HomeMy WebLinkAboutEvaluation ReportIC 5-28-20 St Lucie County Building Dept Permit # 2004-0332 1 flood vents 2 electric verification COVER SHEET MAY 2 g 2020 Permitting D 'partment St. Lucie County, FL DIVISION: 08 00 00—OPENINGS SECTION: 08 95 43—VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD SOLUTIONS, LLC ONE INDUSTRIAL PARK DRIVE, BUILDING 27 PELHAM, NEW HAMPSHIRE 03076 EVALUATION SUBJECT: STATIC FLOOD VENTS ICC ICC ICC SM Look for the trusted marks of Conformity) `2014 Reclplent of prestigious Western SlWWSeismic Policy Council (WSSPCJAWord In Excellence' ILI ASubsidimyof lum ICC-sitiouR�s ES 11, &ion Reports ore not to be construed as repreaenling aar*hcs or Pec rally address �, ®ry other report not et& nor me re to be comrrtby rC ®i endor,. S o1 C wq, o} the report or a acomntendation for its usz There it no Ivarrmtty byICCEvaluation Ser, ce, LLC, express oriW/lea( ar o a+ry f z ft or other matter in this report, or as to anyprodoct covered by dw report bpyright 0 201S ICC Evaluation Service, LLC, All rights rmrved IMES Evaluation Report wuvw.icc_es org I (Still) 423.65g7 I (662) M-0543 DIVISION: 08 00 O&—OpENWGS Section: 08 g8 43 Venta/FoundaUon Flood Vents REPORT HOLDER: �— FLOOD SOLUTIONS, LLC (n CD nj ONE INDUS7pjAL PARK DRIVE BUILDING v 27 PELHAM, NEW HAMPSMRE f 0307E (Still) 325.97/5 www.floodsolutions.com n. �' a A LnfO@floodsolistinns.com La -< i4 iy EVALUATION SUBJECT. C: Z� STATIC FLOOD VENTS 1.0 EVALUATION SCOPE v r 3 Compliance with the following code r', ■ 2018, 2015, 2012 and 2009 Code® lr&nrat'onal Bm7dng ■ 2018, 2015, 2012 and 2009 IJKemaffonal sfdentiel Code® Re Property evaluated: Water flow 2.0 USES Flood Solutions' static flood vents are used to provide for thewalequalization of hydrostatic flood faces on exterior 3.0 DESCRIPTION 3.1 General: Flood Solutions' static flood vents are engineered Permanently open flood vents with no moving parts that automatically allow flood waters to enter and exit enclosed areas. The vends are constructed of aluminum and vailable in four modeis. See Table 1 for model designations and sizes. See Figure 1 for liustrations of the flood vents. 3.2 Engineered Opening: The Flood Solutions static flood vents comply with the design principle noted in Section 26. 2 of ASCFlSE124 forrate ordee of rise and fall Of5 feet per hour (0.423 mmis). in orderto comply with the engineered opening requirement Of ASCEISEI 24, the static flood vents must be instsiied in accordance with Section 4.0 of this report ESR-3760 Reissued Merck 207E Thfsreportis subject to renewal March 2020. A Subsidiary of jheIntemaffonal Code Councils 3.3 Ventilation: Flood Solutions' static flood vents may be used to supply 1 nahhrel ventihaflon for under -floor verdilayon. See Table 1 for net fee area for under -floor ventilation Provided by each of Flood Sohrtien3'sWC flood vents. 4.0 DESIGN AND INVI'ALLATION The Flood Solutions static flood vents are designed to be installed into walls or doors of e3dWng or new construction from the erdedor side Irhstellaof the vents must be in accordance with the mantJfationciurers instructions, the applicable cede and this report In order to comply with the engineered opening design principle noted in Section 2.622 of ASCEfSEI 24. the vends roust be inspGpd as follows: • Wdh a minbnum of two opening on different sides of each enclosed area. • Wdh a mfnimtmh of one Vent for the square footage of enclosed area noted In Table 1. • Belowthebaseftoodelevation. • With the bottom of the Vent located a maximum of 12 inches (305 min) above grade. &0 CONDITIONS OF USE The static flood vents described in this report comply with, ,r are a suitable attemaft to what is specified in, those odes listed in Section 1.0 of this report, subject to the following conditions: 5-1 The emuc Good vents must be Installed in accordance with this report the applicable code and the manufacturers installation Instructions. In the event of a conflict the in*uctions in this reportgoverr. 52 The static Rood vents must not be used in the place of 'breakaway walls' in coastal high hazard areas, but are Permitted fbr use in Conjunction with breakaway wails in other areas. &0 EVIDENCE SUBMITTED 6.1 Manufacturers descriptive fderatum and installation Instructions. 62 Detail dlaunngs. 6.3 Engineering calculations in accordance with ASCEfSEI 24. 6.4 Quality doasnentation In accordance with the ICC-ES Acceptance Criteria for Quality Documentation (AC10), dated June 2014. ^>'�YJJ'dABoraNeromrrnOtrh/r •,,'�a•aomme+�onanlnrleme 27o & n '" r���wnormeryryfo6e OGI[flrtlCJ Iepo/(or�famG'i+�'+mtONdy/he,eJpK 1P�7'Dl'JCC6lvlumbaSovkq Jl..¢g,�orlmpf(rdm C•Prrt81rt®TO/B ICC EYa11mtiW1 Servfee. LLC. Alltlal� BSBNetl- '?�= •. Page 103 7.0 IDENTIFICATION Page 2 of S The Flood Solutions static flood vents nuMbe the name evaluation nsport ood nujn�r (ESR3760). report must be identified mco80 in thisI. the model � a label bearing the TA6LE 1--FLOOD SOLt1T10NS STATIC FLooD VENTS MODEL VENT8IZE RWGH� ING ENCt-OSED (WldthxFlelght) AREACpyFRgGE NETFltEEAREq+ Pn) MOdt (in) ht) FS-1608 rorsr: 1lnet=Z6,4 rtua�1g=3 8 +AvaOable for use es antler-600rvent,Taffon. k� Sic. 5 FS-1412 FS-1616 FS-1608 FS-1608•HEX FIGURE 1—FLOOD SOLUTIONS STATIC FLOOD VENTS ICC-ES Evaluation Report ESR-3760 I -BC Supplement Reissued March 2018 Thisrepoltissubject Lbrenewal March 2020. wvuw.ic- c es 022 I (Boni A2-%Ac87 I (5�) 699-0543 A Subsidiary of the lntemaSonal Coda (.`n„nn110 DPASION: 08 00 ON —OPENINGS Section: 08 95 43—Vardall oundayon Flood bergs REPORT HOLDER: FLOOD SOLUTIONS, LLC ONE INDUSTRIAL PARK pRM BUILDING 27 PELF, NW �fA�yPSHIRE 03076 (800)326-9775 I EVALUATION SOBJECi: STATIC FLOOD ENTS "0 REPORT P OSE AND SCOPE Purpose: The purpose o this evaluation report supplement is to indicate that Flood Solutions' good vents, recognized in ICC-ES master evaluation report ESR-3760. have also been evaluated for compliance with the codes noted below. APPlicable coa editions: la 2017 Florida uildtng Codc_Budit ■ 2017 Florida Building Code —Resider iaf 2.0 CONCLUSIOINS The Flood Solutions flood vents, described in Sections 20 through 7.0 of the master evaluation reportSR-3760. complyE with the Florida ��P���rrurrrrrrlldrng Code—Bw ffng and the Rodda Building Code Residential, Provided the ort and installation are in accordan with the 2015lntemagonal Bur7dtng Code® provisions noted in the master report Use of the Ff a So1lNone' rood vents has 8190 been ftllrnd to be m Compliance with the H1gh-VeloclLy HunIcane Zone Provisions of the Ffodda Bugdfng Code--Buridrfg and the Ronda Bufft Coda— Rddan of For products fallmg Linder Florida Rule 9N-3, verification that the report holder's quality assurance program is audited by a responsibility qualitysuofcaanen� approved by the Florida Building Commission for the type of Itspections being conducted is the ) approved validation entity (or the code official when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued March 2018. inn +onau gfma,mnJalajye rrpaitwaftmmmrnda�/onjorf[sme7rrcre4m••••••�•�a ��+.1�4'^"""�'""C mVrale(¢rym bemm4tad nJ'J+++dmgaralhQmwnmOirsmnort aremmry'Pmd�c�dl'fkr2porl 1°�+Nh'!fX•6wfimuanSaMq llf; aprcsorfmplrrq'� CoPYliBM®20701CC Li21ue9nn 5'ervieal fJ.G MdB��tVed. m� —�.- P49e3 ar3 DIVISION: 08 00 00—OPENINGS SECIWRY: 08 gg 43_V'"FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD SOLUTIONS, LLC ONE INDUSTRIAL PARK DRIVE, BUILDING 27 PELHAM, NEW HAMPSHIRE 03076 EVALUATION SUBJECT: STATIC FLOOD VENTS CC lCC c PNIG Occ 1; USPED Look for the trusted marks of Conformity) '2014 Recipient ofptestigious Western States SelsmicporcyCouncil _(WSSPQAward in Excellence - VC -ES Evaluaffon Reports are not to be comirued as mpjgsaWMg aestkea., or pecifually addressed, nor are they to be cO)U ted as m `M odrer aftbater not ecommendallon forits use There is no warran endorsem¢nt of the svbfeot of the report or a onyfk&ngorothermatterinlhisreport or as oAYICCEvaluationServicg LLC, expressoriupliea( as mryproduct covered by ar report oPYryght m 2018 I= Evaluation Service, LLC All rlglrts reserved i m ASubsiftryof MEMO Evaluation Report ESR-3760 Reissued March 20fa ww.icc-es ore 7h13 MPort is subject t0 rerrewal March 2020. —_. I laoo) a2a.sse�) Iss2) sss-osaa A Subsidiary of the Intemaflonar DIVISION: 08 00 GO—OPENINGSSection: 08 95 43—Ventwr-oundadon Flood Vents REPORT HOL13M FLOOD SOLUTIONS, LLC ONE INDUSTRIAL PARK DRIVE BUILDING 27 PEED S25�n IW, NEW HAMPSHIRE 03076 29 ood o atone core EVALUATION SUBJECT: STATIC FLOOD VENTS 1.0 EVALUATION SCOPE Compflence with the foflowing COdes: ■ 2018, 2015, 2012 and 2009 hnlemaffona/ Budding Code® 0 2e®2015, 2012 and 2009 /nlema6onai Rasidarrlial Property evaluated: Water flow 20 USES Flood Solutions' static flood vents are used to provide for the equalrration of hydrostatic flood forces on exterior walls. 3.0 DESCRIPpON 3.1 General: Flood Solutions' static flood vents are engineered, permanently Open flood vents WM no moving parts that automatically allow flood waters to enter and e)dt enclosed areas. The vents era constructed of aluminum and available in four models. See Table 1 for model designations and sizes. See Figure flood vents 1 for illustrations of the 3.2 Engineered Opening: The Flood Solutions static flood vents comply with the design principle noted in Section 26.2 2 Of ASCE/S4 24 for a rate of rise and fall of feet per hour (0423 nos). In order to comply with the engineered opening requirement Of ASCE/SEI 24, the static flood vents must be installed accordance wflh Section 4.0 of this report in w vVY/I4!/ 3.3 Ventilation: Flood Solutions' static flood vends may be used to supply natural venh7ation for under -floor vemlation. See Table 1 for net tree area for under -floor vertiletien provided by each of Flood Solutions'stHhO Rood vends. AO DESiGNANDINSTALLATION The Flood Solutions static flood vends are designed to be Installed into wads or doors of existing or new signed to be from the erderior side accordance insanuf on of the vents must be in appolabie code and Rds manutachners instructions, the engineered report In Order to comply with the 26.22 Of AS E/gq 24. nthe vents must be Ins le noted in Section follows: metalled as • Wrth a minimum of two opaNng on different Sides of each enclosed area. • With a minimum Of one vent for the square footage of enclosed area noted in Table 1. • Sallow the base flood elevation. • With the bottom of the vent located a maximum of 12 inches (305 mm) above grade. &0 CONDITIONS OF USE The static flood vents described In this report comply with, or are a suitable alternative to what is specified in. those codes fisted in Section 1.0 of this report subject to the following conditions: S�1 The atettc n0oa vents must be Installed In accordance with this report; the appRCable Code and the manufacturer's insiela0on instructions. In the event of a conflict the instructions in th15 report govern. 52 The static flood vends must not be used in the place of breakaway wale' in coastal high hazard areas, but are Parmlted for use in cenjunclion with breakaway wails In other areas. 6.0 EVIDENCE SUBMITTED 6.1 Manufacturer's descriptive Ithrdtum and installation Instructions. 6.2 Detail drawings. 63 Engineering ASCEB4 24. calculations in accordance with 64 Quality documentation in accordance with the CC ES Acceptance Criteria for Quardy Documentation (AC10), dated June 2014. "_ _' /.........a.oro COW06M02018 ICC EmkW a n SeMm, LLC. ApeWy qNS/ 7.0 ID - awau ENTIFICATION The Flood Solutions static Rood vends reoagnaed in this art must be identified by a label bearing One - '"qde 6 Or mnura 3 er� the name (Flood Solutions), the model evaluation report number (ESR-3760). TALE 9—FLOOD SOLUTIONS STAi1C FLOOp VEldTS MODEL VEIdi8lZE ROU0 OPENOIC, 6: (WldihaHeight) SIZE ENCLOSED pnJ (Width;Height) AREACOVERpGE 18 -. _.. •.'m=WzAram; 1it=304.8mm AVafiabie for use as under-doorverdilsdon. FS-1412 FS-1608 FS-1608•HEX FIGURE 1—ROOD SOLUTIONS STAMC FLOOD VENTS NETFREEAMW M ICC_ES Evaluation Report ESR-3760 FBC Supplement Refssued Marsh 2018 Th&reportis subject to renewarMarch 2020. winrw.ic—�rS I ($��,�$699.0543 � 1 (5 �) A SubsidiaryoflSye intemeSonal cmo rn",...."Q DMSION 08 00 W OPENINGS - -- - Section: 08 95 43—Vanta'Fovndayon Flood Vent REPORT HOLDER: FLOOD SOLUTIONS, LLC ONE INDUSTRIAL PARK DRIVE BUILDING 27 (800) 325,9775NMtwipSHIRE �076 EVALUATION SpajECT: STATIC FLOOD I6M3 1.0 REPORT PURPOSE AND SCOPE Purpose: The Purpose this evaluation report Supplement is to indicate master evaluation report ESR�760. Kaye also been eval that FlOod Solutions' Rood vents, recognized In ICC-ES APPIIcable eor!Ia edidorrs uated for compliance with the codas noted below. ■ 2017 Flodda Bu1ldrn I Coda-Bw7dng ■ 2017 Florida IlSuilding Code—Residerrtiar 2.0 CONCLUSIOINS The Flood Solutons Rood Vents. descn'bed in Sections 20 through 7.0 of the master evaluation with the F/odda pm7dmg Code—Bm7drig and the Ronda Bm7din Cod mPort ESR- '60 are In accordsnch with the 2015 rmemaHonal BuAdmg Code® Provisions ons noted in the Waster d m e design and mstaRahcomon Use of the Flopps Sor000na' enoo vents nas also been found to be In compliance with the Mgh-Velodty Huff [cane Zone Provisions ofthe F/odda Brrr7dm9 Coda-.Bw7dmg and the Flodda Bru7ding CodeI ante With t h For products falling under Floday the Rm s Suildin that the report hoidees quafty assuranco program Is audited by a f. quality assurance entity approveddvoliby the Fladde Btn7dirmg Commission for the the responsibility of an approved rdlidation entity (or the code official when the to type of inspections being conducted is the the Commission). Port holder does not Possess an approval by This supplement expires concunen8y with the master report, reissued March 2018_ �e%'I'�dd6oraNa�rermtAr�ep�,{wmmm6'P+W+a/� � ��D�m+m+b6YlUC6vd y••,••,�f ce�� �y/a 6emr� CWYr(9M62W8'CC �' �°+t my/anSv'r orlmpfleQ'� SeMoq LLGMetgyp ..� Paae3 af3 DIVISION: 08 00 00—OPENINGS SECTION: 08 95 43—VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD FLAPS®, LLC EVALUATION SUBJECT: FLOOD FLAPS® AUTOMATIC FLOOD VENTS: MODELS FFWF12; FFNF12; FFWF08, FFNF08; FFWFOS; FFNFOS Icc�� Ic��S� Ic��S� PMG lJSTfD �.-P� 3 FILE COPY 12014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence" A Subsidiary of ]CC -ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. �® There is no warranty by ICC Evaluation Service, LLC, express or implied as to any finding or other matter in this report, or as to any product covered by the report. nano Copyright ®20181CC Evaluation Service, LLC. All rights reserved. IMES Evaluation Report ESR-3560 Reissued September 2018 This report is subject to renewal September2019. www.icc-es.oro 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 08 00 00—OPENINGS Section: 08 95 43—VentrdFoundation Flood Vents REPORT HOLDER: FLOOD FLAPS®, LLC EVALUATION SUBJECT: FLOOD FLAPS® AUTOMATIC FLOOD VENTS: MODELS FFWF12; FFNF12; FFVIfF08; FFNF08; FFWF05; FFNF05 1.0 EVALUATION SCOPE Compliance with the following codes: ■ 2018, 2015, 2012 and 2009 Intemational Building Code (IBC) ■ 2018, 2015, 2012 and 2009 International Residential Code® (IRC) Properties evaluated: ■ Physical operation ■ Water flow ■ Weathering 2.0 USES Flood Flaps® automatic flood vents are used to provide for the. equalization of hydrostatic flood forces on exterior walls. Certain models also allow natural ventilation. 3.0 DESCRIPTION 3.1 General: Flood Flaps® automatic flood vents are engineered mechanically operated flood vents (FVs) that automatically allow flood waters to enter and exit enclosed areas. The FVs are constructed of ABS plastic which serves as the FV's housing, and a front grill that contains an anodized metal screen imbedded in polypropylene plastic. On contact with rising flood water, the grill will disengage from its secured position, allowing flood water and debris to flow through in either direction. The FVs are available in two series as described in Section 3.3. The sealed series models contain two rubber flaps that close the FV to the passage of air when using with conditioned areas or sealed crawl spaces. In the same manner as the grill, the two rubber flaps are pushed open by water pressure, allowing water and debris to flow through the FV in either direction. See Figure 1 for an illustration of the Flood Flaps® automatic FV. 3.2 Engineered Opening: The Flood Flaps® automatic FVs comply with the design principle noted in Sections 2.7.2.2 and 2.7.3 of ASCEISEI 24-14 (2018 and 2015 IBC and IRC) [Section 2.6.2.2 of ASCEISEI 24-05 (2012 and 2009 IBC and IRC)] for a rate of rise and fall of 5 feet per hour (0.423 mmis). In order to comply with the engineered opening requirement of ASCEISEI 24, Flood Flaps® automatic FVs must be installed in accordance with Section 4.0. 3.3 Flood Vent Series Models: Flood Flaps® automatic FVs are available in two series with multiple models and sizes as described in Table 1. The sealed series models, designated FFWF, include two rubber flaps for the prevention of air flow. The multi- purpose series, designated FFNF, omits the rubber flaps. 3A Natural Ventilation: Flood Flaps® automatic FV models FFNF12, FFNF08, FFNF05, and FFNF02 have metal screens with inch by '/4 inch (6 mm b�I 6 mm) openings and provide 37 square inches (0.02 in ) of net free opening to supply natural ventilation for under -floor ventilation. Flood Flaps® automatic FV models FFWF12, FFWF08, and FFWF05 have not been evaluated for use as openings for under- floor ventilation. 4.0 DESIGN AND INSTALLATION Flood Flaps® automatic FVs are designed to be installed into walls of existing or new construction. Installation of the FVs must be in accordance with the manufacturer's instructions, the applicable code and this report Flood Flaps automatic FVs can be installed in wood, masonry and concrete walls up to a thickness of 12 inches (305 mm). In order to comply with the engineered opening design principle noted in Sections 2.7.22 and 2.7.3 of ASCEISEI 24-14 (2018 and 2015 IBC and IRC) [Section 2.6.2.2 of ASCEISEI 24-05 (2012 and 2009 IBC and IRC)], the Flood Flaps® FVs must be installed as follows: ■ With a minimum of two openings on different sides of each enclosed area. in With a minimum of one FV for every 220 square feet (20 m2) of enclosed area. ■ Below the base flood elevation. ■ With the bottom of the FV located a maximum of 12 inches (305 mm) above grade. 5.0 CONDITIONS OF USE The Flood Flaps® automatic flood vents described in this report comply with, or are suitable altematives to what is 1CC-ESEva1vs11oo Repom are nor to be wmlruedmrepme inga thelioar.�yolhermMburer not specificallyaddnrssd, nor are&y lobe construed ar on endorsement fthe sub%eel ofthe report or araro..dationjor itr usa Men is no trarturry by lCCEvaloaaon&Mce, LLC, erprecr or impUed as to arryfinding or other maner in this report, or as ro arryproduct covered by the report Copyright® 2018 ICC Evaluation service, LLC. All rights reserved. Page 1 of 4 ICC-ES Evaluation Report ESR-3560 FBC Supplement Reissued September 2018 This report is subject to renewal September 2019. www.icc-es.org 1 (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 08 00 00—OPENINGS Section: 08 95 43—VentslFoundation Flood Vents REPORT HOLDER: FLOOD FLAPS®, LLC EVALUATION SUBJECT: FLOOD FLAPS®AUTOMATIC FLOOD VENTS: MODELS FFWF12; FFNF12; FFWF08; FFNF08; FFWF05; FFNF05 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that Flood Flaps® automatic flood vents, recognized in ICC-ES master evaluation report ESR3560, have also been evaluated for compliance with the codes noted below. Applicable code editions: ■ 2017 Florida Building Code tiffding ■ 2017 Florida Building Code —Residential 2.0 CONCLUSIONS The Flood Flaps flood vents, described in Sections 2.0 through 7.0 of the master evaluation report ESR-3560, comply with the Florida Building Code —Building and the Florida Building Code —Residential, provided the design and installation are in accordance with the 2015 International Building Code® provisions noted in the master report Use of the Flood Flaps flood vents has also been found to be in compliance with the High -Velocity Hurricane Zone provisions of the Florida Budding Code —Building and the Florida Building Code —Residential. For products falling under Florida Rule 9N3, verification that the report holder's quality -assurance program is audited by a quality -assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued September 2018. ICC-ES Esnloohon Reports are not to be mvtrued as represeraingarsthmter oraryotherattributer nol apecifscully addresred norare thry to be consoved ar an endorsement of the subject of the report or recommendoNonfor its use. There a no wertonly by ICC Ecaluatiau Service, LLC, erpres, or implied, ar to anyfindtng or other matter in this report ore to anyproductmeeredhy the report Copyright 0 2018 ICC Evaluation Servim, L.L.C. M rights reserved Page 4 of 4 ESR-3560 I Most Widely Accepted and Trusted Page 3 of 4 t• 1 ... .. a .i FRVF12 12" DEPTH FFNF08 FIGURE 2-FLOOD FLAPS® AUTOMATIC FLOOD VENT SERIES MODELS 8" DEPTH FFNF05 FIGURE 3-FLOOD FLAPS® AUTOMATIC FLOOD VENTS MULTIPLE DEPTH OFFERINGS 5"DEPTH ESR-3560 I Most Widely Accepted aria r usted Page 2 of 4 specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The Flood Fiapse automatic FVs must be installed in accordance with this report, the applicable code and the manufacturer's installation instructions. In the event of a conflict, the instructions in this report govern. 5.2 The Flood Flaps® automatic FVs must not be used in place of "breakaway walls' in coastal high hazard areas, but are permitted for use in conjunction with breakaway walls in other areas. 6.0 EVIDENCE SUBMITTED Data in accordance with the ]CC -ES Acceptance Criteria for Mechanically Operated Flood Vents (AC364), dated August 2015 (editorially revised October 2017). 7.0 IDENTIFICATION 7.1 The Flood Flaps® models recognized in this report are identified by a label bearing the manufacturer's name, the model number, and the evaluation report number (ESR-3560). 7.2 The report holders contact information is the following: FLOOD FLAPS®, LLC POST OFFICE BOX 1003 ISLE OF PALMS, SOUTH CAROLINA 29451 (843)881.0190 www.floodflaps.com infoOfloodflaos.com TABLE 1—FLOOD FLAP AUTOMATIC FLOOD VENT MODEL SIZES MODEL NUMBER MODEL DESIGNATION ROUGH OPENING (Width X Height) (inches) VENT SIZE (W X H X D) Cinches) ENCLOSED AREA COVERAGE (fe) NET FREE AREA OPENING' (In') FFWF12 Sealed Series 16 x 8 15 /s X / XX 12 220 NA FFNF12 Multi -Purpose 16 x 8 15 /e X 7 /. X 12 2 00 37 FFWF08 Sealed Series 16 x 8 15 /a x /a x 8 220 NA FFNF08 Multi -Purpose 16 x 8 1 /a x 71. x 8 220 37 FFWF05 I Sealed Series I 16 x 8 1 /e x /� x 5 220 NA FFNF05 Multi -Purpose 16 x 8 15 /e x 7 !4 x 5 220 37 'For under -floor ventilation only. FIGURE 1—FLOOD FLAPS®AUTOMATIC FLOOD VENT