PRODUCT EVALUATION
(FOR HVHZ APPROVED PRODUCT)
I z s�;
PRODUCT: DM CLASS 500 26 GA. GALVALUME 5V CRIMP 24"WID
ROOF PANEL (FLPA#27499.17) JUN I
MANUFACTURER: DYNAMIC METALS, LLC ST. Lucie County; Permitting
340 PIKE ROAD
WEST PALM BEACH, FL 33411
To all concerned,
The DM Class 500 Series 26 Ga. Galvalume 5V Crimp 24"Wide Roof Panel, manufactured by Dynamic
Metals LLC, is a non-structural galvalume coated Fluropon painted steel roof panel (50 ksi min) that meets the
requirements of Sections 1507.4 and 1518.9 of the 6th Edition (2017) Florida Building Code. The panel has been
tested per TAS 100 and TAS 125 by Intertek with results shown in test reports G3443.38-450-44 and H2686.02-
450-44, and per TAS 110 by PRI Construction Materials Technologies, with results shown in test reports VLS-004-
02-01 and VLS-005-02-01.
Technical Documentation:
1. Drawing "5VS-HZ"dated 8115119, signed and sealed by Scott Wolters, PE.
2. Test Reports listed above by Architectural Testing, Inc.signed and sealed by Vinu Abraham, PE, and
by PRI Construction Materials Technologies, signed and sealed by Zachary R Priest, PE.
3. Supplemental Calculations to support"5VS-HZ"drawing, signed and sealed by Scott Wolters, PE.
I have reviewed this submittal per the requirements of FAC Product Approval Rule Chapter 61 G20-3.005
(4). Based on the limitations listed below and those provided in the documents above, this product meets all the
requirements of the 6th Edition (2017) Florida Building Code generally, and chapter 15 specifically, including the
HVHZ provisions.
Limitations: This panel is approved for use inside and outside of the HVHZ.
Overall Limitations: Maximum Panel Width: 24" (nominal)
Fastener Spacing across panel: 12" (at Overlaps&Center Rib)
Min. Slope: HVHZ: 2"112"
Non-HVHZ: %2'112" (with Lap Sealant)
3'712" (no Lap Sealant)
5FFCIALIZIN6 IN IMPACT F,F515MNf CUKAINWA15,%O[1? FpONf5, &WIM70W5
s
Field Perimeter&Corner
Installation Installation
Max. Design Pressure: -117.75 psf -206 psf
Fastener Spacing: 4" From Ends, 16" Max. O.C. 4" From Ends, 8" Max. O.C.
Min Panel Fasteners: #10x1 %"HiLo HWH Screw #10x1 '/2'HiLo HWH Screw
with Weather-seal Washer with Weather-seal Washer
Fire Barrier: Where required by code, install an approved fire barrier. Refer to a current
fire directory listing for fire ratings of this roofing system assembly as well
as the location of the fire barrier within the assembly. (See note#2 below)
Note: Outside of the HVHZ, 1" round plastic caps may be used to prevent
galvanic reactions.
Underlayment: Minimum ASTM D 226 Type II with 4"overlaps and 6"end-laps, anchored
with 12 Ga. x 1 '/"galvanized roof nails with 32 Ga.Tin caps spaced 6"
O.C. in rows at the perimeter, at overlaps, and two intermediate rows
staggered and spaced 12"O.C.
(or)
Any underlayment with a valid FLPA or Miami-Dade NOA
Note: Outside of the HVHZ, 1"round plastic caps may be used to prevent
galvanic reactions.
Minimum Substrate: %' (15/32"min)4-ply CDX Plywood, nailed to 2x rafters spaced 24"max.
O.C.with 8d ring-shank nails spaced 4"O.C.
Other Limitations: 1. Roof slope must meet requirements of FBC Sections 1507.4.2 or
1515.2.
2. Fire classification is not a part of this evaluation. Refer to a current
Approved Roofing Materials Directory for fire ratings of this product.
3. Design of substrate is by others and is not a part of this evaluation.
4. Rational analysis, provided by a Florida licensed Architect/Engineer
per FAS 61 G20.3.005(e), may be used for project specific approval by
the local authorities having jurisdiction.
5. All panels shall be permanently labeled with the manfacturer's name
and/or logo, and the following statement, "Dynamic Metals
FL#27499.17, DM Class 500".
SPECIALIZING IN IMPACT P�515TANf CUPfAINWA15,5f0PZFFFONf5, & WINbOW5
Panel Forming: Those 0an6l.8 may be jQ.bs.ite roll'formed.with the.fQllbwing.Dynamid'Metals.machinos, per
approval of 3rd party QA.provider,toAhe dimensions.shown on Drawing- HZ
SSQ-6800617 SSQ75150216, SM6810017
580,6690517 qM456061 5 M-8681 11-8
5 NO
, 4400718 5VU36051,6 VU521'218-
Re-Roofing: The DM'-GIas8,'50Q Series 2.616a..Oal-val'ume5VCrimp--2 4"'.Wi deRoof.Pahell
may.be'i,.st;alted,,overasingi.e'l.layer.of-oxig.tiog,..gsphalt.ghi'n,gles,provide:the exigtiogiroof
meets the requirements of Section 1521 (HVHZ)or Section 15:1'`1 (Ovtside,of,HVH'Z.)-ofthe
Florida Building Code.
If yod have any queslions.or need more information.conceming this;approval please contact me.
Thank you,
W064-N,
6Z354
t
c6tftt - Q
CA.Ors;
FLPE#, 623.54"
S-,rATE OF --t
AUCJJ�' 71119"
0
5.
0.
IN
P\ WNW"
�l
CRIMP 24",VVIDE.
m
\�fj'
ON
OA
WM
i
_ Fafil .41
s�is�s
(k`�Ql�X•Ft�td sSKlkL"�.4,"S.'.`tl�lA; pryN
3 MY �i4'VOcI �K1Sf
^ Ti
_ .
�C4'�"Y.,<,,u..�:2�JQI'� � �. ?�*... �G'rs, S"a'�. �.�,�.�F..''.�� ...-��d'��a' ^"�"�..F�€a�""°'2 •ti.� a`etk' �` �'' Ns
4
$lopt. -
„2'�`r�tldX�ihElRt;{¢Bt�OVCPd�B �wr4� ?
"a�u
„ t
patte��ptofteY ���d
• � C