HomeMy WebLinkAboutAPPRVD Dry HydrantFIRE PROTECTION
MATERIAL SUBMITTALS
FOR:
FFPPLL SSOOLLAARR
DDrryy HHyyddrraanntt
3650 AICO ROAD
FT. PIERCE, FL 34945
Date: May 27, 2020
Our Project Number: FP-265420
Project Manager: Joe Furlong
Prepared By: Thomas Bender
The materials submitted represent the quality of materials specified. All
materials may be substituted at this contractor’s discretion for like
equivalent materials.
W. W. Gay Fire & Integrated Systems, Inc.
2251 Rosselle Street / 2500 N.E. 18th Terrace
Jacksonville, Florida 32204 / Gainesville, Florida 32609
904-387-7973 / 352-380-0317
15
Product Specifications
System: PVC Schedule 40 Pressure Pipe and Fitting System
Scope: This specification covers PVC Schedule 40 pipe and fittings for pressure applications. This system is
intended for pressure applications where the operating temperature will not exceed 140°F.
Specification: Pipe and fittings shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with
a Cell Class of 12454 as identified in ASTM D 1784.
PVC Schedule 40 pipe shall be Iron Pipe Size (IPS) conforming to ASTM D 1785. PVC Schedule 40
fittings shall conform to ASTM D 2466. Pipe and fittings shall be manufactured as a system and be the
product of one manufacturer. All pipe and fittings shall be manufactured in the United States. Pipe and
fittings shall conform to NSF International Standard 61 or the health effects portion of NSF Standard
14.
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry
and shall conform to all applicable plumbing, building, and fire code requirements. Buried pipe shall be
installed in accordance with ASTM F 1668 and ASTM D 2774. Solvent cement joints shall be made in
a two step process with primer conforming to ASTM F 656 and solvent cement conforming to ASTM
D 2564. The system shall be protected from chemical agents, fire stopping materials, thread sealant,
plasticized vinyl products, or other aggressive chemical agents not compatible with PVC compounds.
Systems shall be hydrostatically tested after installation. WARNING! Never test with or transport/store
compressed air or gas in PVC pipe or fittings.
Referenced Standards*:
ASTM D 1784 Rigid Vinyl Compounds
ASTM D 1785 PVC Plastic Pipe, Schedule 40
ASTM D 2466 PVC Plastic Fittings, Schedule 40
ASTM D 2564 Solvent Cements for PVC Pipe and Fittings
ASTM D 2774 Underground Installation of Thermoplastic Pressure Piping
ASTM F 656 Primers for PVC Pipe and Fittings
ASTM F 1668 Procedures for Buried Plastic Pipe
NSF Standard 14 Plastic Piping Components and Related Materials
NSF Standard 61 Drinking Water System Components - Health Effects
*Note: Latest revision of each standard applies.
Short Specification:
Pipe and fittings shall be manufactured from PVC compound with a cell class of 12454 per ASTM D 1784
and conform with NSF International Standards 14 and 61. Pipe shall be iron pipe size (IPS) conforming
to ASTM D 1785. Fittings shall conform to ASTM D 2466.
All pipe and fittings shall be produced by a single manufacturer and shall be installed in accordance with
manufacturer’s recommendations and applicable code requirements. Buried pipe shall be installed in
accordance with ASTM F 1668 and ASTM D 2774. Solvent cements shall conform to ASTM D 2564,
primer shall conform to ASTM F 656. The system is to be manufactured by Charlotte Pipe and Foundry
Company and is intended for pressure applications where the temperature will not exceed 140°F.
GENERAL INFORMATION
22
Plastics Technical Manual
This is to certify that all Plastic Pipe and Fittings manufactured by Charlotte Pipe and Foundry Company are manufactured
in the United States and conform to the following standards:
PVC SCH. 40 SOLID WALL PIPE
ASTM D 1784, ASTM D 1785, ASTM D 2665
FHA UM 79a
FEDERAL SPECIFICATION L-P-320a
NSF STANDARD 14 AND 61
PVC SCH. 40 DWV CELLULAR CORE PIPE
ASTM D 4396, ASTM F 891
NSF STANDARD NO. 14
RePVC® SCH. 40 DWV PIPE WITH RECYLED CONTENT
ASTM D 4396, ASTM F 1760
NSF STANDARD NO. 14
PVC SCH. 40 DWV FITTINGS
ASTM D 1784, ASTM D 2665, ASTM D 3311,
ASTM F1866
FHA UM 79a
FEDERAL SPECIFICATION L-P-320a
NSF STANDARD NO. 14
PVC SDR-21 AND SDR-26 PRESSURE PIPE
ASTM D 1784, ASTM D 2241
NSF STANDARD NO. 14 AND 61
PVC SCH. 40 PRESSURE FITTINGS
ASTM D 1784, ASTM D 2466
NSF STANDARD 14 AND 61
PVC SCH. 40 WELL CASING PIPE
ASTM D 1784, ASTM F 480
NSF STANDARD NO. 14 AND 61
PVC SCH. 80 PIPE
ASTM D 1784, ASTM D 1785
NSF STANDARD NO. 14 AND 61
PVC SCH. 80 FITTINGS
ASTM D 1784, ASTM D 2467
ASTM D 2464 ASTM F 1970
NSF STANDARD NO. 14 AND 61
PVC SDR 35 SEWER MAIN PIPE
ASTM D 1784, ASTM D 3034, SDR 35
ASTM D 3212, ASTM F 477
PVC SEWER AND DRAIN PIPE
ASTM D 1784, ASTM D 2729
PVC THIN WALL PIPE & FITTINGS
ASTM D 1784, ASTM D 2949
NSF STANDARD NO. 14
CPVC FLOWGUARD GOLD® CTS PIPE & FITTINGS
ASTM D 1784, ASTM D 2846
FHA UM-61a
NSF STANDARD NO. 14 AND 61
CSA LISTED ON SPECIFIED ITEMS
CPVC REUZE® CTS PIPE & FITTINGS
ASTM D 1784, ASTM D 2846
NSF STANDARD NO. 14
CPVC CHEMDRAIN® SCH. 40 PIPE & FITTINGS
ASTM D 1784, ASTM F 2618
NSF STANDARD 14
ABS SCH. 40 DWV CELLULAR CORE PIPE
ASTM D 3965, ASTM F 628
NSF STANDARD NO. 14
cNSF® us-dwv
ABS PLUS® SCH. 40 DWV CELLULAR CORE PIPE
ASTM D 3965, ASTM D 4396, ASTM F 1488
ABS SCH. 40 DWV FITTINGS
ASTM D 3965, ASTM D 2661, ASTM D 3311
FHA UM 79a
FEDERAL SPECIFICATION L-P-322b
NSF STANDARD NO. 14
CHARLOTTE PIPE AND FOUNDRY COMPANY
GENERAL INFORMATION
Product Certification
ABS Plus, ChemDrain, ReUze and RePVC are registered trademarks of Charlotte Pipe and Foundry Company.
FlowGuard Gold is a registered trademark of Lubrizol Corp.
23
Pipe Reference GuideMADEIN
U .S.A.
PRODUCT DATA
ABS Plus, ReUze, RePVC, ChemDrain and “You can’t beat the system” are registered trademarks of Charlotte Pipe and Foundry Company.
FlowGuard Gold is a registered trademark of Lubrizol Corp.
Sizes Available
Product 1⁄4 3⁄8 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 5 6 8 10 12 14 15 16
ChemDrain® CPVC
Schedule 40 ★ • • • • • •
FlowGuard Gold®
CPVC CTS SDR 11 • • • • • •
ReUze® CPVC CTS SDR 11 • • • • •
PVC Schedule 80 • • • • • • • • • • • • • • • • •
PVC Schedule 40 • • • • • • • • • • • • • • • •
PVC Schedule 40 DWV ★ • • • • • • • • • • • •
RePVC® Schedule 40 DWV
with Recycled Content ★ • • • • • •
PVC Schedule 30 ★ •
PVC DWV Foam Core ★ • • • • • • • •
PVC Well Casing • • • • • •
PVC SDR 13.5 (PR315) •
PVC SDR 21 (PR200) • • • • •
PVC SDR 26 (PR160) • • • •
PVC SDR 35 Sewer Main
Belled-End ★†
• •
PVC SDR 35 Sewer Main
Gasketed ★† • • •
PVC D 2729 Sewer and Drain ★† • •
ABS DWV Foam Core ★ • • • • •
ABS Plus® Foam Core DWV★ • • • •
★ Non-Pressure
† Not NSF Listed
Notes:
1. End treatments are Plain and Belled. Consult factory for availability.
2. Lengths are 10 and 20 feet (14 and 20 feet for Gasketed Sewer Main). Consult factory for availability and non-standard lengths.
3. PVC Schedule 40 Bell End and PVC Well Casing pipe lengths for sizes 4”, 6”, and 8” are 20 feet plus the bell (20 foot laying length).
4. PVC SDR 35 Sewer Main Pipe in 14 foot lengths are 14 feet plus the bell (14 foot laying length).
29
PVC 4005 1⁄2” x 10’ 06658 .840 .109 600 PSI 15.9
PVC 4005 1⁄2” x 20’ 03922 .840 .109 600 PSI 15.9
PVC 4007 3⁄4” x 10’ 06661 1.050 .113 480 PSI 21.1
PVC 4007 3⁄4” x 20’ 03925 1.050 .113 480 PSI 21.1
PVC 4010 1” x 10’ 06664 1.315 .133 450 PSI 31.3
PVC 4010 1” x 20’ 03928 1.315 .133 450 PSI 31.3
PVC 7100* 1
1⁄4” x 10’ 03945 1.660 .140 370 PSI 42.4
PVC 7100* 1
1⁄4” x 20’ 03946 1.660 .140 370 PSI 42.4
PVC 7112* 1
1⁄2” x 10’ 03947 1.900 .145 330 PSI 50.7
PVC 7112* 1
1⁄2” x 20’ 03948 1.900 .145 330 PSI 50.7
PVC 7200* 2” x 10’ 03949 2.375 .154 280 PSI 68.1
PVC 7200* 2” x 20’ 03950 2.375 .154 280 PSI 68.1
PVC 4025‡ 21⁄2” x 20’ 04205 2.875 .203 300 PSI 108.0
PVC 7300* 3” x 10’ 03951 3.500 .216 260 PSI 141.2
PVC 7300* 3” x 20’ 03952 3.500 .216 260 PSI 141.2
PVC 7400† 4” x 10’ 03953 4.500 .237 220 PSI 201.2
PVC 7400† 4” x 20’ 03954 4.500 .237 220 PSI 201.2
PVC 7500† 5” x 20’ 04837 5.563 .258 190 PSI 272.5
PVC 7600† 6” x 10’ 03955 6.625 .280 180 PSI 353.7
PVC 7600† 6” x 20’ 03956 6.625 .280 180 PSI 353.7
PVC 7800† 8” x 10’ 13087 8.625 .322 160 PSI 532.3
PVC 7800† 8” x 20’ 03958 8.625 .322 160 PSI 532.3
PVC 7910† 10” x 20’ 03959 10.750 .365 140 PSI 754.7
PVC 7912† 12” x 20’ 03961 12.750 .406 130 PSI 997.9
PVC 7914† 14” x 20’ 04862 14.000 .437 130 PSI 1180.1
PVC 7916† 16” x 20’ 04918 16.000 .500 130 PSI 1543.1
PVC SCHEDULE 40 (WHITE) PLAIN END PVC 1120 ASTM D 1785
MAX WORK PART NO. NOM. SIZE UPC # AVG. OD (IN.) MIN. WALL (IN.) PRESSURE WT. PER 611942- AT 23° C OR 73° F 100 FT. (LBS.)
>> PVC Schedule 40 Pipe - Plain End
PVC Pipe: Schedule 40
* Dual Marked ASTM D 1785 and ASTM D 2665.
† Triple Marked ASTM D 1785 & ASTM D 2665 & ASTM F 480.
‡ Dual Marked ASTM D 1785 & ASTM F 480.
NOTE: When ordering, please specify plain end or bell end.
NSF Listed. Meets All Requirements of ASTM D 1784 and ASTM D 1785.
PRODUCT DATA
Testing with or use of compressed air or gas in PVC / ABS
/ CPVC pipe or fittings can result in explosive failures and
cause severe injury or death.
• NEVER test with or transport/store
compressed air or gas in PVC / ABS / CPVC
pipe or fittings.
• NEVER test PVC / ABS / CPVC pipe or
fittings with compressed air or gas, or air
over water boosters.
• ONLY use PVC / ABS / CPVC pipe for water
or approved chemicals.
• Refer to warnings in PPFA User Bulletin
4-80 and ASTM D 1785.
Schedule 80 and Schedule 40 Socket Diameter Schedule 80 Schedule 40
Nominal Entrance Bottom Tolerance Socket Length Socket Length
Size A B C (Minimum) C (Minimum)
1⁄2 0.848 0.836 ±0.004 0.875 0.688 3⁄4 1.058 1.046 ±0.004 1.000 0.719 1 1.325 1.310 ±0.005 1.125 0.875 11⁄4 1.670 1.655 ±0.005 1.250 0.938 11⁄2 1.912 1.894 ±0.006 1.375 1.094 2 2.387 2.369 ±0.006 1.500 1.156 21⁄2 2.889 2.868 ±0.007 1.750 1.750 3 3.516 3.492 ±0.008 1.875 1.875 4 4.518 4.491 ±0.009 2.250 2.000 6 6.647 6.614 ±0.011 3.000 3.000 8 8.655 8.610 ±0.015 4.000 4.000 10 10.780 10.735 ±0.015 5.000 5.000 12 12.780 12.735 ±0.015 6.000 6.000
Scope:
This specification covers PVC Schedule 40 pipe and fittings for pressure applications. This system is intended for
pressure applications where the operating temperature will not exceed 140° F.
Specification:
Pipe and fittings shall be manufactured from virgin rigid PVC (polyvinyl chloride) vinyl compounds with a cell class of
12454 as identified in ASTM D 1784.
PVC Schedule 40 pipe shall be Iron Pipe Size (IPS) conforming to ASTM D 1785. Injection molded PVC Schedule 40
fittings shall conform to ASTM D 2466. Pipe and fittings shall be manufactured as a system and be the product of one
manufacturer. All pipe and fittings shall be manufactured in the United States. Pipe and fittings shall conform to NSF
International Standard 61 and the health-effects portion of NSF Standard 14.
Installation:
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall
conform to all applicable plumbing, fire, and building code requirements. Buried pipe shall be installed in accordance
with ASTM F 1668. Solvent cement joints shall be made in a two-step process with primer conforming to ASTM F 656
and solvent cement conforming to ASTM D 2564. The system shall be protected from chemical agents, fire-stopping
materials, thread sealant, plasticized-vinyl products or other aggressive chemical agents not compatible with PVC
compounds. The system shall be hydrostatically tested after installation. WARNING! Never test with or transport/store
compressed air or gas in PVC pipe or fittings. Doing so can result in explosive failures and cause severe injury or
death.
Referenced Standards:
ASTM D 1784: Rigid Vinyl Compounds
ASTM D 1785: PVC Plastic Pipe, Schedule 40
ASTM D 2466: PVC Plastic Fittings, Schedule 40
ASTM D 2564: Solvent Cements for PVC
Pipe and Fittings
SUBMITTAL FOR CHARLOTTE PIPE®
PVC SCHEDULE 40 PRESSURE PIPE AND FITTING SYSTEM
Charlotte Pipe and Charlotte Pipe and Foundry Company are registered trademarks of Charlotte Pipe and Foundry Company.
FO-SUB-PVC-40 (5-30-19)
Date: ________________
Job Name: ______________________________ Location: _______________________________
Engineer: _______________________________ Contractor: ______________________________
Not all fitting
patterns shown
Bushing
Plug
Cap
Street Quarter BendCrossEighth BendQuarter Bend
Male Adapter
Charlotte Pipe and Foundry Company • P.O. Box 35430 Charlotte, NC 28235 • (800) 438-6091 • www.charlottepipe.com
ASTM F 1668: Procedures for Buried Plastic Pipe
NSF Standard 14: Plastic Piping Components & Related Materials
NSF Standard 61: Drinking Water System Components –
Health Effects
Tee Coupling
Female Adapter
Schedule 40
Tapered Socket Dimensions
PVC SCHEDULE 40 - ASTM D 2466
Sizes Available
Product 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 5 6 8 10 12 14 16
PVC Schedule 40 • • • • • • • • • • • • • • • •
PIPE REFERENCE GUIDE
M A DE IN
U .S.A.
Technical Specification Purple Primer – NSF Listed
Oatey Co.
4700 West 160 th St.
Cleveland, OH 44135
Phone: 1-800-321-9532
Phone: 1-800-321-9535
Visit www.oatey.com for Update Page 1 of 3
Description
• Purple-tinted aggressive primer for use
on PVC and CPVC pipe and fittings.
• Lo-V.O.C. Solvent Cement meets
California South Coast Air Quality
Management District (SCAQMD)
1168/316A
or BAAQMD Method 40 and various
environmental requirements.
• Removes surface dirt, grease and grime
as well as softens the pipe surface to
allow a fast, secure solvent weld.
• For use in areas where plumbing code
calls for verification that a primer has
been used.
• N SF and IAPMO Listed.
• Meets ASTM F656.
Listings
NSF Standard 61 for PW,
DWV and Sewer Waste
IAPMO Listed
Maximum VOC per SCAQMD 1168/316A or BAAQMD Method 40: 550 g/L
INGREDIENTS (CAS Number)
Acetone (67-64-1), Cyclohexanone (108-94-4), Methyl Ethyl Ketone (78-93-3), Red Dye (4477-76-6)
Violet Dye (81-48-1), Tetrahydrofuran (109-99-9)
MSDS Number: 1402E
Product
Number
Size Qty Wgt Product
Number
Size Qty Wgt
30755 4 oz. 24 8 lbs. 307553 4 oz. 48 8 lbs.
30756
30757
30758
30759
8 oz.
16 oz.
32 oz.
Gallon
24
24
12
6
14 lbs.
25 lbs.
24 lbs.
46 lbs.
307563
307573
307583
8 oz.
16 oz.
32 oz.
36
10
6
14 lbs.
25 lbs.
24 lbs.
Technical Specification Purple Primer – NSF Listed
Oatey Co.
4700 West 160 th St.
Cleveland, OH 44135
Phone: 1-800-321-9532
Phone: 1-800-321-9535
Visit www.oatey.com for Update Page 2 of 3
CHEMICAL PROPERTIES
Appearance
Density
Shelf Life
Purple Liquid
6.97 ± 0.2 lbs/gallon
3 Years from Mfg.
Date
Precautions
Read all information carefully before using this product.
DANGER!: CAUSES SERIOUS EYE IRRITATION. HARMFUL IF INHALED. MAY CAUSE DROWSINESS OR
DIZZINESS. MAY CAUSE RESPIRATORY IRRITATION. REPEATED EXPOSURE MAY CAUSE SKIN DRYNESS OR
CRACKING. Long term overexposure to solvents may cause damage to the brain, nervous system,
reproductive system, respiratory system, mucous membranes, liver and kidneys. Contains a chemical
classified by the US EPA as a suspected possible carcinogen. KEEP OUT OF REACH OF CHILDR EN.
PRECAUTIONS: Avoid breathing vapors. Use only outdoors or in a well-ventilated area. Use explosion-proof
electrical/ventilating equipment. Use only non-sparking tools. Take precautionary measures against static
discharge. Wear a NIOSH-approved respirator for organic solvents. Keep away from heat/sparks/open
flames/hot surfaces. No smoking. Vapors may accumulate in low places and may ignite explosively. Keep
container tightly closed and cool. Wear protective gloves and eye protection. Wash thoroughly after
handling. Do not eat or drink while using this product.
EMERGENCY/FIRST AID: CALL 1-877-740-5015 FOR INSTRUCTIONS.
IF SWALLOWED: Immediately call a POISON CENTER/doctor. Do NOT induce vomiting. Rinse mouth. This
product may be aspirated into the lungs and cause chemical pneumonitis, a potentially fatal condition. If IN
EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do.
Continue rinsing. If eye irritation persists, get medical attention. If ON SKIN: Rinse skin with water/shower.
Take off immediately all contaminated clothing. If INHALED: Remove person to fresh air and keep
comfortable for breathing. Call POISON CENTER/doctor if you feel unwell. If medical advice is needed, have
product container or label at hand. FIRE: Use dry chemical, foam, or carbon dioxide extinguisher. Water
spray may be applied to reduce potential vapors or for cooling. Burning liquid extinguished with water will
_oat and may re-ignite on surface of water. SPILLS: Remove all sources of ignition and ventilate area.
Personnel cleaning up the spill should wear appropriate personal protective equipment, including
respirators if vapor concentrations are high. Soak up spill with absorbent material. Put absorbent material
in covered, labeled metal containers. Dispose of contents/ container in accordance with local regulations.
Store in a well-ventilated space. Store locked up.
Technical Specification Purple Primer – NSF Listed
Oatey Co.
4700 West 160 th St.
Cleveland, OH 44135
Phone: 1-800-321-9532
Phone: 1-800-321-9535
Visit www.oatey.com for Update Page 3 of 3
Directions for Use
Store and use at temperatures between -15°F and 110°F. At temperatures outside of this range, special
care must be taken to prepare good joints and prevent exposure to solvents. Stir or shake before using; if
jelly-like, don’t use. Do not thin.
Handle with care! Will stain most materials and surfaces.
1. Cut pipe ends square, chamfer and clean pipe ends.
2. Check dry fit of pipe and fitting. Pipe should easily go 1/3 of the way into the fitting. If pipe bottoms, it
should be snug.
3. Use a suitable applicator at least 1/2 the size of the pipe diameter. For larger size pipe systems use a
natural bristle brush or roller.
4. Apply thoroughly to inside of the fitting socket and to the outside surface of the pipe to the depth of the
fitting. Apply a second coat of primer to fitting socket.
5. While primer is still wet use an appropriate solvent cement for the pipe being joined. Follow application
instructions from cement can.
DO NOT TEST WITH AIR.
Revision Date: 3/15/2013
Technical Specification Regular Clear PVC Cement
Oatey Co.
4700 West 160 th St.
Cleveland, OH 44135
Phone: 1-800-321-9532
Phone: 1-800-321-9535
Visit www.oatey.com for Update Page 1 of 3
Description
Regular-Bodied Clear cement for use on all
schedules and classes of PVC pipe and fittings
up to 4” for Sch. 40 and up to 2” for Sch. 80.
Lo-V.O.C. Solvent Cement meets California
South Coast Air Quality Management District
(SCAQMD) 1168/316A or BAAQMD Method 40
and various environmental requirements.
Recommended for potable water, pressure
pipe, conduit and DWV.
Recommended application temperature 40°F to
110°F / 4°C to 43°C.
Meets ASTM D-2564.
Listings
NSF Standard 61 for PW,
DWV and Sewer Waste
IAPMO Listed
Maximum VOC per SCAQMD 1168/316A or BAAQMD Method 40: 510 g/L
INGREDIENTS (CAS Number)
Acetone (67-64-1), Amorphous Silica (112945-52-5), Cyclohexanone (108-94-4), Methyl Ethyl Ketone
(78-93-3), PVC Resin (9002-86-2), Tetrahydrofuran (109-99-9)
MSDS Number: 1100E
Product Number Size Qty Wgt Product Number Size Qty Wgt
31012 4 oz. 24 9 lbs. 310123 4 oz. 48 8 lbs.
31013 8 oz. 24 15 lbs. 310133 8 oz. 36 15 lbs.
31014 16 oz. 24 28 lbs. 310143 16 oz. 10 28 lbs.
31015 32 oz. 12 27 lbs. 310153 32 oz. 6 27 lbs.
31016 Gallon 6 50 lbs.
Technical Specification Regular Clear PVC Cement
Oatey Co.
4700 West 160 th St.
Cleveland, OH 44135
Phone: 1-800-321-9532
Phone: 1-800-321-9535
Visit www.oatey.com for Update Page 2 of 3
CHEMICAL PROPERTIES
PHYSICAL PROPERTIES
Appearance
Viscosity
Density
Shelf Life
Clear Liquid
Min. 90 cps @73° F ± 2° F
7.47 ± 0.2 lbs/gallon
3 years from manufacture
date
Lap Shear Strength
2 hours
16 hours
72 hours
Set Up Time
30° F to 50° F
50° F to 70° F
70° F to 90° F
(min. ASTM Standards)
250 psi
500 psi
900 psi
6 – 7 minutes
4 – 5 minutes
1 – 3 minutes
Precautions
Read all information carefully before using this product.
DANGER!: CAUSES SERIOUS EYE IRRITATION. HARMFUL IF INHALED. MAY CAUSE DROWSINESS OR
DIZZINESS. MAY CAUSE RESPIRATORY IRRITATION. REPEATED EXPOSURE MAY CAUSE SKIN DRYNESS
OR CRACKING. Long term overexposure to solvents may cause damage to the brain, nervous system,
reproductive system, respiratory system, mucous membranes, liver and kidneys. Contains a chemical
classified by the US EPA as a suspected possible carcinogen. KEEP OUT OF REACH OF CHILDREN.
PRECAUTIONS: Avoid breathing vapors. Use only outdoors or in a well-ventilated area. Use explosion-
proof electrical/ventilating equipment. Use only non-sparking tools. Take precautionary measures
against static discharge. Wear a NIOSH-approved respirator for organic solvents. Keep away from
heat/sparks/open flames/hot surfaces. No smoking. Vapors may accumulate in low places and may
ignite explosively. Keep container tightly closed and cool. Wear protective gloves and eye protection.
Wash thoroughly after handling. Do not eat or drink while using this product.
EMERGENCY/FIRST AID: CALL 1-877-740-5015 FOR INSTRUCTIONS.
IF SWALLOWED: Immediately call a POISON CENTER/doctor. Do NOT induce vomiting. Rinse mouth. This
product may be aspirated into the lungs and cause chemical pneumonitis, a potentially fatal condition. If
IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to
do. Continue rinsing. If eye irritation persists, get medical attention. If ON SKIN: Rinse skin with
water/shower. Take off immediately all contaminated clothing. If INHALED: Remove person to fresh air
and keep comfortable for breathing. Call POISON CENTER/doctor if you feel unwell. If medical advice is
needed, have product container or label at hand. FIRE: Use dry chemical, foam, or carbon dioxide
extinguisher. Water spray may be applied to reduce potential vapors or for cooling. Burning liquid
extinguished with water will _oat and may re-ignite on surface of water. SPILLS: Remove all sources of
ignition and ventilate area. Personnel cleaning up the spill should wear appropriate personal protective
equipment, including respirators if vapor concentrations are high. Soak up spill with absorbent material.
Put absorbent material in covered, labeled metal containers. Dispose of contents/ container in
accordance with local regulations. Store in a well-ventilated space. Store locked up.
Technical Specification Regular Clear PVC Cement
Oatey Co.
4700 West 160 th St.
Cleveland, OH 44135
Phone: 1-800-321-9532
Phone: 1-800-321-9535
Visit www.oatey.com for Update Page 3 of 3
Directions for Use
Store and use at temperatures between 40°F and 110°F. At temperatures outside of this range, special
care must be taken to prepare good joints and prevent exposure to solvents. Stir or shake before using;
if jelly-like, don’t use. Do not thin.
1. Cut pipe ends square, chamfer and clean pipe ends.
2. Check dry fit of pipe and fitting. Pipe should easily go 1/3 of the way into the fitting. If pipe bottoms, it
should be snug.
3. Use a suitable applicator at least 1/2 the size of the pipe diameter. For larger size pipe systems use a
natural bristle brush or roller.
4. Clean pipe and fitting with a listed primer.
5. Apply liberal coat of cement to pipe to the depth of the socket, leave no uncoated surface.
6. Apply a thin coat of cement to inside of fitting, avoid puddling of cement. Puddling can cause
weakening and premature failure of pipe or fitting. Apply a second coat of cement to the pipe.
7. Assemble parts QUICKLY. Cement must be fluid. If cement surface has dried, recoat both parts.
8. Push pipe FULLY into fitting using a ¼ turning motion until pipe bottoms.
9. Hold pipe and fitting together for 30 seconds to prevent pipe push-out - longer at low temperatures.
Wipe off excess.
10. Allow 15 minutes for good handling strength and 2 hours cure time at temperatures above 60°F
before pressure testing up to 180 psi. Longer cure times may be required at temperatures below 60°F or
with pipe above 3".
DO NOT TEST WITH AIR.
Revision Date: 3/15/2013