Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
10 PSI PE. CHART - 5385 CHRISTENSEN RD
PIPE AND TUBING SIZING TABLES Table 15.1(o) Regulators: Nominal Polyethylene Plastic Pipe Sizing Between First -Stage add Second -Stage Outside Diameter (D'S) Gas: undiluted Propane Inlet Pressure: 10.0 psi Pressure Drop: 1.0 psi Specific Gravity: 1.52 Plastic Pipe 54 in. 3/4 in. 1 in. 1'/4 in. I'/i in. 2 Length SDR 9.33 SDR 11.0 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00 (ft) (0.660) (0.860) (1.077) (1.328) (1.554) (1.943) 30 2143 4292 7744 13416 20260 36402 40 1835 3673 6628 11482 17340 31155 50 1626 3256 5874 10176 15368 27612 60 1473 2950 5322 9220 13924 25019 70 1355 2714 4896 8483 12810 23017 80 1261 2525 4555 7891 11918 21413 90 1183 2369 4274 7404 11182 20091 100 1117 2238 4037 6994 10562 18978 la 4 150 990 897 1983 1797 3578 3242 6199 5616 9361 8482 16820 15240 175 826 1653 2983 5167 7803 14020 200 778 1539 2775 4807 7259 13043 225 721 1443 2603 4510 6811 12238 230 681 1363 2459 4260 6434 11560 275 646 1294 2536 4046 6111 10979 300 617 1235 2228 3860 5830 10474 350 567 1136 2050 3551 5363 9636 400 528 1057 1907 3304 4989 8965 450 495 992 1789 3100 4681 8411 500 468 937 1690 2928 4422 7945 600 424 849 1531 2653 4007 7199 700 390 781 1409 2441 3686 6623 800 363 726 1311 2271 3429 6161 900 340 682 1230 2131 3217 5781 1000 322 644 1162 2012 3039 5461 1500 258 517 933 1616 2441 4385 2000 221 443 798 1383 2089 3753 IP$: Iron pipe size. SDR Standard dimension ratio Notes: (I) Capacities are in 1000 Btu/hr. (2) Dimensions in parentheses are inside diameter 2014 Edition