HomeMy WebLinkAboutProduct Approval 1 EVALUATION REPORT OF METAL SALES MANUFACTURING CORPORATION `26 GA. 5V=CRIMP PANEL' FLORIDA BUILDING CODE.6TH EDITION (2017) FLORIDA PRODUCT APPROVAL FL 14645.4-R3 ROOFING METAL ROOFING Prepared For: Metal Sales Manufacturing Corporation. 545 South 3''d Street, Suite 200 Louisville,KY 40202 Telephone: (502) 855-4300 Fax: (502) 855-4290 Prepared;By: Bala Sockalingam, Ph.D.,P.E. Florida Professional Engineer#b2 1216 N Lansing Ave., Suite C Tulsa, OK 74106 16 0 �-- X15 Telephone: (918)492-5992VIEWED FOR FAX: (918)493-3568 �� CODE COMPLIANCE ST. L UCIE COUNTY Rocs This report consists of Evaluation Report(3 Pages including cover) oe1eeia11stls Installation Details (1 Page) ♦♦%%0,50CKgt�N '� Load Span Table (1 Page) qe��♦P�,P��G E N 5�,�'y .11 No 62240 p '-0; * 'r: Report No. C2182-4 ' STATE OF :4u %O • Al ,, . tee' Date: 9.9.17 ',,SFS;• O R e so AL `♦♦♦ e � FL 14645.4-R3 C2182-4 9.9.17 Page 2 of 3 Manufacturer: Metal Sales Manufacturing Corporation Product Name: 5V-Crimp Panel Description: 24" wide coverage with(5) 1/2" high ribs Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Deck Description: Min. 7/16" thick OSB or min. 15/32" thick plywood or min. 3/4" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2017. Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c. (Minimum) in the plywood field and edges. Designed as per FBC 2017. Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1. Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Design Uplift Pressure: 30.0 psf @ fastener spacing of 36" o.c. (Factor of Safety=2) 172.5 psf @ fastener spacing of 6" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8" and installed as per Metal'Sales current installation procedure. At panel ends @ 6" o.c. across panel width At intermediate �@ 12" o.c. across panel wid Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering Systems'. Test Equivalency: The test procedures in UL 1897-04 comply with test procedures prescribed in UL 1897-12. Code Compliance: The product described herein has demonstrated compliance with FBC 2017 Section 1507.4. Product Limitations: Design wind loads shall'be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. The design pressure for reduced fastener spacing may be ? FL 14645.4-R3 C2182-4 9.9.17 Page 3 of 3 computed using rational analysis prepared by a Florida Professional Engineer or based on Metal Sales load span table. This evaluation report is not applicable in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2017 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: UL580 & 1897 Test Reports PRI Construction Materials Technologies MSMC-017-02-01, Reporting Date 9/20/13 x OMWN B/: CMECI(FD 6Y: PANEL OVERLAP °S \5V—CRIMP SEE DETAIL 2 SEE DETAIL 1 FASTENER AT PANEL. REQUIRED FOR PANEL LAT a � ENDS ONLY. - u u u o ii MINIMUM ATTACHMENT: PANEL FASTENER PER UPLIFT g 8d x 2.5" LONG RING SHANK NAIL LOAD TABLE UNDERLAYMENT SHALL BE INSTALLED OR #8 x 2" LONG WOOD SCREWS AS PER MANUFACTURER'S INSTALLATION SPACED ® 6" O.C. IN THE FIELD GUIDELINES & AT EDGES g MIN. 2X- WOOD RAFTER/JOIST/ a; TRUSS AT MAX. 24" O.C. a o TYPICAL PANEL INSTALLATION X—SECTION Z �a C Z)C14 0 ��0 - M #9-16 OR #10-14 WOODSCREWS LL En Y�i WITH SELF SEALING WASHER AT o L MAXIMUM SPACING OF 36" O.C. n J E10 SN �n O 5V-CRIMP 0o MIN 26 GA. YLo tj w GENERAL NOTES: 4j a 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE UNDERLAYMENT FLORIDA BUILDING CODE (FBC). a. a tom OSB 7/16" THICK (MIN.) OR 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.019"). EFFECTIVE COVERING 2n D ETA I L q 1 PLYWOOD 15/32" THICK (MIN.) WIDTH OF PANEL = 24". iR < 3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS v �x SPECIFIED ON THIS DRAWING. n aom 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS #9-16 OR #10-14 WOODSCREWS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS T WITH SELF SEALING WASHER AT ARE GREATER THAN THE DESIGN UPLIFT PRESSURES SPECIFIED ON THIS DRAWING. En m MAXIMUM SPACING OF 36" O.C. 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA N i BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM o a REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. 5V-CRIMP 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS MIN 26 GA. REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS. UNDERLAYMENT DRAWING NO. IREV. DETAIL 2 OSB 7/16" THICK (MIN.) OR 2182-4 PLYWOOD 15/32 THICK (MIN.) SHEEP NO. 1 OF 1 METAL SALES MANUFACTURING CORPORATION 5V-Crimp Uplift Loads (Min. 26 ga.) Description Fastener Spacing Allowable Uplift along panel length Load (in) (Psfl Coverage width: 24" 6 172.5 9 20.0 12 90.0 Panel Fasteners 15 72.0 #9-16 or#10-14 hex head 18 60.0 wood screws with sealed 21 51.4 washer 24 , 45.0 27 ' 40.0 30 36.0 33 32.7 36 30.0 Notes: 1. The bold numbers indicate design loads calculated from test data with safety factor of 2. 2. Panels,must be installed as per Evaluation Report FL 14645.4 and Metal Sales current installation procedure. 3. Three or more spans condition. �e�daac o u�i�iB�e ,,e,�P.g0CKg4� . No 62240 ..•� ;.• STATE OF •;� 0'R 1 0 P.a.N=ovo • ' • 1216 N Lansing Ave., Suite C ®�B Bala Sockalingam,Ph.D.,P.E. Tulsa,Ok 74106 FL 62240 918 492 5992 9,.'Q\.2G� '