Plans Examiner Review Comments and Responses 5/29/20
St. Lucie County Permitting
Florida Power & Light Interstate Solar
1. A SEPARATE PERMIT IS REQUIRED FOR THE DUMPSTER LOCATION.
RESPONSE: THIS PERMIT WAS APPLIED FOR ON 5/22/20.
2. SUBMIT A CROSS-SECTION FOR ROOM 121 FIREWALL FROM THE SLAB TO THE ROOF DECK. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: WILL BE COMPLETED ASAP.
3. PLEASE SUBMIT THE FIRE SPRINKLER PLANS SHOWING THE LAYOUT, PIPE SIZE, HEAD LOCATION AND PENETRATION'S. PLEASE SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: ALL FIRE PROTECTION PLANS WERE SENT VIA THE FIRE CONTRACTOR. I AM FORWARDING THEM TO YOU.
4. PLEASE SUBMIT THE SHOP DRAWINGS FOR THE ELEVATOR. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: ELEVATOR DRAWINGS ARE ATTACHED.
5. PLEASE CLARIFY WHAT WILL BE IN THE MACHINE ROOM. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: ATTACHED WITH ELEVATOR DRAWINGS
6. PLEASE SEE THE PRODUCT REVIEW AFFIDAVIT, METHOD OF ATTACHMENT, SPECIFIES INSTALLATION INSTRUCTIONS ARE ATTACHED. UNABLE TO COMPLETE MY REVIEW, NO PRODUCT APPROVALS WERE ATTACHED
WITH ATTACHMENT. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: ALL PRODUCT APPROVALS HAD COMPLETE INSTALLATION INSTRUCTIONS INCLUDED, BUT DUE TO THE SIZE I HAD TO ATTACH A LINK TO DOWNLOAD THEM. THAT IS WHY I PUT "ATTACHED" IN THE METHOD
OF ATTACHMENT SECTION.
I WILL SEND THEM ALL IN SEPARATE EMAILS TO YOU.
7. FLORIDA PRODUCT APPROVAL NUMBER 15542.2 IS INCORRECT. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: THIS HAS BEEN REVISED.
8.PRODUCT APPROVAL NUMBER FOR THE HURRICANE PROTECTION IS FOR WINDOWS, IF HURRICANE PROTECTION IS NOT BEING INSTALLED PLEASE LEAVE BLANK. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING
CODE.
RESPONSE: REMOVED.
9.NO PRODUCT APPROVAL NUMBER SUBMITTED FOR THE WALL SHEETING. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: WALL PANELS TO BE 26 GA KIRBY RIB (KR2) FL4837.1. THIS HAS BEEN ADDED TO THE PRODUCT APPROVAL SHEET.
10. PLEASE SEE THE ANCHOR BOLT PLAN, AT THE BOTTOM CENTER OF THE PAGE. PLEASE COMPLETE THIS AREA AND RESUBMIT. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
RESPONSE: PLEASE SEE THE ATTACHED KIRBY METAL BUILDING PERMIT PLANS. PAGE A HAS THE ANCHOR BOLTS INFORMATION.