Loading...
HomeMy WebLinkAboutR2C1 -Dry Hydrant 90 A DIVISION OR W.W. GAY sciens FIRE A INTEGRATED g SYSTEMS,INC. FIRE PROTECTION MATERIAL SUBMITTALS FOR: FPL SOLAR Dry Hydrant 3650 RICO ROAD FT. PIERCE, FL 34945 Date: May 27, 2020 Our Project Number: FP-265420 Project Manager: Joe Furlong Prepared By: Thomas Bender The materials submitted represent the quality of materials specified. All materials may be substituted at this contractor's discretion for like equivalent materials. W. W. Gay Fire & Integrated Systems, Inc. 2251 Rosselle Street / 2500 N.E. 18th Terrace Jacksonville, Florida 32204 / Gainesville, Florida 32609 904-387-7973 / 352-380-0317 GENERAL INFORMATION P�HAOUNDR�MTE Product Specifications System: PVC Schedule 40 Pressure Pipe and Fitting System Scope: This specification covers PVC Schedule 40 pipe and fittings for pressure applications. This system is intended for pressure applications where the operating temperature will not exceed 140°F. Specification: Pipe and fittings shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with a Cell Class of 12454 as identified in ASTM D 1784. PVC Schedule 40 pipe shall be Iron Pipe Size (IPS) conforming to ASTM D 1785. PVC Schedule 40 fittings shall conform to ASTM D 2466. Pipe and fittings shall be manufactured as a system and be the product of one manufacturer. All pipe and fittings shall be manufactured in the United States. Pipe and fittings shall conform to NSF International Standard 61 or the health effects portion of NSF Standard 14. Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall conform to all applicable plumbing, building, and fire code requirements. Buried pipe shall be installed in accordance with ASTM F 1668 and ASTM D 2774. Solvent cement joints shall be made in a two step process with primer conforming to ASTM F 656 and solvent cement conforming to ASTM D 2564. The system shall be protected from chemical agents, fire stopping materials, thread sealant, plasticized vinyl products, or other aggressive chemical agents not compatible with PVC compounds. Systems shall be hydrostatically tested after installation. WARNING! Never test with or transport/store compressed air or gas in PVC pipe or fittings. Referenced Standards*: ASTM D 1784 Rigid Vinyl Compounds ASTM D 1785 PVC Plastic Pipe, Schedule 40 ASTM D 2466 PVC Plastic Fittings, Schedule 40 ASTM D 2564 Solvent Cements for PVC Pipe and Fittings ASTM D 2774 Underground Installation of Thermoplastic Pressure Piping ASTM F 656 Primers for PVC Pipe and Fittings ASTM F 1668 Procedures for Buried Plastic Pipe NSF Standard 14 Plastic Piping Components and Related Materials NSF Standard 61 Drinking Water System Components - Health Effects *Note: Latest revision of each standard applies. Short Specification: Pipe and fittings shall be manufactured from PVC compound with a cell class of 12454 per ASTM D 1784 and conform with NSF International Standards 14 and 61. Pipe shall be iron pipe size (IPS) conforming to ASTM D 1785. Fittings shall conform to ASTM D 2466. All pipe and fittings shall be produced by a single manufacturer and shall be installed in accordance with manufacturer's recommendations and applicable code requirements. Buried pipe shall be installed in accordance with ASTM F 1668 and ASTM D 2774. Solvent cements shall conform to ASTM D 2564, primer shall conform to ASTM F 656. The system is to be manufactured by Charlotte Pipe and Foundry Company and is intended for pressure applications where the temperature will not exceed 140°F. 15 GENERAL INFORMATION Plastics Technical Manual Product Certification MADE IN USA This is to certify that all Plastic Pipe and Fittings manufactured by Charlotte Pipe and Foundry Company are manufactured in the United States and conform to the following standards: PVC SCH. 40 SOLID WALL PIPE PVC SDR 35 SEWER MAIN PIPE ASTM D 1784, ASTM D 1785, ASTM D 2665 ASTM D 1784, ASTM D 3034, SDR 35 FHA UM 79a ASTM D 3212, ASTM F 477 FEDERAL SPECIFICATION L-P-320a NSF STANDARD 14 AND 61 PVC SEWER AND DRAIN PIPE ASTM D 1784, ASTM D 2729 PVC SCH. 40 DWV CELLULAR CORE PIPE ASTM D 4396, ASTM F 891 PVC THIN WALL PIPE & FITTINGS NSF STANDARD NO. 14 ASTM D 1784, ASTM D 2949 NSF STANDARD NO. 14 RePVC°SCH. 40 DWV PIPE WITH RECYLED CONTENT ASTM D 4396, ASTM F 1760 CPVC FLOWGUARD GOLD° CTS PIPE & FITTINGS NSF STANDARD NO. 14 ASTM D 1784, ASTM D 2846 FHA U M-61a PVC SCH. 40 DWV FITTINGS NSF STANDARD NO. 14 AND 61 ASTM D 1784, ASTM D 2665, ASTM D 3311, CSA LISTED ON SPECIFIED ITEMS ASTM F1866 FHA UM 79a CPVC REUZE° CTS PIPE & FITTINGS FEDERAL SPECIFICATION L-P-320a ASTM D 1784, ASTM D 2846 NSF STANDARD NO. 14 NSF STANDARD NO. 14 PVC SDR-21 AND SDR-26 PRESSURE PIPE CPVC CHEMORAIN°SCH. 40 PIPE & FITTINGS ASTM D 1784, ASTM D 2241 ASTM D 1784, ASTM F 2618 NSF STANDARD NO. 14 AND 61 NSF STANDARD 14 PVC SCH. 40 PRESSURE FITTINGS ABS SCH. 40 DWV CELLULAR CORE PIPE ASTM D 1784, ASTM D 2466 ASTM D 3965, ASTM F 628 NSF STANDARD 14 AND 61 NSF STANDARD NO. 14 c N S F1 us-dwv PVC SCH. 40 WELL CASING PIPE ASTM D 1784, ASTM F 480 ABS PLUS!-SCH. 40 DWV CELLULAR CORE PIPE NSF STANDARD NO. 14 AND 61 ASTM D 3965, ASTM D 4396, ASTM F 1488 PVC SCH. 80 PIPE ABS SCH. 40 DWV FITTINGS ASTM D 1784, ASTM D 1785 ASTM D 3965, ASTM D 2661, ASTM D 3311 NSF STANDARD NO. 14 AND 61 FHA UM 79a FEDERAL SPECIFICATION L-P-322b PVC SCH. 80 FITTINGS NSF STANDARD NO. 14 ASTM D 1784, ASTM D 2467 ASTM D 2464 ASTM F 1970 NSF STANDARD NO. 14 AND 61 CHARLOTTE PIPE AND FOUNDRY COMPANY ABS Plus, ChemDrain, ReUze and RePVC are registered trademarks of Charlotte Pipe and Foundry Company. FlowGuard Gold is a registered trademark of Lubrizol Corp. 22 PRODUCT DATA PcHAOU DIPE AND R•MTE 1Sq'N Pipe Reference Guide NSF Sizes Available Product 1/4 3/8 1 1/2 1 3/4 1 1 11/4 1 11/2 2 21/2 3 1 4 15 6 1 8 110 12 114 115 16 ChemDrain° CPVC • • • •Schedule 40 * • • FlowGuard Gold° • • • • • • CPVC CTS SDR 11 ReUze° CPVC CTS SDR 11 • • • • • PVC Schedule 80 • • • • • • • • • • • • • • • • • PVC Schedule 40 • • • • • • • • • • • • • • • • PVC Schedule 40 DWV * • • • • • • • • • • • • RePVC° Schedule 40 DWV • • ® • • • with Recycled Content PVC Schedule 30 * • PVC DWV Foam Core * • • • • • • • • PVC Well Casing • • • • • • PVC SDR 13.5 (PR315) • PVC SDR 21 (PR200) • • • • • PVC SDR 26 (PR160) • • • • PVC SDR 35 Sewer Main • • Belled-End *t PVC SDR 35 Sewer Main Gasketed *t PVC D 2729 Sewer and Drain *t • • ABS DWV Foam Core * • • • • • ABS Plus° Foam Core DWV* • • • • * Non-Pressure You can 't beat the system ° t Not NSF Listed N otes: 1. End treatments are Plain and Belled. Consult factory for availability. 2. Lengths are 10 and 20 feet(14 and 20 feet for Gasketed Sewer Main). Consult factory for availability and non-standard lengths. 3. PVC Schedule 40 Bell End and PVC Well Casing pipe lengths for sizes 4", 6",and 8"are 20 feet plus the bell (20 foot laying length). 4. PVC SDR 35 Sewer Main Pipe in 14 foot lengths are 14 feet plus the bell (14 foot laying length). ABS Plus, ReUze, RePVC, ChemDrain and"You can't beat the system"are registered trademarks of Charlotte Pipe and Foundry Company. FlowGuard Gold is a registered trademark of Lubrizol Corp. 23 PRODUCT DATA PcHARLDR•MTE PVC P*ipe , Schedue 40 NSF >> PVC Schedule 40 Pipe - Plain End PVC SCHEDULE 40 (WHITE) PLAIN END PVC 1120 ASTM D 1785 MAX WORK PART NO. NOM.SIZE UPC# AVG.00(IN.) MIN.WALL(IN.) PRESSURE WT.PER 611942- AT 23'C OR 73'F 100 FT.(LBS.) PVC 4005 1/2" x 10' 06658 .840 .109 600 PSI 15.9 PVC 4005 1/2" x 20' 03922 .840 .109 600 PSI 15.9 PVC 4007 3/4" x 10' 06661 1.050 .113 480 PSI 21.1 PVC 4007 1/4" x 20' 03925 1.050 .113 480 PSI 21.1 PVC 4010 1" x 10' 06664 1.315 .133 450 PSI 31.3 PVC 4010 1" x 20' 03928 1.315 .133 450 PSI 31.3 PVC 7100* 1V," x 10' 03945 1.660 .140 370 PSI 42.4 PVC 7100* 11/4" x 20' 03946 1.660 .140 370 PSI 42.4 PVC 7112* 11/2" x 10' 03947 1.900 .145 330 PSI 50.7 PVC 7112* 11/2" x 20' 03948 1.900 .145 330 PSI 50.7 PVC 7200* 2" x 10' 03949 2.375 .154 280 PSI 68.1 PVC 7200* 2" x 20' 03950 2.375 .154 280 PSI 68.1 PVC 4025$ 21/2" x 20' 04205 2.875 .203 300 PSI 108.0 PVC 7300* 3" x 10' 03951 3.500 .216 260 PSI 141.2 PVC 7300* 3" x 20' 03952 3.500 .216 260 PSI 141.2 PVC 7400 4" x 10' 03953 4.500 .237 220 PSI 201.2 PVC 7400 4" x 20' 03954 4.500 .237 220 PSI 201.2 PVC 7500 5" x 20' 04837 5.563 .258 190 PSI 272.5 PVC 7600 6" x 10' 03955 6.625 .280 180 PSI 353.7 PVC 7600 6" x 20' 03956 6.625 .280 180 PSI 353.7 PVC 7800 8" x 10' 13087 8.625 .322 160 PSI 532.3 PVC 7800 8" x 20' 03958 8.625 .322 160 PSI 532.3 PVC 7910 10" x 20' 03959 10.750 .365 140 PSI 754.7 PVC 7912 12" x 20' 03961 12.750 .406 130 PSI 997.9 PVC 7914 14" x 20' 04862 14.000 .437 130 PSI 1180.1 PVC 7916 16" x 20' 04918 16.000 .500 130 PSI 1543.1 *Dual Marked ASTM D 1785 and ASTM D 2665. t Triple Marked ASTM D 1785&ASTM D 2665&ASTM F 480. A WA R N I N G #Dual Marked ASTM D 1785&ASTM F 480. NOTE: When ordering,please specify plain end or bell end. 7T/ sting with or use of compressed air or gas in PVC/ABS NSF Listed.Meets All Requirements of ASTM D 1784 and ASTM D 1785. CPVC pipe or fittings can result in explosive failures and cause severe injury or death. • NEVER test with or transport/store AIR/GAS compressed air or gas in PVC/ABS/CPVC pipe or fittings. NEVER test PVC / ABS / CPVC pipe or fittings with compressed air or gas,or air r over water boosters. " ONLY use PVC/ABS/CPVC pipe for water or approved chemicals. Refer to warnings in PPFA User Bulletin 4-80 and ASTM D 1785. 29 CHARLOTTE PIPE AND FOUNDRY COMPANY® SUBMITTAL 1 • ■ CHARLOTTE • ■ ■ PVC SCHEDULE 40 PRESSURE PIPE AND FITTING SYSTEM Date: Job Name: Location: Engineer: Contractor: Scope: This specification covers PVC Schedule 40 pipe and fittings for pressure applications. This system is intended for pressure applications where the operating temperature will not exceed 140' F. Specification: Pipe and fittings shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with a cell class of 12454 as identified in ASTM D 1784. PVC Schedule 40 pipe shall be Iron Pipe Size (IPS) conforming to ASTM D 1785. Injection molded PVC Schedule 40 fittings shall conform to ASTM D 2466. Pipe and fittings shall be manufactured as a system and be the product of one manufacturer.All pipe and fittings shall be manufactured in the United States. Pipe and fittings shall conform to NSF International Standard 61 and the health-effects portion of NSF Standard 14. Installation: Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall conform to all applicable plumbing, fire, and building code requirements. Buried pipe shall be installed in accordance with ASTM F 1668. Solvent cement joints shall be made in a two-step process with primer conforming to ASTM F 656 and solvent cement conforming to ASTM D 2564. The system shall be protected from chemical agents, fire-stopping materials, thread sealant, plasticized-vinyl products or other aggressive chemical agents not compatible with PVC compounds. The system shall be hydrostatically tested after installation. WARNING! Never test with or transport/store compressed air or gas in PVC pipe or fittings. Doing so can result in explosive failures and cause severe injury or death. Referenced Standards: ASTM D 1784: Rigid Vinyl Compounds ASTM F 1668: Procedures for Buried Plastic Pipe ASTM D 1785: PVC Plastic Pipe, Schedule 40 NSF Standard 14: Plastic Piping Components&Related Materials ASTM D 2466: PVC Plastic Fittings, Schedule 40 NSF Standard 61: Drinking Water System Components- ASTM D 2564: Solvent Cements for PVC Health Effects Pipe and Fittings lz> Schedule 40 /77 6� - - Tapered Socket Dimensions \ B PVC SCHEDULE 40•ASTM D 2466 � Schedule 80 and Schedule 40 Socket Diameter Schedule Schedule 40 Quarter Bend Eighth Bend Cross Street Quarter Nominal Entrance Bottom Tolerance Socket Lengt80 h Socket Length Bend Size A B C(Minimum) C(Minimum) /2 0.848 0.836 ±0.004 0.875 0.688 3/4 1.058 1.046 ±0.004 1.000 0.719 1 1.325 1.310 ±0.005 1.125 0.875 11/4 1.670 1.655 ±0.005 1.250 0.938 Male Adapter Bushing Female Adapter Cap 11/2 1.912 1.894 ±0.006 1.375 1.094 2 2.387 2.369 ±0.006 1.500 1.156 21/2 2.889 2.868 ±0.007 1.750 1.750 - - - 3 3.516 3.492 ±0.008 1.875 1.875 - 4 4.518 4.491 ±0.009 2.250 2.000 6 6.647 6.614 ±0.011 3.000 3.000 Plug Tee Coupling 8 8.655 8.610 ±0.015 4.000 4.000 10 10.780 10.735 ±0.015 5.000 5.000 12 1 12.780 12.735 ±0.015 6.000 6.000 PIPE REFERENCE GUIDE Not all fitting Sizes Available patterns shown Product lh 1 3/4 1 1 111/4 11/2 2 12'/.l 3 1 4 1 5 1 6 1 8 110 1 12 14 116 PVC Schedule 40 • • • • • • • • • • • • • • • • P" Charlotte Pipe and Foundry Company-P.O.Box 35430 Charlotte,NC 28235-(800)438-6091 -www.charlottepipe.com Charlotte Pipe and Charlotte Pipe and Foundry Company are registered trademarks of Charlotte Pipe and Foundry Company. FO-SUB-PVC-40(5-30-19) Reflective Dry Hydrant Sign Dry Fire Hydrant Item Number: DHS Availability: In Stock- Usually ships In 1 Business Day Weight: 3.50 Lbs (& • Dimensions - 12" x 18" Fire Department • Matenal - Aluminum (will not rust) • Surface - Reflective Poly Sheet for Use Only locating In the dark FireHoseDirect.com `® Dry hydrant 12"x 18" reflective sign to mark "No Parking" area around a dry hydrant installation. Metal construction of aluminum will not rust. Highly reflective for night locating by fire department. Sign mounts using 2 approximately 3/8" holes aligned vertically along the center line. Mounting hardware not included. Carbon Steel 6" Flange x 4 1/2" Male NH Item Number: FGM456 Availability: Special Order - Usually ships In 4 - 8 Weeks Weight: 21.00 Lbs • • Outside Diameter Flange -11" • Flange Thickness - 1" • Number of Holes - 8 • Diameter Holes - 7/8" • Diameter Bolts - 3/4" • Bolt Circle - 9 1/2" Carbon Steel 6" Flange x 4.5' Male NH Dry Hydrant Underwater 6" Strainer Support Item Number: DHU6SS Availability: In Stock - Usually ships In 1 Business Day Weight: 2.62 I.bs Our"Made in the USA" dry hydrant underwater strainer supports sizes 6" barrel strainers. Constructed of bronze, this support clamp easily fastens to a 1 inch pipe or rod (pipe/rod not included) by two stainless bolts. This will keep your strainer off of the bottom of your water source and keep debris from entering the pump. Cradles and supports dry hydrants Intake at proper level Includes two stainless steel locking screws 1" O.D. pipe or rod is used for support (rod not included). Horizontal 6" PVC Strainer With Back Flush Cover Item Number: HSBFC6 Availability: In Stock - Usually ships In 1 Business Day Weight: 13.90 Lbs • Material - Schedule 40 PVC • PVC Size - 6 inch • Open Area - Approx, 125 square inches • End Cap - Brass • Length - 40 inches • Internal Diameter- 6 inches • External Diameter - 6 5/8 inches • Weight - 14 pounds Six inch horizontal pvc strainer with brass back flush cover. The horizontal back flush is the preferred strainer which allows the pvc line to be back Rushed. Debris that enters from roadside hydrant fitting opening can be removed by reverse flushing the line into the water source. The back flush flap will open to aid in releasing debris. Back flush flap is drawn closed during suction operation. Install so that flap hangs down due to gravity. Requires a 6" double female PVC coupling for attachment to 6" PVC pipe. Aluminum 4 1/2" NH Rocker Lug Cap Item Number: ACR45 Availability: In Stock- Usually ships In 1 Business Day Weight: 1.95 Lbs • Made in the USA • Female Side - 4.5 inch NH/ NST • The Female Will Only Connect To A Male 4.5 NH / NST • Stainless Steel Chain - 12 inches `�w..w..we• Material - 6061 T6 Aluminum • Finish - Hard Coat Anodized • Complies With NFPA 1963 (Corrosion Resistance) 0. 00 Aluminum adapters are fabricated from seamless extruded 6061-T6 aluminum and hard coat anodized per MIL-A-8625 Type III, Class 1. Threads have a blunt start Higbee cut with indicators on adjacent lugs. Part identifications are permanent and stamped prior to hardcoat. Adapters and components meet the requirements of NFPA 1963. Gasket installed. Oately, Technical Specification Purple Primer — NSF Listed Description • Purple-tinted aggressive primer for use on PVC and CPVC pipe and fittings. • Lo-V.O.C. Solvent Cement meets California South Coast Air Quality - Management District (SCAQMD) 0� 1168/316A or BAAQMD Method 40 and various FOR CpyC,pYC environmental requirements. PURPLE PRIMER,-% • Removes surface dirt,grease and grime +'s {� as well as softens the pipe surface to innPaiMa�ofl.PYOPUP a allow a fast, secure solvent weld. ; ,. • For use in areas where plumbing code calls for verification that a primer has been used. • N SF and IAPMO Listed. • Meets ASTM F656.Listings NSF 0 NSF Standard 61 for PW, IAPMO Listed DWV and Sewer Waste Maximum VOC per SCAQMD 1168/316A or BAAQMD Method 40: 550 g/L INGREDIENTS(CAS Number) Acetone (67-64-1), Cyclohexanone (108-94-4), Methyl Ethyl Ketone (78-93-3), Red Dye (4477-76-6) Violet Dye (81-48-1),Tetrahydrofuran (109-99-9) MSDS Number: 1402E Product Size Qty WRt Product Size Qtv W9t Number Number 30755 4 oz. 24 8 lbs. 307553 4 oz. 48 8 lbs. 30756 8 oz. 24 14 lbs. 307563 8 oz. 36 14 lbs. 30757 16 oz. 24 25 lbs. 307573 16 oz. 10 25 lbs. 30758 32 oz. 12 24 lbs. 307583 32 oz. 6 24 lbs. 30759 Gallon 6 46lbs. Oatey Co. Phone: 1-800-321-9532 150goof 4700 West 160 th St. Phone: 1-800-321-9535 � Cleveland, OH 44135 Visit www.oatey.com for Update Page 1 of 3 Oately, Technical Specification Purple Primer — NSF Listed CHEMICAL PROPERTIES Appearance Purple Liquid Density 6.97±0.2 Ibs/gallon Shelf Life 3 Years from Mfg. Date Precautions Read all information carefully before using this product. DANGER!: CAUSES SERIOUS EYE IRRITATION. HARMFUL IF INHALED. MAY CAUSE DROWSINESS OR DIZZINESS. MAY CAUSE RESPIRATORY IRRITATION. REPEATED EXPOSURE MAY CAUSE SKIN DRYNESS OR CRACKING. Long term overexposure to solvents may cause damage to the brain, nervous system, reproductive system, respiratory system, mucous membranes, liver and kidneys. Contains a chemical classified by the US EPA as a suspected possible carcinogen. KEEP OUT OF REACH OF CHILDREN. PRECAUTIONS:Avoid breathing vapors. Use only outdoors or in a well-ventilated area. Use explosion-proof electrical/ventilating equipment. Use only non-sparking tools.Take precautionary measures against static discharge. Wear a NIOSH-approved respirator for organic solvents. Keep away from heat/sparks/open flames/hot surfaces. No smoking. Vapors may accumulate in low places and may ignite explosively. Keep container tightly closed and cool. Wear protective gloves and eye protection. Wash thoroughly after handling. Do not eat or drink while using this product. EMERGENCY/FIRST AID:CALL 1-877-740-5015 FOR INSTRUCTIONS. IF SWALLOWED: Immediately call a POISON CENTER/doctor. Do NOT induce vomiting. Rinse mouth.This product may be aspirated into the lungs and cause chemical pneumonitis, a potentially fatal condition. If IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing. If eye irritation persists, get medical attention. If ON SKIN: Rinse skin with water/shower. Take off immediately all contaminated clothing. If INHALED: Remove person to fresh air and keep comfortable for breathing. Call POISON CENTER/doctor if you feel unwell. If medical advice is needed, have product container or label at hand. FIRE: Use dry chemical,foam, or carbon dioxide extinguisher. Water spray may be applied to reduce potential vapors or for cooling. Burning liquid extinguished with water will _oat and may re-ignite on surface of water. SPILLS: Remove all sources of ignition and ventilate area. Personnel cleaning up the spill should wear appropriate personal protective equipment, including respirators if vapor concentrations are high. Soak up spill with absorbent material. Put absorbent material in covered, labeled metal containers. Dispose of contents/container in accordance with local regulations. Store in a well-ventilated space. Store locked up. Oatey Co. Phone: 1-800-321-9532 AgppI 4700 West 160 th St. Phone: 1-800-321-9535 —\. Cleveland, OH 44135 Visit www.oatey.com for Update Page 2 of 3 Oately, Technical Specification Purple Primer — NSF Listed Directions for Use Store and use at temperatures between -15°F and 110°F. At temperatures outside of this range, special care must be taken to prepare good joints and prevent exposure to solvents. Stir or shake before using; if jelly-like, don't use. Do not thin. Handle with care! Will stain most materials and surfaces. 1. Cut pipe ends square, chamfer and clean pipe ends. 2. Check dry fit of pipe and fitting. Pipe should easily go 1/3 of the way into the fitting. If pipe bottoms, it should be snug. 3. Use a suitable applicator at least 1/2 the size of the pipe diameter. For larger size pipe systems use a natural bristle brush or roller. 4. Apply thoroughly to inside of the fitting socket and to the outside surface of the pipe to the depth of the fitting. Apply a second coat of primer to fitting socket. 5. While primer is still wet use an appropriate solvent cement for the pipe being joined. Follow application instructions from cement can. DO NOT TEST WITH AIR. Revision Date: 3/15/2013 Oatey Co. Phone: 1-800-321-9532 1S09oof 4700 West 160 th St. Phone: 1-800-321-9535 ,v Cleveland, OH 44135 Visit www.oatey.com for Update Page 3 of 3 Oately, Technical Specification Regular Clear PVC Cement Description Regular-Bodied Clear cement for use on all schedules and classes of PVC pipe and fittings up to 4"for Sch. 40 and up to 2"for Sch. 80. Lo-V.O.C. Solvent Cement meets California South Coast Air Quality Management District Oat8 REGULAR CLEAR Per (SCAQMD) 1168/316A or BAAQMD Method 40 �J� CEMENT and various environmental requirements. Recommended for potable water, pressure pipe, conduit and DWV. Recommended application temperature 40°F to 110°F/4°C to 43°C. Meets ASTM D-2564. Listings NSF 0 NSF Standard 61 for PW, IAPMO Listed DWV and Sewer Waste Maximum VOC per SCAQMD 1168/316A or BAAQMD Method 40: 510 g/L INGREDIENTS(CAS Number) Acetone (67-64-1), Amorphous Silica (112945-52-5), Cyclohexanone (108-94-4), Methyl Ethyl Ketone (78-93-3), PVC Resin (9002-86-2),Tetrahydrofuran (109-99-9) MSDS Number: 1100E Product Number Size Qty Wet Product Number Size Qtv Wet 31012 4 oz. 24 9 lbs. 310123 4 oz. 48 8 lbs. 31013 8 oz. 24 15 lbs. 310133 8 oz. 36 15 lbs. 31014 16 oz. 24 28 lbs. 310143 16 oz. 10 28 lbs. 31015 32 oz. 12 27 lbs. 310153 32 oz. 6 27 lbs. 31016 Gallon 6 50lbs. Oatey Co. Phone: 1-800-321-9532 1Sogoof 4700 West 160 th St. Phone: 1-800-321-9535 �. Cleveland, OH 44135 Visit www.oatey.com for Update Page 1 of 3 Dately, Technical Specification Regular Clear PVC Cement CHEMICAL PROPERTIES PHYSICAL PROPERTIES Appearance Clear Liquid Lap Shear Strength (min. ASTM Standards) Viscosity Min. 90 cps @73° F± 2° F 2 hours 250 psi Density 7.47±0.2 Ibs/gallon 16 hours 500 psi Shelf Life 3 years from manufacture 72 hours 900 psi date Set Up Time 30' F to 50' F 6—7 minutes 50' F to 70' F 4—5 minutes 70' F to 90' F 1—3 minutes Precautions Read all information carefully before using this product. DANGER!: CAUSES SERIOUS EYE IRRITATION. HARMFUL IF INHALED. MAY CAUSE DROWSINESS OR DIZZINESS. MAY CAUSE RESPIRATORY IRRITATION. REPEATED EXPOSURE MAY CAUSE SKIN DRYNESS OR CRACKING. Long term overexposure to solvents may cause damage to the brain, nervous system, reproductive system, respiratory system, mucous membranes, liver and kidneys. Contains a chemical classified by the US EPA as a suspected possible carcinogen. KEEP OUT OF REACH OF CHILDREN. PRECAUTIONS:Avoid breathing vapors. Use only outdoors or in a well-ventilated area. Use explosion- proof electrical/ventilating equipment. Use only non-sparking tools.Take precautionary measures against static discharge. Wear a NIOSH-approved respirator for organic solvents. Keep away from heat/sparks/open flames/hot surfaces. No smoking. Vapors may accumulate in low places and may ignite explosively. Keep container tightly closed and cool. Wear protective gloves and eye protection. Wash thoroughly after handling. Do not eat or drink while using this product. EMERGENCY/FIRST AID:CALL 1-877-740-5015 FOR INSTRUCTIONS. IF SWALLOWED: Immediately call a POISON CENTER/doctor. Do NOT induce vomiting. Rinse mouth.This product may be aspirated into the lungs and cause chemical pneumonitis, a potentially fatal condition. If IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing. If eye irritation persists, get medical attention. If ON SKIN: Rinse skin with water/shower.Take off immediately all contaminated clothing. If INHALED: Remove person to fresh air and keep comfortable for breathing. Call POISON CENTER/doctor if you feel unwell. If medical advice is needed, have product container or label at hand. FIRE: Use dry chemical,foam, or carbon dioxide extinguisher. Water spray may be applied to reduce potential vapors or for cooling. Burning liquid extinguished with water will—oat and may re-ignite on surface of water. SPILLS: Remove all sources of ignition and ventilate area. Personnel cleaning up the spill should wear appropriate personal protective equipment, including respirators if vapor concentrations are high. Soak up spill with absorbent material. Put absorbent material in covered, labeled metal containers. Dispose of contents/container in accordance with local regulations. Store in a well-ventilated space. Store locked up. Oatey Co. Phone: 1-800-321-9532 AgppI 4700 West 160 th St. Phone: 1-800-321-9535 —\. Cleveland, OH 44135 Visit www.oatey.com for Update Page 2 of 3 Dately, Technical Specification Regular Clear PVC Cement Directions for Use Store and use at temperatures between 40°F and 110°F. At temperatures outside of this range, special care must be taken to prepare good joints and prevent exposure to solvents. Stir or shake before using; ifjelly-like, don't use. Do not thin. 1. Cut pipe ends square, chamfer and clean pipe ends. 2. Check dry fit of pipe and fitting. Pipe should easily go 1/3 of the way into the fitting. If pipe bottoms, it should be snug. 3. Use a suitable applicator at least 1/2 the size of the pipe diameter. For larger size pipe systems use a natural bristle brush or roller. 4. Clean pipe and fitting with a listed primer. 5. Apply liberal coat of cement to pipe to the depth of the socket, leave no uncoated surface. 6. Apply a thin coat of cement to inside of fitting, avoid puddling of cement. Puddling can cause weakening and premature failure of pipe or fitting. Apply a second coat of cement to the pipe. 7. Assemble parts QUICKLY. Cement must be fluid. If cement surface has dried, recoat both parts. 8. Push pipe FULLY into fitting using a %turning motion until pipe bottoms. 9. Hold pipe and fitting together for 30 seconds to prevent pipe push-out- longer at low temperatures. Wipe off excess. 10. Allow 15 minutes for good handling strength and 2 hours cure time at temperatures above 60°F before pressure testing up to 180 psi. Longer cure times may be required at temperatures below 60°F or with pipe above 3". DO NOT TEST WITH AIR. Revision Date: 3/15/2013 Oatey Co. Phone: 1-800-321-9532 1S09oof 4700 West 160 th St. Phone: 1-800-321-9535 N./ Cleveland, OH 44135 Visit www.oatey.com for Update Page 3 of 3