HomeMy WebLinkAboutproduct approval (3)16/20/22 kW
GENERAL' _
specifications
C vlz:xr of 3r' 07043 0
Model
Rated Maximum Continuous Power Capacity (LP)
Rated Maximum Continuous Power Capacity ING)
Rated Voltage
Rated Maximum Continuous Load Current — 240 Volts (LP/NG)
Total Harmonic Distortion
Main Line Circuit Breaker
Phase
Number of Rotor Poles
Rated AC Frequency
Power Factor
Battery Requirement (not included)
Unit Weight (Ib/kg)
Dimensions (L x W x H) in
Sound output in dB(A) at 23 It (7 m) with generator operating at normal load'
Sound output in dB(A) at 23 it (7 m) with generator in Quiet -Test" low -speed exercise mode`"
G007035-0, G007036-0,
G007038-0, G007039-0
G007042-0, GO
G007037-0 (16 kW)
(20 kW)
(22 kW)
16,000 Watts'
20,000 Watts'
22,000
16,000 Watts*
18,000 Watts'
19,500
240
240
240
66.6/66.6
83.3/75
91.6/81.3
Less than 5%
Less than 5%
Less than 5%
,
70 Amp
100 Amp
100 Amp
1
1
1
2
2
2
60 Hz
60 Hz
60Hz
1.0
1.0
1.0
12 Volts, Group 26R 540 CCA Minimum or Group 35AGM
650 CCA Minimum
406/186
448/203
466/211
48 x 25 x 29/1218 x 638 x 732
66
66
67
58
58
58
5 min
5 min
5 min
Engine
GENERAL G Force 1000 Series
Type of Engine
2
2
2
Number of Cylinders
999 cc
999 cc
999 cc
Aluminum w/ Cast Iron Sleeve
Cylinder Blocsplacement
Cylinder Block
Overhead Valve
Overhead Valve
Overhead Valve
Valve Arrangement
Solid-state w/ Magneto
Solid-state w/ Magneto
Solid-state w/ Magneto
Ignition System
Electronic
Electronic
Electronic
Governor System
9.5:1
9.5:1
9.5:1
Compression Ratio
12 Vdc
12 Vdc
12 Vdc
Starter
Oil Capacity Including Filter
Approx.1.9 1 L
Approx.1.9 gV1.8 L
Approx.1.9 gV1.8 L
Operating rpm
3,600
3,600
3,600
Fuel Consumption
Natural Gas ION (ma/hr)
1/2 Load
218 (6.17) 204 (5.78) 216 (6.12)
Full Load
309 (8.75) 301 (8.52) 310 (8.78)
Liquid Propane fta/hr (gal/hi [Vhrj
1/2 Load
91.6 (2.52) [9.53) 86 (2.37) [8.99] 93.2 (2,56) [9.70)
Full Load
106.8 (2.94) (11.111 129.6 (3.56) [13.481 140 (3,87) [14.65]
Note, Fuel pipe must be sized for full load. Required fuel pressure to generator fuel
inlet at all load ranges - 3.5-7" water column (7-13 mm mercu(y) for natural gas, 10-12'' water column (19-22 mm mercury)
for LP gas. For Btu content, multiply fta/hr x 2500 (LP) or I0/hr x 1000 (NG). For Megajoule content, multiply ri x 93.15 (LP) or m3/hr x 37.26 (NG)
Controls
2-Line Plain Text Multilingual LCD Display
Simple user interface for ease of operation.
Mode Buttons:Auto
CAutomatic Start on Utility failure. '7'day exerciser.
Manual
Start with starter control, unit stays on. 11 utility falls, transfer to load takes place.
Off
:;. Stops unit. Power is removed. Control and charger still operate.
a
Ready to Run/Maintenance Messages
Standard
Engine Run Hours Indication
Standard
Programmable start delay between 2-1500 seconds
Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable (Brownout Setting)
rom 140-171 V119O-216 V
Future Set Capable Exerciser/Exercise Set Error Warning
Standard
_
RuNAlarm/Maintenance Logs
50 Events Each
Engine Start Sequence
Cyclic cranking, 16 sec on, 7 rest (90 sec maximum duration).
Starter Lock -out
Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger
Standard
Charger Fault/Missing AC Warning
Standard
Low Battery/Battery Problem Protection and Battery Condition Indication
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection
Standard
Under-Frequency/Overload/Stepper Overcurrent Protection
Standard
Safety Fused/Fuse Problem Protection
Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown
Standard
Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown
Standard
High Engine Temperature Shutdown
Standard
Internal Fault/Incorrect Wiring Protection
Standard
Common External Fault Capability
Standard
Field Upgradable Firmware
Standard
"Sound levels are taken from the front of the generator. Sound levels taken from other sides of the
generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying emergency power for the duration
BS5514, IS03046 and DIN6271). * Maximum kilovolt amps and current are subject to and limited by such factors as fuel Btu/megajoule
of the utility power outage. No overload capability is available for this rating. (All ratings in accordance
with
level; also will decrease about 1 percent for each 6 °C (101) above 16 °C (60 fl.
content. ambient temperature. altitude, engine power and condition, etc. Maximum power decreases
about 3.5 percent for each 1,000 feel (304.8 meters) above sea and