HOUSE
MECHANICAL A/C
1373 N. KILLIAN DR., LAKE PARK, FL 33403 Email: WWMIAECRANICALAC.COM Web: Ur-CAG1816081
Project• •
For: ARUBA II- MOULTON RESIDENCE, PORT ST LUCIE PROPERTIES
BRADLEY ST, FT PIERCE, FL 34951
Job:
Date: 10/1512019
By:
Design
Information
Htg
Clg
Infiltration
Outsidedb CF)
41
91
Method Simplified
Inside db (°F)
70
74
Construction quality Semi -loose
Design TD (*F)
29
17
Fireplaces 0
Daily range
-
L
Inside humidity (%)
30
50
Moisture difference (gr/lb)
2
56
HEATING EQUIPMENT
Make
Goodman Mfg.
Trade
FRANKLIN
Model
HKSC08XC
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
100 EFF
8.0
kW
27297
Btuh
31
OF
800
cfm
0.049
cfm/Btuh
0.50
in H2O
COOLING EQUIPMENT
Make GOODMAN
Trade FRANKLIN
Cond GSX160241F*
Coil ASPT33C14A*
AHRI ref 201498266
Efficiency 13.0 EER,
Sensible cooling
Latent cooling
Total cooling
Actual air flow
Air flow factor
Static pressure
Load sensible heat ratio
16 SEER
19116
Btuh
4484
Btuh
23600
Btuh
800
cfm
0.049
cfm/Btuh
0.50
in H2O
0.81
ROOM NAME
Area
(f 2)
Htg load
(Btuh)
Clg load
(Btuh)
Htg AVF
(cfm)
Clg AVF
(cfm)
MB
50
1243
913
61
44
MC
30
594
380
29
18
MBR
176
1857
2043
91
99
DINING
139
1642
1459
80
71
DR
258
3406
3719
167
181
BDRM 3
169
2609
2497
128
121
BTH2
49
733
485
36
24
BDRM 2
154
2595
2462
127
120
H
55
0
0
0
0
f\II IYJ IVYV GYVJ
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
- wWghttsoft-
f��; RightSuite® Universal 201919.0.15 RSU08764
VIM ...6esICUSTOMMODELS%ARUBAII_GR MOULTON 2019.mp Catc=MJ8 Front Doorfams: N
2020-Jan-36 10:21:20
Page 1
HOUSE
1229
16325
16448
800
800
Other equip loads
0
0
Equip. @ 1.00 RSM
16448
Latent cooling
3975
1
1
1
1
OTALS 1229 16325 20423 800 800
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
- wrightsoft• 2020-Jan-3010:21:20
Right -Suite® Universal 201919.0.15 RSU08764 Paget
._Bes1CUSTOM MODELSIARUBA II_GR_MOULTON_2019.rvp Cale =MJB Front Door faces: N
Project Summary
HOUSE
MECHANICAL A/C
1373 N. KILLIAN DR., LAKE PARK, FL 33403 Email: WMV.MECHANICALAC.COM Web: Ur- CAC1816081
Pro*ect Information
Job:
Date: 10/15/2019
By:
For: ARUBA II- MOULTON RESIDENCE, PORT ST LUCIE PROPERTIES
BRADLEY ST, FT PIERCE, FL 34951
Notes:
Weather:
Winter Design Conditions
Outside db
Inside db
Design TO
St Lucie Co Intl, FL, US
Summer Design Conditions
41 OF Outside db
70 OF Inside db
29 OF Design TO
Daily range
Relative humidity
Moisture difference
Heating Summary
Structure 13587 Btuh
Duds 2738 Btuh
Central vent (0 cfm) 0 Btuh
(none)
Humidification
Piping
Equipment load
Infiltration
Method
Construction quality
Fireplaces
0 Btuh
0 Btuh
16325 Btuh
Simplified
Semi -loose
0
Heating
Cooling
Area (fly
1229
1229
Volume (tts)
10962
10962
Air changes/hour
0.70
0.36
Equiv. AVF (dm)
128
66
91 OF
74 OF
17 OF
L
50 %
56 grAb
Sensible Cooling Equipment Load Sizing
Structure
12845
Btuh
Duds
3603
Btuh
Central vent (0 dm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data
y
Rate/swing multiplier
1.00
Equipment sensible load
16448
Btuh
Latent Cooling Equipment Load Sizing
Structure
3090
Btuh
Ducts
885
Stuh
Central vent (0 dm)
0
Btuh
(none)
Equipment latent load
3975
Btuh
Equipment Total Load (Sen+Lat) 20423 Btuh
Req. total capacity at 0.81 SHR 1.7 ton
Heating Equipment Summary Cooling Equipment Summary
Make Goodman Mfg.
Make GOODMAN
Trade FRANKLIN
Trade FRANKLIN
Model HKSC08XC
Cond GSX160241F'
AHRI ref
Coil ASPT33C14A•
AHRI ref 201498266
Efficiency
100 EFF
Efficiency 13.0 EER, 16 SEER
Heating input
8.0
kW
Sensible cooling
19116
Btuh
Heating output
27297
Btuh
Latent cooling
4484
Btuh
Temperature rise
31
OF
Total cooling
23600
Btuh
Actual air flow
800
cfm
Actual air flow
800
Cfm
Air flow factor
0.049
cfrn/Btuh
Air flow factor
0.049
dm/Btuh
Static pressure
0.50
in H2O
Static pressure
0.50
in H2O
Space thermostat
Load sensible heat ratio
0.81
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
WNghdpg. 2020-Jan-3010:21:20
Right -Suite® Universal 201919.0.15 RSU087M Page i
.-6eslCUSTOMMODELSIARUBAII_GR_MOULTON 2019.mp Cale=MJ8 Front Doorfaees: N
Manual S Compliance Report Job:
Date: 10l15I2019
HOUSE ay:
MECHANICAL A/C
1373 N. KILLIAN DR_ LAKE PARK. FL 33403 Email: WWW.MECHANICALAC.COM Web: LIC- CAG1816081
P-roject Intormation
For:
ARUBA II- MOULTON RESIDENCE, PORT ST LUCIE PROPERTIES
BRADLEY ST, FT PIERCE, FL 34951
Cooling
Design Conditions
Outdoor design DB:
91.2°F
Sensible gain: 16448
Btuh Entering coil DB: 75.5°F
Outdoor design WB:
77.1°F
Latent gain: 3975
Btuh Entering coil WB: 62.5°F
Indoor design DB:
74.0°F
Total gain: 20423
Btuh
Indoor RH:
50%
Estimated airflow: 800
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
Split AC
Manufacturer:
GOODMAN
Model: GSX160241F`+ASPT33C14A'
Actual airflow:
800 cfm
Sensible capacity:
19116 Btuh
116% of load
Latent capacity:
4484 Btuh
113% of load
Total capacity:
23600 Btuh
1161/o of load SHR: 81%
Design Conditions
Outdoor design DB: 41.0°F Heat loss: 16325 Btuh
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
Elec strip
Manufacturer:
Goodman Mfg. Model: HKSC08XC
Actual airflow:
800 cfm
Output capacity:
8.0 kW 167% of load
Meets all requirements of ACCA Manual S.
Entering coil DB: 69.5°F
Temp. rise: 34 °F
wNghtcsof - 2020-Jan-3010.21:20
Right-Suite@Universel20l9lg.U.l5RSU08764 Pagel
/H�...Iles\CUSTOM MODELSW2UBA 11 GR MOULTON 2019.iup Colo =MJ8 Front Door faces: N
GENERAL NOTES
To the best of my knowledge these plans
and specs do comply Vth all applicable
codes & 2017 Florida Building
Code,Mechanical.
Energy calculations done using Energy
Gauge— FlaRe92010 & Right—JV
Right-JO is the automated version of the
8th edition of the ACCA Manual J. Right—JO
computes the sizes of heating and cooling
design loads and is thus used for Sizing
residential HVAC equipment
Dud Design done using Right —DI
Right—I)t is the microcomputer version of
the second edition of the ACCA Manual D for
Residential duct design.
These plans supersede and void all previous
plans and specificat%ns,
Dud & grille locations may change due to
o4ner's request or structural limitations.
ALL CFM'S ARE APPROXIMATE, ACTUAL CFM
VARIES UPON CURRENT STATIC PRESSURE OF
HVAC SYSTEM
Job #:
Performed for:
ARUBA II- MOULTON RESIDENCE
BRADLEY ST
FT PIERCE, FL 34951
HVAC NOTES
EQUIPMENT SCHEDULE
CONDENSER- GSX16024 FRANKUN
MAX FUSE-30 M.C.A.-18 VOLT-230
AIR HANDLER- ASPT13'3014A
NOMINAL CFM-80D ryfX A.-7.1 VOLT-230
MOTOR SPEED- TAP 2
HEAT-10KW M.C.A- 54 SAX FUSE- 60
TOTAL SITU— 23,600
SEER RATING— 16
MR] REF#— 20149B266
THERMOSTAT— HON"ELL T6 / PRO9000
REF LINES— 3/4 / 3/8
DETAIL COMPUES WITH FDIC MECH . 301A2
usco "= M aeaun
/� � inrw,laNN: ac
Wy.an[ oeµlb 4 rrEctlOc+i cWml,cldr.
NE DZI I-1 • *13E
r, mNrnau Mntu:
E>M
/ APERNha ran artorne isc,
I Hrm tM�y NAnE-ncr�
j _ r.P>:nneauNrnaga
f9A SLPPo�rr P/fi:
aY Cf11FAAL aINfAACfa1
MECHANICAL A/C
1373 N. KILLIAN DR.
LAKE PARK, FL 33403
LIC-CAC1816081 VVWW.MECHANICALAO.COM
VMVM DaEruu�
Scale: 1 : 83
Page 1
Ri ghtSu ite® Univeml 2019
19.0.15 RSU08764
2020Jan-30 10:21:36
...ELSIARUBA II GR MOULTON 201E