About
Manual J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIG HTJob:Project Summary APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information FY SPEC 445, SYNER GY HOMESFor: 305 BAY STREET, PORT ST LUCIE, FL 34952 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh16263 Struc ture Btuh15712 Ducts Btuh4384 Ducts Btuh6170 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh20647 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh20787 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3129 Ducts Btuh1652 Central vent (0 cfm)Btuh0 CoolingHeating (none) 15971597Area (ft²)Equipment latent load Btuh4781 1528815288Volume (ft³) Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh25568 Equiv. AVF (cfm)5197 Req. total capacity at 0.70 SHR ton2.5 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR4030 AHRI ref Coil TEM4A0B30S AHRI ref 7792032 Efficiency 100 EFF Efficiency 12.0 EER, 14.5 SEER Heating input kW10.0 Sensible cooling Btuh20020 Heating output Btuh34121 Latent cooling Btuh8580 Temperature rise °F33 Total cooling Btuh28600 Actual air flow cfm953 Actual air flow cfm953 Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.82 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House M BATH 2 Exposed wall 147.0 ft 20.0 ft 3 Room height 9.6 ft 8.0 heat/coolft 4 Room dimensions ft14.0x6.0 5 Room area 1597.0 ft²84.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 372 322 1290 705 48 48 192 105 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 9 0 76 95 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 41 0 343 432 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 344 314 1257 687 112 112 448 245 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 30 0 252 971 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 216 181 723 395 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 15 30 126 159 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 460 430 1722 941 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 30 0 252 971 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 1597 1597 1431 2555 84 84 75 134 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 1597 147 5590 0 84 20 760 0 6 c) AED excursion 0 -20 Envelope loss/gain 13284 8121 1476 465 12 a) Infiltration 2979 840 342 97 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 6750 0 Subtotal (lines 6 to 13)16263 15712 1819 561 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 16263 15712 1819 561 15 Duct loads 27%39%4384 6170 27%39%490 220 Total room load 20647 21881 2309 781 Air required (cfm)Air required (cfm)953 953 107 34 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC MASTER BEDROOM 2 Exposed wall 9.0 ft 29.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.0x9.0 ft264.0x1.0 5 Room area 72.0 ft²264.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 72 72 288 158 120 111 444 243 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 9 0 76 95 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 112 97 388 212 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 0 0 0 0 15 0 126 485 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 72 72 65 115 264 264 237 422 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 9 342 0 264 29 1103 0 6 c) AED excursion -14 138 Envelope loss/gain 695 258 2374 1596 12 a) Infiltration 154 43 497 140 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 100 850 Subtotal (lines 6 to 13)849 402 2870 2586 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 1 2 14 Subtotal 849 402 2872 2589 15 Duct loads 27%39%229 158 27%39%774 1017 Total room load 1078 560 3646 3605 Air required (cfm)Air required (cfm)50 24 168 157 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 3 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 CLST 3 2 Exposed wall 11.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft149.0x1.0 ft8.0x2.0 5 Room area 149.0 ft²16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 88 73 292 160 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 15 0 126 485 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 149 149 134 238 16 16 14 26 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 149 11 418 0 16 0 0 0 6 c) AED excursion 9 -1 Envelope loss/gain 970 892 14 25 12 a) Infiltration 188 53 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13)1158 1946 14 25 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 12 20 -14 -25 14 Subtotal 1170 1965 0 0 15 Duct loads 27%39%315 772 27%39%0 0 Total room load 1485 2737 0 0 Air required (cfm)Air required (cfm)69 119 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 4 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN/DINING BATH 2 2 Exposed wall 26.0 ft 6.0 ft 3 Room height 12.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft378.0x1.0 ft6.0x12.0 5 Room area 378.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 132 91 365 200 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 41 0 343 432 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 48 48 192 105 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 180 165 661 361 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 15 0 126 485 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 378 378 339 605 72 72 65 115 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 378 26 989 0 72 6 228 0 6 c) AED excursion -19 -19 Envelope loss/gain 2822 2064 485 201 12 a) Infiltration 668 188 103 29 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 2600 300 Subtotal (lines 6 to 13)3490 4852 588 530 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 16 27 9 15 14 Subtotal 3505 4879 596 545 15 Duct loads 27%39%945 1916 27%39%161 214 Total room load 4450 6795 757 760 Air required (cfm)Air required (cfm)205 296 35 33 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 5 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 HALL 2 Exposed wall 12.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x12.0 ft39.0x1.0 5 Room area 144.0 ft²39.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 96 81 324 177 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 15 0 126 485 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 144 144 129 230 39 39 35 62 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 144 12 456 0 39 0 0 0 6 c) AED excursion 8 -2 Envelope loss/gain 1036 901 35 60 12 a) Infiltration 205 58 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13)1241 1959 35 60 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 13 22 -35 -60 14 Subtotal 1254 1982 0 0 15 Duct loads 27%39%338 778 27%39%0 0 Total room load 1592 2760 0 0 Air required (cfm)Air required (cfm)73 120 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 6 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 LAUNDRY 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.0x2.0 ft8.0x7.0 5 Room area 16.0 ft²56.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 16 16 14 26 56 56 50 90 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 16 0 0 0 56 0 0 0 6 c) AED excursion -1 -24 Envelope loss/gain 14 25 50 66 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 600 Subtotal (lines 6 to 13)14 25 50 666 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -14 -25 270 155 14 Subtotal 0 0 320 821 15 Duct loads 27%39%0 0 27%39%86 322 Total room load 0 0 407 1143 Air required (cfm)Air required (cfm)0 0 19 50 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 7 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU CLST GREAT ROOM 2 Exposed wall 0 ft 28.0 ft 3 Room height 8.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft3.0x3.0 ft250.0x1.0 5 Room area 9.0 ft²250.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 168 153 613 335 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 15 15 126 159 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 168 168 673 368 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 32.3732.37 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 9 9 8 14 250 250 224 400 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 9 0 0 0 250 28 1065 0 6 c) AED excursion 0 -43 Envelope loss/gain 8 14 2700 1218 12 a) Infiltration 0 0 719 203 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13)8 14 3419 1721 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -8 -14 458 246 14 Subtotal 0 0 3878 1967 15 Duct loads 27%39%0 0 27%39%1045 773 Total room load 0 0 4923 2740 Air required (cfm)Air required (cfm)0 0 227 119 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-22 11:28:55 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 8 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIGHTJob:Right-J® Worksheet APRIL 22, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER 2 Exposed wall 6.0 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft8.0x6.0 5 Room area 48.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.300 n 8.40 10.58 0 0 0 0 .G 2 glazing, clr low-e 0.300 n 8.40 10.58 0 0 0 0 .W 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 11 G 2 glazing, clr low-e 0.300 e 8.40 32.37 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 48 28 111 60 G 2 glazing, clr low-e 0.300 s 8.40 10.58 0 0 0 0 D 11D0 0.390 s 10.92 10.34 20 20 223 211 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.300 w 8.40 32.37 0 0 0 0 C 16B-30ad 0.032 -0.90 1.60 48 48 43 77 F 22A-tph 1.358 -38.02 0.00 48 6 228 0 6 c) AED excursion -13 Envelope loss/gain 604 335 12 a) Infiltration 103 29 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)707 364 Less external load 0 0 Less transfer 0 0 Redistribution -707 -364 14 Subtotal 0 0 15 Duct loads 27%39%0 0 Total room load 0 0 Air required (cfm)0 0 2020-Apr-22 11:28:59 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW HUDSON 3- GAR RIG HTJob:Duct System Summary APRIL 22, 2020Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information FY SPEC 445, SYNER GY HOMESFor: 305 BAY STREET, PORT ST LUCIE, FL 34952 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm953cfm953 Total effective length (TEL)ft142 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2115.09.5VlFx0x05.01.0003335757hBATH 2 st2115.09.5VlFx0x07.01.000120732760cBEDROOM 2 st1115.022.0VlFx0x07.01.000119692737cBEDROOM 3 st3115.025.5VlFx0x07.01.0001192274923hGREAT ROOM st3115.025.5VlFx0x07.01.00099682265cKITCHEN/DINING st3115.020.1VlFx0x07.01.00099682265cKITCHEN/DINING-A st1115.020.4VlFx0x07.01.00099682265cKITCHEN/DINING-B st2115.012.1VlFx0x06.01.00050191143cLAUNDRY st1115.026.8VlFx0x05.01.000341072309hM BATH st1115.024.3VlFx0x05.01.00024501078hM WIC st1115.023.0VlFx0x08.01.0001571683646hMASTER BEDROOM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 127 203 1.000 582 8.0 0x0 VinlFlx st3 Peak AVF 364 317 1.000 668 10.0 0x0 VinlFlx st1 Peak AVF 462 433 1.000 700 11.0 0x0 VinlFlx 2020-Apr-22 11:28:59 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...cumnets\Wrightsoft HVAC\FY 445 SPEC- BAY ST.rup Calc = M J8 Front Door faces: SW Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 9530 953 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������