BLOWER DOOR& DUCTLEAKAGE TESTING
TESTINGftADJUSTINGa-BALANCING
TESTING, ADJUSTING LAN I N REPORT
for
DULL/VAN CONY rRUfflON COMPANY
One Planet
7m510 iUvf Highway I N
Port It Lucie, FL 34 952
June 2020
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
r
.10
{
{
Enrtifled
t i 4mmomftmo &W %*pub-"
FAO 6
gmq� % S
I
Pro -Duct Services, ! 915 Rio Vista Rd, Fort Pierce, FL 3494 9
772.528.2076 pro-ductservicesfl(dgmad. cam
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEA KAOETESTINO
TESTING -ADJUSTING -BALANCING
Pro -Duct Services is a National Balancing Council (NBC') certified firm, through
the National Comfort Institute, NCI. The goal of the NBC certified technicians is to
45
VMrh with the design professionals, building owners and other tradesmen to
maximum systemperformanceon all environmentalachieve systems.
Due to the complexity of todayI s HVAC systems and the unique demands of struc-
ture occupants,, having a qualified, certified Testing -Adjusting -Balancing (TAB)
company balance these systems has now become more critical than it has ever
been. NBC certified firms are able to achieve total system balance better than
any other organization worldwide.
Worizing in partnership with the other trades involved in your project is key to
overall project success. Pro -Duct Services will worncloseiv with all involved to en-
0
sure project schedules are met. By utill
zing different pre- balance cheecchlists with
the other trades,, such as sheet metal, pipe fitte
cess can be achieved more reliably and timely.
rs, HVAC and controls, project sucmm
NBC Procedural Standards is trey to achieving the design intent of today'
sophisticated buildings. Understanding systems, their installation, them service
maintenance requirements and procedures,, and the manufacturer's start-up r&w
helps in achieving system total balance for today's structures. Our technical
testing and veroficiverification,coupled with repeat readings, ensure system functionality.
With Pro -Duct Services you can be sure that our testing and ven"ficat6ion process
offers you the best value in the Testing, Adjusting, &Balancing industry.
0
Pro -Duct Services. 1915 Rio Vista Rd, Fort Pierce, FL 34949
772,528,2076 pro-ductservicesfl(&','gmaii.com
Evergreen Tel
d*■
SERVICES
BLOW ER 0 OCR & DUCT LE AK AGE TEST ING
iESTING-ADJUSTING-BALANCING
TEST & BALANCE INSTRUMENTS
emetry Capture Hood 15D0.
Range: 1UU— L5UU UtWl
Accuracy4
:
cal*16ration:
+/1w3%
May 1712019
Evergreen Telemetry Capture Hood 8D=14016
Range: 15-200 CFM
Accuracy:
Calibration:
Evergreen Pressure/V
Range:
Accuracy,.
Calibration:
+/- 3%
May 29, 2019
locelty/Flow Sensing Module -Model SwPVFffiw1V0
1.2, 14-32 inches HG 32* -158° F
+Iamb 3%
June 5, 2019
Evergreen Wrist Reporter WR=401
Pro -Duct Services Technician:
Michael Faurot
Certified NCI Contractor/ Supervisor/Technician
NCI Commercial Certification IQ: 1942"3
—Equipment re -calibration is performed as required by testing guidelines. —
pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl'dgmadxom
A
f
f '
+ � r
IL
- � ' • JIL
wl
J
y -"
r ;AL I L�1_
r
-Al 4Pit
{
..'ll f r � 4 4
• � Y
jr
r� b
Y ors ri �r+v�"�� W h
Y
I ,
M1(7F1A1K1j FA
Has successfully completed the required training and passed
the written exam by the
National III[ rt IRS I Inc.
to perform HVAC commercial system bai&nC!rvg up 10 zu sons
according to NCI practical standards and procedures
Cenified Since
may 9.:019
as adrnnhtned and recognted by
qm.�W� wo
7,
f
■411if
Cd
-1-ow
Imi
Rob F al Pi es Kkmnt
f
)Ir �.� 4AIJ i
41.6 *� ■
4L i
F
4
PrOwDucl Services, l9I5 Rio Vata Rc4 Fi)rl Pierce. FL 34IN9
772.528. ?076 pro-ductservic•esf �d dgmad. c�c�m
PRO -DUCT
SERVICES
BLOWER DOOR & DUCTLEAKAGE TESTINO
TESTING-ADJUSTING-BALANCING
AIRO TLET CHARACTERIZATION
for
Sullivan Construction Company
One Planet 7510 US Hwy I N Port St Lucie, FL
AIR HANDLER 1--East fide
FIN�u
Nnmb*r �� �� D�tl�w C�M
CAM
1 South Lobby CDP 24 x 24 350 356
2 Center Lobby CDP 24 x 24 350 331
3 North Lobby CDP 24 x 24 350 337
4 Restroom Lobby CDP 24 x 24 100 101
5 Restroom West CD 12 x 12 65 57
6 Restroom fast CD 12 x 12 65 61
7 Break Room CDP 24 x 24 200 198
8 Office Confer CDP 24 x 24 150 138
9 Office Main CDP 24 x 24 150 146
Total 1725
Mechanical components cooling, working as designed and match
COMMENTS plan requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772-528.2076 pr(Yductsenlicesfl+dgmaii.com
PRO-DUCT
SERVICES
BLOWER DOOR & DUCT LEAKAGE TESTINO
TESTING -ADJUSTING -BALANCING
AlR OUTLET CHARACTERIZATION
for
Sullivan Construction Company
One Planet 7.S1 US Hwy 1 N. Port St Lucie, FL
AIR HANDLER 2—West Side
Nmmb*t
North Waiting Area
T1fr.
CDP
24 x 24
cirm
350
FINAL
C!M
341
1
2
South Waiting Area
COP
24 x 24
350
343
3
Main Area
CDP
24 x 24
350
338
4
West Office
CD
12 x 12
125
131
Total
1153
Mechanical components cooling, working as designed and match
COMMEPffS plan requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NO STANDARDS AND PROCEDURES +++
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-duclservicesft'a',igmaiJ.cam
r
v
#-0
.op
SERVICES
BLOWERDOOR& DUCT LEAKAGE TESTING
M11 NGoADJ USTI N G-BA NCING
TESTING, ADJUSTING, ALAN IN WARRANTY
for
Suilliovan Construction Company �
One Planet, 751 S Highway I N Port St Lucie, FL
All Testing, Adjusting, &Balancing performed on this project by Pro -Duct Services is under
warranty for a period of One Year from the date of completion of the Test & Balance, unless
otherwise noted. Warranty will be considered null and void if another TAB company is
brought in to evaluate thepro)ed without notifying Pro -Duct Services to be present at the
time of the additional testing.
Date of TAB Testing: tune 22, 2020 Warranty Expiration Date: lune30
.1 2021
lro-Duct Services Authorized Signature:
rwDud Services Technician:
1
Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19429-03
BPI Certification ID:0
5059122
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
I
E� 7i!fd
� �.% W
a Jr
L L:w
MPM s. % . J
�! �-" M, ��- t' - �0
Pro -Duct Services, 1915 Rio Vista R4 Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl(a;gmadxom
JIL
BLOWERDOOR& UUCT LEAKAGE TESTINO
TESTING -ADJUSTING -BALANCING
Pro -Duct Services. 1915 Rio Vis)
772.528.2076 pro -ducts
'a Rd. Fort Pierre, FL 34949
erviees, f l(� gmail. com