Response to comments:
Permit Number: 2002-0505
Building
Q5a. PROVIDE THE CORRECT OCCUPANCY CLASSIFICATION FOR THE SERVICE AREA.
DEPENDING ON THE TYPE OF WORK BEING PERFORMED WILL BE AN 'F' OR 'S'.
A5a. See sheet A-1 for corrections .
Q5b. SEE SECTION 508 FOR REQUIREMENTS ON MIXED USE OCCUPANCIES. SHOW
COMPLIANCE ON THE PLANS.
A5b. See sheet A-1 for corrections. We are considering these spaces as nonseparated
occupancies and applyng the regulation as per section 508.3 of the FBC 2017 6th edition.
Q7. CONFIRM THE CORRECT NUMBER OF EXITS ARE PROVIDED FOR THE OCCUPANTS IN THE
IN THE SERVICE AREA PLUS THE MEZZANINE. (1006)
A7. As per table 1006.2.1 one exit is acceptable for “F” occupancy since occupant load is less
than 49 and common path of travel of 100’ max.
Q8. PLEASE SHOW HOW THE RESTROOMS COMPLY WITH THE ADA SECTION (202.1)
A8. This section of code doesn’t apply to this project. There will be no addition nor alteration to
the existing space.