HomeMy WebLinkAboutPlot Plans & SurveyDESIGN CRITERIA:
APPLICABLE CODES. REGULATIONS & STANDARDS
1. THE 2017 FLORIDA BUILDING CODE, SPECIFICALLY CHAPTER 16
STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CH. 23 WOOD.
2. AA ASM 35 & SPECIFICATIONS FOR ALUMINUM STRUCTURES,
PART 1-A OF THE ALUMINUM DESIGN MANUEL PREPARED BY
THE ALUMINUM ASSOCIATION. INC. WASHINGTON D.C. 2005 ED.
3. ASCE 7-10 & SET
4. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD.
5. ACI318 CONCRETE REFRENCE MANUAL.
WIND LOADS
1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE
1604.5: RISK CATEGORY 1.
2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS
REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE
1609.3.1 EQUIVALENT BASIC WIND SPEED: 150
MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C
3. WIND LOADS PER FBC TABLE 2002.4 (MWFRS)
V ULT = 150 MPH & EXPOSURE = C
FOR 20 X 20 X 0.013" MESH SCREEN
HORIZONTAL PRESSURES ON WINDWARD SURFACES =
43 PSF
HORIZONTAL PRESSURES ON LEEWARD SURFACES =
34 PSF
VERTICAL PRESSURES ON SCREEN SURFACES =
12 PSF
VERTICAL PRESSURES ON SOLID SURFACES =
36 PSF
FOR 18 X 14 X 0.013" MESH SCREEN, APPLIED FACTOR = .88
JO&ALLOWABLE STRESS DESIGN, APPLIED FACTOR = .6
AH 106.4.3: 10 PSF { AREVISION
FOUNDATION DESIGN - __1
FOOTING SIZE EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING
OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED
CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB IS PROVIDED IN
SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING
& OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER
CONCRETE SLAB MINIMUM &'x8" W/ (1) #5 BAR TO BE VERIFIED BY
CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING
DESIGN MINIMUM REQUIREMENTS.
SPECIFICATIONS
THE FOLLOWING SPECIFICATIONS ARE APPLICABLE TO THIS PROJECT:
1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN
THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE
REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE
APPLICABLE:
a. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE
FOLLOWING COMPONENTS:
I. PORTLAND CEMENT TYPE 1 - ASTM C 150
ii AGGREGATES - LARGE AGGREGATE 3/4 MAX. - ASTM C 33
iii. AIR ENTRAINING +/- I %- ASTM C 260
iv. WATER REDUCING AGENT -ASTM C 494
v. CLEAN PORTABLE WATER A. OTHER ADMIXTURES NOT PERMITTED
b. METAL ACCESSORIES SHALL CONFORM TO:
L REINFORCING BARS -ASTM A615, GRADE 60
ii. WELDED WIRE FABRIC - ASTM A185
C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3"
OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT
PERMITTED.
d. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE
INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3
INCLUDING HOT WHEATHER RECOMMENDATIONS.
e. MOIST CURE OR POLYETHYLENE CURING PERMITTED.
f. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE
ARE FOR TERMITES IN COMPLIANCE WITH THE FBC.
g. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR
BARRIER.
2. WHEN PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR
SHALL EPDXY TO DECK OR GROUT TO DECK w/3D00 PSI
GROUT WITH BONDING AGENT
3. WHEN APPLICABLE FOR NEW SLAB ADDITION TO ADJACENT
DRILL & EPDXY #5 X 8" REBAR INTO EX. FOUNDATION WITH 1"MIN.
HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE
(OR EQUAL) 48" O.C. TYP. ALL LOCATIONS
4. WHEN APPLICABLE FOR NEW FOOTER TO EXISTING, DRILL &
EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1"MIN. HOLE,
EMBED 6" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE
(OR EQUAL) TYP. ALL LOCATIONS
S. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHERWISE
NOTED.
ALUMINUM SPECIFICATIONS
1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS
OTHERWISE NOTED.
2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH
# 12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER.
3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050".
4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS
(KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024
INCHES.
5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN
WIND SPEEDS EXCEED 75 MPH PER FBC.
6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS
APPROVED BY FLORIDA ENGINEERING U.C.
5. 1"X2" & 1"X3" NON STRUCTURAL MEMBERS MAY BE USED
INTERCHANGEABLY.
FASTENER SPECIFICATIONS
1. FASTENERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER
ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS
OR BETTER, INSTALLED TO MFG. SPECIFICATIONS)
2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS,
FASTENERS AND SCREENS TO MANUFACTURING SPECIFICATIONS.
3. WHERE WOOD DECK IS PRESENT USE 1/4" X 3-1/2" GALV. LAG
SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE
SPECIFIED.
4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST
A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED
1 /4" X 2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS
B. FOR WOOD APPLICATION USE IT 14 X 2-0/4" WOOD SCREW AT
24" O.C. AND 6" FROM ENDS.
C. FOR ALUMINUM APPLICATION USE #10 X 1-1 /2" SMS OR TEK
SCREW AT 24" O.C. AND 6" FROM ENDS
D. WHERE 1"X2" INSTALLED THROUGHOUT AN "OPEN VIEW"
SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS
MASONRY SPECIFICATIONS
1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD
HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED
ON TYPE M OR S MORTAR.
2. ALL MORTAR SHALL BE TYPE M OR S.
3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE
MAXIMUM COARSE AGGREGATE SIZE OF 3/8".
4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING
REINFORCEMENT WHEN GROUT POUR EXCEEDS 5-0" IN
HEIGHT.
MISCELLANEOUS
1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL
COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC
R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS.
2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A
MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME.
IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH
WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO
ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME.
3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN
THE FIELD.
4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR
SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI
GROUT WITH BONDING AGENT.
5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE
COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED
STRUCTURE.
6. ALL 2X4 & GREATER ARE TO BE 2 x 4 SMB: 2'k4"x0.044"x0.100"
UNLESS OTHERWISE INDICATED.
RESPONSIBILITIES
1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED
CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING
CODES, LOCAL ORDANANCES. AND THE ENGINEER SHALL
BE NOTIFIED OF ANY DISCREPANCIES.
2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION,
THE CONTRACTOR SHALL VERIFY AND ENSURE INSTALLATION
HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH
MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH
THE ATTACHED DETAILS.
3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN
ENCLOSURES; ALL OTHER "EXISTING SCREEN ENCLOSURE"
FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED
IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE
EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND.
ALUMINUM MEMBERS DIMENSIONS
HOLLOW SECTIONS
2 x 2: 2'x2'x0.044"
2 x 3: 2'x3'x0.050"
2 x 4: 2"x4"x0.050"
2 x 5: 2"x5'x0.050"
OPEN BACK SECTIONS
1 x2: 1"x2"x0.044"
I x3: 1"x3'x0.045"
SNAP SECTIONS
2 x 2 SNAP: 2"x2"x0.045"
2 x 3 SNAP: 2x3"x0.050"
2 x 4 SNAP: 2X4"x0.045"
SELF MATING (SMB)
2 x 4 SMB: 2"x4"x0.044"x0.109'
2 x 5 SMB: 2"x5"x0.050"x0. 100"
2 x 6 SMB: 2x6"x0.050"x0. 120'
2 x 7 SMB: 2"x7x0.057'x0.I20'
2 x 8 SMB: 7x8" %D.D72"x0.124"
2 x 9 SMB: 2'k9"x0.082'k0. 124'
2 x 10 SMB: 2"x10"x0.092'x0.398"
DETAIL A
..............
O G
= D o
=0:Lu:O 10
w 4
Q C
j v ....PROF
/�y
/////i//111111111kx\\\x
\
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY
..1�
(,�� L/
v
SOCC (Y v r
C.03 V�
File Copy
J O
LLo
J
m
co
o I
Z Z
0
O
-D
of
0� p
U
U
J
w
w Q
O co-
Z (if
LL Lo
�
LLJ
.�
N
M
C
V -
� ^•i77
w<_j
QC¢v
Q
U
N�
L.1_ r
O
J
LL
a
w
I`
O
CO
v
M
I
� J
Z LL
O
Z
OCi
w
ro
Z d
n
= w
w
wOa
CD
0
J
o
O I` O
1
w
LL LO LL
'o
rr
a
I DESIGN DATE: 12/13/2019 1
REVISION 1:
02/03/2020
REVISION 2:
DATE
PAGE:
DRAWN BY:
KHV
SCALE:
NTS
1 11
u
ROOF RISE
a• .)--------------
/
i
I
g
i
i
S I
I
w I
3'-0"CHAIR RAIL
12" x 12" FOOTER�
BRICKPAVER
DECK OPTION
O SODDED GRpOE
2i_7u MIN.
17. /-71 12105 CONIBAa
FOOTING NOTES OMINUOUS
1. PROVIDE I-I/Y COVERAGE TOP, SIDES. BOTTOM AND I"BETWEEN ADJACENT REBAR LAPS.
2. PROVIDE MIN. 3"COVERAGE OF REBAR FOR ALL CONCRETE IN CONTACT WITH THE EARTH.
3. FOOTING CONCRETE SHALL BE MIN. 3000 PSI AT 28 DAYS
i. FOOTING REINFORCEMENT SHALL BE MIN. GRADE <0
S. PROVIDE POSITIVE DRAINAGE AWAY FROM STRUCTURE TO CITY / CO. REQUIREMENTS
6, PROVIDE 2SW PST BEARING (TYPICAL) UNDER FOUNDATION
). SEE GENERAL NOTES FOR WING INTO EXISTING FOUNDATIONS
8. SEE GENERAL NOTES FOR ADDITIONAL CONCRETE INFORMATION & SPECS.
DETAIL "J" FOOTINGS
SCALE: NTS
17'-9"
20'_4"—I
..... :
F HOST 24" O/H STRUC. GUTTER
s 2X3
--------- 2X3
I
2X3
0
I
1
fV
�
2X3X.050 DIAG. BRACE TYP.
2X3
i
2X3
y_x
m
m
2X3
m
m
m
:2
m
N
m
2
X,-.-
N
/;%:2X3N
m
x
m
N
N
N x
N
2X3
2X3
2X3
3X2
%
T
-- -------------
„ --
i
`
lx3 TYP.
X2X3
ED
ED DO
ED
2X3
m
x
x
L°
LG
x
N
x
1,1
_
�
p
N
N N
N
N
2X3 TYP.
}I -
1
2X3
1X3 TYP.
I2X3
1
7'_5"__— _4_
7' B" ,.1_-7'-8"
7- g'—
I 7 8" —i
2X3X.050 DIAG. BRACE TYP.
J
0
Q� /!/ N
O
LL
O
a
N
cC) m
.,
Lu
2 O•z-
m
N
_C9
i o
M
U'
O
�bd ••..
w
ELI
//////lllI
IIIIIIITL�\\\
U
1"
REVIEWED FOR
CODE COMPLIANCE
STR L_UCIE COUNTY
BOCC
File Copy
ROOF RISE PROFILE
SCALE N.T.R
2x2x3ANGLE
W/ (3) #14 TEKS
EACH SIDE
'HORIZONTAL OR SLOPED
EDGE MEMBER/ 1-12'X1x.062 RED.
2x2xl/8 ANGLE EAVE RAIL TO
OR PURLIN
W/ (4) #12x3/4" TEKS
POST W/ (8) #14 EA. CLIP
EACH SIDE IT
0
TABLE "E"
°
o
BEAM PER PLAN
EDGE MEMBER
BEAM Ott EACH SIDE/SIZE
0 o
NOTCHED TO RECEIVE
COLUMN WITHIN
BEAM
j
OR PURLIN
I0 0 °
1 °
(2X6 ILLUSTRATED)
2X2X125 ANGLE
Wl (4) #14 TEKS
INSTALL BRACE
TO CORNER
NOTE' BRACE MAY
I� BRACE
is
1-1/2'Wx.062 RECEIVER CHANNEL
_ W/ (4)#12x3/4" TEKS
EACH SIDE(TYP.)
j PURLIN
2x3
4112
2x4
5112
2%5
5/12
I I
COLUMN PER PLANS
FROM CORNER
DETAI "D"
DETAIL
I I
- ROOF BRACING CONNECTION
SCALE: NTS
2 x 7
7/12
2x6
8/14
2x9
9/14
2 x 10
9/14
ION
MAINTAIN MIN, OF 5/8"AM SMS
O.C. TY
FROM EDGE OF BEAM SMS O.C. TYP.
DETAIL E - UPRIGHT
TO BEAM
CONNECTION
SCALE:
MS
1/8"xZ` 2"ANGLE �
4 -#14 SMS INTO COLUMN
3/8" x 4" TAPCON
MIN 4"SLAB 30DO PSI
CONC. wRBERMESH \
CONC. FOOTING
SELF -MATING OR
SNAP SECTION TYP.
1"x3" O.B. BASE PLATE-TYP.
0 0 2-14'x 1/4"MASONRY ANCHOR
1-Y.." MIN. CONC.
ANCHOR EMBEDMENT
2" MIN. INCREASE DISTANCE
WHEN GREATER THAN 2x4
......... ....... UPRIGHT IS USED
SIDEVIEW NOTE
WHERE PAVERS ARE PRESENT USE 5116'
TAPCON XL (RED HEAD MFG.) MASONRY
ANCHORS TO PENETRATE UNDERLYING
CONCRETE FOOTING 2-IM' (MIN.)
4-#14 SMS INTO COLUMN
,/3/8"x4"TAPCON 2 @ SLAB (BEYOND)
I // 2-1/4"X1/4"TAPCON2@tx3 BASE
E PLATE ANCHORED
w/ 1/4" MASONRY
6" MAX EACH SIDE
AND 24" O.C. MAX
CONC. FOOTING BELOW—/ FRONT VIEW
DETAIL "B" - 2"x4" OR LARGER SELF MATING
UPRIGHT TO DECK DETAILS SCALE: NTS
(4) #10xl1/2" SMS INTO
SCREW BOSSES,
u FASTEN TOP OF HEADER TO INTERSECTING
125 ANGLE ii 2"x3"MEMBER w/(2)910 SMS w/1"
Ix3/4"TEKS PENETRATION INTO SCREW BOSS OF
EACH SIDE 2"x3"MEMBER-TYP, BOTH SIDES
2x2x.125 ANGLE
W/ (2) #10 SMS INTO COL
81/4" x 2-1/4" TAPCON THRU
O.B. INTO CONCRETE
1.1/2" (MIN.) EMBEDMENT
ALTERNATE BASE PLATE CONNECTION
ATTACH 2"x3" TO BASE PLATE
(INTERNAL) W(2) 0104" SMS
PURLIN
MEMBER
ALUMINUM INTERNAL OR EXTERNAL
UPRIGHT, BEAM -SNAP,
SELF MATING, OR HOLLOW
DETAIL "C" - GIRT OR PURLIN TO BEA
ORPOSTDETAIL SCALE:NTS
114'. TAPCON (RED HEAD MFG. OR EQUAL) WITHIN 6" OF
COLUMN 11/2" PENETRATION INTO UNDERLYING FOOTING
DETAIL'F' •DOOR JAMB 8 HEADER
. O° �.'ti;''%
�o�..°
C:
J cq
O
ZD ^o
O
z
W
z°
''�//llll
111 Hk\ x.
U�
J O
Ln
Z Z
Q O
U
n/
LL
p U
wJODD-
W Q
L,L Lo •�
Z
~
W r N
(_
f�M C
Z�O�-c
W
cQ
Q G
=
�Q-
U
Ora
0
J �
12-
REVIEWED FOR
CODE COMPLIANCE
ST° LUC®IE COUNTY
®OCC
Ql \
He Copy
°x2"x.063"- DIM. TO MATCH PURLIN
IZE RECEIVING CHANNEL
PURLIN
1) #12 SMS INTERNAL TO EAVE
AIL (2) #12 EACH SIDE INTO PURLI
W
Z LL
Z
F W
EAVE RAIL - 3xL
"
O
U
w
1n U
Z D_
N
0UPRIGHT
W
W O D-
ix30PEN BACK
EXTRUSION
O
p
'
Z)0¢
Lo Ir
0
0UL r- 0
2x2xl/8 ANGLE EAVE RAIL T
Y
UL
POSTW/(B)#14EA. CLIP
z
O
O
I
I
0
0
a
DESIGN DATE:
12/13/2019
REVISION V
02/03/2020
DETAIL "G" -SLOPED PURLIN
REVISION 2:
DATE
PAGE:
CONNECTION SCALE:NTS
DRAWN BY:
KHV
/�
SCALE:
NTS
J
FOR BEAMS ABOVE 2x8 INSTALL
GUTTER BRACE AT MIDPOINT
BETWEEN BEAMS 81NCLUDE 2"
GUTTER BRACE AT EACH BEAM
LOCATION
BEAM
A
F(2) #12 SMS
0
.044 RECEIVING CHANNEL,
FASTEN w/(1) #12 SMS
EACH SIDE OF BEAM
2x2x4x1/8"ANGLE
EA. SIDE OF BEAM
w/(4) #14 TEKS
EACH LEG EACH S
ANGLE W/ (4) #14 TEKS
SIDE VIEW
TOP VIEW
DETAIL "H"
SCALE: NTS
WOOD SCREWS@ V
IG @ EACH GUTTER BRACKET
18" D.C. MAX.
ABEDMENT SHALL BE 2"
R TO
18" O.C.
(2) #12 SMS
(2)#14x2"
WOODSCREW
EXISTING WOOD FASCIA
STRUCTURAL
GUTTER
o
0 FJo
I
IF 0 0 0
0 0 0
I
`P" 4 0 0
0 0 0l I
0
F
3116"5052-H32 GUSSET
1\ Y F
INTERNAL OR EXTERNAL
8" INTO EA. SIDE TYP.
F
(2X6SMB ILLUSTRATED)
SCREW QUANTITY
NOTE F
INSTALL FASTENERS ALONG PERIMETER OF GUSSET
2X6 AND LESS THAN 3 ROWS OF(4)#14
-BEAM JOINT 3/9'MIN, FROM EDGE. FASTENERS
FOR 2X7 AND GREATER 4 ROWS OF(4)#14
MAY BE STAGGERED TO INSURE PROPER
QUANTITY PER TABLE B-1
'NOTE: FOR SPANS OVER 33' ADD ANOTHER ROW
FASTENER PATTERN MAY APPEAR DIFFERENT
FROM ILLUSTRATION.
MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS.
MAINTAIN 3/8" MIN, FASTENER SEPARATION FROM
BEAM JOINT OR EDGE OF BEAM LAP
FASTENERS MAY BE EVENLY SPACED AROUND
EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT.
FASTENERS MAY BE STAGGERED TO INSURE
PROPER QUANTITY PER TABLE BA
DETAIL "K" GUSSET CONNECTION
SCALE:NTS
.050" GUTTER STIFFNER
FASTEN TO FASIA w(2)
#12x2" WOOD SCREW
FASTEN TO GUTTER w(2)
#12SMS
DETAIL "M" BEAM & PURLIN TO GUTTER
CONNECTION SCALE:NTS
(2) 912 SMS
2x2x1a' ANGLE w/(2)
#12 SMS EA- LEG,
SMB L
1/8"x2'k4" STRAP
(2) #12 SMS INTO BEAM
(2) #12 SMS INTO GUTTER
2x2x1/8" ANGLE w/(2)
#12 SMS EA. LEG ,
WHEN BEAM & PURLIN
HIT ON CORNER -
FASTEN OUTSIDE OF
BEAM 8 PURLIN
W 1/9W'12" ANGLE
8 (4) #12 SMS EACH LEG
FASTEN INSIDE CORNER
(BEAM TO PURLIN)
w/ 1/8"x2"x2" ANGLE
w/(2) #12 SMS
INTO EA. MEMBER
(BEAM 8 PURLIN)
4 WOOD SCREWS
FASCIA
GIRT
I
o ,u
SIDE VIEW \ , STRUCTURALGUTTER
POST
(2) #12 TEKS (TYP.)
EA. MEMBER (FOR
SPANS OVER 32'
USE #14 TEKS)
x 3 x 0.05 .�.�,.
LATERAL "IC' -BRACING
CONNECTION DETAILS
V
6063-T6 ALLOY PLATE
GIRT
(2) GUTTER BRACES
(ONE SIDE) OR STRONGER
EACH w/(2)#12 SMS
FASCIA
INTO GUTTER B(2)#14
WOOD SCREWS INTO FASCIA
K-BRACE
2x3%0.050 CHAIR RAIL
(2) #12 SMS
SMB
1/8'1Q'X4" STRAP
(2) #12 SMS INTO BEAM GIRT
(2) #12 SMS INTO GUTTER STRUCTURAL GUTTER
'ALTERNATELY USE 2x2x1/8ANGLE
TOP VIEW
DETAIL "L" CORNER CONNECTION
SCALE:NTS
K-BRACE
2 x 3x 0,050
BRACE(TYP
3 x 0.050
NCE (TYP.)
C-;
Q:� N
O O_:p
Z o w
=(7:L) 1O Q
O
EAVE RAIL
1"x 3" O.B.
PATIO SECTION
EWER FOR
.OMPLIANCE
—K-BRACE
CIE COUNTY
EOCC
File sC®PY
0
O O GIRT (CHAIR RAIL)
-- 0
(2) 912 TEKS IT
EA. MEMBER IF
SPANS OVER 3
USE #14 TEKS)
LATERAL"K"-BRACING
CONNECTION DETAILS
U
c:)
c\I
Lo
m
0
.J
co
M
ZZp
O
�y
LL
CD
U
U
O
WJODDm
LU <
LL Lo
.0
Z 2'
~
r
W
r—
v—
~^CD
z
0
v
c
Q
U
0 �
W
O
C)O
1h
LL
Nr
rn
T
O
z
U
LLl
a
0
U)
Z LL
O
O
LLf
co U
C)
u
n
Z D'
2: W_
UJ
x
W O O-
O
Q
> u
r-
Y
O
OLO
w
LL LL
O
a
SIGN DATE:
12/13/2019
(ISION 1: 02/03/2020
(ISION 2: DATE
PAGE:
LWN BY: KHV
1LE: NTS
t 15.2' EAST NORTH LINE OF THE SE 1/4 OF THE NE 1/4 NE CORNER
1/4 ( OF THE SE 1/4
1/4 I OF THE NE.1/4
SCALE: 1"=100'
APPROXIMATE
TOP OF DITCH
APPROXIMATE TOP OF DITCH SINGLE FAMILY FD.%" I.R.
„ , RESIDENCE NO CAP
S. 89'36 55 E. 1227190 0 o
FD )k" I.R. 1GAR0.01� --� ¢
W/CAP"RLS 2391" F.F.E.= v r16.9'x22' CONCRETE DRIVE van O °
} WITNESS CORNER 27.90' EAST ' s 577,7' tii � a 4 y,
rn IJ 4'x24' CONC. SLA n CONCRETE WALK a M Z 3 O`
z g£ • 3 2'x5' CONC. PAD (PUMP) QLL
o ram- w 6z1,s'' a2y 5.51 ACRES f N am¢ I•rnN i
_. •2'0 .3� A G .0 U ado 3:
4'xl VCONCRE WALK
rn ZI 12'x18' COVERE PORCH r az.s' - - , ,� 561,2' . ^ O C.)� ,
m I N. 00'32 51 E a t3 0
1\ 1 STORY RESIO bE N 11.18' (D&M) Z o
POND F.F.E: 22.iO N. 89'36'55" W. 300.00' D&M .. z �o'I�
g FD 1" LPIPE N. 8936'55" W. 624.55' (M) INGRESS —EGRESS SET Ya" I.R. • 2
WITNESS CORNER , , g EASEMENT W/CAP. F3435 p
4 x4 CONC. pAD
27.13' EAST I
d mo SET,, LR: FD.Y2" LR.
. VACANT' 3'x4' COVERED ENTRY W/CAP #3435 CAP UNREADABLE ,
n
SETBACK REQ
FRONT
' SIDES
CNR SIDES
Note: REAR
Elevations shown Hereon ore NAVD 88 based on a bench run ZNG• S
l from NGS Monument D201 (PID—AF3319) elevation 17.47, TECHTo convert to NGVD 29 add 1.54 feet per NGS calculations. Certified to: '
41.5' WEST Harbor Community Bank OWNER. Stephanie M. Fowler
SW CORNER OF THE N 1/2 Brian C. Fowler & Stephanie M. Fowler PERMIT TYPE: Building Residential (SFR)
OF. THE SE 1/4 Homecrete Homes, Inc. Building
OF THE NE 1/4 SEE SHEET 2 OF 2 FOR DESCRIPTION AND SURVEYOR'S REPORT First American Title Insurance Company Bug (Misc.) Garage
Address: 5775 Johnston Road
CERTIFICATE OF SURVEYOR
I herehy aeru'y the' fhie Survey wua made under my JAMES A. FOWLER, P.S.M. FINAL SURVEY
b at bagq kaoChurvl d�°�ee'�i r '�1B 6495 OXFORD CIRCLE, u1 O1 '
VERO BEACH, FLORIDA 32966
J S A. V028R, P.S.M. q �SPIi�iIl' StGp]�IlBnAe Fowler'
F RIDA,REGISTRATION No. 3435 FLORIDA LICENSE N0. eJ435 DRAWN BY:.D.F. SCALE: 1"= 100' DAIS: 12-13-2013 SHEE 1 OF 2