HomeMy WebLinkAboutR DOty Engineering0'-0" OP
r--------
i
i
i
i
L-----------------------
m
A_---12"x12" REINFORCED FOOTER
---------------------------------
1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET -BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON -HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET -BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x1" SELF -DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF -DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH.
10. 12GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
-TO BE TER I E TREATED AND,COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION
CONCREIL
-MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
-ALL OPEN i REAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED T SLOPE AWAY FROM THE STRUCTURE
-MINIMUM GRADE 40 STEEL
-REBAR MAY 13E BENT IN SHOP OR FIELD PROVIDED:
-THE RTBAR IS BENT COLD
-THE DI ETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6-BAR DIAM RS: AND
-REINFCFCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT I CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. ESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZO LLY TO 6" VERTICALLY.
-COVER:
-2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CON T WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF J" FOR FINE
GROUT, 4ND J" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH CR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATIO
-METAL ACCE,SORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TC WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TC WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
SWINGING
DOOR
J"x54" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES
AND EVERY OTHER END -WALL POST
2" MIN. B,
GRAD -
-I.
TT
F-12"
MINIMUM SOIL BEARING
CAPACITY 2,000 PSF(TYP.)
RAIL
N
2,500 PSI 4"
CONCRETE SLAB WITH
W.W.F. OR FIBER MESF
(2) #5 REBAR ® 6" O.C.
CONTINUOUS WITH MINIMUM
12" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR DETAIL
2 5" PLAN VIEW DOOR FRAMING
1 if J" RECESS
4" OOR WIDTH
ELEVATION VIEW
DOOR FRAMING
" RECESS
75j 4„ OOR WIDTH
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
MIN. 2,500 PSI 4" CONCRETE SLAB WITH W.W.F. (OR FIBER _
MESH) AND 12"x12" REINFORCED FOOTER PERIMETER
---------------
- - BOLL -LP -------------------------------
ry� DOOR
-4
0'-0
-40
ROLL--UP ----------------------
DOOR
-4
0'-0"
0
_I
jm rllkni� o4olb-, -aqwl a
CODE VERSION jFBC 2017 6th Edition�j
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II-B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
ENCLOSURE ENCLOSED OPEN
INTERNAL PRESSURE COEFF. +/— 0.18/0.0
IMPORTANCE FACTOR 11.0
ROOF DEAD LOAD 11OPSF
b P-L. I
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
2,000 SO. FT.
MTB
5/13/20
5504 Birch Dr_, Ft. Pierce
401 X 50'W X 14'H
0
,
r3
LLJ
�atthew T. BaldWin P.E.
z
Florida License #64608
Q
w J
Sheet: CA— 1 0 F 6
0
I
0
I
5
1 0
0'-0
0'
3-4
12
Q3
1 —0 5
1
0
d
21
0
I
0l
3'-4"
CA" ANWHEN
—0
S
I
i�
0" "O C SPX
,0
CODE INFORMATION
N
CODE VERSION
F2017 6th Edition
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
10'-0"
ROLL —UP
DOOR
0
0
10'-0"
ROLL —UP
DOOR
-
o
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
IND
SQUARE FOOTAGE
12,000 SQ. FT.
REVISIONS
REV
REV
DESCRIPTON
DATE
BY
30'-0" 10'-0"
FRONT END WALL
OnaWn er: MTB
DATE: 5/ 13/20
LOCOON: 5504 Birch Dr., Ft. Pierce
SIZE: 401 X 50'W X 14'H
O
I
`w ,�tr� ` ,✓irk
�
LLJ
— —
U
��66 Ili 16 31_
30'—O"
10'-0"
MattheW T. BaldWin P.E.
Florida License #64608
REAR END WALL
w
[Sheet, CA-2 OF 6
0
0'-0"
ROLL —UP
FRONT END WALL
REAR END WALL
4
0'
0'
CODE VERSION
FBC 2017 6th Editior
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
0
ROOF LIVE LOAD
0PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
2,000 SQ. FT.
DESCRI
MTB
5/13/20
5504 Birch Dr., Ft. Pierce
40'L X 50'W X 14'H
7
LIJ
�
jy \
>
Matthew T. Baldwin P.E.
Florida License #64608
wz
w
Sheet: CA-4 OF 6
sWiNGiNG
DOOR
LEFT SIDE
RIGHT SIDE
LEFT/RIGHT SIDE LEAN—
1 ' 1
(CODE VERSION IFBC 2017 6th Editionll
ASCE-7-10
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
2,000 SQ. FT,
MTB
5/13/20
5504 Birch Dr., Ft. Pierce
407L X 50'W X 14'H
u)
W 20
Matthew T. Baldwin P.E.
W Florida License #64608
� (n Sheet: CA-5 CC 6
MINIMUM 6" TS NIPPLE. NIPPLE MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH SECURED TO WALL POST WITH
(4)#12-14x1" SELF—DRILLING/_2"x2"x2"
(4)#12-14xi" SELF —DRILLING Ir
SCREWS SCREWS 2"x2"x2" 16 GA. ANGLE CLIP
NIPPLE TO 16 GA. ANGLE CLIP
V ABASE RAIL NIPPLE TO f�" T SECURED WITH (4) #12-14xj"
BASE RAI SECURED WITH (4) #12-14er" 2"x2"x2" 16 GA. ANGLE CLIP SELF —DRILLING SCREWS
SELF —DRILLING SCREWS SECURED WITH (4) #12-14xj"
SELF —DRILLING SCREWS SINGLE OR DOUBLETS
I —I 11—I 1.=11 -1 HEADER
I-1 I III I . . 111=1 ! -
INTERMEDIATE POST TO
POST TO BASE RAIL END POST TO BASE RAIL HEADER/BASE RAIL/OR HEADER CONNECTION
CONNECTION CONNECTION WINDOW RAIL DETAIL DETAIL OPTION 1
2"x2%2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xj"
SELF —DRILLING SCREWS
NON—STRUCTURAL HEADER OR
WINDOW RAIL TO POST DETAIL
2"x2"x2" 16 GA, ANGLE CLIP SECURED
WITH (4) #12-14xj" SELF —DRILLING
SCREWS 26 GAUGE ROOF SHEATHING SECURED WITH
r-VARIES (1)1u12-14x4" SELF —DRILLING SCREWS
MAX. SPACII`
r-3" MIN.
D. MAX. SP*CING
VARIES
SIDE WALL ROLL -UP
DOOR/FRAME OUT
HEADER DETAIL
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
_en �-
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-14x1" SELF —DRILLING
SCREWS TO EACH RAFTER,
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SC) 12 14xj" SELF —DRILLING
INGLE OR DOUBLETS
EADER
HEADER CONNECTION DETAIL
OPTION 2
N
TO 1
MINIMUM 6" TS NIPPLE.
NIPPLE SECURED TO WALL
POST WITH (4)#12-14xi"
SELF —DRILLING SCREWS
POST TO TRUSS
CONNECTION
INSTALL PER MANUFACTURERS INSTRUCTIONS"
2 — 2"x2"x2" 16 GA. ANGLE CLIPS
"
IPPLE TO
SECURED WITH (4) #12-14xj"
TRUSS
SELF —DRILLING SCREWS (PER CLIP)
#12-14xi" SELF —DRILLING
SCREWS ® 10" O.C. MAX.,
#14x1" SELF —DRILLING
SCREWS ® 6" O.C. MAX.
& 6" MAX. FROM CORNERS
1"x2�" 16 GA.
U— A
U—CHANNEL BRACE, MIN.
3" MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
TO 7' POST, MIN
24" OVER 7' POST. MIN.
FROM CORNERS VERTICALLY
45' TO MAX. 60' FROM
HORIZ. (EXCLUDE
END —WALLS). SECURED
INTERIOR EXTERIOR
Z„
Z
8
L
WITH(DR#12-1UNG SCREWS.
�12"
MINIMUM 6" TS NIPPLE. NIPPLE
t" MINIMUM 24" TS
SECURED TO WALL POST WITH
NIPPLE
(4)#12-14x4" SELF —DRILLING
DOOR FRAME TO POST
ROLL —UP DOOR TO
SCREWS
BOX SAVE RAFTER TO
TRUSSED RAFTER
LEAN—TO TO TRUSS
CONNECTION
POST CONNECTION DETAIL
CONNECTION
POST CONNECTION
CONNECTION DETAIL
DESIGN PRESSURES
— 165 Mph
ROOF
+23.3/-51.6
WALLS
+25.4/-28.6
DOORS
+25.4/-28.6
WINDOWS
1 +25.4/-28.6
1
2
3
4
5
ZONE
+ 12.0
—26.8
+ 14.9
—40.7
+23.3
—51.6
+24.2
—25.9
+25.4
—28.6
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 — R 1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL12765.3—R5
SERIES 3100
CODE VERSION IFBC 2017 6th Edition ji
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
1. U
65m
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
0PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
2,000 SQ. FT.
MTB
5/13/20
5504 Birch Dr_, Ft. Pierce
401 X 50'W X 14'H
Cn
J
Q
Matthew T. Baldwin P.E.
♦—
Florida License #64608
w W
0
Sheet: CA— 6 0 F 6