HomeMy WebLinkAboutProduct Approval L. Roberto Lomas P.E. Engineering Evaluation Report
1432 Woodford Rd.
Lewisville,NC 27023 Report No.: 513769A
434-688-0609
rllomas@lrlomaspe.com
IVCD
Manufacturer: Viwinco,Inc.
Morgantown Business Park JUN 2-2 2020
P.O. Box 499
Morgantown, PA 19543 ST. Lucie County; Permitting
Product Line: Oceanview Impact Horizontal Slider 72"x 60"
Compliance:
The above mentioned product has been evaluated for compliance with the requirements of the Florida Department of
Business and Professional Regulation for Statewide Acceptance per Rule 61 G20-3.005 method 1(a).The product listed
herein complies with requirements of the Florida Building Code.
Supporting Technical Documentation:
1. Approval document:drawing number 08-02939 Revision A, prepared, signed and sealed by Luis Roberto
Lomas P.E.
2. Report No.: ATI-C7471.01-109-47 signed by Michael D.Stremmel P.E.
Architectural Testing Inc.,York, PA
AAMANVDMA/CSA 101/I.S.2/A440-11
Design pressure: ±50.13psf
Water penetration resistance 7.52psf
3. Report No.: ATI-C7471.02-109-47 signed by Michael D. Stremmel P.E.
Architectural Testing Inc.,York, PA
ASTM El 886-05 and ASTM Ell 996-05
ASTM El 886/E1996 Large Missile Impact, Level D,Wind Zone 3
ASTM E1886/E1996 Cyclic Load Test, ±50.Opsf design pressure
4. Anchor calculations, report number 513769-1A, prepared, signed and sealed by Luis Roberto Lomas P.E.
Limitations and Conditions of use:
• Maximum design pressure: ±50.Opsf
• Maximum unit size: 72"x 60"
• Units must be glazed per ASTM El 300-04/09,see installation instructions for glass details.
• This product is not rated to be used in the HVHZ.
• This product is impact resistant and does not require impact protection in wind borne debris regions, up to wind
zone 3.
• Frame material to be rigid PVC.
Installation:
Units must be installed in accordance with manufacturer's installation instructions and approval document 08-02939
Revision A.
Certification of Independence:
Please note that I don't have nor will acquire a financial interest in any company manufacturing or distributing the
product(s)for which this report is being issued.Also, I don't have nor will acquire a financial interest in any other entity
involved in the approval process of the listed product(s).
1 • ♦ /_
*•• 051 -
• f
1 �-
TATE OFORID
w
�//11111111��
1 of 1 Luis R. Lomas, P.E.
FL No.:62514
. FILEL P 07/10/2017
Document Title: Doc No: FRM 81-43
Impact Performance Rev No: 4 Page: 1 Of: 1
j<gySTON Certification
C ERTIFIcATIo NB.'INC.
Authorization Report
Required By: PRO B1-03
gF-CEIUED
JUN' 2 2 2020 CAR & Product ID Number: 464 - 231.
Issue Date: 8/22/2013
sT. Lucie County,Permitting Revision Date: 4/30/2020
Expiration Date: '6/26/2023
Company Code: 464
This Certification Authorization Report(CAR) is issued by Keystone Certifications, Inc. (KCI) after full validation review,
and is based on a,standardized evaluation of the product conducted by an independent accredited laboratory in
accordance with the specified referenced standard. Actual fenestration product performance may vary based on many
factors, including installation, condition of the walUroof substrate and the age of the product and installation
components.
This report indicates the product is eligible for the application of Keystone Certification Program certification labels.
Licensee stipulates in affixing-certification labels to products, that those products are representative of the specimen
evaluated and documented for certification authorization. Only products bearing such a certification label shall be
considered certified. The information in this report can be verified atwww.keystonecerts.com.
Licensee Information: Product Information:
Viwinco, Inc. Model: Oceanview Impact Horizontal Slider
851 Hemlock Rd, Morgantown Business Par Operator Type: HS
Morgantown, PA 19543-0499 Config: EM/IM, GS-5/16°Ann Lami IG
USA Max Width: 72
Max Height: 60 -
Corresponding Structural CARS: 464-471.0
Referenced Standard: Product Rating:
ASTM E1886/E1996-05 Missile Level D, Wind Zone 3, DP +/-50, 72x60 XX
Qualifying Test Information:
Test Report No: ATI-C7471.02-109-47
Test Report Expiration: 6/26/2023
Authorized Signature: Keystone Certifications, Inc.
2020.04.30 145 Limekiln Rd., Suite 100B
New Cumberland, Pennsylvania 17070
Phone: 717-932-8500
13.37.03 -04'00' Fax: 717-932-8501
PYVVV4W KEYSTONECERTS.COM
FILE
Document Title: Doc No: FRIVI 81-02
Structural Performance Rev No: 7 Page: 1 Of. 7
KEYSTONE
CCRTIFICA'r1oN6.INC. Certification
Authorization Report
Required By: PRO B1-03
RECEIV CAR & Product ID Number: 464 - 471.0
Issue Date: 7/22/2013
JUIN 2' 2 2'102.0 Revision Date: 4/30/2020
Expiration Date: 6/26/2023
ST. Lucie County, Permitting Company Code: 464
This Certification Authorization Report(CAR) is issued by Keystone Certifications, Inc. (KCI) after full validation review,
and is based on a standardized evaluation of the product conductedby an independent accredited laboratory in
accordance with the specified referenced standard.Actual fenestration product performance may vary based on many
factors, including installation, condition of the wall/roof substrate and the age of the product and installation
components.
This report indicates the product is eligible for the application of Keystone Certification Program certification labels.
Licensee stipulates in affixing certification labels to products, that those products are representative of the specimen
evaluated and documented for certification authorization. Only products bearing such a certification label shall be
considered certified. The information in this report can be verified atwww.keystonecerts.com.
Licensee Information: Product Information:
Viwinco, Inc. Model: S-Series/Cambridge Horizontal Slider
851 Hemlock Rd, Morgantown Business Pa Operator Type: HS
Morgantown, PA 19543-0499 Config: EM/IM
USA Max Width: 72
Max Height: 60
Referenced Standard: Product Rating:
AAMA/WDMA/CSA 101/I.S.2/A440-11 Class LC-PG50 1826x1521 (72x60)-Type HS XX
Qualifying Test Information:
Test Report No: ATI-C7471.01-109-47
Test Report Expiration: 6/26/2023
Authorized Signature: Keystone Certifications, Inc.
\2020.04.30 145 Limekiln Rd. Suite 1006
New Cumberland, Pennsylvania 17070
13:32:36 -0400" Phone:, 717-932-8500
Fax: 717-932-8501
FI
LE
WWW.KEYSTONECERTS.COM
REVISIONS
REV DESCRIPTION DATE APPROVED
A REVISED INSTALLATION DETAILS 07/10/17 R.L.
FIT LE C"O PY
NOTES: 15. FOR ANCHORING THROUGH FRAME INTO WOOD FRAMING OR 2X BUCK USE #10 WOOD
1. THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED TO COMPLY WITH SCREWS WITH SUFFICIENT LENGTH TO ACHIEVE A 1 1/4" MINIMUM EMBEDMENT INTO
REQUIREMENTS OF THE FLORIDA BUILDING CODE. SUBSTRATE. LOCATE ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION DETAILS.
2. WOOD FRAMING AND MASONRY OPENING TO BE DESIGNED AND ANCHORED TO PROPERLY 16. FOR ANCHORING THROUGH FRAME INTO MASONRY/CONCRETE USE 3/16" TAPCONS WITH
TRANSFER ALL LOADS TO STRUCTURE. FRAMING AND MASONRY OPENING IS THE 4" MINIMUM EMBEDMENT INTO SUBSTRATE WITH 2EVE C
T
T
T E
F
SUFICINLENGTH O AHIA 1 1
RESPONSIBILITY OF THE ARCHITECT OR ENGINEER OF RECORD. /
3. 1X BUCK OVER MASONRY/CONCRETE IS OPTIONAL. 1/2" MINIMUM EDGE DISTANCE. LOCATE ANCHORS AS SHOWN IN ELEVATIONS AND
4. WHERE SHIM OR BUCK THICKNESS IS LESS THAN 1-1/2" WINDOW UNITS MUST BE INSTALLATION DETAILS.
ANCHORED THROUGH THE FRAME IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED 17. FOR ANCHORING THROUGH FRAME INTO METAL STRUCTURE USE #10 SMS OR SELF
INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE SECURELY FASTENED DIRECTLY INTO DRILLING SCREWS WITH SUFFICIENT LENGTH TO ACHIEVE 3 THREADS MINIMUM BEYOND
MASONRY, CONCRETE OR OTHER STRUCTURAL SUBSTRATE MATERIAL. STRUCTURE INTERIOR WALL. LOCATE ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION
5. WHERE WOOD BUCK THICKNESS IS 1-1/2" OR GREATER, BUCK SHALL BE SECURELY DETAILS.
8. ALL FASTENERS TO BE CORROSION RESISTANT.
FASTENED TO MASONRY, CONCRETE OR OTHER STRUCTURAL SUBSTRATE. WINDOW UNITS MAY 1
BE ANCHORED THROUGH FRAME TO SECURED WOOD BUCK IN ACCORDANCE WITH 19. INSTALLATION ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ANCHOR
MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS. MANUFACTURER'S INSTALLATION INSTRUCTIONS AND ANCHORS SHALL NOT BE USED IN
SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM STRENGTH SPECIFIED BELOW;
6. WHERE 1X BUCK IS NOT USED DISSIMILAR MATERIALS MUST BE SEPARATED WITH APPROVED
COATING OR MEMBRANE. SELECTION OF COATING OR MEMBRANE IS THE RESPONSIBILITY OF A. WOOD: MINIMUM SPECIFIC GRAVITY OF G=GTH
B. CONCRETE: MINIMUM COMPRESSIVE STRENGTH OF 2,000 PSI. -1
THE ARCHITECT OR ENGINEER OF RECORD. C. MASONRY: HOLLOW/FILLED BLOCK PER ASTM C90 WITH Fm=2,000PSI MINIMUM.
0.42
7. BUCKS SHALL EXTEND BEYOND WINDOW INTERIOR FACE SO THAT FULL FRAME SUPPORT IS D. METAL STRUCTURE: STEEL 18GA (.048") FY=33KSI/FU=52KSI OR c
PROVIDED. ALUMINUM 6063—T5 FU=30KSI .048" THICK MINIMUM p I'll
8. FOR FIN INSTALLATION SHIM AS NEEDED. FOR FRAME INSTALLATION SHIM AS REQUIRED AT nEACH ANCHOR LOCATION WITH LOAD BEARING SHIM. SHIM WHERE SPACE OF 1/16" OR O ;
GREATER OCCURS. MAXIMUM ALLOWABLE SHIM STACK TO BE 1/4". �
9. SHIMS SHALL BE LOCATED, APPLIED AND MADE FROM MATERIALS AND THICKNESS CAPABLE
OF SUSTAINING APPLICABLE LOADS. D � } !i
10. WIND LOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD ANCHOR CALCULATIONS. (D ;v
11. FRAME MATERIAL: EXTRUDED RIGID PVC. 3 o
12. UNITS MUST BE GLAZED PER ASTM E1300-04/09, SEE SHEET 2 FOR GLASS DETAILS.
13. APPROVED IMPACT PROTECTIVE SYSTEM IS NOT REQUIRED FOR THIS PRODUCT IN WIND
BORNE DEBRIS REGIONS. j
14. FOR ANCHORING THROUGH FIN INTO WOOD FRAMING OR 2X BUCK USE #6 WOOD SCREWS
WITH SUFFICIENT LENGTH TO ACHIEVE A 1 1/4" MINIMUM EMBEDMENT INTO SUBSTRATE.
LOCATE ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION DETAILS.
SIGNED:07/10/2017
PI oIN o� ass \\`.\J�S,1R I IL O�/i
MORGANTOWN, PA 19543 `",•��GEN,9- -y �
OCEANVIEW IMPACT HORIZONTAL SLIDER =*• 0 51 *=_
72" X 60"
NOTES TAT OF
TABLE OF CONTENTS i�ic .F P
DRAWN: DWG NO. REV / �s �0R10•G\���
SHEET NO. DESCRIPTION NG. 08-02939 A
SDATE /ONALIE���`�
1 NOTES NTS 08/08/16 1 OF 6
2 ELEVATIONS L.ROBERTO LOMAS P.E. Luis R. Lomas P.E.
1432 WOODFORD RD LEWISVILLE,NO 27023 FL No.: 62514
3 — 6 INSTALLATION DETAILS 434-639-0609 rllomas@lrlomaspe.com
REVISIONS
REV DESCRIPTION DATE APPROVED
A REVISED INSTALLATION DETAILS 07/10/17 R-L-
72" MAX FRAME WIDTH 72" MAX FRAME WIDTH
6" MAX MAX60.C. 6" MAX 6" MAX2D.C. 6" MAX
15/16"
6" MAX 6" MAX
1/8" TEMP 1/8" ANN
J� EXTERIOR •090 PVB KURARAY
1- 12„ 1/8' ANN
60" 16" 60" MAX STEEL SPACERINTERIOR
MAX MAX MAX O.C. SYSTEM
HEIGHTFRAME
D.C. � HEIGHTFRAME
T => DOW
NSTAGLAZE
1/2" BITE SILICONE
SETTING BLOCK GLAZING DETAIL
6" MAX 6" MAX
OCEANVIEW IMPACT HORIZONTAL SLIDER OCEANVIEW IMPACT HORIZONTAL SLIDER
EXTERIOR VIEW EXTERIOR VIEW
FRAME INSTALLATION FIN INSTALLATION
DESIGN PRESSURE RATING IMPACT RATING
±50.OPSF LARGEANDSMALL
MISSILE IMPACT
MISSILE LEVEL D,WIND ZONE 3
NOTES:
1. MAXIMUM SASH SIZE: 35" X 54 1/2"
2. MAXIMUM D.L.O.: 31 1/2" X 50 3/4"
3. (2) 3/8" X 3/16" WEEPSLOT AT 4 3/8" FROM OUTSIDE CORNER OF BOTTOM RAIL, GLAZING TRACK SIGNED:07/10/2017
AND INTERIOR WEB AND 3 3/8" FROM OUTSIDE CORNER OF BOTTOM RAIL BOTTOM SURFACE.
4. (2) 1/2" X 1/8" WEEPSLOT AT 5" FROM OUTSIDE SILL EXTERIOR SCREEN LEG. VIWINCO INC. \\\11111111///
5. (4) 1" X 1/8" WEEPSLOT AT 5" FROM OUTSIDE CORNER SILL EXTERIOR SASH TRACK. P.O. BOX 499 \�� 5 R• Lp�li/�
6. (2) 1" X 1/8" WEEPSLOT AT 1 3/8" FROM INSIDE CORNER OF SILL EXTERIOR SIDE OF INTERIOR MORGANTOWN, PA 19543 ``�v•�\CENSFgcf����
PANEL TRACK.
7. (2) 1" X 1/8" WEEPSLOT AT EACH END OF SILL INTERMEDIATE WALL. OCEANVIEW IMPACT HORIZONTAL SLIDER *•41-TAYrOF
095�1
8. (2) 1" X 1/8" WEEPSLOT AT 3 5/8" FROM OUTSIDE CORNER OF SILL EXTERIOR FACE. 72" X 60" �,0 'Z'O,
ELEVATION ��o_, ,
DRAWN: DWG NO. REV ��F• CORIOP•
A. (2)METAL CAM LOCK WITH KEEPER AT 1Z'FROM EACH END OF INTERIOR SASH MEETING STILE
HARDWARE 08-02939
A
SCALE DATE
B. SLIDER SASH T-BOLT AT TOP OF INTEROR AND EXTERIOR MEETING STILES NTS 08/08/16 2 OF 6
C. ALUMINUM REINFORCEMENT 10006608 AT INTERIOR AND EXTERIOR SASH MEETING STILES L.ROBEROM MLLE,P.ENC( ) f432WOODFORORD LEWISVILLE Luis R. Lomas P.E.D. ALUMINUM REINFORCEMENT 5516-1 AT INTERIOR AND EXTERIOR SASH MEETING STILES 434-688-0609 dlomas@Idomaspe.com FL No.: 62514
7/16" MIN. REVISIONS
I EDGE DISTANCE REV DESCRIPTION DATE APPROVED
WOOD FRAMING I A REVISED INSTALLATION DETAILS 07/10/17 R.L.
OR 2X BUCK
BY OTHERS 1 1/4" MIN.
EMBEDMENT
El
APPROVED 1/4" MAX.
SEALANT SHIM SPACE 1 1/4" MIN. 1/4" MAX.
❑Uol 0 a EMBEDMENT SHIM SPACE L— � INTERIOR
O O 7/16" MIN. 0 0
�--�- #10 WOOD SCREW EDGE DISTANCE ❑ �� U
#10 WO �T
OD
SCREW I L°
0
EXTERIOR INTERIOR WOOD FRAMINGp El
OR 2X BUCK O
BY OTHERS
EXTERIOR
APPROVED
SEALANT
JAMB INSTALLATION DETAIL
WOOD FRAMING OR 2X BUCK INSTALLATION
O O O O I TO BE SET
NLA BED OF
aAPPROVED SEALANT
APPROVED
SEALANT 1/4" MAX.
SHIM SPACE NOTES:
0 1. INTERIOR AND EXTERIOR FINISHES,BY OTHERS,
NOT SHOWN FOR CLARITY.
WOOD FRAMING t 2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
OR 2X BUCK DESIGNED IN ACCORDANCE WITH ASTM E2112
BY OTHERS SIGNED:07/10/2017
VERTICAL CROSS SECTION PI O.N O 499 \\��WICO INC. �9'R I,�IO �ii��
WOOD FRAMING OR 2X BUCK INSTALLATION MORGANTOWN, PA 19543 =��V•�\GENSF:9s���
OCEANVIEW IMPACT HORIZONTAL SLIDER _1k• 0 051 *=
72" X 60"
INSTALLATION DETAILS �;0, TAT OF •t�
DRAWN: DWG N0. REV �•�COR�OP
08
SCALE NTS DATE 08/08/16 sOA
eEr9 OF 6
3
L.ROBERTO LOMAS P.E. Lomas P.E.
1432 WOODFORD RD LEWISVILLE,NO 27023 LUIS R.FL NoL62514
434-688-0609 rllomas@lrlomaspe.com
5/8" MIN REVISIONS
EDGE DISTANCE REV DESCRIPTION DATE APPROVED
A REVISED INSTALLATION DETAILS 07/10/17 R.L.
1/4" MAX.
METAL SHIM SPACE
STRUCTURE
BY OTHERS
APPROVED D a
SEALANT
1/4" MAX.
a❑ ❑ ❑� r SHIM SPACE
I INTERIOR
10 SMS OR � p �
SELF DRILLING 5/8" MIN. ❑I
SCREW EDGE D+STANCE
o0
❑ ��
#10 SMS OR
SELF DRILLING O °
EXTERIOR INTERIOR SCREWS E 0
METAL APPROVED
EXTERIOR
STRUCTURE SEALANT
BY OTHERS
JAMB INSTALLATION DETAIL
SILL TO BE SET METAL STRUCTURE INSTALLATION
o O o o IN A BED OF
aAPPROVED SEALANT
APPROVED
SEALANT
1/4" MAX. NOTES:
-10 NOT
SPACE 1. INTERIOR AND EXTERIOR FINISHES,BY OTHERS,
METAL NOT SHOWN FOR CLARITY.
STRUCTURE - ---]-T 2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
BY OTHERS DESIGNED IN ACCORDANCE WITH ASTM F2112
SIGNED:07/10/2017
CO INC.
PI O.NBOX 499 J` R IIL o
MORGANTOWN, PA 19543 v•%r'EIV&
OCEANVIEW IMPACT HORIZONTAL SLIDER =*4"TAY 0,�8 51 *=
72" X 6D VERTICAL CROSS SECTION INSTALLATION DETAILS �
METAL STRUCTURE INSTALLATION -0
DRAWN; DWG NO. REV �i��'PFS'�CpR10Q'G�Z'\:
scuE NTS DATE 08/08/16 OS SHHEET49 OF 6 A
L.ROBERTO LOMAS P.E. Lomas P.E.
1432 WOODFORD RD LEWISVILLE,NO 27023 LUIS R.FL NoL62514
434-668-0609 dlomasCTalrlomaspe.com
2 1/2" MIN. REWSIONS
EDGE DISTANCE REV DESCRIPTION DATE I APPROVED
CONCRETE/MASONRY A REVISED INSTALLATION DETAILS 07/10/17 R.L.
BY OTHERS
a c 1 1/4" MIN.
OPTIONAL 1X BUCK " "•• •d a•. ' EMBEDMENT
SEE NOTES 3 — 7 " "' 1 1/4" MIN. 1/4" MAX.
SHEET 1 --� EMBEDMENT SHIM SPACE
CONCRETE/MASONRY
❑ BY OTHERS . .v 0•
APPROVED 1/4" MAX. a
SEALANT SHIM SPACE e`
❑�f0L OPTIONAL 1X BUCK °
a SEE NOTES 3 — 7 °
SHEET 1 a•0°
0 ED 3/16" TAPCON INTERIOR
3/16" TAPCON Dae •°a• ❑ o
� • .°: DQ o e
EXTERIOR
2 1/2" a ��
INTERIOR EDGE '• O�
DISTANCE °• ❑
J •a ..e. a o
EXTERIOR
SILL TO BE SET APPROVED
SEALANT
IN A BED OF
APPROVED SEALANT JAMB INSTALLATION DETAIL
O O O O
APPROVED CONCRETE/MASONRYINSTALLATION
a
SEALANT ❑
NOTES:
1/4" MAX 1. INTERIOR AND EXTERIOR FINISHES,BY OTHERS,
OPTIONAL 1X BUCK SHIM SPACE NOT SHOWN FOR CLARITY.
SEE NOTE 3 - 7 O ❑ 2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
SHEET 1 DESIGNED IN ACCORDANCE WITH ASTM E2112 SIGNED:07/10/2017
CONCRETE/MASONRY VIWINCO INC. \\�
\\\\R IIS o
BY OTHERS e. P.O. BOX 499 \\\
a ' ° °' °• e. a MORGANTOWN, PA 19543 `�V•�\C+ENSFgcP���
cb ° e OCEANVIEW IMPACT HORIZONTAL SLIDER
*• 0, 5�1# `••
INSTALLATION DETAILS ��l, TAT OF M.,'r
DRAWN: DWG N0, REV ���'°F•'ctpItIOP•
SCALE DATE 08-02939 A / 0NA`���\G���
VERTICAL CROSS SECTION NTS 08/08/16 5 OF 6
CONCRETE/MASONRYINSTALLATION L.ROBERTOLOMASP.E. Luis R. Lomas P.E.
1432 WOODFORD RD LEWISVILLE,NC 27023 FL No.: 62514
434-688.0609 rllomas@trlomaspe.com
Ar
REVISIONS
APPROVED REV DESCRIPTION DATE APPROVED
SEALANT
BEHIND FIN 1 1/4" MIN. A REVISED INSTALLATION DETAILS 07/10/77 R.L.
EMBEDMENT
#6 WOOD WOOD
SCREW FRAMING
BY OTHERS
1/4" MAX.
SHIM SPACE WOOD FRAMING 1/4" MAX
3/8" MIN r BY OTHERS SHIM SPACE
EDGE DISTANCE � =L❑❑
a
❑�0 #6 WOOD
SCREW o
1 OD
1 1/4"
❑� o 0
MIN.
EMBEDMENT a�
o0
APPROVED
EXTERIOR INTERIOR SEALANT O�
BEHIND FIN
3/8" MIN 0
EDGE DISTANCE
JAMB INSTALLATION DETAIL
WOOD FRAMING OR 2X BUCK INSTALLATION
a0 0 0 0 �
❑ NOTES.,
1. INTERIOR AND EXTERIOR FINISHES,BY OTHERS,
NOT SHOWN FOR CLARITY.
D
1/4" MAX 2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
0 {-SHIM SPACE DESIGNED IN ACCORDANCE WITH ASTM E2112+ SIGNED:0711012017
38MIN j 0I"" -T VIWINCO INC. \\�11�II�IIIv,,
EDGE DISTANCE P.O. BOX 499 \`\vJ\c?\G� S��119���i
MORGANTOWN, PA 19543 = F
#6WOOD SCREw FRAMING OCEANVIEW IMPACT HORIZONTAL SLIDER *�• /�0 p61
1 1/4" MIN. BY OTHERS 72" X 60" �,o,{(,,,� �`
FIN INSTALLATION DETAILS gTAT OF
APPROVED EMBEDMENT ��• <u
BEHINDSEA�FIN VERTICAL CROSS SECTION NT DRAWN: DWG NO. REV �i��'PFs
WOOD FRAMING OR 2X BUCK INSTALLATION DATE 08-02939 A //,,S�ONAy1E��\��
SCALE NTS 08/08/16 6 OF 6
L.ROBERTO LOMAS P.E. Lomas P.E.
1432 WOODFORD RD LEWISVILLE,NC 27023 LUIS R.FL NoL62514
434-688-0609 rllomas�7ulrlomaspe.cam