HomeMy WebLinkAboutElectrical Conduits plansBUCHANAN P.E. CONSULTING, INC. ELECTRICAL mMECUANICAL xPLUMBING ■STRUCTURAL E- Al 677 Jr N E- E- %Z I iV Cam' 6191 W. Atlantic Blvd. Suite #2 Margate FL 33063 Ph.(954)590-3300 Fax (954) 590-2232 Cell: (954)292-4988 February 20,2017 To: City of Fort Pierce Re: 121 N Jenkins Road Fort Pierce, FL Subject: Electrical Conduits The engineered plans do not call for above or below ground placement of electrical conduit. The contractor has the option to decide as long as they follow all applicable codes. All above ground wiring to be in EMT conduits, but underground wiring can be in PVC except where it is required by code, see below. On page E-4 a reference to section 514 (motor fuel dispensing facilities) underground wiring below is the code from NEC-2011: 514.8 Underground Wiring. Underground wiring shall be installed in threaded rigid metal conduit or threaded steel intermediate metal conduit. Any portion of electrical wiring that is below the surface of a Class I, Division 1, or a Class I, Division 2, location [as classified in Table 514.3(B)(1) and Table 514.3(B)(2)] shall be sealed within 3.05 in (10 ft) of the point of emergence above grade. Except for listed explosion proof reducers at the conduit seal, there shall be no union, coupling, box, or fitting between the conduit seal and the point of emergence above grade. Refer to Table 300.5. If I can be any further assistance please don't hesitate to contact me. Buchanan P.E. Consulting, Inc. ,,%4iksN BUC)Z#,, �\oElys• • 8 Y. T < E OF • ��, '.,�O.NAL O R t oNG�aw.� F E B 2 0 2011 E Sincerely, Raja Buchanan P.E.