0
0
10
0
0
'0
- -- 0'
0
0
0
0
-�0
0
0
0
O
o
0
0
0
0
-0
0
0
0
0
--0
0
0
0
0
__0
0
0
0
0
---0
,. 0
0
0
0
0
0
0
0
----" 0
0
0
0
0
..-___0
0
0
0
0
G
W
0
0
0
0
C_-_ _-
F
�
_, O,b32
0.989
-. nW'�
�
__,__,`.80
10
�_-_
:_;;-=64
277
,�,_,96
0
,Ai_
_;=, 58
, 158
�
,�," 158
0
�_
,-,,,;,_ 142
0
., �..: 253
0
6
c)AED.1son
-42
-70
Envelopelosslgain
1178
1270
142
183
12
a) Infiltration
b) Room ventilation
144
0
39
0
0
0
0
0
13
Internal gains O=pants@ 230
Applianoeyother
0
0
0
0
0
2000
Subtotal (lines 6 to 13)
1322
1309
142
2183
14
15
Leseodemalload
Leshansler
Redistribution
Subtotal
Dudloads
29%
35%
0
0
0
13M
379
0
0
0
1309
456
29%
35%
0
0
7
148
42
0
0
11
2194
764
Total room load
Air required (dim)
1701
77
1765
75
191
9
2958
126
_ Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-7rw wrlgl�GsoeR- 2019-Oct-2810.01.46
�� Right-Sdte®Universal 201919.0.01 RSU08101 Page 7
SHOWS- 2169MOdel-8301 Castelle Coutnp Calc=MJ8 FrortDoorfaoes:NW
wrightsoft Right-J® Worksheet Job:
Entire House Dace:
Quick Calcs, Inc. By:
317 St Lude Lane, Fort Pierce, FL 34946 Phone: 772466-6799 Email: quG¢alcs@aol.00m
1
2
3
4
5
Room name
EVOSedNall
Room height
Room dimensions
Room area
Master Bedroom
38.0 It
10.0 ft heaVmol
18.0 x 13.0 ft
234.0 ft'
WIC
6.0 it
8.0 ft heaVcool
1.0 x 34.0 ft
34.0 ft'
Ty
Construction
number
U-value
(BWhfiv °F)
Or
HTM
(BWh4t)
Area (ft0
or perimeter (it)
Load
(Btuh)
Area ("
or perimeter (to
Load
(BWh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gros
NIP/S
Heal
Cool
6
11
13A'4as
4A5-2om
4A5-2om'•
11D0„,„�„_„-,
13A4os
11_DO
C143
0.770
0.770
'-,,,-,„_-O.Wi)
0.143
0.390
-We-
ne
ne
_ne_
se
se
�-400
21.56
' 2156
, 10.92
400
10.92
4 00
'2156
2166
2156
2156
_._1092
4.00
21.56
21.56
1092
'-fig
36.90
36.90
19.3.4
2.19
10.34
77219
19.31
19.31
28.30
30.64
10.39
2.19
36.90
36.90
10.34
-- 180
- 30
0'
0
130
0
0
0
0
0
0
0
-15d
0
0
_O
130
0
"u U
0
6
0
0
-" 661
647
0'
�,,�._,, ()
521
0
-328
1107
0
m.,,,. _0
. 6
0
0
;� ..0
�'ry 0
0
0
0
---d
0
0
__. 0
- -d
0
0
0
.G
D,
W
�D
284
0
4 8
0
48
0
-"- U
0
0
0
0'
-0
0
0
0
0
192
0
105
0
W"'
13A-0ocs
4A5-2om.
4A5-2om
4AS-20M
4A5-2om
11D0
4A5-2cm
4A5-2om
11DO
6.143
0.770
0.770
- 0.770
0.770
�0.390
0.143
4 0.770
0.770
0.390
sri
sw
sw
sw
W
ew
_-
nw
nw
w
m
0
0
0
0
0
_.__.�.0
203
0
0
210
-0
0
0
.'0
.0
-„-- ,,,_0
111
0
0
199
0
0
0"
0'
0
0
0
0
0
0
0
0
0
6
0
0
_--_-_0
0
0
0
0
-0
0
0
0
0
-,0
0
0
0
0
=54
0
G
.-.__
W13A4ors
III-
tG
70
0
0
19
�0
51
0
0
19
����DD
F
j68r30ad „-,
22A-Qrl
0,032
0.989
-
.J.
-
„„,_, 090
27.69
�._7,60'
;234
;,_,_.,_,23q
38
-2-1-0_=__374'-�"34
1052
_
34
. 34
6
36
166
0.00
234
6
c)AEDe ursion
-95
-6
Envelope loss/On
3443
2310
389
154
12
a) Infiltration
b) Roomvenlilaton
684
0
183
0
1
1
86
0
23
0
13
Internal gains Oovpants@ 230
Applianrf4other
2
460
0
0
0
0
Subtotal(lines6ht 13)
4127
2953
475
177
14
15
LeseMemalload
Lestransfer
Redistribution
Subtotal
Ductloads
29%
35%
0
0
9
4136
1186
0
0
16
2969
1034
29%
35%
0
0
0
475
136
0
0
0
177
62
Total room load
Air required (rim)
5322
239
4002
170
611
28
238
10
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-rWwrY9'+�sosR- A .RSU08101 2019-Oct-2810:014
...s Homes-2169 Model -8301 Castello Coutrup Calc=MJS FTortDoorfaces:JW Page
WrightsofC Right-M Worksheet Job:
Entire House Date:
Quick Calcs, Inc. ey:
317 St Lude Law, FortPierce, FL 34946 Pwre: 772-466-6799 Email: gUduala@aol.mm
1
2
3
4
5
Room name
Elposeduell
Room height
Room dmensons
Room area
Water Bathroom
5.0 It
8.0 it heat/mol
1.0 x 99.0 it
99.0 ft2
WIC
6.0 it
8.0 it heah'mol
1.0 x 34.0 it
34.0 ft'
Ty
Construction
number
U-value
(Btuhfit -*9
Or
HTM
(BtuhMtl
Area (ft=
or perimeter (ft)
Load
(Btuh)
Area (ft2)
or perimeter (Iq
Load
(Bluh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gros
N/P/S
Heat
Cool
6
11
G
13A-0as
4A5-2om
4A5-2om
11D0
13A-4ocs
11DO
13A'-flocs
4AS-2om
4A5-2om -
4A5-2om
4AS20m =..
11D0_,._._.--_
13A4ozs
4A5-2am
4A5-2om
11D0
,16B-30ad„ s.-„ _
22A-tpl _
'0.143
0.770
0.770
�0.390
ne
, ne
ne
_pe_
:e
se
� :400
2156
2156
10.92
4.00
10.92
2.19
36.90
36.90
-10.34
2.19
10.34
-'0
0
0
0
• 0
0
0
0
----0
0
0
,„,_,-0
6
0
0
` 0
-6
0
0.
0
---0
0
0
- 0
6
0.
0
-0
6
A
0
0
eD,
W
L-D
W'"
N-
0.143
0.390
0143
0770
0.770
0.770
0.770
0.390
0.143
0.770
0.770
0.390
�,.-003P
0.969
40
0
40
0
160
0
88
0
48
0
48
0
192
0
105
0
sv
srr
sw
sw
se'
_W-
ma
nw
nw
w
_;
-
400
2156
2156
21.56
2156
e�1092
4.00
21.56
21.56
10.92
.090
27.69
219
1931
19.31
28.30
30,64
-10.34
219
36.90
36.90
10.34
_, :f60
0.00
0
0
0
0
,0
---0
0
0
0
6
;,„� 99
99
'- 0
0
0
0
0
--0
0
0
0
0
m 99
5
0-`0
0
0
' '. 0
0
---0
0
0
0
0
,--,89
136
0
0
0
• 0
0
0
A
'0
0
_0
0
0
0
0
�„_ 34
34
- 0
0
0
0
0
--0
0
0
0
0
"' 0
0
0
0
0
--0
0
0
0
0
0
0
0
0
• '0
,_,_,_,_-.0
0
0
0
0
W
�0
0
0
0
0
„�158
0
D
C-
F
39
-6
�._ ,_�30
166
;,_-i54
0
6
c) AED exmr ion
-8
6
Emelope losagain
387
238
389
154
12
a) Infiltration
b) Roomvenfilation
72
0
19
0
1
86
0
23
0
13
Intemal gains O=pants@ 230
Appliancesrother
0
0
0
0
0
0
Subtotal(lines6 to 13)
459
257
475
177
14
15
Less edema]load
Lesstransfer
Redistribution
Subtotal
Ductloads
29%
35%
0
0
7
466
134
0
0
11
268
93
29%
35%
0
0
0
475
136
0
0
0
177
62
Total room load
Air required (o1n)
599
27
362
15
611
28
238
10
Calculations approved bVACCAto meetall requirements of Manual J 8th Ed.
-rk- wrf9hGsoTi- 2019-Od-281001A6
RigH-SdLOUrimml201919.0.01 RSU08101 Page 9
...a Hones-2169 Model- 8301 Castelle CouLnp Calc=MJ8 FrortDoorfaces:NW
wrightsoft• Right-JO Worksheet Job:
Entire House Dace:
Quick Calcs, Inc. By.
317 St Lude Lam, FortPleree, FL 34946 Phone: 772-466-6799 Email: qudmalcs@aol.mm
1
2
3
4
5
Room name
Elposed%di
Room height
Room dimensions
Room area
Linen
0 it
8.0 it heat/cool
5.0 x 4.0 It
20.0 ft2
utlity
O ft
8.0 it heat/cool
7.0 x 12.0 It
84.0 ft2
Ty
Construction
number
U-value
(BtjWF)
Or
HTM
(Btuml
Area (ft')
or perimeter (11)
Load
(BWh)
Area (M
or perimeter (f0
Load
(Bluh)
Heat
Cod
Gross
N/P/S
Heat
Cool
Gros
NOS
Heat
Cool
6
11
G
13A-0ofs
4A5-2om
4AS2orn
111)0-
13A4=
11D0
13A-0as
0S2om
4A5.20M
4A5-2am
4AS20m
-11D0L___-.__
13A-4ocs
4A5-2om
4A5.2om
11D0
16&30atl.
22A-tpl
"--OA43
0.770
0.770
0.390
0.143
0.390
0.143
0.770
0770
0.770
0.770
.390
ne
ne
ne.:,
_W_
se
se
S
, sa
sW
sv
sv
_W_
nW
my
ma
my
=
400
'2156
2156
`10.92
4.00
10.92
__ 400
2156
2156
'2156
2156
10.92
4.00
21.56
21.56
1092
� �,.0.90
27.69
219
36.90
36.90
10.34
2.19
10.34
219
1931
1931
2830
30.64
-10.34
2.19
36.90
36.90
10.34
0
0
0
-0
0
0
0
_ _ 0
0
0
0
- '0
0
. 0
6
- 0
0
0
0
' 0
0
0
0
'0
0
0
0
0
0
0
0
0
0
0
-0
0
0
W
L-D
W
G
W
G
_
C�_,�
F
0
0
0
0
0
0
0
0
-0
0
0
0
0
0
0
0.
0
;'----0
0-
0
0
0
0
_ 6`
0
0
0
0.
r_ o
0
0
0
0
0
__0
0
0
0
D
0
0
0
0
0
0
__0
0
0
0
0
0
--a
0
0
0
0
0
�___0
0
0
0
0
0.143
0.770
0.770
0.390
v0.032
0.989
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
__o
0
0
0
0
0
0
0
0
0
0
0
0
1.80
0.00
=20
20
__'20
0
,119
0
=32
0
'-`�.89
84
.,.v84
0
w,75
134
0
0
6
c)AED emersion
-1
-20
Envelope lossigain
18
31
75
115
12
a) Infiltration
b) Roomeentilation
0
0
0
0
0
0
0
0
13
Intemalgaim O=pants@ 230
Applianceslother
0
0
0
0
0
500
Subtolal(llnes6to13)
18
31
75
615
14
15
Lesseldemalload
Lesstransfer
Redistribution
Subtotal
Dudloads
29%
35%
0
0
0
18
5
0
0
0
31
11
29%
35%
0
0
9
84
24
0
0
16
631
220
Total room load
Air required(dm)
23
1
42
2
109
5
850
36
Calculations approved WACCA to meet all requirements of Manual J 8th Ed
,-rk- �^!-rtgti, �a rt' 2019-Od-2610:01.46
U Riga-S rte®Uriversa1201919.0.01 RSU08101 Page 10
...s Homes-2169Model-8301Castelle Coutnp Calc=MJ8 Frort Door faces: NW
wrightsoft Right-JO Worksheet Job:
Entire House Date:
Quick Calcs, Inc. By:
317 St Lucie Lane, Fort Pierce, FL 34946 Ptore: 772-466-6799 Email: gdd=los@aol.eom
1
2
3
4
5
Room name
EVosedvrall
Room height
Room dimensions
Room area
Hall 1
O ft
8.0 It heatl000l
7.0 x 5.0 It
35.0 fl'
Pantry
O ft
8.0 ft heatloaol
3.0 x 4.0 It
12.0 12
Ty
Construdon
number
U-value
(Btuhfti°F)
or
HTM
(Btuh)ft=)
Area (111
or perimeter (9)
Load
(Stuh)
Area (M
or perimeter (it)
Load
(BWh)
Heal
Cool
Gros
N/P/S
Heat
Cool
Gros;
WP/S
Heat
Cool
6
.
11
13A4ocs
4A5-2dm
11D0. - __ _
13A-0OCs
11D0.„
13li4as �•"""�"
4A5-2om
4A5-2om
4AS-2am
4A540m
.11D0
13A-4ocs
4A5-2om
4A5-2am
11D0_
,16B30ad__'-_
22A-tpl
f).143
0.770
..: 0.770
0.390
0.143
0.390
0.143
0.770
0.770
0.770
0.770
ne
ne •
ne
-ne:
se
se
67v
srr..
av
sH
se
_W-
nw
rw
m
m
400
21.56
2156
1092
4.00
10.92
400
2156
2156
1 2156
2156
_�10.92
4.00
21.56
21.56
10.92
090
27.69
2.19
36.90
36.90
10.34
2.19
10.34
2.19
1931
1931
2630
3064
-.10.34
2.19
36.90
36.90
10.34
�,J,60
0.00
0
0
, 0
0
0
0
0
0
0
-___,_0
0
0
--0
= 0
0
__O
0
0
0-0-0-0
0
0
__O
0
0
0
0.
__,_0
0
0
0
0
0
0
0
0
,. 0
0
0
0
0
0
0
0
I�G4A5r2om
DODO,
W
0-
0
W- -
G
--0
0
0
0
0
„0
0
0
0
0
'--0
0
0
0
0
0
� A
0
0
0
0
0
0
0
0
0
0
0
0
01
.0
0
0
,-_ -0
0
0
0
0
'-0
0
0
0
0
0:-_---
0
0
0
0
0
0
0
0
0
0
'-0
0
0
0
0
�, ._0
0
0
0
0
W
---0.390
i 0.143
0.770
0.770
0.390
�0,032
0.989
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
D
F
--35
35
�35
0
- 31
0
��56
0
_._..._ 12
12
�1-_12
0
�11,
0
79
_ 0
6
c)AED exanson
-2
-1
En elope losstgain
31
54
11
19
12
a) Infilhallon
b) Roomventilaton
1
0
0
0
0
1
0
0
0
0
13
Internal gains'. O=pants@ 230
Applianoas/other
0
0
0
0
0
0
Subtotal (lines 6 to 13)
31
54
11
19
14
15
LesseMemalload
Lestransfer
Redistribution
Subtotal
Ductloads
29°Ao
35%
0
0
-31
0
0
0
0
S4
0
0
29%
35%
0
0
0
11
3
0
0
0
19
6
Total room load
Air required (am)
0
0
0
0
14
1
25
1
Calculations approved bVACCA to meet all requirements of Manual J 8th Ed.
-'}/- wri9hisof[- 2019-Oct-2810:01:46
�A "" ' Riglt-SUteQUniveml20l919.0.01 RSU0810l Page 11
...s Homes-2169 Model- 8301 Castelle Coutnp Calc=MJ8 Frort Doorfaees:NW
+wrightsoft• Duct System Summary o te:
Entire House By:
Quick Calcs, Inc.
317 St Lucie Law, Fort Pierce, FL 34946 Phone: 772-466-6799 Email: quickcelcs@aol.com
For: Adams Homes -2169 Model,Adams Homes
8301 CRISTELLE COURT, FT. PIERCE, FL34951
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest fiction rate
Actual air flow
Total effective length (TEL)
Heating
0.50
in H2O
0
in H2O
0.50
in H2O
0.250 / 0.250
in H2O
0.269
in/100ft
1333
cfm
186 It
Cooling
0.50
in H2O
0
in H2O
0.50
in H2O
0.250 / 0.250
in H2O
0.269
in/100ft
1333
cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
Bath
h 1175
53
44
0.506
5.0
Ox0
MFx
8.8
90.0
st3
Bedroom2
h 3682
166
102
0.481
8.0
Ox0
VIFx
14.0
90.0
st3
Bedroom3
c 1971
76
84
0.440
6.0
Ox0
MFx
23.6
90.0
stl
clout
h 412
19
7
0.516
4.0
Ox0
VIFx
6.8
90.0
st3
Dirirg Room
c 2692
99
114
0.332
6.0
OX 0
VIFX
40.6
110.0
st4
Family Room
c 2423
79
103
0.431
7.0
OXO
VIFX
26.1
90.0
st1
Family ROOmA
c 2423
79
103
0.441
7.0
OXO
VIFX
23A
90.0
st1
Foyer
c 1731
67
73
0.334
6.0
Ox0
MFx
39.8
110.0
st4
Kitcwn
c 2958
9
126
0.281
7.0
Ox0
VIFx
47.9
130.0
st5
Linen
c 42
1
2
0.347
4.0
Ox0
VIFx
54.1
90.0
st2
Living Roam
c 2926
89
124
0.325
7.0
OX 0
MFx
43.6
110.0
st4
Master Bailroom
h 599
27
15
0.353
5.0
OXO
MFx
51.8
90.0
st2
Master Bedroom
h 2661
120
85
0.360
7.0
Ox0
VIFX
48.8
90.0
st2
Master Bedmom-A
h 2001
120
85
0
0
OXO
VIFx
0
0
Nook
h 1701
77
75
0.278
7.0
OX 0
VIFx
49.8
130.0
st5
Pantry
c 25
1
1
0.327
4.0
Ox 0
VIFx
42.8
110.0
st4
suroomBedroom4
h 4281
193
134
0.417
8.0
Ox0
VIFX
30.0
90.0
st1
utility
c 850
5
36
0.269
4.0
Ox0
VIFx
55.6
130.0
st5
mc1
h 611
28
10
0.348
4.0
Ox0
VIFX
53.6
90.0
st2
WIC
h 611
28
10
0.338
4.0
Ox0
VIFx
58.1
90.0
st2
C Wrightsoft" 2019-ocF2e 1o:o1:47
-- -.-•.�.�....v...., Rlgh-Sute®Uriversa1201919.0.01 RSU08101 Page 1
...s Homes-2169Model-8301Castelle Coutnp Galt=MJB Fror9Doorfaces:Nw
Supply Trunk Detail Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(CIM)
FR
(fpm)
(in)
(in)
Material
Trunk
st2
PeakAVF
203
122
0.338
581
8.0
0 x 0
VinIFIX
st5
PeakAVF
90
236
0.269
535
9.0
0 x 0
VinlFlx
s14
st4
PeakAVF
346
549
0.269
514
14.0
0 x 0
VInIFIX
st1
st1
PeakAVF
773
973
0.269
697
16.0
0 x 0
VInIFIX
st3
PeakAVF
237
153
0.481
537
9.0
0 x 0
VInIFIx
Name
Grille
Size (in)
Htg
(cim)
Clg
(cfm)
TEL
(ft)
Design
FR
Ueloc
(fpm)
Diam
(in)
HxW
(in)
Stud/Joist
Opening (in)
Dud
Matl
Trunk
rbi
Ox0
1333
1333
0
0
0
0
Ox 0
VIFx
wri_ghtsoft• zo19-oe-zelo:al:a't
.•rt••Right-Stte®UNvrW201919.0.01 RSU08101 Paget
...s Homes-2169Model-8301 Castelle Coutnp Calc=MJB Fmrt Doorfaces:NW
Vi
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction:
Permit #:
JoUnformation
Builder: Adams Homes Community: Lot: NA
Address: 8301 Cristelle Court
City: Ft. Plerce State: FL Zip: 34951
Air Leakagp Test, Results Passing results must meet either the Performance, Prescriptive, or ERI Method
I.O PRESCRIPTIVE METHOD-Thebuildingor dwelling unit shall be tested and verified :as having,anair leakage rate,of not exceeding 7 air.
changes per'hourat a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones, l and,2.
Q P,ERF.ORMANCEor ERI METHOD -The building or dwelling unit shall tie tested and!verified as,having an air leakage rate of not exceeding,..
. the selected,ACH(50) value, as shown on Form R405-2017 (Performance) or R406-2017 (ERI)„section labeled ,as infiltration, sub -section ACH50.
ACH(50) specified on Form, R405-2017-Energy Calc (Performance) or R406-2017
x 60 = 19428 = Method for calculating building volume:
CFM(5O) Building Volume ACH(50)
O Retrieved from architectural plans
❑ PASS
0 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(0, (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and Flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing :Company.
Company Name: "Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
10/28/2019 10:00:68 AM EnergyGauge® USA 6.0.03 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1