HomeMy WebLinkAboutProject Information+ wrightsofto Project Summary Date: May 1, 2020 UNIT 1 By: QUICK CALCS, INC. 317 ST. LUOE LN., FT. PIERCE, FL34946 Phone:772-466-6799 F=772.466fi796 Email: OUKXCALCS@AOL.COM Promect Information For: LOT #37 4824 WATERSONG WAY, ST. LUCIE COUNTY, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TO 28 OF Design TO 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grllb Heating Summary Sensible Cooling Equipment Load Sizing Structure 26964 Btuh Structure 25657 Btuh Ducts 4329 Btuh Ducts 3511 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Bbuh (none) (none) Humidfication 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 31293 Btuh Use manufacturer's data n RatelsWng multiplier 0.95 Infiltration Equipment sensible load 27710 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2686 Btuh Ducts 3781 Btuh Central vent (0 cfm) 0 Btuh Heatingg Cooling (none) Btuh Area(ft� 2465 2465 Equipment latent load 6467 Volume (ft3) 23589 23589 Airchanggesthour 028 0.15 Equipment Total Load (Sen+Lat) SHR 34177 3.3 Btuh ton Equiv.AVF (cfm) 111 60 Req. total capacity at0.70 Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade Model Cond 24ANB748CO031 AHRI ref Coil FV4CNB006 AHRI ref 5635352 Efficiency 100 EFF Efficiency 13.5 EER,17 SEER Heating input 11.9 wV Sensible cooling 33600 Btuh Heating output 40772 Btuh Lateatcooling 14400 Btuh Temperature rise 23 OF Total cooling 48000 Btuh Actual air flow 1600 cfm Actual air flow 1600 cfm Airflowfactor 0.051 cfm/Btuh Air flow factor 0.055 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. •Fkl• wrighttsoft• 2020-May-0510:12.60 tX .. Right RSUOB101 Page 1 �...t FPAQWATERSONG-LOT#374824WATERSONGWAY.mp Calc=MJB Front Doorface .SW +wrightsofte Project Summary Date: May 1, 2020 UNIT 2 By: QUICK CALCS, INC. 317 ST LUCIE LN., Fr. PIERCE, FL 34946 Phone:772-466-6799 Fax 772466b796 Emaii:OUICKCALCS@AOL.COM Pirdect Information For: LOT #37 4824 WATERSONG WAY, ST. LUCIE COUNTY, FL Notes: Desi_qn Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daly range L 50 % Relative humidity Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19047 Btuh Structure 20140 Btuh Ducts 4450 Btuh Ducts 3097 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 23497 Btuh Use manufacturer's data n Ratelswing multiplier 0.95 Infiltration Equipment senslbleload 22075 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1708 Btuh Ducts 2595 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coolingg (none) 4304 Btuh Area(ft2) 1758 1758 Equipment latent load Volume (fP) 16575 16575 Airchangges/hour 0.28 76 0.15 41 Equipment Total Load (Sen+Lat) Req. total 0.70 SHR 26378 2.6 Btuh ton EquivAVF (cfm) Cape* at Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIERAIR CONDITIONING Model Cond 24ANB736AO031 AHRI ref Coil FV4CNB006L AHRI ref 7875378 Efficiency 100 EFF Efficiency 13.5 EER,17.5 SEER Heating input 7.2 kW Sensible cooling 25200 Btuh Heating output 24610 Btuh Latent cooling 10800 Btuh Temperature rise 19 OF Total cooling 36000 Btuh Actual air flow 1200 cfm Actual air flow 1200 cfm Air flow factor 0.051 cfm/Btuh Air flow factor 0.052 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat rato 0.84 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrlghteoft- 2020-May-0510;12:60 Right-SuiteOUnNe=1201919.0.07 RSU08101 pd0e p ACCA' ...tF\AaWATERSONG.LOT#374824WATERSONGWAYavp CWc=MJ8 FrontCm faees SW I# wrightsof - Right-J® Worksheet 'a� UNIT 1 �� May T, zozo QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email: OUICKCALCS@AOL.COM 1 Room name UNIT FLEX ROOM 2 Exposed wall 2728 ft 36.0 ft 3 Room height 98 it d 10.0 A heat(cool 4 Rcomdimenstans 18.0 x 18.0 It 5 Roomarea 2464.5 IF 324.0 fF Ty Construction U-value Or HTM Area gF) Lead Area Load number (BtuW--°F) Pump) or perimeter (9) (Btuh) or perimeter (f) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NrPS Heat Cool 6 W 13B450cws 1OA-v 1013-v 1Ac1ov OD54 0820 08DO 09M no. ne ne ne 1.79 2296 16BO ODO 089 14,90 25.00 0.00 477 48 24 0 293 0 0 0 526 1102 403 0 261 715 600 0 180 48 -0 0 132 0 0 0 237 1102 0 0 117 715 0 0 11 1Aclov 1A-r1obd 09M 1.080 no no 0.00 0.00 0.00 p ODO 0 0 0 0 0 0 0 0 0 0 0 0 0-. 0 0 0 1A-r1omd 1270. ne 35.66. 43.03 112 0. 3983 4819 0 0 0 0 ,W 13&5ocws 0.064 a 1.79 089 93 31 56 28 0 0 0 0 LG 1A-r1omd 13B5a:ws 1270 0.064' a as 35SO 1.79 2987 0.89' 62 678 64 542 2205 972 _ 1840 482 0 '180 0 160 0 287 0 142 1Dc2om 0870 se ODO 0.00 0 0 0 0 0 0 0 0 1 D-c2om 0870 se 0.00 0.00 0 0 0 0 0 0 0 0 10c2om 0870 se 0.00 .0.00 0 0 0 0 0 0 0 0 ID-c2ov 1Dc2ov 0570' 0570 se se 1595 15.96 4730 36.14 20 18 0 7 319 287 946. 650 20 0 0 0 319 0 946 0 lD-c2cv 0570 se 15.96 37.73 42 15 670 1585 0 0 0 0 1D-c2ov se: 1596 37.73 56 20 894 2113 0 0 0 0 13136ocws ,0570 0.054 sw 1.79 089 338 229 411 204 0 0 0 0 10A-m 1.670 sw 0.00 ODO 0 0 0 0 0 0 0 0 10A-m 1.670 sw 46.76 1598 40 40 1870 639 0 0 0 0 1OA-v 0820 sw 22.96 1521 48 48 1102 730 D 0 0 0 113c2om 0870 sw 080 OAD 0 0 0 0 0 0 0 0 11Dc2om OEM sw Om 0.00 0 0 0 0 0 0 0 a 10c2ov o570 sw 1596 2029 5 5 80 101 0 0 0 0 1Dc2ov 0570 sw 15.96 30.55 16 10 255 489 0 0 0 0 13BSacws OA64 my 1.79 0.89 1023 929 1664 826 0 0 _ 0 0 1/4h1w 0.900 mw 2520. 49.12 20 0 5D4 982 0 0 0 0 11Dc2om 0870 mry 0.00 080 0 0 0 0 0 0 0 0 1Dc2om 0870 mv- OOO 0.00 0 0 0 0 0 0 0 0 - 1Dc2ov 0570 w 1596 4691. 8 0 128 375 0 0 '0 0 11Dc2ov 0570 mr 15.96 4691 24 0 383 1126 0 0 0 0 IDc2ov- - 0570 my 1526 4691 42 0 670 1970 0 0 0 0 P 12C41sw 0.091 - 255 128 476 476 1212 610 iW 150 382 192 C 16X19-Omd OAO8 _- 1.59 1.49 113 . 113 ' 178 167 _ 43 43 67 63 F 19C-19csco 0.049 - 0.48 025 727 727 346 185 0 0 0 0 F '22A-tpl 0989 - 27.69I 0.00 846 101 2797 b 324 36 997 0 F 22A-tpI 0989 - 27.69 0.00 98 19 529 0 0 0 0 0 61 c)AED excursion 0 -53 Envelope loss/gain 23546 22446 3391 2124 12 a) Infiltration 3419 981 472 135 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants (ni? 230 1 230 0 0 Appliancestother 20M 0 Subtotal Qines 6 to 13) 26954 25657 3863 2259 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0863 14 Subtotal 26964 25657 3 2259 15 Duclloads 16% 14% 4329 3511 0% O% 0 0 Total room lead 31293 29168 3863 2259 Air required (cfm) 1600 1600 197 124 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. G Ad- wrlgh2ooTY- 2020-May-0510:12:50 . A •- -- Right-SuILOUniversal 201919.0.07 RSU081o1 Pagel ...tH1AaWATERSONG-LOT#374824WATERSONGWAYrup Calo=MJB Front Nor faces: SW wrightsoft° Ri ht-M Worksheet Job: U19 iT 1Date: May 1, 2020 QUICK CALCS, INC. 317 ST. LUCIE LN., FT PIERCE, FL 34946 Phone: 772466-6799 Fax: 772-466-6796 Email: QUICKC4LCS@AOL.COM 1 Room name LAUND. CABANA 2 Egmsedwall 17.0 R 10D R 3 Room height 10D R heaRcwl 10.0 R hmVcool 4 Room dimensions 10.0 x 7.0 R 10.0 x 10.0 R 5 Room area 70.0 fF 1OOD R' Ty Construction number U-value (Btuh/fVF) Or HTM (Btuh41'1 Area (IF) or perimeter (it) Load (Bluh) Area (R°) or perimeter (it) Load (Bluh) Heat Cool Gross N/P/S Heat Cool Gross N/PiS Heal Cool 6 13B504ws 0.064 ne 1.79 0.89 100 76 136 68 0 0 0' 0 11 1OA-v 10Bv 1Aclov 1Aclov 1A-rlobd 1A-rlomd 13BSacws 0820 0.600 0900 0-000 1.080 1270 0.064 ne ne ne ne ne ne a 2296 16BO OOO 0.00 0.00 35M 1.79 1490 25.00 0.00 0.00 0.00 43.03 089 0 24 0 0 0 0 0 0 0 0 0 0 _ 0 0 0 403 0 0 0 0 0 0 '600 0 0 0 0 0 0 0 0 0 0 . 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 G ,W Y-G 1A-r1omd 1313Z c 1D-c2om 10c2onn 1 Dc2om 1Dc2ov 1Dc2ov 1270 '0.064 0.870 0870 0870' 0570 0570 a sw se se se se se. 3556 1.79 -0.00 0.00 ODD 1596 1596 29.67 0.69 '0.00 0.00 0.00 47.30 36.14 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ,. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 113c2oe 1Dc2cv 13B6aws 10A-m 1OA-m 1OA-v 1113c2om 0S70 0570 0064 1.670 1.670 0820 0270 se se sw sw sw sw sw 1596 1596.. 1.79 0.00 46.76 2226 000 37.73' 37.73 089 000 1598 1521 ODD 0 , 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0- - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Dc2om 10c2ov 1Dc2ov 13B5dcws 1A-hlod 11Dc2cm 1Dc2om 0870 0570 0570 0.064 0900 0870 0270 sw sw sw ma- mid rlw nw ODO 1596 1696 -1.79. 2520 OAO '0.00 000 2029 3055 029 49.12 0.00 0.00 0 0 0 70 0 0 0 0 0 0 70 0 0. 0 0 0 0 125 0 0 0 0 0 0 62 0 0 0 0 0 0 100 0 0 0 0 0 0 _ 100 0 0 0 0 0 0 179 0 0 0 0 0 0 89 0 0 0 1Dc2ov 1Dc2ov iDc2ov 12C-Osw 0.670 0570 0.570 0.091 nw riw ma - 1596 1596' 1596 2S5 4691 4691 4691 128 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C _ 16X19-Omd 0.408 - 159 1.49 10 _ - 10 16 , - 15 - 0 ` 0 - 0 0 F 19C-19cscp 0.049 - 0.48 025 0 0 0 0 0 0 - 0 0 F 22A-tpl - 0989 - 27.69 0.00 70 17 471 0 100 10 277 0 F 22A-Ipl 0989 - 27.69 OAO 0 0 0 0 0 0 0 0 6 c)AEDexcursion -76 -14 Envelope lossfiain 1151 668 456 75 12 a) Infiltration 223 64 131 38 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6to 13) 1374 732 587 113 Less external load 0 0 0 0 Lessmansfer 0 0 0 0 Redistribution 0 0 200 39 14 Subtotal 1374 732 788 151 15 Duct loads 24% 18% 330 129 0% 0% 0 0 Total room load 1704 861 788 151 Air required(cim) 87 47 40 8 f :aICu Batons approved b;rACCA to meat all requirements of Manual J 8bl Ed. _ -Fk- . A...lticfC- 2020-May-0510:12:50 g-®..Paget tMAQWATERSONG-LOT#374824WATERSONGWAYrup Calc=MJB Front Doorfams:SW I wrightsoft Right-M Worksheet j°a UNIT 1 Date: may 1, 2020 QUICK CALCS, INC. 317 ST. LUCIE LN., FTPIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email: OUICK(ALCS@AOL.COM 1 Room name STAIR FOYER 2 Exposedwall 11.0 it 27.0 it 3 Room height 10.D it heallcool 9A it heaycool 4 Room dimensions 9.0 x 11.0 it 1.0 x 228.0 8 5 Rcomarea 99.0 fF 228D iP Ty Construction U-value Or HTM Area QF) Load Area Load number @Wh7P-*F) Q3tutvt� or perimeter QQ (Eiuh) or perimeter (it) (Bluh) Heat Cool Gross N/P/S Heat Cool Gross N/P5 Heat Cool 6 W 1313-5ocws 1014-v 0.064 OZ20 'ne ma 1.79 2296 0.89 14.90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 dOB-V 0500 no 16,80 25.00 0 0 0 0 0 0 0 0 tActov 0900 ne. OAO 0.00 0 0 0 0 0 0 0 0 11 1Actov 0900 no 0.00 0.00 0 0 0 0 0 0 0 0 tAttobd 1.080 ne 0.00 0.00 0 0 0 0 0 O 0 0 1A-Nomd 1270 no 35.56 43.03 0 0 0 0 0 0 - 0 0 Ito L-C 136.5ocws to-riomd 0.064 1270 a a 1.79 3556 OB9 2957 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13B5ocws - 0.064 se 1.79 0B9 0': 0: 0 0 0 0 0 -, 0 1Dc2om 0270 se OAO 0.00 0 0 0 0 0 0 0 0 1Dc2om 0B70' se Ow 0.00 0 0 0 0' 0 0 0 0 1Dc2om 0B70 se OOO 0.00 0 0 0 0 0 0 0 0 1Dc2ov 0570 se 15% 47.30 0 0 0 0 0 0 0 0 tDc2ov 0570 se 1595 36.14 0 0 0 0 0 0 0 0 1D-c2ov 0570 se 15.96 37.73 0 0 0 0 0 0 0 0 1Dc2ov - 0.570 se ,. •1596 37.73 _ 0, 0 0 0 0. -0 0 0 1365ocws 0A64 sw 1.79 0B9 0 0 0 0 75 27 49 24 10A-m 1B70 sw 0.00 0.00 0 0 0 0 0 0 0 0 1OA-m 1.670 sw 46.76 1528 0 0 0 0 0 0 0 0 1OA-v OB20 sw 2226 1521 0 0 0 0 48 48 1102 730 113c2om 0.870 sw 0m 0.00 0 0 0 0 0 0 0 0 1Dc2om OB70 sw 0100 OAO 0 0 0 0 0 0 0 0 1Dc200 0570 sw 1596 2029 0 0 0 0 0 0 0 0 1D-c2ov 13&Socws 0570 0.064 sw nw 1596 1.79 3055 OB9 0 110 0 110 O 197 0 98 0 179 0 159 0 284 0 141. 1A-h1w 0900 my 2520 49.12 0 0 ' 0 0 20 0 504 982 1Dc2om 0.870 w 0.00 OAO 0 0 0 0 0 0 0 0 9Dc2om OB70 my 0.00 ODD 0 0 0 •.0 0 0 0 0 1Dc2ov OB70 ma 1596 4691 0 0• 0 0 0 0 0 0 1Dc2ov 0.570 my 1596 4691 0 0 0 0 0 0 0 0 1Dc2ov 0570 nw _ 1596 4691 0 0 0 0. 0 0 0. 0 P 12C4)sw 0.091 - 255 128 0 0 0 0 226 226 575 289 C 16X19-Omd•. 0.408 - 1.59 1A9 0 0 0 - 0- 0 0 0 0 F 19C-19cscn 0.049 - 0.48 025 0 0 0 0 0 0 0 0 F 22A-tpI OM - .27.E 0.00 99 - 11 ., 305 0 228 27 748 0 F 22A4pl 0989 - 27.69 Ono 0 0 0 0 0 0 0 0 6 c)AED excursion -15 781 Envelope loss/gain 502 83 3262 2949 12 a) Infitlration 144 41 332 95 b) Room ventilation 0 0 0 0 13 Intemalgains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qimes 6 to 13) 646 124 3594 3044 Less mdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -646 -124 700 200 14 Subtotal 0 0 4294 3244 15 Dud loads 0% 0% 0 0 0% 0% 0 0 Total room load 0 0 4294 3244 Air required(cfm) 0 0 220 178 Ctaln datinns approved hvACC-A to inapt all requirements of Mangy tal _I 8th Fri wrlghesofC- 2020-May-0510:12:50 °-•�- ^---°-^• Right-SuitreltUniversal 201919.0.07 RSU08101 Page ...tHVAQWATERSONG-LOT#374624WATERSONGWAYrup Calc=MJ8 Front Doorfaces SW wrightsoft Right-J® Worksheet Job: UNIT 1 Date: May 7, 2020 By: QUICK CALCS, INC. M7 ST. LUCIE LN., FL PIERCE, R.34946 Phone:772-48M799Fm:772A66-6796 Email: QUICKC4LCS@AOL.COM 1 Room name ELE GREATROOM 2 6q)osed wall 0 It 678 it 3 Room height 10.0 it heat(000l 9A ft heat/cool 4 Room dimensions 5.0 x 5.0 it 1.0 x 5915 it 5 Room area 25.0 fF 591.5 IF Ty Construction number U-value MWh1F-°F) Or HTM (Btuw Area (fF) or perimeter (tq Load (Btuh) Area OF) or perimeter (it) Load (BWh) Heat Cool Gross N/PS Heal Cool Gross M S Heat Cool 6 IV 13B-5ocws 0.064 no 1.79 0.89 0 0 0 '0 197 a5 153 76 11 10A-v 10B-v 1Aclov 1Aclov IA-rlobd 1A-r1omd 131!15acws 1A-rlomd 13B-5ocws 11)c2om 1Dc2om 1Dc2om 1Dc2ov 1Dc2ov 0820 OBOD 09M 0900 1.080 1270 0.064 1270 0064 0.870 OB70 0870 0570' 0570 ne ne ne no no no a a se . se se se. se se. 2296 16BO 0.00 '0.00 0.00 35.56 1.79 3556 1.79 000 0.00 000 1596 1526 1490 25.00 0.00 0.00. 0.00 43.03 089 29.67 029' 000 0.00 0.00 47.30 36.14 0 0 0 0 0 • 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '0 0 0 . 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0' 0. 0 0 0 0 0 0 112 93 62 141 0 0 0 0 0 0 0 0. 0 0 - 0 31 54 85 0 0 0 0 0 0 0 0 0. 0 39M 56 2205 152 0 0 0 0 0 0 .0 0 0 0 4819 28 1840 76 0 0 0 0 0 W L-G IV 1Dc2w 1Dc2ov _ 1311Scows 10A-m 1CA-m 70AN 1Dc2om 0570 ,0570 0064 1B70 1.670 0B20 OB70 se se-; sw sw sw sw sw 15.96 15.96 1.79 0.00 46.76 2226 ODD 37.73 37,73. OB9 0.00 1598 1521 000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 56 0 0 0 0 0 0 .. 20 0 0 0 0 0 0 894 0 0 0 0 0 0 2113 0 0 0 0 0 1Dc2om 1Dc2w 10c2ov 139-5ows to-htov 1Dc2om 1Dc2om OB70 0570 0570 OD64 0" 0870 OB70 sw sw sw mu M m mw 000 1596 1596 1.79. 2520 0.00 0.00' 000 2029 3055 0,89 49.12 0.00 0.00 0 0 0 0. 0 0 }- 0 0 0 0 '0 0 0 -0 0 0 0 0 0 0 0 0 0 0 - 0 0 ,0 0 0 0 0 207 0 0 0 D O 0 165 0 0 - 0 0 0 0 295 0 0 0 0 0 0 147 0 0 0 1Dc2ov 1Dc2ov 1Dc2ov 12C-Osw 0570 0570 0.570 0.091 my nw nw - 1596 1596 - 15.96 4691 4691 4691 128 0 0 0 100 0 0 0 100 '0 0 0 255 0 0 0 128 0 0 .42 0 0 0 0 0 0' 0 670; 0 0 0 .1970 0 P _ C 16X190md 0.408, • _2.55 159 1A9 0 , 0 0. 0 60 60 95 89 F 19C-19cscp 0.049 - 0,48 025 0 0 0 0 75 75 36 19 F F 22AApl 22A-tpl 0989 0989- - 27.69 27.69 - 0.00 000 25 0 0 0 i 0 0 0 0 0 0 0 0 0 0 0 0 6 c)ArD excursion -14 -1231 Envelope losstgain 255 114 8539 9945 12 a) Infiltration 0 0 836 240 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 255 114 9315 101115 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -256 -114 0 0 14 Subtotal 0 0 9375 10185 15 Duclloads 0% 0% 0 0 24% 189/6 2252 1788 Total room load 0 0 11627 11973 Air required(cfm) 0 0 594 657 Calculatons approved byACCA to meet al! requirements of Manual J 8th Ed -FW wrighesoTt- 2020-May-0510:1250 •- -•• - RightSuiLOUniversal 201919.007 RSU08101 Page ...t"CWATERSONG-LOT9374824WATERSONGWAYmp CaIc=W8 FrontDDorfaws:.Sw t i wrightsoft Right-M Worksheet Job: UNIT 1 Date: may 1, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LN., FL PIERCE, FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email: OUICKC4LCS@ACL.00M 1 Room name STAIRWAY KITCHEN 2 Egwsed wall 25.0 It 15.0 ft 3 4 5 Room height Room dimensions Room area 9.4 it heatfcool 1.0 x 251.0 ft 251.0 ft' 9A It ImUcool 20.0 x 15.0 S 300.0 ft' Ty Construction U-value Or HTM Area (T) Load Area Load number (Stui (BtuM12) or perimeter (fl) (Btuh) or perimeter (f) (Stuh) Heat Cool Gross N/P/S Heat Cool Gross NrPrS Heat Cool 6 11 W 133-50cws 1OA-v 40F=v 1Aclov 1Actov 1A-riobd 1A-riomd . 13&5ocws 0.064 0820 OB00 0900 0900 1.080 1270 0.064 ne me ne ne ne ne ne.. a 1.79 2296 1680 ODO 0.00 ODO 3556 1.79 0.89 , 14X 2600 0.00 OD0, 0.00 43.03 089 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0'. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D D 0 0 0 0 0 0 0 0 0 0 W, 1A-r1omd 136Socws 1Dc2om 1Dc2cm 1D-02om 1Dc2ov 1Dc2ov 1270 0.064 0.870 0870 0.8m 0570 0570 a se se se se se se 3556 1.79 0.00 ODD ODD 1596 1596 29.67 OB9 0.00 0.00 ODD 4720 36.14 0 0 0 0 0 0 0 0 - 0 0 0 0 0. 0 0 0 0 0 0 0 0 _ 0 0 0 0 0 0 0 0 141 0 0• 0 0 18 0 - 123 0 0 0 0 7 0 220 0 0 0 0 287 0 109 0 0 0 O 650 -G ID-c2ov 113c2ov 13BSwws 1aA-m 10A-m 10A-v 11Dc2om '0570. •0570 0064 1.670 1.670 0820 0870 se se sw sw sw sw sw 15.96 1596 1.79 ODO 46.76 22.96 ODO 37.73 37.73 029 0.00 ism 1521 0.00 -0 0 0 0 0 a 0 0 0 0 0 0 0 0 0 0 a 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 a 0 a 0 0 0 0 D 0 0 0 0 0 0 0 0 0 0 0 G 1Dc2om 1Dc2w ICI-02M 13B-5dcw_s to-htov 11D-c2om 11D-02om OB70 0570 0570 OD64 0" ONO 0270 sw sw sw w nw 'nw nw ODD 1596 1596 1.79 2520 ODD ODO ODO 2029 3055 089 49.12 ODD 0.00 0 0 0 235 0 0 0 0 0 0 '211 0 0 0 0 0 0 378 0 0 0 0 0 0 188 0 0 0 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 113-02ov '1Dc2ov 1D-02ov 12C-0sw 0570 0570 OB70 0.091 mw riw nw - 1596 1596 1596 255 4691 4691 4691 128 0 24 . 0 0 0 0- 0, 0 0 "' 383 .. 0 0 0 1126 0 0 0 0 0 0 0 0 0 0 0' 0 0 0 0 0 0 0 P .0 '16X19-0md -0.408 - 1.59 1A9 0 0 _ 0 _ 0 0 0- 0 0 F 19C-19cscp 0.049 - OAS 025 56 56 27 14 225 225 107 - 57 -.F F 22A-tpl 22A-tpl 0989 0.989 - 27.69 27.69 0.00 ODO 0 5 0 0 0 14 - 0 0 0 0 0 0 0 0 0 0 61 c)AEDexcursion 296 21 Envelope toss/gain 902 1624 615 838 12 a) Infiltration b) Roomventilation 308 0 a8 0 185 0 53 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianceslother 01 2000 Subtotal(Iines6to13) 1109 1713 799 2891 Less erdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 9 4 0 0 14 Subtotal 1118 1717 799 2891 151 Dud loads 24% 18%1 269 301 24% 18% 192 507 Total room load 1387 1 2018 w 3398 Air required (cfm) 71 111 51 186 Calculations approved byACCA to meet all requirements of Manual J 81h Ed. - wrl9titC®olvc- 2020-May-0510:12:50 A -• •-^- RIght-Sulte®Unlversal 201919.0.07 RSU08101 Page ...tMAQWATERSONG-LOT#374624WATERSONGWAY.mp Calo=MJB Front Doorfams: SW wrightsoft- Right-J® Worksheet Job. UNIT 1 Date: may 1, 2020 QUICK CALCS, INC. By 3W ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466.6799 Fax: 772-466-6796 Email: OUICKOALCS@AOL.COM 1 Room name LAUNDRY BEDROOM4 2 Egmsed wall 9D it 28D it 3 Room height 9A ft hest(ceol 9A 1t heat/cool 4 Room dimensions 1.0 x 82.0 it 1D x 204.0 ft 5 Room area 82.0 fF 204.0 IF Ty Construction U-value Or HTM Area OF) Load Area Load number (BtuhAf--°F) (BtuW or perimeter (1) (Btuh) or perimeter (10 (Btuh) Heal Cool Gross N/P/S Heat Cool Gross NIPS Heat Cool 6 W' 13B-5wws t0A-v 0.064 '0220 no ne 1.19 2296 -089 14.90 0 0 0 0 0 0 - 0 0 0 0 0 0 0 a 0 0 te&v 0.600 ne 16BO 25DO 0 0 0 0 0 0 0 0 1Ac1ov 0900 ne 000 0.00 0 0 O 0 0 0 0 0 11 1Aclov 0900 no 0.00 •000 0 0' 0 - 0 0 0 0 0 1A-rtobd 1DW ne 0.00 000 0 0 0 0. 0 0 0 0 IA-rlomd 1270 no 35.56 - 43.03 0 0 0 0 0 -. 0 01 0 t-C 1313-5ocws 0.064 a 1.79 089 0 0 0 0 0 0 0 0 1A-riomd 1270 a 3556 2987 0 0 0 0 0 0 0 0 13B-5ocws 0.064 se 1.79 , OB9 85 71 127 _ 63 132 104 . 186 92 11Dc2om 0270 se 0.00 0.00 0 0 0 0 0 0 0 0 110c2om 0870 se 000 0.00 0 0 •0 0 0 0 0 0 1Dc2om. 0870 se' 000 0.00 0 0' 0 0 0 0 0 0 1Dc2ov 0570 se 1596 4780 0' 0 0 0 0 0 0. 0 10o2ov '0570 se, 1596 36.14 0 0 0 0 0 0 0 O 1Dc2ov 0570 se 1596 37.73 14 5 223 628 28 10 447 1056 9Dc2ov - 0.5m se 1596 37.73 0 ,. 0 0 0 0 0 0 0 13B6oc= OD64 sw 1.79 089 0 0 0 0 132 79 141 70 10A-m 1870 sw 0.00 000 0 0 0 0 0 0 0 0 10A-m 1.670 sw 46.76 15M 0 0 0 0 40 40 1870 639 10A-v 0B20 sw 22M 1521 0 0 0 0 0 0 0 0 tDc2om 0870 sw 000 000 0 0 0 0 0 0 0 0 113c2om OB70 sw O00 o00 0 0 0 0 0 0 0 0 iDc2cv 0570 sw 1596 2029 0 0 0 0 5 5 80 101 ID-c2ov 0570 sw 15.96 3055 0 0 0 0 8 5 128 244 13B-50cws OD64 w 1.79. 089 0 0 0 0 0 0 0 0 to-h1ov 0.900 rrw 2520. 49.12 0 0 0 0 0 0 0 0 1Dc2om 08m rmv 000 0.00 0 0 0 0 0 0 0 0 11Dc2cm 0870 my 0.00 0.00 0 0 0 0 0 0 0 0 1Dc2ov IDc2ov 0570 0570 mw nw. 1596 15.96' 4691 4691 0 0 0 0 0 0 0 0 0 '0 0 0 '0 0 0 0 1Dc2ov _.0570 mw. 1596 4621 0 0 0 0 0 0 0 0 P 12C-0sw 0.091 - 255 128 0 0 0 0 0 0 0 0 C 16X79-0md 0.408 - A59' 1.49 0 0 0 '0 0 0 0. 0 F 19C•19cscp 0.049 - 0.48 025 82 82 39 21 190 190 90 48 'F- 22A-ipl 0989 - ,. 27.69 0.00 0 .0 0 - 0 0 0 _ 0 0 F 22A-tpl 02N - 27.W 0.00 0 0 0 0 14 2 53 0 6 c)AEDexcursien 200 -126 Envelopeloss/gain 389 812 2995 2126 12 a) Infiltration 111 32 345 99 b) Roomventlation 0 0 0 0 13 Infemalgains: Occupants@ 230 0 0 1 230 Applianceslother 0 0 Subtotal( lines 6 to 13) 500 844 3340 2455 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 1 0 14 Subtotal 500 844 3340 2455 15 Duct loads 24% 18% 120 148 24% 18% 802 431 Total room load 620 15M 4143 2886 Air required(ofm) 32 54 212 158 Calculatons approved byACCA to meet all requirements of Manual J 8th Ed. # - wrlghesaoft- 2020-May-0510:12:50 A&h•-° - - ^ Right-SuWUnlversa1201919,0.07 RSUD8101 Page ...t M61QWATERSONG-LOT9374824WATERSONGWAYmp Calc=MJB Front Door faces: SW F�+ wrightsoft Rht-J® Worksheet Job' 1 Date: May 7, 2020 M By: QUICK CALCS, INC. 317 ST LUCIE LN., Fr.. PIERCE, FL 34946 Phone: 772-466-6799 Fax:772-466.6796 Email: OUICKCALCS@AOL.COM 1 Room name ELEVATOR BATH 4 2 Exposed wall 0 8 9.0 It 3 Room height 9.4 It heatbool 9A 8 heaUcool 4 Room dimensions 5.0 x 5.0 0 5.0 x 13.0 O 5 Room area 25.0 IF 65D 1F Ty Construction number U-value (BtuhAFR F) Or HTM (BtuhAt) Area (W) or perimeter (ft) Load (Btuh) Area or perimeter (f) Load (Btuh) Heat Cool Gross NIPS Heal Cool Gross NIPS Heat Cool 6: W 130-5ocws 16A-v 0.064 0,820 ne ne • 1.79 2296 0.89 1490 0 0 0 0 0 0 0 0 0 0 0• 0 0 0 0 0 106-v OEM ne 16.80 25.00 0 0 0 0 0 0 0 0 tAc1w -0900 ne 0.00 000 0 0 0 0 0 0 0 0 11 1Aclov 0900 ne 0.00 000 0 0 •0 0 0 0 0. 0 IA-rlobd• 1.060 ne 0.00 000, 0 .0 0 0 0 0 0 0 1A-rlomd 1270 ne 3556 43.03 0 0 0 0 0. 0 0 0 IW '-G 1313Socws 1A-rlomd 0.064 1270 a a 1.79 3.556 OB9 29.67 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 13135ocws 0.054 se 1.79 0B9 O 0 0 0 0 0 0 0 1Dc2om - 0370 se OOO 0.00 0 0 0 0 0 0 0 0 iDc2om 0870 se : 000 0.00 0 0 0 0 0 0 0 0 113c2om 0B70 se O00 0.00 0 0 0 0 0 0 0 0 lDc2w 0570 se 1596 4730 0 0, 0 0 0 0 0 0 11Dc2ov 0570 se 1596 36.14 0 0 0 0 0 0 0 0 lDc2w 0570 se 1596 37.73 .0 0• 0 0 0 0 0 0 lDc2w 0.570 se 1596 , 37.73 0 - 0, 0 0 0 0 0 0 13135acws 0.064 sw 1.79 OB9 0 0 0 0 47 39 70 35 10A-m 1.670 sw 0.00 ODO 0 0 0 0 0 0 0 0 1OA-m 1B70 sw 46.76 1598 0 0 0 0 0 0 0 0 10A-v 0ffi0 sw 2296 1521 0 0 0 0 .0 0 0 0 1Dc2om 0B70 sw 000 000 0 0 0 0 0 0 0 0 1Dc2om OB70 sw ODD 0A0 0 0 0 0 0 0 0 0 lDc2w 0570 sw 1596 2029 0 0 0 0 0 0 0 0 iDc2cv 0570 sw 1596 3055 0 0 0 0 8 5 128 244 13B5ocws OD64 nw 1.79 OB9 0 0 0 0 38 38 67 33 lXhtov 0900 rm 2520 49.12 0 0 0 0 0 0 0 0 1Dc2om OZ70 nw 000 000 0 0 0 0 0 0 0 0 10-c2om - 0.870 nw 000. 000 0 0 0. 0 0 0 0 0 lDc2w 0570 nw. 1596 4691 0' 0 '0 0 0 0 0 0 1Dc2ov 0570 nw 1596 4691 0 0 0 0 0 0 0 0 1Dc2ov - OS70 mx 15.96. 4691 0 0 0 -. 0 0 0 0 0 P 12COsw 0.091 - 255 128 0 0 0 0 0 0 0 0 C 16X19-Omd - 0.408 - 159' 1.49 0. ., 0 _ -0 0 .0 _ 0 0 0 F 19C-190scp 0.049 - 0.48 025 25 25 12 6 60 60 - 29 15 F 22A-tpl 0989 - 27.69' 0.00 - 0 0 0 , - 0 0 - 0 . 0 0 F 22A4pI 0989 - 27.69 0.00 0 0 0 0 5 1- 19 0 6 c)AED excursion -1 138 Emelope Iosslgain 12 6 313 466 12 a) IMilhation 0 0 111 32 b) Roomvemllation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 Applienceslother 0 Subtotal Qines 6t3l3) 12 6 423Less 100 external load 0 0 J24%. 0 Less transfer 0 0 0 Redistribution -12 -6 4 2 14 Subtotal 0 0 427 500 15 Duct loads 24% 18% 0 0 18% 103 88 Total room load 0 0 530 588 Air required(cfrn) 0 0 27 32 r alnj damns arprOLrarl biyArvr:A to meet M! requirements of Manua! J 8th Ed. -rk- wrlghesoTt- 2020-May-0510:12.50 A - - Right-Suite®Universal 201919.0.07 RSUCS101 Pagel ...tHAQWATERSONG-LOT#374824WATERSONGWAY.mp Calo=MJB Front Doorfaces:SW wrightsoft Ri'�% 1aqht-J® Worksheet Job: V/YDate: May 1, 2020 BY: QUICK CALCS, INC. 3W ST. LUCIE LN., FL PIERCE, FL 34946 Phone: 7724666799 Fax:772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name POWDER NC 2 2 Exposed wall 18D ft 0 it 3 Room height 9A ft heat/cool 12D it heat/cool 4 Room dimensions 1D x 80D ft 40 x 5.0 It 5 Room area 80.0 1F 20.0 RT Ty Construction number U-value (BtuMF-*F) Or HTM (BtuhM Area M or perimeter (1) Load (Stuh) Area (IFj or pedmeter (It) Load (Btuh) Heal Cool Gross MRS Heal Cool Gross N/P/S Heal Cool 6 11 W 1313-50cws 1OA-v 10B-v 1Aclov 1Aclm 1A41obd IA-rlomd - 13B-5o 1A-rlomd ]3B5ocws 1Dc2om 1Dc2om 1Dc2om 110c2av 10c2ov 1Dc2ov 1Dc2ov 13BSoc%Fs 10i 10A-m 1OA-v ID-c2om 0.064 0820 0.600 0900 02W 1.080 1270 0.064 1270 0.064 0.870 0870 0870 0570 0570 OS70 0570 0064 1870 1.670 0820 0870 ne ne no ne ne ne ne a _e :se as se se se as se se sw sw sw sw sw 1.79 2296 1620 000 0.00 o00 35.56 139 3556 1..79 0.00 0.00 0.00 1596 1596 15.96 1596 1.79 0.00 46.76 2296 000 0.89 1490 25.00 0.00 0.00 0.00. 43.03 089 29.67 0.89 0.00 0.00 0.00 4730 36.14 37.73 37.73 029 000 1598 1521 0A0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 85 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 85 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 152 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 75 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0- 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0_ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 w 1I10c2om 110c2ov 10c2ov 1313-5 v 10-h1ov 1Dc2om 10c2on 0870 0570 0570 OD64 0900 .0870 0870 sw sw sw rrw riw my my 000 1596 1596 -1.79 2520 0.00 000 000 2029 3055 . 029 49.12 0.00 000 0 0 0 85 01 0 0 0 0 0 77 0 0 0 0 0 0 137 0 0 0 0 0 0 68 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Dc2ov 11[1c2ov 1Dc2dv 12C-Osw 0570 0570 0570 0.091 nw rev my - 16% 1596 1596 255 4691 4691 4691 128 8 0 .0 0 0 0 0 0 128 0 0 0 375 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C 16)(190md "0.408 - 159 1A9 0 0 0 0 _ 0 0 0- 0 F 19C-19cscp 0.049 - 0.48 025 9 9 4 2 5 5 2 1 F 22A4p1, 09B9 - 27.69 000 a 0 0 0 0 0 0 0 F 22A-ml 0969 - 27.69 0.00 71 16 442 0 3 0 0 0 61 c)AED excursion 931 0 Envelope loss/gain IBM 614 2 1 12 a) Infiltration b) Roomventilation 222 0 64 0 0 0 0 0 13 Internal gains: Occupant @ 230 0 0 0 0 Appliancestother 0 0 Subtotal Qines6to 13) 1085 677 2 1 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 1 0 -2 -1 14 Subtotal 1081 678 0 0 15 Duclloads 24% 18% 261 119 249'0 18% 0 0 Total room load 1346 797 1 1 0 0 Air required (cfm) 69 44 0 0 Calculatons approved bvACCA to meet al! requirements of Manual J 8th Ed. -: • wrlgl+lsoTt- 2020-May-O 10:12:50 • -^ Right-SuibaOUnlveml201919.0.07RSU08101 Page ...tH\AQWATERSONG.LOTk374824WATERSONGWAY.mp Calc=MJB Front D90rboes:SW F�1 wrightsoftt, R"ght-J0 Worksheet Job: " �T 2 Date: May 1, 2020 BY: QUICK CALLS, INC. 317 ST LUCIE LN, Ff.PIERCE, FL 34946 Phone:772-46M799 Fax:772-066-6796 Email: OUICKC4LCS@AOL.CJM i Room name UNIT2 MASTER BATH 2 E)osed well 1899 It 36D It 3 Room height 9A ft d 9A ft heatbool 4 Roomdimensions 1.0 x 200D ft 5 Room area 1768.0 IF 200.0 IF Ty Construction number U-value (Btuty F) Or HTM (BWW Area M or perimeter (It) Load (stub) Area (ft) or perimeter (tt) Load (BWh) Heat Ccol Gross NIPSS Heat Cool Gross NIPS Heat Cool 6 11 . 13&5ocvas t0A-v loam 1Aclov tAclov lA-rlobd 1A-rlomd 13B-5ocws 1A-riomd 13B-- cw - 1 Dc2om 1Dc2om 1Dc2om 1Dc2ov 1Dc2ov 0.064 0820 0.600 09DO 0900 1.080 .1270 0.064 _ 1270 0.064 0.870 0870 OB70 0570 OB70 -ne ne ne ne no ne no a a se se se se se se 1.79 0.00 000 2520 2520 3024 000 0.00 0.00 1.79 24.36 24.36 2436 ODD 0.00 - 029 0.00 ODO 57.34 57.34 40.18 0.00 0.00 0.00 0.89 43.38 4338 43.38 ODD ODO 263 0 0 24 28 80 0 0 _ 0 ' 630 10 48 20 0 0 132 0 0' 0 0 0 0 0 _ 0 661 5 24 10 0 0 236 6 0 605 693 2419 .0 0 0 988 ` 244 1177 487 0 0 117 0 0 1376 1577 3214 0 0 0 491 434 2097 868' 0 0 132 0 0 24 28 0 0 0 0_ 56 0 0 0 0 0 80 0 0 0 0 0 0 0 0 56 0 0 0 0 0 144 0 0 605 693 0 0 0 _ 0 " - 101 0 0 0 0 0 71 0 0 1376 1577 0 0 0 _ 0 50 0 0 0 0 0 W 1Dc2ov .ID-c2W 1313Sarws 10Ai 10Am 10aw 11Dc2om 0570 0570 0064 IBM lHM 0B20 0870 se se. sw sw sw sw sw ODO 0.00 1.79 46.76 ODO ODO 2436 0.00 000 0.89 4220 ODD ODD 4338 0 0 263 80 0 0 10 0 O. 164 4 0 0 5 0 O 293 3741 0 0 233 0 0_ 146 3376 0 0 416 0 _ O 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 11Dc2om 1Dc2ov 1Dc2ov 13B-5ocws 1A-hiw 1 Dc2om 1Dc2om ONO 0570 0570 0.064 0900 OB70 0870. sw sw sw rw nw rw Ov+ 2436 ODO 0.00 1.79 0.00. 2436 2426, 4338 ODO 0.00 0.8.9 0.00 58.95 58.95 10 0 0 637 0 10 20 5 0 0 607 0 0 0 244 0 0 1088 0 244 487 434 0 0 540 0 589 1179 0 0 0 150 0 0 0 0 0 0 150 0 0 0 0 0 0 270 0 0 0 0 0 0 134 0 0 0 '1Dc2ov 1Dc2ov 1Dc2ov 12C-D w 0.570 0570 0570 0.091 rw my nw - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0. 0 '0 0 .0. 0 0 0 . 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P 'C 16X19-Omd `0.408 - 159 1.49 1758 1758 2787' 2613 _ 200 200 _ 317 297 F F F 19C-19cscp 22A4pl_ 22A4p1 OD49 0.989 OB89 - - - 0.00 .0.00 27.69 0.00 0.00 ODO 0 0 200 0 0 26 0 0 732 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 61 c)AED excursion 1 0 -494 Envelope lossfgain 16698 19465 2129 3112 12 a) Infiltration b) Roomventllatfon 2349 0 674 0 443 0 127 0 13 Intemalgains: Occupants 230 0 0 0 0 Applianceslother 0 0 Subtotal(Iines 6 to 13) 19047 20140 2572 3239 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19047 20140 2572 3239 15 Ductloads 23% 1545 4450 3097 Z3% 15% 601 498 Total room load 23497 23238 3173 3737 Air required (cfm) 1200 1200 162 193 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. i}F wrlQhtmoft- 2020-May-0510:12:50 Rlght-SUIte®Unherrml201919.0.07 RSU08101 Page ...t"QWATERSONG-LOTk374824WATERSONGWAY.mp Cale-MJB Frontl3oorfaws:SW wrightsoft- Right-ga7ht-M Worksheet Job: V/V�r 2 Date: May 1, 2020 By: QUICK CALCS, INC. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email: QUICK(ALCSdAOL.00M 1 Room name TOILET MWIC 2 Exposed wall 4.0 ft 12.0 it 3 Room height 9.4 it heaUcool 10.0 it heatfccol 4 Room dimensions 6.0 x 4.0 ft 1.0 x 83.0 ft 5 Room area 24.0 tF 83.0 tF Ty Construction U-value Or HTM Area M Load Area Load number @WhfiF-°F) (EftuW or perimeter JD (Btuh) or perimeter (f) (Bluh) Heat Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 W 13B-5ocws 1OA7v 0.064 0820 ne ne 1.79 0.00 OA9 0.00 0 .. 0 0, 0 0 0 0 0 0 0 - 0 0 0 0 , 0 0 108-v 0.600 ne ODO 0.00 0 0 0 0 0 0 0 0 1Ac1ov 0900 ne 2520 5734 0 0 0 0 0 0 0 0 11 1Aclov 0900 ne 2520 57.34 0 0 0 0 0 0 0 0 1A-riobd. 1.080 ne 3024 40.18. 0 0 0 0 0 0 0 0 1A-r1omd 1270 ne AA0 0.00 - 0 0 0 0 0, - 0 0 0 W 13BS0cws IA-riomd 0.064 1270 a a 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13B-5ocws 0.064 se -1.79 0.89 0 0 0 _ 0 0 _ 0 _ 0 0 '1Dc2om 0270 se 24.36 43.38 0 0 0 0 9 0' 0 0 113-c2om 0870 se 24.36 43M 0 0 0 0 0 0 0 0 1Dc2om 0870 se 2436 43.38 0 0 0 0 0 0 0 0 1D-c2w 0570 -se OJ]O, 0.00 0 A' 0 0 0 0 0 0 4Dc2cv 0570 se OAO 0.00 0 0 0 0 0 0 0 0 1Dc2ov 0570 se 0.00 OAO 0 0 .0 0 0 a 0 0 IDc2ov - 0570 se 0.00 0.00 -.,. 0 0 0 0 0 0 0 0 W 13B-Socws OD64 sw 1.79 089 0 0 0 0 0 0 0 0 10A-m 1670 sw 46.76 4220 0 0 0 0 0 0 0 0 1OA-m 1.670 sw MOO ODD 0 0 O D O 0 0 0 10A-v 0,320 sw 0.00 DAO O 0 0 0 0 0 0 0 1Dc2om 0870 sw 2436 4338 0 0 0 0 0 0 0 0 1Dc2om 0870 sw 2436 4338 0 0 0 0 0 0 tl 0 1Dc2om 0570 sw 000 OAO 0 0 0 0 0 0 0 0 ID-c2ov 0570 sw 0.00 0.00 0 0 0 0 0 0 0 0 !13B-Socvim OD64 M - 1.79 029 38 28 49 25 120 120 215 107 1A-h1w 0900 my 0.00 OAO 0 0 0 0 0 0 0 0 1 Dc2om '0870 my .2436 5825 10 0 244 589 0 0 0 0 1Dc2orn 0870 rw 2436 5895 -0 0 0 0 0 0 0 0 1 Dc2ov 0570 nw 0.00 0.00 0 0 0 0 0 0 0 0 1Dc2ov '0.570 w 0.00 0.00 0 0 0 0 0 0 0 0 1Dc2ov 0570 nw 0.00 0.00 0 0. 0 0 . .0 0 0 0 P 12C-0sw 0.091 - 0.00 000 0 0 0 0 0 0 0 0 C 16X190md 0.408 - .159 1.49 _ ,24 24 38 36 83 83 132 123 F 19C-19cscp 0.049 - 0.00 0.00 0 0 0 0 0 0 0 0 F 22A4pl_ o9B9 - - OAO 0.00 "a 0 0 0 0 0 0 0 F 22A-tpi 0989 - 27M 0.00 0 0 0 0 0 0 0 0 6 c)AEDexcurslon 151 -30 Envelope loss/gain 331 800 347 200 12 a) Infiltration 49 14 157 45 b) Roomvenfilation 0 0 0 0 13 Internal gains: Occu"ma @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6to 13) 380 815 504 245 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 150 76 14 Subtotal 380 815 654 321 15 Ductloads 23% 15% 89 125 23% 15% 153 49 Total room load 469 940 807 371 Air required(cfm) 24 49 41 19 Calculalons approved byACCA to meet aIl requirements of Manual J 8th Ed. ,c tea- wrighesoit- 2020-May-0510:12:50 . P. ••^-• -- •F -- RightSuite®Universal 2019 %0.07 RSU08101 Page 10 .AH4AQWATER50NG-LOTM374824WATERSONGWAYmp Calc=MJB FrontiDoorfaces:SW F ! wrightsoft• -J® Worksheet Job: 2 Date: May 1, 2020 M 6y: QUICK CALCS, INC. 317 ST. LUCIE I.R. FT. PIERCE, FL 34946 Phone:772-466-6799 Fax:772-465-6796 Email: OUICKCALCS@AOL.ODM 1 Room name WIC WIC 2 3 Bposedwall Room height 0 ft 9A ft heaNcool 6.0 ft 9A it hea tool 4 5 Roomdimensions Room area 8.0 x 6.0 ft 48.0 fP 7.0 x 6.0 ft 42.0 ft Ty Construction U-value Or HTM Area QF) Load Area ( Load number @WhMF-°F) (BtuM or perimeter Q9 (Btuh) or perimeter (f) @tuh) Heal Cool Gross WPIS Heat Cool Gross MPS Heat Cool 6 11 W 13B-5ocxs 1OA7v 10EW 1Ac1w 1Aciw IA-rlobd 1A-Aomd 1313S0cws 1A-riomd 13BSocws iDc2om iDc2om 1Dc2om 1Dc2w 1Dc2w 1Dc2w 1Dc2w 138-5aws 10A-m 1OAm 10P- 1Dc2om 113c2om 1Dc2w 1Dc2w ,1s 1313 1A-h1ov 113c2om 1Dc2om 0.064 0B20 0.600 0900 0900 1.080 1270 D.064 1270 0.064 0,970 0B70 OB70 0570 0570 OEM :0570 OD64 1.670 1.670 0220 0.870 OB70 0570 0.670 0.064. 0.900 0B70 OB70 ne ne ne ne no ne no a a se se se se se se se se sw sw sw sw sw sw sw sw w nw wu w 1.79 ODD ODD 2520 2520 3024 0.00 0.00 0D0 1.79 24.36 2436- 2436 ODO ODO 0.00 ODO 1.79 46.76 ODO 0.00 2436 2436 ODO 0.00 1.79 ODO 2436 2436 OB9 0.00 0.00 57.34 57.34 40.18 0.00 0.00 0.00 Om 4338 4328 4338 0.00 0.00 0.00 ODO on 4220 ODO ODO 4338 4338 ODD 0.00 OB9 0.00 5895' '5895 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 56 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 00 0 0 0 _ 0 56 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 101 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 50 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 IW '-G 1Dc2ov 1Dc2w iDc2w 12C41sw 0.670 0570 0570 OD91 wa nw nw - ODO 0.00 ODD 0.00 0.00 0.00 0.00 0A0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C 16X19-0md OA08 - 159 1A9 48 48 76 71 42 42 67 62 F 19C-19cscp 0.049 - ODO ODO 0 0 0 0 0 0 0 0 -F F 22A4pl 22A-0 0989 0289 - - 0.00 27.69 0.00 ODO 0 0 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 0 6 c)AED excursion -8 -14 Ewelope loss(gain 76 64 168 98 12 a) Infiltration 0 0 74 21 b) Roomve I[Mon 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal Qines 6to 13) 76 64 242 119 Less exlemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 76 64 242 119 15 Duct loads 23% 15% 18 10 23% 15% 56 18 Total mom load 94 73 298 138 Air required(cfm) 5 4 15 7 Cal !!aeons approved byACGA to meet all requirements of Manual J 8th Ed G -F41- wrlsF+e�soie- 2020-May-0510:1250 - Righ4Suite®UnNersal 201919.0,07 RSUD8101 Page 11 ...t"C1WATERSONG-LOT#374824WATERSONGWAY.mp Calc=MJ8 FmntDDorfaoe&SW F� wrightsoft' Right-J® Worksheet Job: UNIT 2 Date: may 1, 2020 By: QUICKCALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-166-6799 Fax:772-4666796 Emil: 0UICKCALCS@AOL.00M 1 Room name M48TER SUITE BEDROOM2 2 Epiosed wall 339 it 13D it 3 4 Room height Room dimensions 9A it heaVcwl 1.0 x 415D 8 9A 8 heaVcool 15.0 x 13D fl 5 Roomarea 415.0 fF 195.0 IF Ty Construction number U-value (Btuh4F-°F) Or HTM Area OF) or perimeter (I) Load (Bhrh) Area (IIO or perimeter (9) Load (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/PIS Heat Cool 6 1313-5ocws 0.064 ne 1.79 0.89 132 52 92 46 0 0 0 0 11 10A-v 10B-v 1Ac1ov 1Aclov IA-r1obd IA-Aomd 0820 0.600 0900 0900 1.080 1270 ne no ne ne ne no ODO ODO 2520 2520 3024 ODO 0.00 0.00 57.34 5734 40.18 0.00 0 0 0 0 80 0 0 0 O 0 0 0 0 0 0 0 2419 0 0 0 0 0 3214 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 13BSocws 0.064 a 0.00 0.00 0 0 0 0 0 0 0 0 1A-r1omd 138Socws 1Dc2om 1Dc2om 1Dc2om 10c2w 1Dc2w 12M 0.064 0270 0870 0870 0570 0570 a 3e se se as se se 0.00 1.79 2436 2436 2436 ODO ODD 0.00 0.89 4338 4338 4338 ODO ODO 0 188 0. 24 0 0 0 0 164 0 12 0 0 0 0 294 0 589 0 0 0 0 146 0 1048 0 0 0 0 122 0 0 20 0 0 0 102 0 0 10 D 0 0 183 0 0 487 0 0 0 91 0 0 868 0 0 1Oc2w 1Dc2w 1311Socws 10A-m 10A-m 10A-v 1D-c2om O,570 0570 OD64 1.670 1.670 0820 0870 se se sw sw sw sw sw ODO 0.00 1.79 46.76 ODO ODO 2436 OAO ODO 089 4220 ODD ODD 4338 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11)c2om 1Dc2w 1Dc2ov 138Sacws 1A-h1w 1Dc2om 1Dc2om 0870 0570 0570 0.064 D900 0870 0870 sw sw sw my my m✓ m+ 2435 ODO 0.00 1.79 0.00 2436 24,36 43.38 O.00 0.00 029 0.00 6825 58.95' 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 0 0 0' 0 0 O 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 1Dc2w 1Dc2w 1Dc2ov 12C41sw 0570 0570 .0570 0.091 m ma mr - ODO 0.00 0,00 OAO OAO 0.00 ODO ODO O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C 16X19-Omd OA08 - 159 1.49 415 415 658 617 195 195 309 290 F 19C-19cscp OD49 - 0.00 ODO 0 0 0 0 0 0 0 0 F 22A4p1 0989- - ODO - 0.00 0 0 0 0 0 0 0 0 F 22A4p1 0289 - 27.69 0.00 1 0 1 0 0 0 0 0 61 c)AEDexcurslon 1 -562 248 Envelope loss/gain 4053 4508 980 1496 12 a) Infiltration 419 120 160 46 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliancestother 0 0 Subtotal Qines 6 to 13) 4472 46M 1140 1542 Less Worrell load 0 O 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4472 4629 1140 1542 15 Dud loads 23% 15% 1045 712 23% 15% 266 237 Total room load 5516 M40 14W 1779 Airrequlred(chn) 2. 276 72 92 Calculations approved byACCA to meet all requirements of Manual J 8th Ed Rlght-Sulte®Unlversa1201g 19.0.07 R8U08101 2020-May0510:12:50page 12 F ...IMP.QWATERSONG.LOT#974824WATERSONGWAY.rup Calc=MJ8 FrontCoorfaces SW wrightsoft- Ri ht-M Worksheet JOb: V��T 2 Date: May 1, 2020 By: QUICKCALCS, INC. 317 ST. LUCIE LN., FL PIERCE, FL 34946 Phone: 772-466-6799 Fax:772-466-6796 Email: OUICKCALCS@AOL.WM 1 Room name HALLWAY STARWAY. 2 Fxposedwall 28.0 It 13D It 3 4 Room height Room dimensions 9A It heat(cool 1.0 x 336.0 ft 9A ft hmVcwl 8D x 13D It 5 Room area 336.0 IF 104.0 IF Ty Construction number U-value (BtuhM'-°F) Or HTM (Bt MF) Area (IF) or perimeter (ft) Load pwh) Area (IF) or perimeter (1) Load @Wh) Heal Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 W 13B5aws 10A-v OD64 0820 ne ne 1.79 ODO 089 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11. 1OBv 1Aclov 1Ac1w OB00 0900 0900 ne ne ne ODO 2520 2520 0.00 57.34 5734 0 0 0 0 0 0 a 0 0 0 0 0 0 0 0 0 0 0 a 0 0 0 0 0 1A-rlobd t.GO no 3024 40.18 0 0 0 0 0 0 0 0 1A-r1omd 1270 no ODO 0.00 0 0 0 0 0 0 0 0 W, 13BSocws 0.064 a 0.00 0.00 0 0 0 0 0 0 0 0 Y-C 1A-rlomd 1270 a 0.00 0.00 0 0 0 0 0 0 0 0 1313Eocws 1 Dc2om _ 0.064 0.870 se se 1.79 24.36 0.89 43.38 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Dc2om 1Dc2om 1Dc2ov 1Dc2w 0.870 0.870 0570 0570 se se se se 2436 2436 ODD 0.00 43.38 4338 ODO ODO 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Dc2ov 05M se 0.00 ODO 0 0 0 0 0 0 0 a 1Dc2ov 13B5ocws 1OA-n 104-m 1a4v 05M OD64 1870 1.670 OB20 se sw sw sw sw ODO 1.79 46.76 ODD ODO ODO OB9 4220 ODO ODD 0 85 40 0 0 0 45 2 0 0 0 8O 1870 0 a 0 40 1688 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Dc2om 0870 sw 2436 4338 0 0 0 0 0 0 0 0 1Dc2om 110c2ov iDc2ov 13B-Socws 0270 0570 0570 0.064. sw sw sw nw 2435 ODO ODO 1.79 433E 0.00 ODO 0.89 0 0 0 179 0 0 0 159 0 0 0 284 0 0 0 141 0 0 0 122 a 0 0 122 0 0 0 219 0 0 _ 0 109 1A-h1ov 10c2om 1 Dc2om 0.900 OB70 0.870 nw my my 0.00 2436 24.36 0.00 5895 5895 0 a 20 0 0 0 0 0 487 0 0 1179 0 0 0 0 0 0 0 0 0 0 0 0 10c2ov 0570 nw 0.00 0.00 0 0 0 0 0 0 0 0 1Dc2ov 1Dc2ov 12C-Osw 0570 0570 OD91 my nw - 0.00 0.00 0.00 0.00 0.00 ODO 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C 16X194hnd OAD8 - 159 1.49 336 336 533 499 104 104 165 155 F 19C-19cscp OD49 - 0.00 0.00 0 0 0 0 0 0 0 0 IF 22A4pl 0989 - ODO 0.00 0 0 0 0 0 0 0 0 F 22A-tpl 0989 - 27B9 0.00 73 6 168 0 0 0 0 0 6 c)AEDexcurston 487 34 Envelope loss(gain 3423 4034 384 230 12 a) IMtitration 345 99 160 46 b) Roomventilabon 0 0 0 0 13 Internal gains: Occupants@ 230 Appliances/other 0 0 0 0 0 0 Subtotal Qines 6 to 13) 3768 4133 544 276 Less exlemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 394 200 4i44 -276 14 Subtotal 4162 4333 0 0 15 Ductloads 23% 15% 972 666 23% 15% 0 0 Total mom load 1 5134 4999 0 0 Air required(cim) 262 258 0 0 Calculations approved byACCA tD meet all requirements of Manual J 8th Ed. '�' wrlghesofC- 2020-May-0510:12.50 Aft • -� _. Right-Suite®Unberse1201919.0.07 RSU08101 Page 13 ..tH1AQWATERSONG-LOTil374824WATERSONGWAYrup Calc=MJ8 FrontDoorfaws:SW I wrightsoft° Ri' ht-J® Worksheet Job: 21 T 2 Date: May 1, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466-6799 Fax: 772466-6796 Email: QUICKC4LCS@AOL.COM 1 Room name BATH WIC 2 Exposed wall 5.a ft 5.0 ft 3 Room height 9A ft heaUcool 9A it heaUcool 4 5 Room dimensions Room area 10D x 5.0 4 50D IF 10.0 x 5.0 ft 50D fF Ty Construction U-value Or HTM Area M Load Area (T) Load number (8luW*F) (bump) or perimeter (ft) (Btuh) or perimeter (1) (Btuh) Heat Cool Gross NiPS Heat Coot Gross N/PS Heat Cool 6 11 W 13BZocws 10A-v 10B-v tActov 1Aclov 1A?1obd %rlomd 13B-5ocws 0.064 0220 0.600 ''0.900 0.900. 1D80 1270 0.064 ne me ne ne ne ne ne a 1.79 ODD ODM 2520 2520 3024 0.00 0.00 0.89 0A0 ODO 57.34 5734 40.18 0.00 0.00 '0 0 , 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 01 0 _ 0 0 -0 -0 0 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 WLC 1A-r1omd 1270 a 0.00 0.00 0 0 0 0 0 0 0 0 13B-5ocwm 1Dc2onn 11Dc2om 1Dc2om. 0.064 0870 0270 0870 se se se se 1.79 24.36 2436 24.36 0.89 4338 4338 4338 47 10 0 ,0 37 5 0 0 66 244 0 0 33 434 0 0 47 0 0 0 - 47 0 0 0 84 0 0 0 42 0 0 0 1Dc2ov 0570 se 0.00 ODO 0 0 0 0 0 0 0 0 1Do2ov 0570 as 0.00 DO0 0 0 0 0 0 D 0 0 1Dc2ov 1D-c2ov - 0570 0570 se se 0.00. 0m 0.00 0A0 0 0_ .0 0 .0 0 0 0 0 0 0 0 0 o a a 1315-5 a 0.064 sw 1.79 089 O 0 0 0 0 0 0 0 10A-m 1b70 sw 46.76 4220 0 0 0 0 0 0 0 0 10A-m 1570 sw 0DO MDO 0 0 0 0 0 0 0 0 10A-v 11)c2om 0820 0870 sw sw 0.00 2436 ODM 4338 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 113-c2om 1D-c2ov 1Dc2ov 13135ocws 0870 0570 0570 OD64 sw sw sw nw 2436 ODO 0.00 139 4338 MOO 0.00 089 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 to-hlov 0-00 mw ODO 0.00 0 0 0 0 0 0 0 0 1Dc2om :0870 ma 2436 58.95 0 a 0 0 - 0 0 0 0 iDc2om 0870 rw 2436 58.95 0 0 0 0 0 0 0 0 1Dc2ov 0570. nw 0.00 0.00 0 0 0 0 0 0 0 0 iDc2ov 0.670 w 0.00 0.00 0 0 0 0 0 0 a 0 iDc2ov. 0570 ma 0.00 0.00 0 0 0 0. 0 .0 0 0 P 12C-Osw OD91 - 0.00 ODO 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 - 159 tA9 - 50 50 79 74 50 50 79 74 F 19C-19csco 0.049 - 0.00 0.00 0 0 0 0 0 0 - 0 0 IF 22A4pl 0289 - ODO: 0.00 _ 0 0 0 0 _ 0 0 0 0 F 22A-tpI 02M - 27,69 OOO 0 0 0 0 0 0 0 0 6 c)AED excursion 134 _14 Envelope lossigain 389 675 164 102 12 a) Infiltration 62 18 fit 18 b) Roomventlation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6to 13) 451 692 225 119 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 451 692 225 119 15 Ductloads 23% 15% 105 105 23% 15% 53 18 Total room load 556 799 278 138 Air required(cfm) 28 41 14 7 r_nim rlatinns annrnvad by ACCA to meet all requirements of Manual _I 8th Fri, ,e -Fk- wrl9tilsoTe� Y•VV•VVV••V VYY•V•VV V•• •v 2020-MaY-0510:1250 . A •- - RightSuite®Universal 201919.0.07 RSU08101 Page 14 ...tHWQWATERSONG-LOTN374824WATERSONGWAYmp Calc=MJB FrontCoorfaoes SW I wrightsoft• Right-M Worksheet Job. V/YIr 2 Date: May 1, 2020 QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:77246G6799 Fax:772466-6796 Email: QUICKCAL(9IDAOL.COM 1 Room name BEDROCM3 BATH 2 Exposed wall 27.0 0 7.0 it 3 Room height 9A 8 heat/oeol 9A it heat/cool 4 Room dimensions 14.0 x 12.0 it 1.0 x 43.0 8 5 Roomarea 168.0 F 43.0 fF Ty Construction U-value Or HTM Ama (if) Load Area QF) Load number (BWh4P-°F) or perimeter (I) mwh) or perimeter (10 (Btuh) Heal Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 W 139-Sows 104-v 0D64 0B20 no ne 1.79 0100 089 ODO 0 0 0 0 0 0 0 0 0 0 0 0 0 a 0 0 1013V 0800 ne ODO 0.00 0 a 0 0 0 0 0 0 1Aclov 0.900 ne 2620 57A 0 a 0 0 0 0 0 0 11 1Aclov 0900 ne 2520 5734 0 0 0 0 0 0 0 0 to-rtobd 1.080 ne 3024 40.18 0 0 0 0 0 0 0 0 1A-r1omd 1270 ne ODO 0.00 0 0 . 0 0 0 0 0.. 0 µY 138S0cws 0.064 a 0.00 0.00 0 0 0 0 0 0 0 0 �G 1A-rlomd 1270 e ODO 0.00 0_ 0 0 0 0 0 0 0 13BSocws 0.054 _ se 1.79 OB9 113 89 _ 159 79 :0 0 0' 0 G 1Dc2om OB70 se 2426 4338 0 0 0 0 0 0 0 0 iDc2om 0870 se 2436 4338 24 12 589 1048 0 0 0 0 1Dc2om 0870 se 2436 4336 a 0 0 a 0 0 D 0 113c2ov OS70 se ODD ODD 0 0 0 0 0 0 0 0 11Dc2ov 0570 se ODO ODO 0 0 0 a a 0 0 0 11Dc2o✓ 05M se 0.00 ODO 0 0 0 0 0 0 0 a 1D-c2ov O.570 se 0.00 ODO 0 0 0 0 0 0 0 0 13B-5ocers OD64 sw 1.79 OB9 132 82 146 73 47 37 67 33 10A-m 1.670 sw 46.76 4220 40 2 1870 1688 0 0 0 0 10A,m 1.670 sw OD0 ODD 0 0 0 0 0 0 0 0 10A-v OB20 sw 0.00 O100 0 0 0 0 0 0 0 0 113c2om 0.870 sw 2436 4338 D 0 0 0 10 5 233 416 1Dc2om OB70 sw 24-46 4338 10 5 244 434 0 0 0 a 1Dc2ov ID-c2ov 0570 0570 sw sw ODD ODD ODO 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 138-5ocws 0.064 rw 139. 029 9 9 17 8 19 19 34 17 1A-h1ov o.90O rw ODO 0.00 0 0 0 0 0 0 0 0 1Dc2om O.870 rw 2436 58,95 0 0 0 0 0 0 0 0 1Dc2om 0870 rw 2436 58,95 0 0 0 0 0 0 a 0 1Dc2ov 0570 na 0.00 0.00 0 0 0 0 0 0 0 0 1Dc2ov 0570 nw 0.00 0.00 0 0 0 0 0 0 0 0 1Dc2ov .0570 rw 0.00 ODO 0 O 0 0 0 0 _ 0 0 P 12C-Osw 0.091 - 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-Omd 0.408 - 159 _ 1.49 168 168 266 250 43 43 68 64 F 19C-19cscp 0.049 - ODO 0.00 0 0 0 0 a a 0 0 F _ 22A4pl a.B89 - 0.00 0.00 0 0 0 0 0 0 0 0 F 22A41 0-%9 - 2789 ODO 98 16 4W 0 28 5 126 0 6 c)AED excursion -145 182 Envelopelossigam 3727 3434 529 712 12 a) Infiltration 332 95 86 25 b) Roomventilation 0 0 0 0 13 Intemalgains: Occupants @ 230 0 o 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 4060 3530 615 737 Less e#emal load 0 0 0 0 Less bansfer 0 0 0 0 Redistribution 0 0 D 0 14 Subtotal 4060 3530 615 737 15 Dud leads 23% 15% 948 543 23% 15% 144 113 Total room load 5008 4072 758 WO Airrequired(chn) 256 2010 39 44 Caln latons approved by ACCA 4-o Teat all reguRementS of INanLal;f Rih Erl, wrlgFxeaotR- y,VV,YYV•,V approved V• •__• • 2020-May�0510:12:50 --- Right-Suite4DUniverea1201919.007 RSU08101 Page 15 ...tH%AQWATERSONG-LOTp374824WATERSONGWAYrup C81c=MJ8 Front Door Mmv SW * wrightsofte Duct System Summary UNIT 1 QUICK CALCS, INC. 317 ST. LUCIE LN.,FF.. PIERCE, FL34946 Phone:772-066-6799 Fax:7724166-6795 Email OUlCKC4LCS@AOL.Oi For: External static pressure Pressurelosses Available static pressure Supply/return available pressure Lowest friction rate Actual air flow Total effective length (TEL) LOT #37 4824 WATERSONG WAY, ST. LUCIE COUNTY, FL Heating 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.163 ln/100ft 1600 cfm 306 ft Supply Branch Detail Table Job: Date: May 1, 2020 By: Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.163 in/100ft 1600 cfm Name Design (131uh) Htg (cfm) Clg (cfm) Design FR Diam Qn) HxW (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH c 588 27 32 0.321 4.0 Ox 0 VIFx 11.0 145.0 st8 BEDROOM4 h 4143 212 158 0.272 8.0 Ox 0 VIFx 19.0 165.0 st8 CABANA h 788 40 8 0.193 5.0 Ox 0 VIFx 64.0 195.0 st11 FLEXROOM h 3863 197 124 0.180 8.0 Ox 0 VIFx 63.0 215.0 st11 FOYER h 2147 110 89 0276 6.0 Ox 0 VIFx 26.0 155.0 13119 FOYER -A h 2147 110 89 0.329 6.0 Ox 0 MR 17.0 135.0 st9 GREATROOM c 2993 149 164 0205 7.0 Ox 0 VIFx 49.3 195.0 st7 GRFATROOM-A c 2993 149 164 0.207 7.0 Ox 0 VIFx 46.8 195.0 st7 GREATROOM-B c 2993 149 164 0.234 7.0 Ox 0 VIFx 39.0 175.0 st7 GREATROOM-C c 2993 149 164 0.235 7.0 Ox 0 VIFx 38.0 175.0 st7 KITCHEN c 1699 25 93 0.272 6.0 Ox 0 VIFx 29.0 155.0 st7 KITCHEN -A c 1699 25 93 0.282 6.0 Ox 0 VIFx 22.0 155.0 st7 LAUND. h 1704 87 47 0.163 4.0 Ox 0 VIFx 71.0 235.0 st11 LAUNDRY c 992 32 54 0.251 5.0 Ox 0 VIFx 24.0 175.0 st8 POWDER h 1346 69 44 0.415 5.0 Ox 0 VIFx 5.6 115.0 st2 STAIRWAY c 2018 71 111 1 0.410 7.0 Ox 0 VIFx 1 7.0 1 115.0 1 st1 wrightsoft' t RghtSuiteOUnive=1201919.0.07 RSU08101 ECA...i"QWATERSONG-LOT#374824WATERSONGWAY.mp Calo=MJB Front Doorfamv. SW 2020-May-0510:12.52 Page 1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st9 PeakAVF 544 357 0.163 693 12.0 0 x 0 VinlFbr st3 st10 PeakAVF 325 179 0.163 596 10.0 0 x 0 VnlFtK SO st11 PeakAVF 325 179 0,163 596 10.0 0 x 0 VinlFtx st10 st3 PeakAVF 544 357 0.163 693 12.0 0 x 0 VinlFbc s12 PeakAVF 339 289 0251 768 9.0 0 x 0 VinlFbc st8 PeakAVF 271 245 0251 613 9.0 0 x 0 VinlFhc st2 st1 PeakAVF 716 954 0.205 892 14.0 0 x 0 V'mlFbc st7 PeakAVF 645 843 0.205 789 14.0 0 x 0 VinlFIx st6 st6 PeakAVF 645 843 1 0.205 789 14.0 0 x 0 VinlF6c st1 Return Branch Detail Table Name Grille Size (in) i Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk W Ox 0 1600 1600 0 0 0 0 Ox 0 VIFx wrightsoft• 2020-May-0510:1252 ,,,,...,e.,.„ Rl9ht-Sulte®UnNersa1201919,0.07 RSU0910t Paget ..tKAG1WATERSONG.LOT#374824WATERSONGWAV.rup G91o=MJ8 FrontOoorfaeea:SW + wrightsoft® Duct System Summary UNIT 2 QUICK CALCS, INC. 317STLUGELN.,Fr..PERCE,FL34946Fhone:772466-6799 Fa 772.466-6796 Emil: OUIGKGALCS@AOL.00M For: External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) LOT #37 4824 WATERSONG WAY, ST. LUCIE COUNTY, FL Heating 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.161 in/100ft 1200 cfm 310 It Job: Date: May 1, 2020 By: Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.161 in/100ft 1200 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Dud Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 c 799 28 41 0.370 4.0 Ox 0 VIFx 15.1 120.0 st4 BATH c 850 39 44 0.345 4.0 Ox 0 VIFx 10.0 135.0 st5 BEDROOM c 1779 72 92 0.321 7.0 Ox 0 VIFx 16.0 140.0 st4 BEOROOM3 h 5008 256 210 0.298 8.0 Ox 0 VIFx 13.0 155.0 sty HALLWAY h 2499 131 129 0 0 Ox 0 ShMt 0 0 HALLWAY -A h 2567 131 129 0.255 6.0 Ox 0 ShMt 16.0 180.0 st4 Mwlc h 807 41 19 0.208 4.0 Ox 0 VIFx 40.0 200.0 st4 MASTER BATH c 3737 162 193 0.161 6.0 Ox 0 VIFx 50.0 260.0 st4 MASTERSUITE h 2758 141 138 0.164 7.0 Ox 0 VIFx 44.6 260.0 st4 MASTERSUITE-A h 2758 141 138 0.198 7.0 Ox 0 VIFx 32.0 220.0 st4 TOILET c 940 24 49 0.175 4.0 Ox 0 VIFx 46.0 240.0 st4 we h 94 5 4 0.246 4.0 Ox 0 VIFx 23.0 180.0 st4 WIC2 h 298 15 7 0.266 4.0 Ox 0 VIFx 27.8 160.0 st4 WIC3 h 278 14 7 1 0.336 4.0 Ox 0 VIFx 13.6 135.0 st5 Trunk Htg Clg Design Veloc Diam H x W Dud Name Type (cfm) (dm) FIR i (fpm) (in) (in) Material Trunk st4 PeakAVF 760 810 0.161 757 14.0 0 x 0 VinlFlx st5 PeakAVF 309 261 0.298 699 9.0 0 x 0 VinlF6c wrightsoft" 2020-May-0510:12:52 ti ..ry..,� ..��..�.,.�..,.„ RlghtSulte®Unimml201919.0,07RSU08i01 rCA Page 3 /R. ...tHMQWATERSONG•LOT#374824 WATERSONG WAYrup Calo=MJB Front Doorfaces:SW Return Branch Detail Table Name Grille Size (n) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) StudlJoist Opening (n) Duct Mat Trunk rb2 Ox 0 1200 1200 0 0 0 0 Ox 0 VIFx -F�- wrightsoft• 2020-May0510:1252 .�....,_...., RlghtSulte®UnNeml201919.0.07RSW8101 Page CA ...tHWQWATERSONG•LOT#374824WATERSONGWAV.mp Colo=MJ8 FmntDowfece9:SW