HomeMy WebLinkAboutBuilding PlansGulf Coast Supply and MFG Sv Crimp Metal roofing FL #11451.12
26 ga. 5v crimp metal roofing attached to plywood deck using #9 x I.S"
wood screws with self sealing washer at 12" o.c. max spacing over A5TM D
(type 2) 30 lb felt underlayment installed with min_ 4' aide laps and 6" end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
�aLed 4".oc. at all laps �and �two Jstaggered�rows 12` o.c. in field. Attach
12"
12"
5/8" thick light textured
stucco on typical concrete ® Q
block construction
-------------------------ce------------
Vi
o'
Finish Columns with 5/8" thick x 8"w cut
5/8" thick cut coral coral finished stucco bands
finished stucco bands RIGHT ELEVATION
SCALE: 1/4" = 1'-0"
MAU
ELEVATION MOTES:
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11651.12
24 ga. 5v crimp metal roofing attached to plywood deck uamg #9 x 1.5'
wood screws with self sealing washer at 12" c.c. max spacing over ASTM D
(type 2) 30 Ib felt underlayment installed with min. 4 side laps and L" end
laps Fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced L o.c. at all laps and two staggered rows 12" o.c. in Field. Attach
deck to trusses uamg attachment detail on this sheet
Finiv A.i u�"n ,.mw a Wl ui Stucco on Lyrical concrete
fshed stucco bands block construction
REAR ELEVATION
- Overhangs at 1'-0" unless otherwise noted on Roof Plan
- Roof pitch at 4:12 unless otherwise noted
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11451.12 - ,Any changes to this plan shall be submitted to the architect
24 ga. 5v crimp metal roofing attached to plywood deck using 49 x 1.5"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D for approval 1n writing prior to Starting construction.
(type 2) 30 lb felt underlayment Installed with min. 4 side laps and 6" end ALL
laps Fastened with corrosion resistant tin caps and with 1.25" ring shank nails - Return ALL Stucco Bands Into Window or Door.
spaced L" o.c. at all laps and two staggered rows 12" o.c. in field. Attach
deck to trusses using attachment detail on this sheet
SCALE: 1/4" = 1'-0"
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11451.12
2L ga. 5v crimp metal roofing attached to plywood deck using 49 x 1.5"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment Installed with min_ 4' side laps and L' end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced L" o.c. at all laps and two staggered rows 12" o.c. in field. Attach
deck to trusses using attachment detail on this sheet
12
12
4 SLOPE 4 SLOPE
8'-1" T O.B.
8'-1" T.O.B. ly
.H. 1 r
12" tE:
r
5/8" thick x 8"w cut . 5/8" thick x 8"w cut
❑ coral finished stucco bands ®®®
3 coral finished stucco bands 3 �a
5/8" thick light textured ®®®
stucco on typical concrete -
block construction
-O"=Finished Floor - - - - - - - - - - - - - - - - - - - - - - - -- 5/8" thick light textured
stucco on tgpical concrete
block construction
LEFT ELEVATION FRONT ELEVATION
Product Approval Submittal Affidavit
Opening Schedule Swing Doors, Overhead Doors, Sliding Doors, Windows & Skylights
Opening
Type
NOA/FL
NUMBER
Product
Model #
Manufacturer
Glass
Attachment method
IEST
iration
Dae
Design Pressure
of Approved Tests
1,2,3
t4
FL# 239.9
Single Hun
g g
SH-110OA
I act
PGT
5/IL"
V4' ilia. tapcorts w/ min. 13/8' penetrate eo ye
spaced par pr ues approval. Contractor osl'iall adhere to
min. edge distances specified in Product approval
+ 65.0/-80.0 PSIF
IL-0330.02
Overhead
Garage Door
Model 824/811
L -0" mmax height
D QB
h wed I'd
Tes ixa"vert. uses af"x "6t""H'i"Itti HLC e black 6lieve KGi R. LG e•" OC.
"aI S s :° a Jul i'kr4. ,AeJ N " I.K alyrKv`.t t..M.� a
mt a I.s' s41 d.t"* e. t Oc to a reels "dlariw prodmt arum
sIe VIL' boding gisk w roar andta.
10-9-21
+ 50.0/-60.0 sF
p
B
FL# IL614_I
Fiberglass
Design Pro/
amoagth Pro
Jeld-Wen
Elco 1/4' din. to con with min 1.25' embedment at 3' max
tram corners and p17.5" o.c. max, thereafter in head and jambs.
+ 50.0 PSF
C
FL# 251.4
Sliding Glass
Door
Series 11O
SGD
PGT
I" mom
Type "GSA"
1/4" die, tepcome w/ min. 1 3/4" penetration to be
epacad per product approval. Contractor shall adhere to
min. 2 I/2" edge distances specified in Product approval
+ 60.0 PSF
-
Product
NOA/FL
NUMBER
Model #
Manufacturer
Attachment Method
sg
Ezpuation
Da
Design Pressure
of Approved Tests
MUlllon3
FLU 241.1
1" x 2 3/4" x .315'
PGT
Install per fastener type and epacmis shown in Table IA and IB
en product approval on sheet 6 of 22.
+ 58.0 PSF
Roof
FL# 11451.12
5V Crimp
Metal Roofing
Gulf Coast Su i
in y
and manufacturing
2L ga. 5v crimp metal roaring attached to plgwood deck using #9 x 1.5"
wood screws with seer sealingwasher at 12' D.C. Max spacing over ASTM D
(t a 2) 30 lb Pelt undarlmint installed with min. 4e side laps, and L' and
sP s ap
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
at all laps and two staggered r rows 12" o.c. In field. Attach
spaced L' trusses
deck to trusses using attachment dotal on roof plan
- 108.5 P$F
Siding
stucco on Block
Soffit
FL# 12198.3
Model T4 12" vented
Vinyl Soffit
Kagcan
Install using 2" x 2" battens at V D.C. screwed to soffit framing using
#8 x 3" wood screws at each truss. Install soffit tc battens using
0.12" dia. x 1.5" Iona ring shank ngils with 3/8' d ,Hurricane
+55.0/-35.0 PSF
Panels
I have reviewed the above and approved it
by my seal below. ( Architect or Engineer of Record
SCALE: 1/4" = 1'-0"
2" x 4" top plate 11
1/2" drywall ceiling on truss bottom cord
1/2" drywall on
" x 4" studs at 16" o.c.
base -board 11 11 ,,, 2 x 4" P.T. bottom plate
\ 4" concrete slab with fibermesh OR
Cxd" #10/10 WWM on 6 mil Visqueen over
clean compacted termite treated fill
Interior Non-Bearina Partition
Braden It
Braden AIA, FA
/ Architects
- Planners
411
S.E. Coconut Avenue
Tel :
(112) 281-8258
Fax :
(112) 281-8283
E-mail:
bradenala9comcast.net
W(onne Building Corp_
The Grand Carlton
Spanish Lakes
St. Lucie County Florida
/8" thick x 8"w cut
)ral finished stucco bands
1/8" Thick cut coral stucco over paper
backed wire lath nailed to substrate through
one layer of 15 lb felt using 8d nails. Substrate
to be 19/32" CDX Plywood nailed at 6" o.c.
in field and edges with IOd ring shank galvanized
nails into truss webbing.
SCALE: 1/4" = 1'-0"
®®
5/8" thick x 8"w cut
coral finished stucco bands
Finish Columns with
5/8" thick cut coral
finished stucco bands
ALL CONTRACTOR WARRANTIES BEGIN WHEN THE CLOSING
OCCURS BETWEEN THE BUYER AND WYNNE BUILDING CORP.
AND WILL CONTINUE FOR ONE YEAR FROM THAT DATE
PERMITTING
INFORMATION (FORM 100)
Florida Building Code Residential: Lth Edition and ASCE 1-10 for Wind Loading
Building Design is: Enclosed Risk Categor : II Wind Velocity: 4.5 mph ultimate
Mean
Roof Height: II'-0p" Roof Pitch:
Internal Pressure Coal is ent: ±Q1IL-
SubJectability to damage from: Weathering: Negligible Termites: Vera Heavu
Width of Roof End Zone: 3'-4" Wind Speed: I45 mph ultimate
Wind Exposure Classification: C
yo LOOP 2J2
CH
Adjustment factor for Exposure Height: 1.21 x 0.6 = 0.126 ASD design
Load Combination: ASCE 1-10 Section 2.4 DL+LL; DL+O.LWL; O.6DL+O.6WL
Components E Cladding Wind Pressure (NET) Roof Zone: I. +20.L/-32.L psf
Roof Zone: 2. +20,L/-51.0 pal
Roof Zone: 3. +20.L/-84.0 psF
Components f Cladding Wall End Zone Width: 3'-4"
Components t Cladding Wind Pressure (NET) Wall Zone: 4. +36.8/-38.1 paf
= Roof Zone I
Wall Zone: 5. +35.8/-41.8 paf
Walla Zone 4
Components E Cladding Wind Pressure (NET) on Garage Door:+32.0/-40.3psf
Shear Walls Considered for Structure? Yes
® = Roof Zone 2
Continuous Load Path Provided? Yes
Walls Zone 5
Are Components an Cladding DeiaT Provided? Yea
END ZONE
Minimum Sal Bearing Pressure: 2.Boo psi, Presumptive: X By Test: psi
= Corner Zones
SEE PRODUCT APPROVAL FOR IMPACT P O ECTION FOR OPENINGS
Roof Zone 3
ROOF LIVE LOAD: 31 paf ROOF DEAD LOAD: 10 psf
FLOOR LIVE LOAD---4-5- pef FLOOR DEAD LOAD: l0 sf
JOB ADDRESS: 03 Mdr FdClflco
Date Drawn Revisions
G3-25-20
GARAGE
LEFT Drawn bg:����
C.C.U. R VIEWED FOR
Checked by: CODE COMPLIANCE
D.R.B.
Sheet Comm #
OF 5
5/7
FLOOR FLAN
CRASH POST DETAIL
TYPICAL
NOTES: SCALE 1/4" = 1'-0"
36" high by 4" diameter
I.
Contractor to verify ALL notes and dimensions prior to
steel crash post. Floor
proceeding with work.
Requirements.
Flange with 4 - to
anslon bolts Into
2.
Contractor to STRICTLY enforce ALL OSHA Q
slab l3/8"t 50 ksi steel plate)
la
3.
ALL Lumber to be used as Beam, Rafters, etc... to have
4.
a minimum 1,400 P.S.I. fiber stress.
4.
No dissimilar metals to touch.
''"
2h
2
�'
5.
ALL Concrete used for slabs shall be min. 2,500 PSI concrete.
o
ALL Concrete used for vertical filled cells, cons. tie beams etc.. to
"'
shall be 3,000 P.S.I. concrete and/or 4,000 P.S.I. grout mix
�3/8"
4.
Drywall at ceilings shall be leveled and attached to bottom chord
�/�
' "
"
of trusses With screws per FBC R102.3.5.
o 04"
1.
ALL wood in contact with concrete shall be pressure treated,
�2'
8.
ALL wall dimensions are nominal and not finished wall or stud dimensions.
9.
ALL plumbing fixtures to be low flow.
10.
Contractor to Provide Drain at water heater in accordance
with the current edition of the Florida Plumbing Code.
11.
Contractor to Provide a 2'-8" wide door at one bathroom for
handicap accessibility requirements.
'A
12.
Lowest finished floor to be set bg Governing Building Department
13,
surveyor to set in field.
Separation between residence and garage shall be per FBC R302.6
14.
Door between garage and residence shall be 1-3/4"t 20 min. rated door
w.H. = Water Heater
15.
Wall and Ceding shall have a flame -spread classification of not greater than 200 per FBC
R302.9.1
14.
Wall and ceiling finishes shall have a smoke -developed index of not greater than 450 per
FBC R302.9.2
11.
All exposed attic insulation materials installed on attic floors shall have a critical radiant
I" x 6Masonry Beam
" P.T. Buck Walled to
flux not less than 0.12 watt per square centimeter. Exposed foam plastic insulation
block with case hardened nails
materials exposed on the underside of the roof deck or on the attic walls shall comply
prior to door attachmen
18.
with F.B.C. R314 - see permit info box of code edition
Gyypsum board material shall conform to ASTM C3b, C'19, C415, C514, C00, C931
=..
C`f60, C1002, C1041,C1111, C1118, C1218, C1395, or C139L and shall be installed
according to the following: (FBC R-T02.3.5)
Drywall
Thickness
Location
Orientation
Framing
Member
Max. spacing
of fasteners
Nail sizing options for
installation of drywall into
Spacing
Maximum
wood framing memb era
Nails
Screws
2" x min, thickness
Ceiling
Perpendicular
24"
T,
12"
13ga 1 3/8 " long with 19/44" head
OR
0.098" diameter x 1 1/4" long
annular -ringed or 5d cooler nail
y2 °OR
Wells
Either
16"
8"
I6"
0.080" dia. xx 1 5/8" long with
Direction
15/64" head
OR
Ggpsum board nail 0.086" die.
x 15/8" with 9/32" head.
Ceding
Perpendicular
24"
-1"
12"
13ga 1 5/8 0loong with 19/44" head
0.098" diameter x 1 3/8" long
annular -ringed or Ld cooler nail
e
0.092" din. xx 1 1/8" long with
Walls
Either
16"
8"
16"
Direction
I/4" head
OR
Ggpsum board nail 0.0915" die.
x 1 I/s" with 19/64" head.
Install SGD thru buck into
block with 3/I6" tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20." o.c. max
thereafter at head per product approval
Use 3/14" tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20" o.c. max
thereafter at sill per product q rc
19. ALL ceramic tile surfaces installed shall conform to ASTM A108.1 thru A108.6,
A108.1, A118.1, A118.3, A136.1 and A131.1
20. Cement, fiber -cement or glass mat gypsum backers in accordance with ASTM
C1288, C1325, OR CII18 and installed I.A.W. manufacturers recommendations shall
be used as backer for the wall tile in tub areas and wall panels in shower areas.
21. Insulation including facings such as retarders or vapor permeable members installed
within floor -ceiling assemblies, roof -ceiling assemblies, wall, crawl spaces and attics
shall have a flame spread index not to exceed 25 With an accompanying smoke
developed index not to exceed 450 when tested in accordance with ASTM E 84.
Insulation shall comply with F.B.C. R316-
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11651.12
d
26 go. 5v crimp metal roofing attached to plywood deck using #9 x 1.5"
woo screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment installed with min. 4' side laps and 6" and
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced 6 o.c. at all laps and two staggered rows 12" o.c. in field. Attach
deck to trusses using attachment detail on this sheet
Simpson HETA 20 or equal
hurric no anchor at each truss 12
with (10) IOd x 1 1/2" nails PRE-ENGINEERED TRUSSES
( 24' o.c.) supporting Max. 4 �- at 24"o.c. TYPICAL
1810lbs. up rt (shop drawings by manufacturer)
Aluminum Dnp
Edge 8 Fascia
; --7
2" x V Sub -Fascia
Kaycan full o vent vinyl soffit installed
using I/8" die shank x IS' long gaiv.
roofing nails with 3/0' dia. head per
product approval - see chart sheet 31
5/8" thick light textured
stucco on typical concrete \
block construction
#5 bar vert. w/
30" overlap
at each filled cell
Grade
rR-30n fiberglass
hord of trusses
with smooth finish
Two rows of beam block filled with concrete
and (l) 95 bar cost. in each row. Substitute
precast lintel filled with concrete and (1) #5
bar cont. for bottom row over openings
1/2" drywall over I" x furringg
strips at 16" o.c. with R4.1 Pi -foil
insulation on typical 8" Block walls
All drywall to be installed per FBC R102.3.1
T and shall meet all pertaining ASTM codes.
ao Mortar to be Type "M" only proportioned per FBC R601.1
and Mortar Jonts shall comply with FBC R601.2.1.
Provide Dur-O-Rock at all wet areas (ex. showers, tubs etc...)
Fill cell with concrete and
(l) 45 bar vert. (typical).
Max. spacing shall not exceed
Wood 48" unless otherwise noted
see foundation plan notes for
ase spacing at openings
4" concrete slab with fibermesh OR
L"x4" #10/10 WWM on 6 mil Visqueen over
/ clean compacted termite treated fill
II1 IIII-IIII ,
,,
1=I 111 I I h l l
III -IIII_ I IIII _I I _ 14"w x IS Concrete footing
with (2) #5 bars cunt. and #5
14" transverse bars at 48" o.c.
TYFICAL SECTION
Scale : 1/2" = 1'-0"
J
N.T.S.
Head
fixed door
sliding door
AREA CALCULATIONS
Living A/C =
144L
sq.
ft,
Front Porch =
141
sq.
ft.
Rear Porch =
200
sq.
ft.
Garage =
321
sq.
ft.
Total Under Roof=
2108
sq.
ft.
Total Cubic Ft =
11,5L8
2' VTR
1- I I
�r�l 12„
12" ER
1 BATH
i I LAV-1
r
LAV-I 2„
wm-I we -I 2 2"
2" LAUNDRY 3" 2"
2" 12' AAY JIL2, VTR
31,
®T-1 3P s-1 I
2, KTICHEN 2
LAv-I
2„I
3"
2"
3" we-1
BATH #2
„
2"
3n 9T-1
PLUMBING RISER
To septic
I" x 6" P.T. Buck nailed to O
block with case hardened nails
prior to door attachment
Masonry Wall 31
L -
11/2"
Bottom Track Typical Flooring
Sill Install SGD thru buck into
block with 3/14" tap-a*)n with
Sliding D oor D e t a I 1 I from
penetration at L" ." max.
from eacfi corner and 20." o.c. max
thereafter at Jambs per product approval Jamb
At Masonry Wall NTS
Window
Schedule
Mark
Size
Rou h O en.
Window Descrl tion
PRESSURE ZONE
I.
4'-5Y8"x 5'-3'/e"
54%s"x 63W,
Single Hung
ZONE 4
2.
V-2%8"x 5'-3 %"
'15' x 63 %;`
Single Hung
ZONE 4
3.
2'-2" x 3'-2 1/2"
2l%2"x 38V
Single Hung
ZONE 4
4.
4'-5%"x 4'-2%"
54%e"x 54Ys"
Single Hung
ZONE 4
ALL
Windows to be aluminum
windows w/ tint
and mullions per
elevations.
ALL windows to withstand pressures in permit info box on
sheet I
ALL windows in bathrooms to
be tempered
All
rough opening
dimensions
to be verified bg contractor
with
manufacturer s specs prior to construction
Door Schedule
Mark
Size
Rough Opening
Door Description
PRESSURE ZONE
A
9'-0" X T-O"
108" x 84"
Overhead Garage Door
ZONE 4
B
3'-O" X 6'-8"
41 %,"x 83s/i°
Fiberglass Panel - Inswin
ZONE 4
C
6'-08 X 6'-8"
14" x 81 '�;' ;(; o -
Sliding Glass Door
ZONE 4
D
2'-0" X C-8"
Solid Core - Wood
- 6-Panel -Bi-Fold
Finished 24" x 81 %2"
E
2'-6" X 6'-8"
Solid Core - Wood
- 6-Panel
F
5'-0" X 6'-8"
Solid Core - Wood
- 6-Panel - Bi-Fold
G
2'-8" x 6'-8" x I %,"
Solid Core Wood, Steel, or Masonite Door
H
2'-8" X 6'-8"
Solid Core - Wood
- 6-Panel
J
2'-6" X 6'-8"
Solid Core - Wood
- 6-Panel - Bi-Fold
K
2'-8" X 6'-8"
Solid Core - Wood
- 6-Panel - Bi-Fold
ALL Exterior doors to withstand pressures stated in permit info
box on sheet 41
GARAGE DOOR SPECIFIED IN PRODUCT APPROVAL FORM AND SHALL
WITHSTAND THE PRESSURES STATED IN PERMIT INFO BOX ON SHEET #I
All rough opening dimensions to be verified bg contractor
k with manufacturer s specs prior to construction
12"
OPTIONAL
PATIO/SLAB
O1771 1 IEFE °° N
EGRESS ILL A
12" x 12" Concrete column /
block ild
wvert.
intoo
((2)#1 bars tied into
lintels above
O
o
�
O
�
O
Covered Porch
D
a
° OO P D OO P OO
D
03
c
�
MASTER 1
=
a0crm
BEDROOM 8'-O" tol9'-8" A.F.F.
°
a m o
8'-0" A.F.F. V aulte Ceding
'n
~LLinIRV
Flat Ceiling
1hM
GRE
R O
o001,
_
'
� I
I
ON °
D
Rod 8 helf I
4"
I
H.B.
I`
Vanity to e 9 i I N
34 y.2 hig I w
C14
�
r I
C L O E I A.F.F.
�
D
P o 2" x 6" knee -wall 8'-0" to 9'-e"
Q below counter top IRVI Vaulted Ceiling
rr r I
DINING
1s, - - - -� ROOM
8 Rod 8 all he F: I
C
Q
OcAeINE
it
I
O 4
W
`� I vanity to be
T H \<
O
,4 o
I 34 Y2"high
I O
hl„Wall 11' 9 %," -o 3/4"
iv
f
®
Hi
KITCHEN 3'-a" 1 0
T
4-
Veni
thro
Dryer
h wall
t - - I-I/2" N
- -
-flan
l -O" e'A.F.F. Over g
�y
- Flat Ceiling o 0
10'-51, 4'-1"
•q
Upper cabinets to D
Ref. 3'-O"4"
cNv
2" filler
ext nd over
N
B
•! BATH � 2
Rgqwwrt�dNVy�
-
O I ening R"ar-V+nt
8 Shelf
O
O o ® -Rod -i
R-II Batts Ineleeian W.H. `a N _ E - - -
O
A/C
4"4 steel Ballard 1
`r
#1
See detail op Shis_sbste �„ $ I
I O
m
I 22' x 54" � �S >
N
Provide autoLoi Attie Aeeeu O
-,with
closer L light- J
-
22" �_ a'-O" A.F.F.
N7i
IkJ Flat Ceiling
�Q
150 Amp s 4" _om u'-6°
non -
on
Meter
Panel m
��
a
in SECOND m`
a
/� E BEDROOM n
EGRrN
G�4R,4GE EssY
O'-4" A.F.F. O ° MT
I
I Flat Ceiling r l]
c11
O y
D D o..
D
(]3
O
q
r - - - - - - - - - - - - - - - - - EGRESS
FE
Block wall in °
garage to be 1 = r C010
struck block
D
1 ° O O
- C CvER 1D
I 12" x 12" concrete column block filled
�
®RC with can rate and (2) bars vert. tie
1
0
into lintels ibove
;n
I
1 ® 1
0
D
3 �
-
9'-0" 3'-5"
2'-8" 2'-8"
4'-2" 5'_4"
15'-101,
5'-4"
3'-4"
9'-6"
Install windows thru buck into
block with 3/10 tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20.' o.c. max
thereafter at ,Iambs and 20" o.c. max.
Exterior face at head and sill per product approval
of wall Buck to be I' x 4' PT
Attach buck to block wall with
1/4" die. Elco conic screws with min.
1 1/4" penetration at 12" o.c. max
and 4" max from each corner thru
Exterior face 2" x 6" PT Buck
of wall -\ / \
I'x4" P.T. Buck nailed to INSTALL VULKEM BLOCK SEALANT �_#e wood screws thru jamb into buck
block with case hardened nails ON ALL JAMB, HEADER, AND at each hinge and 15" o.c. max and
Detail at W I n d oW S prior to window attachment SILL BLOCK PRIOR TO BUCK Detail at Door prior to door attachment
INSTALLATION
NTS NTS
Braden It Braden AIA, FA Anne Building Corp. Date Drawn : Revisions : Sheet Comm 4
Architects - Planners GARAGE 3-30-20
411 S.E. Coconut Avenue LEFT Drawn by: 2 O - � S
Tel : (112) 281-8258 The Grand Carlton 6143 MAR C.G.U. 2.
Fax : (112) 281-8283 PACIFICO CODE COMPLIANCE
E-mail;bradenala9comcast.net Spanish Lakes Checked by: ""r' LUCIE COUNTY
r St. Lucie County Florida D.R.B. OF 5
r—I -----
I 7<UQ., I UICt-�L IN _/ I T__ �__?:
I. ALL FOOTING ARE DESIGNED FOR A MINIMUM OF 2,500 PSF SOIL
BEARING CAPACITY. IF ANY SUB -SOIL, MUCK OR NON -UNIFORM
CONDITIONS EXIST, REPORT TO ARCHITECT AND OBTAIN
PROPER ENGINEERING DATA FOR DESIGN.
2. ALL SLABS AND FOOTINGS TO BE A MINIMUM 2,500 PSI AT 28 DAYS
ALL COLUMNS, FILLED CELLS, AND BEAMS SHALL BE MIN. 3000 PSI
BE 3000 PSI OR 4,000 PSI GROUT MIX AT 28 DAYS
3. POISON SOIL AND COVER W/ b MIL. VISQUEEN WITHIN 24 HOURS. NO
SOIL POISONING TO BE ACCOMPLISHED OUTSIDE OF FOUNDATION.
4 GROUND FLOOR SLAB TO BE A MINIMUM 4" THICK W/ 6X4 I0/10
WELDED WIRE MESH REINFORCING ON L MIL. POLYETHYLENE VAPOR
BARRIER ON TERMITE TREATED, CLEAN MACHINE COMPACTED FILL
(MINIMUM 95% DENSITY). LAP POLYETHYLENE 12" MINIMUM. FIBERMESH
MIX MAY BE SUBSTITUTED FOR WELDED WIRE MESH.
5• LOT TO BE CLEARED OF ALL SMALL PLANT GROWTH AND DEBRIS
BEFORE FILL IS BROUGHT IN. FILL MATERIAL SHALL CONSIST OF
CLEAN GRANULAR SAND CONTAINING LESS THAN 10% MATERIAL
PASSING THE US STANDARD NO. 200 MESH SIEVE. PLACE
STRUCTURAL FILL IN LOOSE LAYERS OF 12" IN THICKNESS AND
COMPACT EACH LIFT TO AT LEAST 95% OF ITS MODIFIED DRY
PROCTOR VALUE.
`• GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY DISCREPANCIES OR OMISSIONS TO THE
ATTENTION OF THE ARCHITECT.
GARAGE FLOORS TO BE SMOOTH TROWEL FINISH (SLOPPED PER
FOUNDATION PLAN). PROVIDE 1-1/2" RECESS FOR OVERHEAD DOOR
FCLAD/470N FLAN
B. SLOPE ALL PORCH SLABS, COVERED WALK, ETC. AWAY
FROM HOUSE TO DRAINS (IF PROVIDED) PER PLANS
9. DESIGN LOADS ARE AS FOLLOWS:
ROOF (DL+LL) = 41 PSF
WIND VELOCITY = PER PERMIT INFO BOX ON SHEET 41
EXPOSURE ="C"
10. ALL REINFORCING STEEL SHALL BE GRADE 40, MEETING ASTM A-I6, E
A-35 SPECIFICATIONS. ALL ANCHOR TO BE A - 30l STEEL,
II. ALL DOWELS, SLEEVES, CONDUITS, INSERTS, BLOCKOUTS, ANCHOR
BOLTS AND FRAMES SHALL BE IN PLACE PRIOR TO POURING CONCRETE.
FOR OPENINGS AND SPECIAL FEATURES OMITTED ON THESE PLANS,
SEE ARCHITECTURAL OR MECHANICAL PLANS WHERE APPLICABLE.
12. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS:
FOOTING: 3"
BEAMS: 1-1/2"
13. LAP ALL REINFORCING STEEL A MINIMUM OF 48 BAR DIAMETERS.
14. USE STRUCTURAL GRADE WOOD WITH A MINIMUM Fb OF 1400 PSI
IS. ALL STANDARD LUMBER SHALL BE SYP WITH A MINIMUM Fb OF 1000
PSI OF NO.2 SOUTHERN PINE, UNLESS NOTED OTHERWISE.
14. ALL LUMBER IN CONTACT WITH ANY CONCRETE OR MASONRY SHALL BE
PRESSURE TREATED. FASTENERS TO HAVE MIN. G185 RATING.
I. Any changes to plans must be submitted to the architect
for approval before proceeding with construction.
2. Contractor shall be responsible for verification of all
notation and dimensions before starting construction.
3. Soil conditions assumed to be 2500 psf. Should any other conditions be
encountered, the architect Shall be notified in writing for revision
-4. Verify all recess thickness at showers, tile, etc....
5. Contractor to provide filled cell with concrete and 1 45 bar vert. at 48"
o.c. max. Provide (1) filled cell on each side of openings up to 5'-11" wide.
and Provide (3) filled cells on each side of openings from 10'-0" and up
Contractor to see plans for any other condition used. Foundation walls
shall have filled cells at 24' o.c. unless otherwise noted (see section)
6. Contractor to provide for Form Board Survey - Form Board Survey
to be provided to Truss Company prior to truss construction
-1. Contractor to provide for soil test prior to construction and provide
a copy of soil test to architect for review prior to construction
S. ALL Reinforcing steel Shall be grade 60, meeting ASTM A-l6 and
A-35 specifications. ALL Anchors to be A-301 steel.
9. Provide a minimum of 3" concrete protection at footings and
1-1/2" concrete protection at beams for ALL reinforcing bars.
#5 bar vert. w/
30" overlap Fill cell with concrete and
t (t U Thicken edge to 8"x8"
SCALE: 1/4" = 1'-0"
Termite Protection for New
Construction.
Soil treatment used for subterranean termite prevention
inside the foundation perimeter shall be done after all
excavation, backfilling and compaction is complete.
If soil area is disturbed after initial chemical soil treatment
area shall be re -treated with a chemical soil treatment
including spaces boxed or framed.
Treatment must be in accordance with the rules and laws
established bg the Florida Department of Agriculture and
consumer services.
Protective sleeves around metallic piping penetrating
concrete slab on grade floors shall not be of cellulose
containing materials and shall receive application of
termicide in annular space between sleeve and pipe.
at each filled a
(U #5 bar ver . ypica .
Max. spacing shall not exceed with concrete and 4" concrete slab with fibermesh OR
48" unless otherwise noted one #5 bar continuous CxC' #10/10 WWM on 10 mil Visqueen over
Wood see foundation plan notes for clean compacted termite treated fill
Base spacing at openings GRAD
4" concrete slab with fibermesh OR
'' `` ':`
Vx6" #10/10 WWM on 6 mil Visqueen over .•
m
/ clean compacted termite treated fill in
Grade aD6.
_— V III IIIIEMIIP1I ICE III1=
_IIII
-1 I I—ICI—IIII IIII IIII— 14"w x 18"d Concrete footing
I I-1 I I II I I IIII—IIII- with (2) #5 bars cunt. and #5
transverse bars at 48" o.c.
TYPICAL FOOTING DETAIL
SCALE 1/2" = 1'-0"
4" concrete slab with fibermesh OR
6 xb #10/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
#5 bar cont_
Step per
foundation plan
DETAIL AT
12" x 12" concrete column
block filled with concrete
and (2) #-1 bars vert. tied
into lintals above
Top of rooter
16" below finished floor
#5 bars cont. bottom steel
-> I
GARAGE STEPDOWN
SCALE 1/2" = 1'-0"
SIN=
Contractor to provide
proper foundation chairs
for proper steel installation
PORCH SLAB EDGE DETAIL 30 min.
SCALE 1/2"
#5 bar vert. w/
30" overlap Corner Steel Lap
at each filled cell
n t s
#5 bar Cont. in curb Fill cell with concrete and
11 (1) #5 bar vart. (typical). Filled Cell Masonry Column With One
Max. spacing shall not exceed #5 From Footing To Tie Beam
Wood
Curb height 48" unless otherwise noted
Vert% based on Base see foundation plan notes for Cone. Fill To Be 3000 PSI
foundation plan spacing at openings See Floor Plan For Location
4" concrete slab with fibermesh OR
VxV #10/10 WWM on 6 mil Visqueen over
:r clean compacted termite treated fill
Grade '
IIII-11 III-IIII=IIII_„II�1= Sin le Filled Cell Column
11�Ii11—tin C11111 nnll�Iliil IIII�Ii�I�I `� NTS
I-1 I I I—� • .
71rn
W1,
30"x30"AC concrete
I —column footing with (4)
III #5 bars each way
30 rl
OLUMN FOOTING DETAIL
SCALE 1/2" = I'-
—I 14"w x 18"d Concrete footing
II with (2) #5 bars cont. and #5
transverse bars at 48" o.c.
SCALE 1/2" = 1'-0"
0
2" x 6" PT wood secured with
1/2"dia. x ' expansion anchors
with 2" sq.
washer at 18" o.c. overhead door track secured to wood
C
iamb per manufacturer's product approval
Garaqe Door Jamb Detail
GARAGE DOOR TO WITHSTAND PRESSURES STATED NTS
IN PERMIT INFO BOX ON SHEET 41. SEE PRODUCT
Filled Cell Masonry Column With One
45 From Footing To Beam Each.
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
Double Filled Cell Column
NTS
0
�r
c+l
(V
0
N
e .
I'_-y PATIO/SLAB
° — — — — — —1 I — — — T
-- ° -- —°
r------Fi ---- io fi8
Filled cell under 1
Fi girder above
24"
Rear Patio/Slab r
1 J to be poured separate 0
r from the house slab. -0 F
1 ° rn I
Thicken footing to
24% x 14"d x 24"L
PI under filled cell 1 'a —
under girder bearing. LQ ° Q — - — ° ° �E)
— — — —
--O
Rear Patio/Slab to
be flush with bottom of
sliding door recess. 1 r_
Slope 1/2"
I 1;-
I
I i'o
I FI 1
D
I
4" concrete slab with fiber esh OR
b"x6" 410/10 WWM on 6 mil V squeen over
clean compacted termite treated fill
I FI
ZI
I
—i
V
of -
I o
D �
I
I
FI I 0
D
D ---L —
1
(d w.H. I
#I I 4"0 Steel Ballard—
d filled w/ Concrete 0
FS a > I I O
IFQIIa �
I �► a I I
Ea_� I I
I
Et!
II E t a
1 A
L _ �a
CIDC4J
as
cy 00
°' a o
° i O `U OE
I
faI
U
I
I
I
I
FI
I
I
I
1:
II
x I
°
IL
�I
-
J
F5 1
r F4
IL—
-----------�0
1.5" Recess for 00 °
' —
° ° ——— — — — — — — ° °
-
°
arage Uoor
JQ
Extend curb steel into footingbar vfilled cell
at et curb trranan sittion
to end of "Z" bar
#5 bar cant in
concrete curb
I Ln
I
F21" L----------------------- m
24"
OD
Li
ro
#5 "Z" bar at each2" Cont. bottom steel
cant steel bar. — see foundation plan
STEPPED FOOTING DETAIL
Braden It Braden AIA, FA
Architects - Planners
41-1 S.E. Coconut Avenue
Tel (112) 281-8258
Fax (112) 281-8283
E-mail: bradenaia0comcast.net
Stuart_ FL 3499L UAAC000032
SCALE 1/2" = 1'-0"
Wanne Building Corp.
The Grand Carlton
Spanish Lakes
St. Lucie County Florida
12" x 12" concrete column block filled
with concrete and (2) #1 bars vert. ti
into lintels above
N-n
noav m
5 o a
FOOTiNGrt
SCHEDULE
Mark
size
Description
FI
14"W
x 18"1)
MONOLITHIC FOOTING
WITH 2 #5 BARS CONTINUOUS
F
17111
X 12"D
MONOLITHIC FOOTING
WiTH (2) #5 BARS CONTINUOUS
Q
30"
x 30" x IL"D
COLUMN FOOTING WITH (4) #5 BARS EACH WAY
F
8"W
x 811D
THICKEN SLAB EDGE
WITH I #5 BAR CONTINUOUS
F5
14"W
With
x 18"D
Curb at Garage
MONOLITHIC FOOTING
WITH 2 #5 BARS CONTINUOUS — CURB a 0'0"
Date Drawn
Revisions
GARAGE
3-30-20
LEFT
Drawn bg:
6143 MAR
C.C.U.
PACIFICO
Checked bg:
D.R.B.
Sheet Comm #
REVIEWEDR ,; t 2 ®- s S
CODE COMP1JftW
ST. LUCIE COUNTY 3- B
IROCC OF 5 i
R00F SHEETING
ATTACHMENT DETAIL
I. Minimum Nall Size = 8d ring shank (min. 2.5" long)
2. Minimum Screw Size = #8 x 2"
3. Minimum Sheathing Thickness 19/32" COX PI(gwood
4. Use nails or screws based on pressure for roof stated
in permit info box on these plans for zone 3
Ke
Area
Edge
Field
Fastener
Pressure
Zone 1
6"
4"
8d ring shank
45 psf
Zone 2
4"
6"
111 ring shank
psf
Zone 3
4"
4"
8d ring shank
84 psf
** Zone 3a
6"
6"
48 wood screw
112.5 psf
** Use nails or screws based on pressure for roof stated
in permit info box on these plans for zone 3
Concrete
/ Lintel
Column
Verify with Plan
12 "x 12"
lumn Block
v#1
Rebar
Rebar 1.48 Bar Dia.
Min. Overlap
to Lintel Attachm&nt
NTS
Provide #5 bars with min. 48 bar Provide #5 bar set in pro -cast
diameters overlap into beam. Tie lintel into beam where length of
filled cell steel into continuous beam block steel the opening calls for it.
Provide Cast -Crete
aU8-OB/01 precast
lintel set in mortar -
Min. 8" Bearing
f= zi..'j
Provide PT Buck
attached per jamb
stails into filled CI
4" Pre -cast
Sill
Filled Cell
r #5 bars with min. 48 bar
rs overlap in filled call. Tie
oil steel into continuous
steel.
Concrete Footing
��'.1. a ;•:!*,� (see footer schedule
for exact sizes)
DETAIL AT WINDOW OPENING IN
CBS WALL scale: 1/2" = I'
SINGLE PLY REAR GIRDER TRUSS
Nail 2" x 4" blocking to vert. leg of
truss with IOd x 1.5 nails at 4" c.c.
'v Install Simpson MGT into wail using
r+ 5/8" dia. threaded rod set min. 12'
into wet beam and (22) IOd nails into truss
R-II batts
TRUSS BLOCKING DETAIL
AT GIRDER STRAPPING
AT CENTER BEARING POINT
1/8" thick light textured stucco installed per
ASTM C 9 .4 over ASTM D type 2 paper backed
wire lath nailed to substrate through one layer of
ASTM D Tggpe 2 felt paper using 8d nails. Substrate
to be 19/32' CDX Plywood nailed at 6" c.c. in field
and edges with IOd ring shank nails into studs.
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11151.12
26 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5"
wood screws with self sealing washer at 12" o.c_ max spacing over ASTM D
(type 2) 30 lb felt underlayment installed with min. 4 side laps and 6" end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced 6 o.c. at all laps and two staggered rows 12 o.c. in field. Attach
deck to trusses using attachment detail on this sheet
LINTEL SCHEDULE
Mark
Window
or Do
Unit
WI
Lintel
Size
Cast -Crete
Specification
Rows of
"H' Block
Above
" "
Bottom
Steel
Size
Top
Steel
Size
Max.
Gravity
Load
(PLF)
Max
Uplift
Load
(PLF)
Max
Lateral
Load
(PLF)
L22
2'-2'
3'-L"
BPS-OBAT
I
#5
9069
1369
1024
L31
2'-L"
2'-8`
3'-1'
4'-O"
BF8-OBAT
1
#5
2561
1363
163
L45
4'-5'
5'-10'
8F8-OBAT
I
#5
1105
loci
339
L50
5'-O"
L'-6"
are-OBAT
1
#5
1238
835
121
LLO
L'-8'
T-L"
8F8-OB/IT
1
#5
1011
121
534
L80
8'-O"
9'-4"
8F8-IB/2T
1
#5
2
#5
152
591
612
L40
9'-0"
10'-4"
8P8-IB/2T
I
#5
2
#5
L43
530
401
L9015
9'-O`
10'-4`
01=I4-IB/2T
ONE
1
#5
2
#5
1533
1183
401
LI00
lo'-O"
ll'-48
ere-IS/2T
1
85
2
#5
582
494
452
LIOOB
10'-0"
II'-4"
BPIL-IS/2T
ONE
1
#5
1 2
1 #5
1 13LL
1028
452
LI20
12'-O`
13'-4.
BPS-IB/2T
I
95
2
85
411
428
324
1.120E
12'-O"
13'-4"
BPIL-I5/2T
ONE
1
85
2
#5
1015
110
324
LI40
14'-O`
IS'-4"
BPI6-IB/2T
ONE
1
#5
2
409
259
LILO
IL'-O"
IT-4"
8F8-IB/2T
1
#5
2
t8gij1250
Soo
192
194
BPIL-IS/2T
ONE
I
#5
2
950
500
194
- ALL LINTELS SHALL BE MADE BY CAST-CRETE.
- LINTELS SHALL BE FILLED SOLID WITH 3000 PSI CONCRETE
- REFER TO CAST-CRETE CATALOG FOR ALL INFORMATION REGARDING
LINTEL CONSTRUCTION, HANDLING INFORMATION, AND SAFE LOAD REQ.
REQUIREMENTS
- LINTELS OVER 14'-0" LONG ARE TO BE PRESTRESSED.
5impson HETA 20 or equal
hurricane anchor at each truss
with (10) IOd x 1 1/2" nails —
( 24" o.c.) supporting Max.
Ie101bs. uplift
Aluminum Drip"
Edge t Fascia
12"
2" x 6" Sub-Fasci
Kaycan full o vent viagl soffit installed
usingg 1/8' dia shank x 1.5' long gaiv.
roaring nails with 3/8' dia. head per
product approval - see chart sheet #1
12' x 12' concrete column
block filled with concrete
and (2) #1 bars vert. tied-�
into lintels above
thicken edge to 8"x8'
with concrete and
one #5 bar continuous
BEYOND
Top of factor
IL" below finished floor
12
4
Aluminum Drip
Edge t Fascia
Flash and Counter
Flash
Nail ledger to
gable end truss
with (2) IOd " �ils
at each web
" hi -rib lath
vertical wood
a to provide
:ration Into
3/4' penetration
members
5/8" thick light textured
stucco on typical concrete
block construction
Varies - see plan
#5 bar Vert. w/
30" overlap
at each filled cell
Rear Patio/Slab to
be flush with bottom of
sliding door recess.
Step
per
foundation
plan
Slope
per
foundation
plan
T
Trusses at 24" o.c.
see shop drawings
by others
Frame ceiling transition's
as needed using metal studs
field veriF9 exact configuration
and sizes
Brace Gable end
with 2" x 4' SYP 42
art back riailed to bottom
Of top chords using (2) IOd
nails at each truss
R-30 Batts
1 batts
Drywall ceiling
see typical section
nts
PRE-ENGINEERED WOOD TRUSSES
S 24"o.c. TYPICAL
( shop drawings bg manufacturer )
N
a
�
X
s
O �v1
N
a
a
2�
a ei
ti
O
tn°`r00
CV
u
IN
Q
s`
w
Brace Gable end
with 2" x 4" SYP #2 min.
aft back nailed to bottom —
or top chords using (2) IOd
nails at each truss
yR-30 blown fiberglass
in bottom chord of trusses
-1/2" drywall with smooth finish
Two rows of beam block filled with concrete
_and (U #5 bar Cont. in each row. Substitute
precast lintel filled with concrete and (1) #5
bar cont. for bottom row over openings
1/2" drggwall over I" x furring
strips of IL" o.c. with R4.1 f_foil
-insulation on typical 8" Block walls
All drywall to be installed per FBC R102.3.1
and shall meet all pertaining ASTM codes.
Mortar to be Type "M" only proportioned per FBC R601.1
and Mortar �ointa shall coinply with FBC R601.2.1.
Provide Dur-O-Rock at all wet areas (ex. showers, tubs etc.,.)
Z
Strap truss to wall
using Simpson MGT with
Simpson
HETA 20
5/8' dia.
threaded
rod with min 12" embedment
hurricane anchor
at each truss
into beam
(22) IOd
either wet
nails into
set or in epoxy with
truss. Add blocking to
( 24" o.c.)
supporting Max.
pp
truss leg
per detail
on this sheet%
HETA 20 1810
lbs. uplift
FUN
511111111111111 IS
MOVE E WROWMA "MAIN
AF14
NZA
u
ww'AMEN
'Em
ig
PAP
FA HIM
INS
MILLIZ
Alwil
NMI
PA
IFe
.
ilk
FIII cell with concrete and O O L %
(1) #5 bar Vert. (typicaU.RN
f�
HETA 20
O
W
N
N
X
r
OUU7
N
i'a o a
a
a
to w
ti
,a 1O 0LL
E 00
r _
u n
r
Max. spacing shall not exceed
48"' unless otherwise noted
see foundation plan notes for
— OVERHANGS
AT 1'-0" UNLESS OTHERWISE
NOTED ON THIS SHEET
spacing at openings
— ROOF PITCH
AT 4:12 UNLESS OTHERWISE
NOTED ON THIS SHEET
4" concrete Blab with esh mil Visqueen over
L"x6" #10/10 WWM on L mil Vien
— TRUSS SHOP
DRAWINGS TO BE PROVIDED BY MANUFACTURER
/clean compacted termite treated fill
— ANY CHANGES TO THIS PLAN SHALL BE
SUBMITTED TO THE
FtttjIjI-
14
Ical Section at Front
F orc
ARCHITECT FOR APPROVAL IN WRITING PRIOR TO STARTING CONSTRUCTION.
ALL TRUSS TO TRUSS CONNECTIONS BY
TRUSS MANUFACTURER
ARCHITECT TO REVIEW TRUSS SHOP DRAWINGS PRIOR
TO CONSTRUCTION FOR LAYOUT AND UPLIFT VERIFICATION
CONTRACTOR TO PROVIDE FOR FORM BOARD SURVEY AND TO PROVIDE
FORM BOARD SURVEY TO TRUSS COMPANY PRIOR TO TRUSS CONSTRUCTION
A=LIFE SAFETY WARNING
This symbol identifies Life Safety Warnings that should be read
given special attention by all persons installing trusses.
5PAGING NOTE
AL TRUSSES ARE TO BE SET
AT 2'-0h ON CENTER
EXGFPT AS NOTED
MULTIPLE PLY TRUSSES MUST BE
ASTENED TOGETHER PER ENGINEERING
BEFORE SETTING. REFER TO
ENGINEERING DRAWING TO DETERMINE
IF MULTIPLE PLY.
DON'T LIFT TRUSSES
WITH SPANS LONGER THAN
30' BY THE PEAK.
CONSULT BCSI
30' Span'ior less Al 30' to 60' Span
o degrees Spree er Bar
or less
f_— �2 —10 r hag F—
1 Apo ox 2/3 to --se
log Line span approx. Is 1/2 of Span
REFER TO BCSI REFER TO BCSI
Truss must be set this way if crane used. Truss must be set this way if crone used.
not moron. This is an exomple, truss may not match.
Truss Is an example, your truss mcy
Insist crane operator sets truss this way.
,s'st crane operator sets tress this way.
All load bearing walls, headers,
beams & lintels must be in place
at indicated height before trusses
A are installed. AL
AIR ".4iriL7I_F�FR NOTE
UNLESS NOTED ELSEWHERE ON THIS LAYOUT, THESE TRUSSES
ARE NOT DESIGNED FOR AIR HANDLERS IN THE ROOF OR FOR
ANY OTHER A/C REQUIREMENTS. THIS MAY BE IN CONFLICT
WITH BUILDING CODE AND A/C DESIGN REQUIREMENTS.
CONSULT WITH BUILDING DEPARTMENT AND A/C CONTRACTOR.
U REPRESENTS A HANGER
Carrying Girder
For Truss to Truss
Connections see
hanger/connectorTNailsmustbeas
tabs o
schedule in engineeringe nails.
package.
Carried Truss
SEAT PLATES BY CHAMBERS
INDICATES LOAD BEARING WALL
REQUIRED BY TRUSSES
SUPPLIED BY BUILDER
AT A HEIGHT OF 8'-1"
, ABOVE FINISHED FLOOR
12
4.00 r -
r upset=1/4" heel=315/16"
PLUMB CUT END
2 x 4 Top Chord
WALL HEIGHT 8'-1"
TYPICAL END DETAIL
12
4.00
12 2.00 8�
M
upset=1/4" heel=315/16"
PLUMB CUT END
2 x 4 Top Chord
WALL HEIGHT 8'-1"
END DETAIL: A
i
A ARRANGE WITH CRANE OPERATOR IN ADVANCE FOR A SPREADER BAR OF 17' - 231 IN LENGTH
® Do not stand on trusses until they are braced per BCSI & properly nailed to straps & hangers
GARAGE LEFT
FABRICATION AGREEMENT
TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED & RETURNED
The legal description of the property where the trusses will be Installed is:
The undersigned acknowledges and agrees:
1-. Trusses will be made In strict accordance with this truss placement diagram layout,
which Is the sole authority for determiningsuccessful fabrication of the trusses,
2. All dimensions In this layout have been verified by the undersigned.
3. Unless wrltten notice a provided by car ed mail to Chambers Truse withln ten (10)
days of delivery the undersigned agrees that
no Dackoharges will be allowed. In the event
such written notice Is furnished Chambers Trues shall have three (3) bug`ness days in which
10 begin repairs required, or to substitute othetbusses, at Chambers opton,'
4. The undersigned acknowledges maselpt of "BCSI 1-03" summary sheet by Tot & WrCA.
5. Dellvery b to Job site, It Is the buyer's' responsibility to make the Job sits suitable for
delivery. Chambom Truss has the sole authority to determine the suitablllty of the Job site or a
portion of the job site for delivery. Chambers Truss will be responsible for dump delivery only.
The buyer Is responsible for additional dellverr expenses If Chambers Trues has to redeliver
because Job she Is not prepared for delivery or buyer Is not prepared for delivery of trusses.
Buyer Is responsible to Chambers Truss for towing mats due to she condtions.
e. Pride as shown Iq paregimph 7 below Is subject to change If any changes are, made In
this. layout A $50 per hour fee for revisions may be charged by Chambers Truss.
7. This Is a PURCHASE ORDER to Chambers, Trues of the sum agreed to, or If no.
agreement a reasonable price, Invoice will be made on delivery and paid within terms of net
'on delivery. Involve may. be made at scheduled date of. delivery If buyer cannot accept
delivery of fabricated trusses. The undersigned agrees to pay Chambers.Tryss reasonable
artome)'s fee for collections In event of payment not timely made. 1.12 % per month service
charge will be added for all sums not paid within terms.
S. Signature or Initals anywhere on this sheet constitutes agreement to all tens herein.
9,In consideration of Chambers Truss extending credt for this material the undersigned
uncondNor lly guarentees payment when due of any and all Indebtedness owed to
'Chambers Truss by any entity receiving materiel and the undersigned agrees to pay such
Indebtedness Including attorneys fees, it default In payment for material be made by the
reclplent 1.
10. In the event of any Iltgatlon concerning this agreement, the items furnished hereunder
or payments referred to herein, the. parties agree that the sole venue for any such action will
be Saint !Adis County, Florida.
11. Design responslbli les are per "National Standard And Recommended Guidelines On
Rasponsibllltes For Construction Using Metal Plate Connected Wood Trusses
ANSUTPVWTCA 4 -2002-
DATED
SIGNED
FOR TrTLE
Aspreaderbar May beMgL#edper"BC I-W`toPirelli Irytay&damage,
Multiple ply trusses must be fastened together per engineering
before they are set, failure to do so can result In roof collapse.
Temporary and permanent bracing are required and can save life
and property and Is the r4sponstblllty of the truss erector.
Study the contents of the Information packet Included on delivery
before setting trusses.
Trussesmustbesetandbraced pBrdwlgntDpreventhiL Erdamiage.
Trusses must be set plumb and Square
Do notset bunks or stack of plywood, roofing material or any
other concentrated loads on trusses, this can cause collapse.
DO NOT SET TRUSSES USING THIS LAYOUT
USE LAYOUT DELIVERED WITH TRUSSES TO SET TRUSSES
CHAMBERS TRUSS INC
e_
3105 Oleander Avenue
Fort Pleri Florida 34982-6423
800-551-5932
Fort Pierce 772-465-2012 Fax 772-465-8711
Vero Beach 772-569-2012 Stuart 772-286-3302
.•e-� m.,,. rua■.eeocTt7l rRS rom
The Architect's or Architect's representative's
shop drawing
approval is NOT a
"double check" of the contractor.
The contractor
shall remain responsible
for checking field measurements and
other construction
criteria. Architect's
approval covers
general roof shape,
review of truss
strapping, and loading on
structure from
vity and uplift loads and
►IEWED FOR their,
sp
�tive location
COMPLIANCE
roved By
Date:
J{CIE((C((��OUNTY
��
" OCC92 0/93.2 MITEK 4.2
DESIGN CRITERIA
County
SAINT LUCIE
Building Department
SAINT LUCIE COUNTY
Wind Design Criteria
ASCE 7-2010
Wind Design Method
MWFRS/C-C hybrid Wind ASCE 7-10
Roofing Material
Shingle or Shake
Loading in PSF
Roof R.D.L.
`I
Top Chord Live
20
Top Chord Dead
7 4.2
I
oBottom
Chord Live
10 Non -Concurrent
N
-
Bottom Chord Dead
10 3
TOTAL Load
37 7.2
r (
Duration Factor
1.25
c
Wind Speed
165mph
�
Top Chord C.B.
Sheeting by builder.
N
Bottom Chord C.B.
Sheeting by builder.
�J
Highest Mean Height
14'-0"
`r-,
Building Type
ENCLOSED
Building Category
II:Non Restrictive
Exposure Category
C
Barrier Island
No
Conforms to FBC 2017
W
Cn
Q
GARAGE RIGHT �
13 TRUSS DRAWINGS ARE ATTACHED 70 LAYOUT
r�.y.L.—Re5uaa11t� Ueau Luau %,.t5.=Gon➢nuous bri
Verify DESIGN CRITERIA shown above with the
building department and your engineer.
Design Criteria is the responsibility of the
Building Designer and/or Engineer of Record.
Chambers Truss Inc. Drawing Name: M11323
Scale: 1 /4 = 1'
72 total trusses, 13 different trusses.
MI 4: SAE ACAD: SAE Reviewed By:
Date:04/24/12 Revised:02/21/18
FOR
WYNNE BUILDING CORP.
DESCRIPTION:
62' GRAND CARLTON III
PAGE 1 of 1 CUSTOMER INITIALS EACH PAGE
M 11323 7l Z3/
�7&3 ► 6( `2,u rre.0