Loading...
HomeMy WebLinkAboutGenerator specs, 22 KW Specs?0 22 kW INCLUDES: • True Power" Electrical Technology i Two-line multilingual digital LCD EvolUtiOn rI controller (Engl ish/Spanish/French/Portuguese) a 200 amp service rated smart switch transfer switch available • Electronic governor • Standard Wi-Fi® connectivity • System status & maintenance interval LED indicators ! Sound attenuated enclosure • Flexible fuel line connector Natural gas or LP gas operation • 5 Year limited warranty 0 Listed and labeled by the Southwest Research Institute allowing installation as close as 18 in (457 mm) to a structure." `Must be located away from doors, windows, and fresh air intakes and in accordance with local codes. hkps:Ilassets.swri.orgliibrary/Directory0fListedProductsl Constructionlndusiry1973 DoC_204_13204-01-01_Rev9-pdf FEATURES 0 rN INNOVATIVE ENGINE DESIGN & RIGOROUS TESTING are at the heart of Gen- erac's success in providing the most reliable generators possible. GeneraCs G- Force engine lineup offers added peace of mind and reliability for when it's needed the most. The G-Force series engines are purpose built and designed to handle the rigors of extended run times in high temperalures and extreme operating conditions. `CTRICAL TECHNOLOGY: Superior harmonics and sine wave form produce less than 5% Total Harmenic Distortion for utility quality power. This allows confident operation of sensitive electronic equipment and micro -chip based appliances, such as variable speed HVAC systems. TEST CRITERIA: ✓ PROTOTYPE TESTED ✓ NEMA MG1-22 EVALUATION ✓ SYSTEM TORSIONAL TESTED ✓ MOTOR STARTING ABILITY MOBILE LINK* CONNECTIVITY: FREE with select Guardian Series Home standby generators, Mobile Link WI-Fi allows users to monitor generator status from any- where in the world using a smartphone, tablet, or PC. Easily access information such as the current operating status and maintenance alerts. Users can connect an account to an authorized service dealer for fast, friendly, and proactive service. With Mobile Link, users are taken care of before the next power outage. GENERAL' GUARDIAN° SERIES Residential Standby Generators Air -Cooled Gas Engine Standby Power Rating G007038-1, G007039-1, G007038-3, G007039-3 (Aluminum - Bisque) - 20 kW 60 Hz G007042-2, C007043-2, 0007042-3, G007043-3 {Aluminum - Bisque) - 22 WV 60 Hz or C®US ! J � .41P us LISTED �`�' RLTEST- u�k� Note: CETL or CUL certification only applies to unbundled units and units packaged with limited circuit switches. Units packaged with the Smart Switch are FTL or UL certified in the USA only. O SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION: This state-of-the-art power maximizing regulation system is standard on all Generac mod- els. It provides optimized FAST RESPONSE to changing load conditions and MAXI- MUM MOTOR STARTING CAPABILITY by electronically torque -matching the surge loads to the engine. Digital voltage regulation at �1%. O SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer network provides parts and service know-how for the entire unit, from the engine to the small- est electronic component. O GENERAC TRANSFER SWITCHES: Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line is offered with its own transfer systems and controls for total system compatibility. GENNERC (&(*@/% r,' I PROMISE "k� GENERAC' a3. 20/22 kW Engine • Generac G-Force design • "Spiny--lok" cast iron cylinder walls • Electronic ignition/sparkadvance • Full pressure lubrication system • Low oil pressure shutdown system • High temperature shutdown Features and Benefits Maximizes engine "breathing" for increased fuel efficiency. Plateau honed cylinder walls and plasma moly rings help the engine run cooler, reducing oil consumption and resulting in longer engine life. Rigid construction and added durability provide long engine life. These features combine to assure smooth, quick starting every time. Pressurized lubrication to all vital bearings means better performance, less maintenance, and longer engine life. Now featuring up to a 2 year/200 hour oil change interval. Shutdown protection prevents catastrophic engine damage due to low oil. Prevents damage due to overheating. • Revolving field Allows fora smaller, light weight unit that operates 25% more efficiently than a revolving armature generator. • Skewed stator Produces a smooth output waveform for compatibility with electronic equipment. • Displaced phase excitation Maximizes motor starting capability. • Automatic voltage regulation Regulating output voltage to ±1 % prevents damaging voltage spikes. • UL 2200 listed For your safety. Transfer Switch (if applicable) • Fully automatic Transfers vital electrical loads to the energized source of power. • NEMA 319 Can be installed inside or outside for maximum flexibility. • Remote mounting Mounts near an existing distribution panel for simple, low-cost installation. Evolution'" Controls • AUTO/MANUAUOFF illuminated buttons Selects the operating mode and provides easy, at -a -glance status indication in any condition, • Two-line multilingual LCb display Provides homeowners easily visible logs of history, maintenance, and events up to 50 occurrences. • Sealed, raised buttons Smooth, weather -resistant user interface for programming and operations. • Utility voltage sensing Constantly monitors utility voltage, setpoinis 65% dropout, 80% pick-up, of standard voltage. • Generator voltage sensing Constantly monitors generator voltage to verify the cleanest power delivered to the home. • Utility interrupt delay Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default setting of 5 seconds by a qualified dealer. • Engine warm-up Verifies engine is ready to assume the load, setpoint approximately 5 seconds. • Engine cool -down Allows engine to cool prior to shutdown, setpoint approximately 1 minute. • Programmable exercise Operates engine to prevent oil seal drying and damage between power outages by running the generator for 5 minutes every other week. Also offers a selectable setting for weekly or monthly operation providing flexibility and potentially lower fuel costs to the owner. • Smart battery charger Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature. Compatible with lead acid and AGM -style batteries. • Main line circuit breaker Protects generator from overload. • Electronic governor Maintains constant 60 Hz frequency. Unit • SAE weather protective enclosure Sound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding winds up to 150 mph (241 km/h). Hinged key locking roof panel for security. Litt -out front for easy access to all routine maintenance items. Electrostatically applied textured epoxy paint for added durability. • Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries. • Small, compact, attractive Makes for an easy, eye appealing installation, as close as 18 in (457 mm) away from a structure. GENERAC' 20/22 kW Features and Benefits Installation System • 14 in (35.6 cm) flexible fuel line connector Listed ANSI Z21.75/CSA 6.27 outdoor appliance connector for the required connection to the gas supply piping. • Integral sediment trap Meets IFGC and NFPA 54 installation requirements. Connectivity (Wi-Fi equipped models only) • Ability to view generator status • Ability to view generator Exercise/RuR and Total Hours • Ability to view generator maintenance information • Monthly report with previous month's activity • Ability to view generator battery information • Weather information Monitor generator with a smartphone, tablet, or computer at any time via the Mobile Link application for complete peace of mind. Review the generator's complete protection profile for exercise hours and total hours. Provides maintenance information for the specific model generator when scheduled maintenance is due. Detailed monthly reports provide historical generator information. Built in battery diagnostics displaying current state of the battery. Provides detailed local ambient weather conditions for generator location. GENERAC� 20/22 kW Specifications Model G007038-1, G007039-1 G007042-2, G007043-2 G007038-3, G007039-3 G007042-3, G097043-3 (20 kW) (22 (20 kW) (22 kW) Rated maximum continuous power capacity (LP) 2C,000 wafts' 0 Watts` 20,000 Watts` 22,000 Watts' Rated maximum continuous power capacity (NG) 18,000 Watts' 19,500 Watts " 18.000 Wafts" 19,500 Watts' Rated voltage 240 Rated maximum continuous load current -2,�0 volts (LP/NG) 93.3175.0 91,7 / 81.3 83.3 / 75.0 91.7 / 81,3 Total Harmonic Distortion Less than 5% Main line circuit breaker 90 amp 100 amp 90 amp 100 amp Phase 1 Number of rotor poles 2 Rated AC frequency 601 Power factor 1.0 Baltery requirement (not included) 12 Volts, Group 26R 540 CCA minimum or Group 35AGM 650 CCA minimum Unit weight (lb / kg) 448 / 203 466 / 211 436 / 198 445 / 202 Dimensions (L x W x H) In / cm 48 x 25 x 29 / 121.9 x 63.5 x 73.7 Sound output in cl at 23It (7 m} with generator operating at normal load"` 67 67 67 67 Sound output to dB(A) at 23 It (7 mj with generator in Quiet -Test" low -speed exercise made" 55 57 55 57 Exercise duration 5 min Engine Engine type GENERAC G-Force 10D6 Series Number of cylinders 2 Displacement 999 cc Cylinder block Aluminum w/ cast iron sleeve Valve arrangement Overhead valve Ignition system Solid -slate w/ magneto Governor system Electronic Compression ratio 9.5:1 Starter 12 VDC Oil capacity including filter Approx 1.9 q1 /1.8 L Operating rpm 3.600 Fuel consumption Natural gas ft9/hr (m3/hr) 1/2 Load 204 (5.78) 228 (6,46) 164 (4.64) 203 (5.75) Full Load 301 (8.52) 327 (9.26) 287 (8.13) 306 (8.66) Liquid propano ft3/hr (gal/hr) [Uhr] 1/2 Load 87 (2.37) [8.99] 92 (2.53) [9.57] 86 (2.36) [8,951 92 (2.53) (9.57] Full Lead 130 (3.56) [13.481 142 (3.90) 114.77] 136 (3,74) [14.151 142 (3.90) (14.77] Note: fuel pipe must be sized for full load. Required fuel pressure to generator iuei inlet at all load ranges - 3.5-7 in water column (0.87-1.74 kPa) ter NG,10-12 in water coiumn (2.49-2.99 kPa) for LP gas. For BTU content, multiply I01hr x 2500 (LP) or H3/hr x 1000 (NG), For Megajoule content, multiply m3Jrr x 93.15 (LP) or m3/hr x 37.26 (NG). Controls Two-line plain text multilingual LCD Simple user interface for ease of operation. Made buttons: AUTO Automatic start on utility failure. Weekiy, Si -weekly, or Monthly selectable exerciser. MANUAL Start with starter control, unit stays on. 11 utihty falls, transfer to Toad lakes place. OFF Stops unit. Power is removed. Control and charger still operate. Ready to Run/Mainlenance messages Standard Engine run hours indication Standard Programmable start delay between 2-1500 seconds Standard (programmable by dealer only) Utility Voltage Loss/Return to Utility adjustable (hrownout setting) From 140-171 V/ 190-216 V Future Set Capable Exerciser/Exercise Set Error warning Standard Run/Alarm/Mairdenance logs 50 events each Engine start sequence Cyclic cranking, 16 sec on, 7 rest (90 sec maximum duration), Starter lock -out Starter cannot m-engage until 5 sec after engine has slopped. Smart Battery Charger Standard Charger Faull/Missing AC warning Standard Low Baltery/Battery Problem Protection and Battery Condition indication Standard Automatic Voltage Regulation with Over and Under Voltage Protection Standard Under-Frequency/Overload/Sleppsr Overcurrent Protection Standard Safety Fused/Fuse Problem Protection Standard Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard Overcrank/Ovarspeed (C 72 Hz)/rpm Sense Loss Shutdown Standard High Engine Temperature Shutdown Standard Internal FaulVlncorrect Wiring protection Standard Common external fault capability Standard Field upgradable firmware Standard **Sound levels are taken from the front at the generator. Sound levels taken from other sides of the generator may he higher depending on installation parameters. Rating definitions - Standby: Applicabie for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating- (All ratings in accordance with BS5514, IS03046 and DIN6271). * Maximum kilovolt amps and current are subject to and limited by such factors as tact BTU/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases approximately 3.5%for each 1,000It (304.8 m) above sea level; and also will decrease approximately 1 % for each 10 °F (6 °C) above 6D °F (16 °G). GENERAC' 20/22 W Service Rated Smart Switch Features • Includes digital power management technology (DPM) standard. • Intelligently manages up to tour air conditioner loads with no additional hardware. • Up to eight additional large (240 VAC) loads can be managed when used in conjunction with Smart Management Modules (SMMs). • Electrically operated, mechanically -held contacts for fast, clean connections. • Rated for all classes of load, 100% equipment rated, bath inductive and resistive. • 2-pole, 250 VAC contactors. • Service equipment rated, dual coil design. • Rated for both aluminum and copper conductors. • Main contacts are silver plated or silver alloy to resist welding and sticking. • NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor mounting flexibility. Dimensions 200 Amps 120/240,1d Open Transition Service Rated Height Width H1 N2 W1 W2 Depth in 26.75 30.1 10.5 13.5 6.91 cm 67.95 76.45 26,67 34.29 17.55 Wire Ranges Conductor Lug Neutral Lug Ground Lug 400 MCM - #4 350 MCM - #6 2/0 - #14 Model No.. of potes Current rating (amps) Voltage rating (VAC) Utility voltage monitor (fixed)` -Pick-up -Dropout Retun to Utility` Exercises hi -weekly for 5 minutes' ETL or UL listed Enclosure type Circuit breaker protected Lug range *function of Evolution controller Exercise can be setto weekly or monthly Switch Options G007039.1 (20 kW) G007043-2 (22 kw) G007039.3 (20 kW) G007043-3 (22 kW) 2 200 120/240,1N 80% 65% Approx.13 sec Standard Standard NEMA/UL 3R 22,000 250 MCM - #6 GENERACO 20/22 kW Available Accessories Model # Product Description G005819-0 26R Wet Coll Battery Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet cell battery for use with all air-cooled standby product (excluding PowerPact'). G007101-0 Battery Pad Warmer . Pad warmer rests under the battery. Recommended for use if temperature regularly falls below 0 °F (-18 °C). (Not necessary for use with AGM -style batteries). G007102-0 Oil Warmer Oil warmer slips directly over the oil fifter. Recommended for use if temperature regularly falls below 0 IF (-18 G). G007103-1 Breather Warmer Breather warmer is for use in extreme cold weather appkcations. For use with Evolution controllers only in climates where heavy icing occurs. G005621-0 Auxiliary Transfer Switch The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load that may not Contact Kit be needed. Not compatible with 50 amp pre -wired switches. G007027-0 - Bisque Fascia Base Wrap Kit The fascia base wrap snaps together around the bottom of the new air -coaled generators. This offers a sleek, con - (Standard on 22 kW) toured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base. 0005703-0 - Bisque Touch -Up Paint Kit If the generator enclosure is scratched or damaged, it is important to touch up the paint to protect from tuturE corro- sion. The touch-up paint kit inclades the necessary paint to correctly maintain or touch up a generator enclosure. G006485-0 Scheduled Maintenance Krt Generac's scheduled maintenance kit provides all the items necessary to perform complete routine maintenance on a Generac automatic standby generator (ofl not included). G007005-0 Wi-Fi LP Tank Fuel Level The Wi-Fi enabled LP tank fuel level monitor provides constant monitoring of the connected LP fuel tank. Monitoring Monitor the LP tank's fuel level is an important step in verifying the generator is ready to run during an unexpected powerfailure. Status alerts are available through a free application to notify users when the LP tank is in need of a refill. G007000-0 (50 amp) Smart Management Module Smart Management Modules (SMM) are used to optimize the performance of a standby generator. It manages large G007006-0 (100 electrical loads upon startup and sheds them to aid in recovery when overloaded. In many cases, using SMM's can amp) reduce the overall size and cast of the system. G007169-0 Mobile Link"' Cellular The MobllB Link family of Cellular Accessories allows users to monitor generator status from anywhere in the world, Accessories using a smart phone, tablet, or PC. Easily access information such as the current operating status and maintenance alerts. Users can connect an account with an authorized service dealer for fast, friendly, and proactive service. With Mobile Link, users are taken care of before the next power outage. Dimensions & UPCs Model UPC G007038-1 696471014185 G007038-3 6964710741B5 G007039-1 696471074192 G007039-3 696471074192 G007042-2 696471074208 G007042-3 696471074208 G007043-2 696471074215 G007043-3 696471074215 GENERACg 72; 2l LEFT SIDE VIEW FRONT VIEW Dimensions shown are approximate. See installation manual tar exact dimensians. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES. Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com 02020 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Part No. A0000221268 Rev. B OY2812020