HomeMy WebLinkAboutTruss=LIFE SAFETY WARNING
HIP CARRIER LOCATED AS DIMENSIONED ON LAYOUT
This symbol identifies Life Safety Warnings that
should be read and given special attention to all
persons installing trusses.
SPACING NOTE
All trusses are to be set 2'-0" on
center except as noted.
MULTIPLE PLY TRUSSES MUST BE FASTENED
TOGETHER PER ENGINEERING BEFORE
SETTING. REFER TO ENGINEERING DRAWING
- TO DETERMINE IF MULTIPLE PLY.
Z—!\
_ DON'T LIFT TRUSSES
WITH SPANS LONGER THAN
30' BY THE PEAK.
CONSULT BCSI
30' Sp n or less ��
Spre Ear pan
Bar f
IfI
60 degrees
or less
do
Tag fine � 112pPmx —.0
20 to
Tag line �Iz a Sm. sessismill
REFER TO SCSI
Truss must be set this way N crane is used.
Truss is an example, your truss may not match.
Insist crane operator sets truss this way.
REFER TO BCSI
Truss must be set this way I crane is used.
Truss is an example, your truss may not match.
Insist pane operator sets truss this way.
All load bearing walls, headers,
beams, & lintels must be in place
at indicated height before trusses
are installed.
AIR HANDLER NOTE
Unless noted elsewhere on this layout, these trusses are not
designed for air handlers in the roof or for any other A/C
requirements. This may be in conflict with building code and A/C
Design requirements. Consult with Building Department and A/C
Contractor.
't WARNING !
The size of these trusses makes it necessary that they e set by a profeesional builder
familiar with and experienced in the problems and dangers of setting large span trusses.
The builder and erector should consult with an engineer licensed in Florida specializing
in wood roof trusses about the safe erection of these trusses. The engineer should be at
the job site when trusses are erected to provide supervision and advice.
SEAT PLATES BY CHAMBERS TRUSS
Hatch Legend
ATTIC STORAGE
CEILING @ 111- 211
BEARING @ 101- 611
REPRESENTS A HANGER
HANGER SCHEDULE
USE
CARRIED
TRUSS
HUS26 FOR 2X4, SUH46 FOR 4X2 EXCEPT AS SHOWN
CARRYING HANGER ID FASTENER FOR FASTENER FOR
TRUSS CARRIED TRUSS CARRYING TRUSS
G RB
G RR
THD26-2 (12) 10d nails (18) 16d nails
GRB
GRH
THD26-2 (12) 10d nails (18) 16d nails
GRA
GRL
THDH26-3 (8) 16d nails (20) 16d nails
*Please refer to Standard Engineering package for general instuction on installing hangers
10d=0.148" x 3" 16d=0.162" x 3 1/2"
�tARRANGE WITH CRANE OPERATOR IN ADVANCE FOR A SPREADER BAR OF 31' - 36' IN LENGTH!!
!`_ Do not stand on trusses until they are braced per BCSI & properly nailed to straps and hangers !!
NOTES:
*DRAWN FROM INCOMPLETE PLANS,
PLEASE VERIFY ALL CONDITIONS SHOWN ON THIS LAYOUT.
*ENTRY BEAMS BY OTHERS BEARING AT 14-- 4".
*MASTER BATH COFFER CLG NOT POSSIBLE.
*COFFER CEILINGS ADJUSTED FOR TRUSS EFFICIENCY.
IMPORTANT NOTE
IT IS THE RESPONSIBILITY OF THE PERSON SIGNING
THIS LAYOUT TO VERIFY THAT THE ROOF
PITCH, HEEL CONDITIONS, OVERHANGS, TRUSS SPANS,
AND OTHER CONDITIONS SHOWN IN THIS LAYOUT
ARE CORRECT, MAY DEVIATE FROM PLANS.
TRUSSES WILL BE BUILT PER THE LAYOUT ONLY.
37-05-00 19-07-00
r
r
r
r-
Q
I
0
0
0
J7
�3
J5
P�
o
a I<
a
'.a
'.a
'a
'a
a
,a
'a
'a
a
a
I
y
m
K
J
I
3-PLY
}
I
O♦
r
H
MV8
zz'/,
zzz
zzz
zzz,z
zzzzizz--zz
zz'
zzi
zzz
;Y/
t2zz
zzz
zzz
yx�
zz
',zzz,
N
,'/,
,�
z
�,ZX
2zz'zzz
,,
,z
',zz'.zz
,Y :111
zz
,,,
zz'.zzz
4413-03-11
zzz
,,,
zzz'.;zz'zz2
-
z'
zzz:zr,z'.zzzzzz
,,,,,,.
zzz'zz2'zzz
, , ,
Y'
z��cs z'
,, ,, ,
-
zzz
,,,
, , ,
zzz
z:zz
, ;„
z:zz
,',
,
MV6
;. o
MV4
MV2
P
���
` �O
�
MV211
I.
,zzz
,zzz
7-00-00
z
oo. o
2-oa-oo
z-oo-oo
�.16-00-00
.
9
`�
�O♦
'.12 OS 0
�J
:
Ova
0-00 t
11,14
7-00-00
5-00-00
V8
B 02-06
izazzi:i
z zzz
0
o
V,2
'I
Giziiz
iz
,
vc
1
MV4.
I
o
z z'
z z z
z z zz
z z
vB
MV6.
i
om
MV4
VA
MV8
11
3-PLY
E
Gv� .6
0
R
j
o
0
o
-
/ / / / / I/
ST RR/ GE
✓O
6-01-00
�0
e
4
0
0
GR11 E
K✓g
-
6-02-00
o
0
"
IQ
o
0
0
2-07-05 6-05-06
2-07-05
JS
J
2-04-00
6-01-00
2-04-00
25-11-00
ik
20-04-00
57.00-00
CORNDER JACKS
ARE NOT BEVELED.
SEE STANDARD
ENGINEERING.
O.C. CO5 LI' I
CORNERJACKS
JACKS
ONLY
CORNER DETAIL
OVERHANGS NOT SHOWN FOR CLARITY
PLUMB CUT END
2X4 TOP CHORD
WALL HEIGHT 10'-6" 12
END DETAIL: TYPICAL 5rr
4-01
0
1-02-00
PLUMB CUT END
2X4 TOP CHORD 12
BEAM HEIGHT 14'-4" 5f12
END DETAIL: (A)
4-01
14-N-00
0
to
PLUMB CUT END
2X4 TOP CHORD
WALL HEIGHT 10'-6" 12
END DETAIL: (B) 5r--
4-01 8-00
fc6
1- 2
2-08-00
fir I
PLUMB CUT END
2X4 TOP CHORD
WALL HEIGHT 10'-6"
END DETAIL: (C)
4-01
8-00
0
1- 2-00 m
2-08-00
SECTION BEHIND ENTRY N.T.S.
U
(00
10'- 6' BEARING
FABRICATION AGREEMENT
TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED & RETURNED
he undersigned acknowledges and agrees: -
1. Trusses will be made in strict accordance with this truss placement diagram layout, which is the sole authority for
etermining successful fabrication of the trusses.
2. All dimensions in this layout have been verified by the undersigned.
3. Unless written notice is provided by certified mail to Chambers Truss within ten (10) days of delivery the
ndersigned agrees that no backcharges will be allowed. In the event such written notice is furnished Chambers Truss
hall have three (3) business days in which to begin repairs required, or to substitute other trusses, at Chambers option.
Rer 10 days of delivery remedy will be according to Florida statute 558.
4. The undersigned acknowledges receipt of "BCSI" summary sheet by TPI & WTCA
5. Delivery is to job site. It is the buyer's responsibility to make the job site suitable for delivery. Chambers Truss has
he sole authority to determine the suitability of the job site or a portion of the job site for delivery. Chambers Truss will
e responsible for dump delivery only. The buyer is responsible for additional delivery expenses if Chambers Truss has
o redeliver because job site is not prepared for delivery or buyer is not prepared for delivery of trusses. Buyer is
esponsible to Chambers Truss for towing costs due to site conditions.
6. Price as shown in paragraph 7 below is subject to change if any changes are made in this layout. A $50 per hour
ee for revisions may be charged by Chambers Truss.
7. This is a PURCHASE ORDER to Chambers Truss of the sum agreed to, or if no agreement a reasonable price.
nvoice will be made on delivery and paid within terms of net on delivery. Invoice may be made at scheduled date of
Slivery if buyer cannot accept delivery of fabricated trusses. The undersigned agrees to pay Chambers Truss
easonable attorneys fee for collections in event of payment not timely made. 1-112 % per month service charge will be
added for all sums not paid within terms.
8. Signature or initials anywhere on this sheet constitutes agreement to all terms herein.
9. In consideration of Chambers Truss extending credit for this material the undersigned unconditionally guarantees
ayment when due of any and all indebtedness owed to Chambers Truss by any entity receiving material and the
ndersigned agrees to pay such indebtedness including attorneys fees, if default in payment far material be made by the
ecipient.
10. In the event of any litigation concerning this agreement, the items furnished hereunder or payments referred to
erein, the parties agree that the sole venue for any such action will be Saint Lucie County, Florida.
11. Design responsibilities are per IDNational Standard And Recommended Guidelines On Responsibilities For
Dnstruction Using Metal Plate Connected Wood Trusses ANSIrrPIMITCA 4 - 2002M
12. Warranty is per Chambers Truss Warranty attached.
DATED__
IGNED___
OR_____- TITLE
A spreader bar may be required per "BCSI" to prevent injury 8 damage.
Multiple ply trusses must be fastened together per engineering before they are
set, failure to do so can result in roof collapse.
Temporary and permanent bracing are required and can save life and property
and is the responsibility of the truss erector.
..-4T 1
Study the contents of the information packet included on delivery before
setting trusses.
Trusses must be set and braced per design to prevent injury & damage.
Trusses must be set plumb and square
Do not set bunks or stack of plywood, roofing material or any other
concentrated loads on trusses, this can cause collapse.
DO NOT INSTALL TRUSSES USING THIS
USE PLAN DELIVERED WITH TRUSSES TO SET TRUSSES
LOAOINGIDESIGN CRITERIA REDUCIBLE
PER CODE SUCH AS SEC 1604.6A
DESIGN CRITERIA
County
Saint Lucie County
Building Department
- Saint Lucie County
Wind Design Criteria
ASIDE 2010
Wind Design Method
MWFRS(Directional)/C-C hybrid Wind ASCE 7-10
Roofing Material
Shingle or Shake
Loading in PSF
Roof R.D.L. Floor
Top Chord Live
20 0
Top Chord Dead
7 4.2 0
Bottom Chord Live
`10-Non Conccurent 0
Bottom Chord Dead
10 3 0 -
Total Load
47 7.2 0
Duration Factor
1.25 0
Wind Speed
170mph
Top Chord C.B.
Sheathing by builder
Bottom Chord C.B.
Sheathing by builder
Highest Mean Height
15,
Building Type
Enclosed
Building Category
ll: Non Restrictive
Exposure Category
C>Open Terrain with scattered obstructions
Miles from Ocean
5
Conforms to Florida Building Code 2017
R.D.L.=Restraining Dead Load
C.B.=Continuous Bracing
Verify DESIGN CRITERIA shown above with the
building department and your
engineer.
Design Criteria is the responsibility of the
Building Designer andfor Engineer of Record
Chambers Truss Inc. Drawing Name: 76703
SCALE: 1 /4" = 1 —0"
161 total trusses, 59 unique designs
Designer: BLW Reviewed by:
Date: 04/09/20 Revised 05/06/20
FOR
Fat Robasson
DESCRIPTION:
PHILIPPE
Page 1 of 1 CUSTOMER INITIALS EACH PAGE
76703
1
T20150968
5x8 = 3x4 II 3.4 = 5.8 =
5 28 6 29 7 30 8
7x14 MT18H8 - 3.4 = 16 15 14 12
5.8 - 7.8 = 3x4 = 4,6 -
3.12 3x4 3x4
4.00 12
FY'1r.SR•iJO:
4
3x5 =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) Ode6
L/d
PLATES
GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 1.00
Vert(LL)
-0.42 18-19 >999
360
MT20
244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.77
V ' ILN,
-0.89 18-19 >482
240
MT18HS
2441190
BCLL 0.0
Rep Stress Incr
YES
WB 0.88
Hom(CT)
0.34 10 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Wind(LL)
0.62 18-19 -689
240
Weight: 196 lb
FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied.
BOT CHORD 2x4 SP M 30
`Except`
BOT CHORD
Rigid ceiling directly
applied
or 3-8-2 oc bracing.
6-16: 2x4 SP No.3, 2-19: 2x4 SP M 31
WEBS 2x4 SP No.3 *Except*
3-19: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Horz 2=208(LC 11)
Max Uplift 2=-921(LC 12), 10=-921(LC 12)
Max Grav 2=1383(LC 1), 10=1383(LC 1)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-6053/4579, 3-4=-5628/4405, 4-5=-2839/2311, 5-6=-2870/2422, 6-7=2&45/2403,
7-8=-2534/2175,8-9=-2396/2033, 9-10=-2819/2244
BOT CHORD 18-19=-2437/3173, 17-18=-1799/2581, 6-17=-245/315, 15-16=-247/388,
14-15=-1550/2171,12-14=-1930/2541,10-12=-1930/2541, 2-19=4167/5647
WEBS 5-18=366/701, 5-17=-443/524, 8-14=-336/450, 9-12=-6/262, 9-14=-592/535,
3-19=-270/557, 4-19=-1680/2425, 4-18=-799/793, 7-15=-572/556, 15-17=-1586/2178,
8-15=438/59217-17=-287/444
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=1511t; B=45ft; L=36ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2)-1-2-0 to 2-0-13, Interior(1) 24-13 to 11-0-0, Exterior(2) 11-0-0
to 16-0-8, Interior(1) 16-0-8 to 24-8-0, Exterior(2) 24-8-0 to 29-8-8, Intedogl) 29-8-8 to 36-10-0 zone;C-C for members and forces &
MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should vertfy
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joints) except Ql=lb)
2=921, 10=921.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9964 Pants East Blvd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq Wsfgn Mram antl READ NOTES ON T-t ANO INCLUDED NITEK REFERENCE PAGE Nl4T/73- 1gPo3rzp15 BEFORE USE. ��-
Deagn valid for use only vd h MITek®wnnec- This deagn is based only upon peramstars shown, and is for en Individual building component, not
I tmsa system. Before use, the budding designer ,at verify the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Bradng indicated is to prevent b-ing of individual truss web and/or chord memb-nly. Adda-alte r, and permanent bracing MiTek'
s always n paired fo, stalblity and to prevent collapae with possible personal injury antl propedy damage. For general gu,d.- regartling the
fabdcatron, atorege, delivery, erection and bracing of Wawa and trues systama, see ANS-11 quality CrlNna, OSB-89 antl Bc8/Buffding Component 6904 parka East BIM.
.4, lnyolmadon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nex -, VA 22314. Tampa, FL M610
5x8 =
6x8 i
Job Reference (o
8.330s 028 Mr
ID:I?Oy9y4e_wm9VIH6D8c7UzSVDB-0RD84RZxnCI
ZObO 26-9-0 29
fi O am 3
44 = 50 =
Scala=1:62.8
7x14 MT18HS = 15 14 13 12
SA — 7.8 =
3x10 � 3x6 = 4.5 =
4.00 12
2-&0 9-0-0 14-&0 204t-0 268-0 35.8
2Z 64-0 5-8-0 &PO 8-0-0 9-0-0
Plate Offsets (X,Y)- 12,0-2-5,Edge1, I2:0-4-9,0.0-01. [3:0-2-12,0-1-2]. I5:0.5-12,0-2A1 I7:0.3-0,Edgel. I9:0-5-12,0-2A1. I11:0-M,0-0-11, I11:0-1-2,Edge1, I16:0-2-12,0-2A1.
f18:0.8-5,Edge1
LOADING (pat) SPACING- 2-0-0 CSL DEFL. in (loc) Udell L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.97 Verf(LL1 -0.42 17-18 >999 360 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.86 Vert(CT) -0.80 17-18 >533 240 MT18HS 244/190
BCLL 0.0 Rep Stress Incr YES WB 0.98 H..(CT) 0.36 11 n/a n/a
BCDL 10.0 Code FBC2017/rP12014 Matrix -MS Wind(-L) 0.6317-18 >682 240 Weight: 186 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied.
BOT CHORD 2x4 SP M 30'Except' BOT CHORD Rigid ceiling directly applied or 3-6-15 oc bracing.
6-15: 2x4 SP No.3, 2-18: 2x4 SP M 31 WEBS 1 Row at midpt 14-16
WEBS 2x4 SP No.3 `Except"
3-18: 2x6 SP N0.2
REACTIONS. (lb/size) 11=1319/Mechanical, 2=1384/0-8-0
Max Horz 2=170(LC 11)
Max Uplift 11=-821(LC 12), 2=-923(LC 12)
FORCES. gb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-26=-5917/4737, 3-26=-5878/4739, 3-27=-5515/4583, 4-27=-5493/4596, 4-5=3203/2673,
5-28=-3674/3043, 6-28=-3674/3043,6-7=-3605/2988,7-8=-3605/2988, 8-29=-3053/2569,
9-29=-3053/2569, 9-10=-2616/2147, 10-30=-2821/2380, 30-31=-2829/2373,
11-31=-2879/2372
BOT CHORD 17-18=-2531/3222, 16-17=-2171/2905, 6-16=-325/401, 14-15=-379/514,
13-14--1751/2387,12-13=-1751/2387,11-12=-2108/2631, 2-18=-4373/5484
WEBS 517=-681/848,5-16=-761/974,14-16=-1950/2578,8-16=-449/642,8-14=-653/637,
9-14=-667/884, 9-12=-214/399, 10-12=-360/438, 3-18=226/540, 4-18=-1821/2208,
4-17=-724/756
NOTES-
1 ) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=36ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 2-0-13, Interior(1) 2-4-13 to 9-0-0, Extenor(2) 9-0-0 to
14-0.8, Interior(1) 14-M to 26-8-0, Exterior(2) 26-8-0 to 31-8-8, Intenor(1) 31-8-8 to 35-8-0 zone;C-C for members and forces &
MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) All plates are 3.4 MT20 unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit
between the bottom chord and any other members.
8) Refer to girder(.) for truss to truss connections.
9) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 821 Ib uplift at joint 11 and 923111 uplift
W joint 2.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 6634
6904 Pahe East BNd. Tampa FL 33610
Dena:
May 6,2020
A wARNINO-."y—is. Parameters antl READ NOTES ON T-t ANO INCLUDED Admsx REFERENCE PAGE A-- — 14Poarze15 BEFORE USE. ��-
Design valid for use only— MI —nneclom. This —la ie based only upon parameters shown, and is for en ,ndividual bu,idi,g component, not
I wss system. Before use, the budding designer ,at verify the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent bulling of individual truss web and/or chord membersonly. Adddionaltemporary and permanent bracing MiTek'
s always mguired fo, staGlity and to prevent collapse with possible personal injury antl pmperry damage. For general gux.—regartling the
fabdcatron, atmage, delivery, erection and bracing of Wasea and trues y,dam., see ANS-11 quality CrlNria, OSB-89 antl BC Building Component g90q Parke Eest BIM.
.4, lnrormetron available /ram Truss Plate InsdMe, 218 N. Lee Street, Suite 312, Nex —, VA 22314. Tampa. FL M610
Scale=1:61.2
5.8 W18HS =
sailWB — salt=
5.00 12
4 5 28 29 8 7 8 30 31 9 10
7z14MT1BHS = 15 14 13 12
6zto — 7x8 =
3z10 4xe = 3x8 =
4., 12
241-0 7-0-0 148-0 T. 28.8-0 354t-0
2A-0 4-0-0 7-8-0 T. &8-0 7-0-0
LOADING (psf) SPACING- 2-0-0 CSI. DEFL in (loc)/dell L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.96 VanI_L) -0.53 16 >814 360 MTZ0 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.94 Van CT) -1.00 16-17 >428 240 MT18HS 244/190
BCLL 0.0 ' Rep Stress Incr YES WB 0.79 Horz(CT) 0.38 11 n/a n/a
BCDL 10.0 Cade FBC2017TrP12014 Matrix -MS Wind(LL) 0.79 16 >541 240 Weight: 177111 FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied.
BOT CHORD 2x4 SP M 30 *Except' BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing.
6-15: 2x4 SP No.3, 2-18: 2x4 SP M 31
WEBS 2x4 SP No.3 *Except*
14-16: 2x4 SP M 30, 3-18: 2.6 SP No.2
OTHERS 2x4 SP No.3
REACTIONS. (Ib/size) 11=1319/Mechanical, 2=1384/0-8-0
Max Horz 2=136(LC 11)
Max Uplift 11=-821(LC 12), 2=-923(LC 12)
FORCES. (Ib) -Max, Comp/Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-26=-5819/4750, 26-27=-5785/4755, 3-27=-5779/475634--5472/4680, 4-5=-3397/2790,
5-28=-4987/3987,28-29=-4987/3987,6-29=-4987/3987:6-7=-4871/3912, 7-8=-4871/3912,
8-30=-3950/3192,30-31=-3950/3192,9-31=-3950/3192,9-10=-2617/2203, 10-32=-2796/2249,
32-33=-2799/2238, 11-33=2860/2232
BOT CHORD Ill 8=-2535/3345, 16-17=-3323/4325, 6-16=-250/282, 14-15=-443/522, 13-14=-2665/3441,
12-13=-2665/3441,t-12=-1942/2579,2-18=-4385/5388
WEBS 4-17=-544/838, 14-16=-2574/3485, 8-16=-757/988, 8-14=-677/619, 10-12=-097/794,
3-18=-199/513,9-14=-388/673, 9-12=1094/862, 5-17=-1162/974, 5-16=-515/821,
4-18=-1890/1995
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=361t; save=5ft; Cat. 11,
Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2)-1-2-0 to 2-4-13, Intenor(1) 2-4-13 to 7-0-0, Extenor(2) 7-0-0 to 12-0-8
, Intenor(1) 12-0-8 to 28-8-0, Exterior(2) 28-8-0 to 33-8-8, Interior(1) 33-8-8 to 35-8-0 mne;C-C for members and forces & MWFRS for
reactions shown; Lumber DOL=1.60 plate grip DOL=1 SO
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) All plates are 3x4 MT20 unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
7) ' This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit
between the bottom chord and any other members.
8) Refer to girder(s) for truss to truss connections.
9) Bearing aljoint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of
bearing surface.
10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 821 Ib uplift at joint 11 and 923 lb uplift at
joint 2.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34819
MiTak USA, Inc. FL Cart 6634
6904 Padre East BNd. Tampa FL 33610
pets:
May 6,2020
'&WARNING -.,a, —is. param antl READ NOTES ON TNfs Ass) aNCLUVED NITEIr RE —El —PAGE NI67473— 1dXdaoV15 BEFORE USE. ��-
Dealgn valid for use only wdh MITe nd.ld a. This d-le is based only upon parameters shown, and is for an Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl Dropedy mcorporete this design into the overall
builtling design. Bracing indicated is in prevent bulling of individual truss web and/or chord membe—nly. Adda—altemporary and permanent bracing MiTek'
s always reguiretl for staGlily antl to prevent wllapse with possible personal injury antl Drapery tlama9e. For general guitlance rag d, the
labdcatron, atomge, delivery, erection and bracing of Wasea and trues systems, see ANS-11 quality Criteria, OSB-89 antl BCSf Building Component g9Oq parka East BIM.
.4, arns,madon available from Truss Puts InsgMe, 218 N. Lee Street, suite 312, Neear im, VA 22314. Tampa, FL M610
I
T20150971
i
3x8 =
5
FY'1r$IkCEU
3.8 3.4 11 5x8 MT18HS = 3M 11 3x8
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) War L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.74 Ve di-L) -0.37 10-12 -657 360 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.94 Vert(CT) -0.60 10-12 >404 240 MT18HS 244/190
BCLL 0.0 Rep Stress Incr YES WB 0.66 H.. T) 0.04 8 n/a n/a
BCDL 10.0 Code FBC2017/rP12014 Matnx-MS Wind(LL) 0.25 10-12 >977 240 Weight: 96 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 31 TOP CHORD Structural wood sheathing directly applied or 4-3-12 oc pudins.
BOT CHORD 2x6 SP No.2 *Except* BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing.
8-11: 2x6 SP 240OF 2.0E
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 8=0-8-0
Max Hom 2=169(LC 11)
Max Uplift 2=-518(LC 12), 8=-518(LC 12)
Max Grav 2=1069(LC 18), 8=1069(LC 19)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=2055/838, 34=-1753/853, 4-5=-174/870, 5-6=-171/870, 6-7=-1753/857,
7-8=-2058/842
BOT CHORD 2-12=-602/1824, 10-12=-602/1824, 8-10=-602/1824
WEBS 7-10=0/643, 3-12=0/637, 4-6=-2748/1096
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsh, h=15ft; B=45ft; L=24ft; eave=oft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 10-2-0, Exterior(2) 10-2-0
to 13-2-0, Interior(1) 13-2-0 to 21-6-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) All plates are MT20 plates unless otherwise indicated.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will 8l between the bottom chord and any other members.
6) Ceiling dead load (5.0 Pat) on member(s). 3-4, 6-7, 4-6
7) Bottom chord live load (40.0 psf) and additional bottom chord dead load (5.0 psf) applied only to room. 10-12
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at -lb)
2=518,8=518.
9) ATTIC SPACE SHOWN IS DESIGNED AS UNINHABITABLE.
is
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33610
Date:
May 6,2020
'&WARNING-ve",y .n parameters antl READ NOTES ON TN ANO INCLUDED M1TEx REFERENCE PAGE Nl4T/73—la-15 BEFORE USE. ��-
Daslgn valid for use only— MIT—nnectom. This —la is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at vadfy the applicability of design parameters antl properly Incorporate this design into the overall
building design. Braung indicated is to prevent bulling&individual truss web and/or chord memb—nly. Adda—alte r, and permanent bracing MiTek'
s always repaired bo, stalblity and to prevent collapse with possible personal injury antl property damage. For general guitlance raga d, the
fabdcatron, smmge, delivery, erection and bracing of Wawa and trues systems, see ANS-11 Qualify criteria, OSB-89 antl BcS1 Building Component g90q Parke East BIM.
.4, lnyorm s— available from Tmss P to la—, 218 N. Lee Street, Suite 312, Nex —, VA 22314. Tampa, FL M610
T20150972
5.00 12
3.6 —
EE1dIER!
N
3x6 =
Scale=1:59.2
9-2-14
9-2-14
17-10-0
8-7-2
265.2
8.7.2
3541-0
9-2-14
Plate Offsets (X,Y)-
rl:0-1-2,Edgel, ri:0-0-0,0-0-11. rl:05-1,04-121,
f9:0-1-2,Edue1
LOADING (pat)
SPACING- 2-0-0
Cat.
DEFL.
in (loc) War
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.41
Vert(LL)
-0.16 12 >999
360
MT20 2441190
TCDL 7.0
Lumber DOL 1.25
BC 0.56
Vert(CT)
-0.34 10-21 >999
240
BCLL 0.0 '
Rep Stress Incr YES
WB 0.84
Ho.(CT)
0.11 9 n/a
n/a
BCDL 10.0
Code FBC2017ITP12014
Matrix -MS
Wind(LL)
0.24 12 >999
240
Weight: 172 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly
applied or 4-0-2 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD Rigid ceiling directly applied or
5-3-9 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (Ib/size) 1=1320/Mechanica1, 9=1320/0-8-0
Max Horz 1=304(LC 11)
Max Uplift 1=-823(LC 12), 9=-823(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 1-22=-2863/2089, 2-22=-2814/2099, 2-3=-2602/1909, 34=-2492/1926, 4-23=-1800/1441,
5-23=-1736/1452,5-24=-1736/1452,6-24=-180011441,6-7=-2492/1926, 7-8=-2602/1909,
8.25=-2815/2099,9-25=-2863/2089
BOT CHORD 1-14=-1818/2619, 13-14=-1365/2101, 12-13=-1365/2101, 11-12=-1365/2101,
10-11=-1365/2101, 9-10=-1818/2613
WEBS 5-12=-750/1048, 6-12=-746/622, 6-10=-296/535, 8-10=408/440, 4-12=-746/622,
4-14=-296/534, 2-14=407/440
NOTES.
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=1511; B=45ft; L=36ft; save=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extenor(2) 0-0-0 to 3-6-13, Interior(1) 3-6-13 to 17-10-0, Exteriod2)
17-10-0 to 214-13, Intenor(1) 214-13 to 35-8-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber
DOL=1.60 plate grip DOL=1.60
3) All plates are 3x4 MT20 unless otherwise indicated.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcumsnt with any other live loads.
This item has been
5) `This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
electronically signed and
will fit between the bottom chord and any other members.
sealed by Lee, Julius, PE
6) Refer to girder(s) for truss to truss connections.
using a Digital Signature.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 823lb uplift at joint 1 and 823lb uplift at
joint 9.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 6634
6604 Parke East BNd. Tampa FL 33610
Date:
May 6,2020
,&WARNING- va", Wsign Paramamrs READ NOTES ON AND avCLUDEO MITEx REFERENCE PAGE Ml4]/73—la-2015 BEFORE USE. ��-
Daslgn valid for use only— MI —radeclom. This —la is based only upon parametars shown, and is for en ,ndividual builtling component, not
abusssystem.Beforeuse, me bu6ding designer must verify the applicability o!tlesi9n parametersantl my Aylncorpotale Imsdesigninto.noverall
builtling tlesign. Braung indiratetl isb prevent bulling of indivitlual truss web andlor chord members only. Atltlitional temporary and permanent bracing MiTek'
s always reguiretl rod slx.c. antl to and br .idg se witM1 .and
le pe,sonal n., s..ntl Droperry dS-11 For genCmwr idan 89 add B lM1e
fa 4, ann, maage, delivery, erection antl bracing of Wawa antl W ss systems, see ANSVA 22 Quality Criteria, OSB-89 antl BLS/Builtling Component T.ar parka M61BIM.
Sateyln/ormetlon available /ram Truss PWIe InsgMe, 218 N. Lee Street, Suite 312, AleeaMna, VA 22314. Tampa. FL 38810
i
pd'l a
5x8 =
5.6 =
5 6
Scale = 1:59.7
16 15 14 13 12 11
4.5
4x8 = 3.6 = 4a5 =
=
9-2-14 17-0-0 11"-0 26-5 4 35-&It 9-2-14 7-9-2 1A-0 7-94 9-2-12
Plate Offsets (X,Y)— fl:0-0-0,0-0-11, f1:0-1-2,Edgal, f3:0-3-0,Edge1, f5:0-3-0,0-2-41, f6:030,0-241, I8:0-3-0,Edgej, [10:0-1-2,Edge], (10:0-0-0,0-0-1j
LOADING (psf) SPACING- 2-0-0 CSI. DEFL in 0-) /dell L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.42 Vlart(LL) -0.16 14 >999 360 MTZO 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.55 Vad(CT) -0.34 i6-21 >999 240
BCLL 0.0 ' Rep Stress Incr YES WB 0.71 Horz(CT) 0.11 10 n/a n/a
BCDL 10.0 Code FBC2017TrP12014 Matrix -MS Wind(LL) 0.24 14 >999 240 Weight: 182 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 4-04 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 5-2-7 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (Ib/size) 1=1320/Mechanical, 10=1320/Mechanical
Max Horz 1=-290(LC 10)
Max Uplift 1=-823(LC 12), 10=-823(LC 12)
FORCES. (lb) - Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-25=-2864/2161, 2-25=2816/2171, 2-3=-2601/1978, 3-4=-2530/1995, 4-5=-1849/1570,
5-6=-1663/1508,6-7=-1849/1570, 7-8=-2530/1995, 8-9=-2601/1978, 9-26=2817/2172,
10-26=-2866/2162
BOT CHORD 1-i6=-1891/2621, 15-16=-1466/2098, 14-15=-1466/2098, 13-14=-1024/1663,
12-13=-1452/2098,11-12=-1452/2098, 10-11=-1886/2616
WEBS 2-16=410/446, 4-16=-294/552, 4-14=723/637, 5-14=418/533, 6-13=-417/533,
7-13=-724/638, 7-11=-293/551, 9-11=411/447
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf, h=15ft; B=45ft; L=3611; eave=511; Cat. II;
Ezp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 3-6-13, Intedor(1) 3-6-13 to 17-0-0, Extedor(2) 17-0-0 to
23-6-13, Interior(1) 23-6-13 to 35-8-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Provide adequate drainage to prevent water pondmg.
4) All plates are 3x4 MT20 unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit
between the bottom chord and any other members.
7) Refer to girder(s) for truss to truss connections.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 823 lb uplift at joint 1 and 82311, uplift at joint
10.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34819
MiTak USA, Inc. FL Cart 6634
Bets Padre East BNd. Tampa FL 33610
Data:
May 6,2020
,&WARNING-vedq—isn parameters antl READ NOTES ON TN ANO INCLUDED NITEIr REFERENCE PAGE Nl67473— 1aPo3rza15 BEFORE USE. ��-
Daslgn valid for use only cosh MIT—nneclors. This —la is based only upon parameters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl pro dy In ,o ,,a this design into in, overall
building design. Bradng indicated is to prevent bulling of individual truss web and/or chord memb—nly. Addda—l—,omary and permanent bracing MiTek'
s always reguiretlforshGlily antl to prevent collapse witM1 possible personal injury antl Drapery tlamage. For general guitlance regartling lM1e
fabdcatron, storage, delivery, erection and bracing of Wawa and trues y,dam., see ANS-11 Quality criteria, OSB-89 antl Bcsf Building Component g9pq parka East BIM.
.4, lnsafm seda, available from Truss Puts InsgMe, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tamps, FL M610
0 15-0-0 20-8-0 27-11-11 IN.,
N 3
0- 7-3-11 5-&0 7311 7-0.9
Scale=1:60.3
Sail =
5.00 12 Ida -
3 23 244
12 11 10 9 8 7
3.5 = 3.4 II 3.6 = 3.8 =3x6 3x4 3.6 =
3x4 II 3x4 = 3.4 II
3.4 11 3.4 11
]a-s tso-0 W 27-11-1t 3se-B
7-8-s 7-3-11 S&0 7511 7435
Plate Offeets (X,Y)- t2:0-0-0,0-3-01, 13:0-5-4,0-24j, f4:0-3-0,0-24j, f5:0-4-0,0.34 j, f6:0-0-2,0-Mj, I6:0-1-9,0-4-13j
LOADING (psf) SPACING- 2-0-0 CSI. DEFL in Qoc)/dell L/d PLATE$ GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.55 Vert(LL) -0.16 9-10 >999 360 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.53 Vert(CT) -0.31 10-12 >999 240
BCLL 0.0 ' Rep Stress Incr YES WB 0.31 Horz(CT) 0.11 6 n/a n/a
BCDL 10.0 Code FBC2017/rP12014 Matrix -MS Wind(LL) 0.24 9-10 >999 240 Weight: 174 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 3-11-13 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 5-0-2 oc bracing.
WEBS 2x4 SP No.3 WEBS 1 Row at midpt 2-10, 3-9, 5-9
REACTIONS. (Ib/size) 1=1320/Mechanical, 6=1320/Mechanical
Max Horz 1=256(LC 11)
Max Uplift 1=-823(LC 12), 6=-823(LC 12)
FORCES. (Ib)- Max. Comp./Mex. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-21=-2844/2201, 2-21=2798/2215, 2-22=-2080/1718, 3-22=1994/1739, 3-23=1851/1719,
23-24=-1851/1719,4-24=-1851/1719,4-25=-1995/1739,5-25=-2081/1718, 5-26=-2798/2215,
6-26=-2844/2201
BOT CHORD 1-12=-1957/2584, 11-12=-1957/2586, 10-11=-1957/2586, 9-10=-1289/1850, 8-9=-1941/2585,
7-8=-1941/2585, 6-7=-1941/2584
WEBS 2-12=0/326, 2-10=-903/734,3-10=-254/479, 4-9=-291/480, 5-9=-903/734, 5-7=0/325
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=36ft; eave=5ft; Cat. II;
Exp C; End, GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 3-6-13, Inlenor(1) 3-6-13 to 15-0-0, Extenor(2) 15-0-0 to
20-0-8, Interior(1) 20-0-8 to 20-8-0, Extehor(2) 20-8-0 to 25-8-8, Intenor(1) 25-8-8 to 35-8-0 2one;C-C for members and forces 8 MWFRS
for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit
between the bottom chord and any other members.
6) Refer to girder(s) for truss to truss connections.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 823 lb uplift at joint 1 and 823 lb uplift at joint
6.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34869
MiTak USA, Inc. FL Cart 6634
6604 Pants East BNd. Tampa FL 33610
Data:
May 6,2020
,&WARNING-vereyWs;6n parameters antl READ NOTES ON T-t ANO INCLUDED N1TEfr REFERENCE PAGE Nl4T/73- 1dX3cdV15 BEFORE USE. ��-
Dealgn valid for use only- MITek®wnnec- This deagn is based only upon parameters shown, and is for an Individual building component, not
I tmsa system. Before use, the builtling designer ,at verify the applicability of design parameters antl propedy Incorporate this design into the overall
builtling design. Bradng indicated is to prevent bulling of individual truss web and/or chord membersonly. Adda-al-tomary and permanent bracing MiTek'
s alwaysre i,edfix staGlity and to prevent collapae with possible personal injury antl D.,dy damage. For general gu,d.-regartling the
labdcatron, atmage, delivery, erection and bracing of Wawa and trues systama, see ANS-11 quality Criteria, OSB-89 antl BCSf Building Component g90q Perks East BIM.
.4, lnyofmadon available from Truss Puts la-, 218 N. Lee Street, Suite 312, -a-, VA 22314. Tampa, FL M610
Scale = 1:58a
5x8 =
5.6 _
3 23 4 24 5
13 12 11 M27 10 9 8
4x6 = 3x8 = 3.6 =
3a8 = 4x6 =
7-&6 13-0-0 22-8-0 I 27-11-10 I
35.8-0
7A-6 5-3-10 9A-0 5-3-t0
7-8-6
Plate Offsets (X,Y)—
f 1:0-0-2,0-0-01, j3:0-3-0,0-24j, f5:0-M,0-24j, 17:0-0-2,0-04 j, 17:0-1-3,Od-13j
LOADING (psf)
SPACING- 2-0-0
CS.
DEFL in (loc) /dell L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.51
Vert(LL) -0.24 9-12 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.56
Vert(CT) -0.52 9-12 >827 240
BCLL 0.0 '
Rep Stress Incr YES
WB 0.51
Horz(CT) 0.11 7 We n/a
BCDL 10.0
Cade FBC2017TrP12014
Matrix -MS
Wind(LL) 0.26 9-12 >999 240
Weight: 175 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly
applied or 3-10-4 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or4-11-5
oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 1=1320/Mechanical, 7=1320/Mechanical
Horz 1=222(LC 11)
Ma.H1
Max uplift 1=-823(LC 12), 7=-823(LC 12)
FORCES. (Ib)- Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-22=-2817/2237, 2-22=2769/2250, 2-3=-2253/1890, 3-23=-2031/1830, 4-23=-2031/1830,
4-24=-2031/1830,5-24=-2031/1830,5-6=-2253/1890,6-25=-2769/2250, 7-25=-2817/2237
BOT CHORD 1 -13=-198512601,12-13=-1985/2601, 11-12=-1576/2156, 11-26=-1576/2156,
26-27=-1576/2156,10-27=-1576/2156,9-10=-1576/2156,8-9=-1967/2556,7-8=1967/2556
WEBS 2-12=-684/635, 3-12=-448/619, 4-12=321/277, 4-9=-321/277, 5-9=-448/619, 6-9=685/635
NOTES
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; 13=451t; L=36ft; eave=5ft; Cal. II;
Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 3-6-13, Intenor(1) 3-6-13 to 13-0-0, Extenor(2) 13-0-0 to
17-10-0, Interior(1) 17-10-0 to 22-6-0, Exlenor(2) 22-8-0 to 27-11-10, Interior(1) 27-11-10 to 35-8-0 wne;C-C for members and forces 8
MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are 3x4 MT20 unless otherwise indicated.
This item t1aS been
Thisitemhelectronicallysigned
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
'
g and
6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit
between the bottom chord and any other members, with BCDL = 10.0psf.
Sealed by Lee, Julius, PE
7) Refer to girder(,) for truss to truss connections.
using a Digital Signature.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 823Ib uplift at joint 1 and 823I1b uplift at joint
Printed copies of this
7.
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34819
MiTak USA, Inc. FL Cart 6634
6604 Pants East BNd. Tampa FL 33610
Data:
May 6,2020
D valid
VerHyly— paramamrsaatl READ N—la— rise AND rNLLUDEar Mtars h.n.R NLE r.n, Mividua3nvdi,g. p1,6EFOot��-
Dealgnvalitlforuseonlyw6b,buddl d,,ig,, This arty t is based onlyupon,.g, a,rat—rand isfor en I,tl,,uat builtling comp orient, not
I buss system. Before use, io ed is td designer ,at of the applicability o! design parameters antl my Ay lncorpomle this design into IM1e overall
builtling tlesign. Bradng intliratetl is prevent bulling of indivitlual truss web andlor cbortl members only. Atltlitional temporary and permanent bracing MiTek'
s always roguirod for staGlily and io and br .ing f witM1 . and le pe,syste i s, s.. tl Droperry dS-11 ality eras guidon 89 add B lM1e
f 4, ann, stomga, delivery, erection and bracing of , 21 and trues systems, see ANSVA 22 14. Criteria, OSB-89 antl BLS/auiltling Component 8904 parka East M61BIM.
Sateyln/ormetlon available /ram Truss PWIe InsgMe, 218 N. Lee Street, Suite 312, AleeaMna, VA 22314. Tampa. FL 38610
3x6 =
5x8 =
5.8 =
50n F� - 3 25 26 4 27 28 5
14 13 72 11 10 9 8
3as = 3x8 = 3.6 =
Scale = 1:58a
744A 11-f1-D 17-11}0 24-8-0 27-11-12
35440
7A-4 3-3-12 8-10-0 6-10-0 3312
76�
Plate Offsets (X,Y)—
fl:06-2,0-0<7, f3:0312,0-261. f5:0-5-12,0-2-8j, r7:0-6-2,0-0-4j, 17:0-0-11,0-0-13j
LOADING (psf)
SPACING- 2-0-0
CS.
DEFL in (Ioc) /dell L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TIC 0.51
Vert(LL) -0.18 11 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.56
Vert(CT) -0.36 11-13 >999 240
BCLL 0.0 '
Rep Stress Incr YES
WB 0.56
Horz(CT) 0.11 7 n/a n/a
BCDL 10.0
Code FBC2017TrP12014
Matrix -MS
Wind(LL) 0.28 11 >999 240
Weight: 176111 FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Stmctural woad sheathing directly
applied or 3-9-2 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or4-10-13
oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (Ib/size) 1=1320/Mechanical, 7=1320/Mechanical
Max Horz 1=188(LC 11)
Max Uplift 1=-823(LC 12), 7=-823(LC 12)
FORCES. (Ib)- Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-23=-2817/2256, 23-24=2767/2258, 2-24=-2721/2270, 2-3=2414/2055, 3-25=2617/2262,
25-26=-2617/2262, 4-26=-2617/2262, 4-27=-2617/2262, 27-28=-2617/2262, 5-28=-2617/2262,
56=-2414/2055, 6-29=-2721/2270, 29-30=2767/2258, 7-30=-2817/2256
BOT CHORD 1-14=-1995/2554, 13-14=-1995/2554, 12-13=-1614/2191, 11-12=-1614/2191,
10-11=-1598/2191,9-10=-159812191,8-9=-1979/2554, 7-8=-1979/2554
WEBS 2-13=-582/536, 3-13=-324/467, 3-11=-449/631, 4-11=-429/512, 5-11=-449/631,
5-9=-324/467, 6-9=582/536
NOTES.
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf, h=15ft; B=45ft; L=36ft; eave=5ft; Cat. II;
Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 3-6-13, Inledor(1) 3-6A3 to 11-0-0, Exterior(2) 11-0-0 to
16-0-8, Interior(1) 16-0-8 to 24-8-0, Extedor(2) 24-8-0 to 29-8-8, Intedor(i) 29-8-8 to 35-8-0 zone;C-C for members and fames 8 MWFRS
for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
This item has been
3) Provide adequate drainage to prevent water ponding.
electronically signed and
ey Sg
4) All plates are 3x4 MT20 unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Sealed by Lee, Julius, PE
6)This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit
using a Digital Signature.
between the bottom chord and any other members.
Printed Copies Of this
7) Refer to girder(s) for truss to truss connections.
document are not considered
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 823 lb uplift at joint 1 and 82311, uplift at joint
7.
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34819
MiTak USA, Inc. FL Cart 6634
I Parke East BNd. Tampa FL 33610
Data:
May 6,2020
,& WARNING-vedq—is. parameters antl READ NOTES ON TR ANO INCLUDED NITEIr REFERENCE PAGE Nl4T/73— 1pPoarzpl5 BEFORE USE. ��-
Dealgn valid for use only wdh MIT—nnectom. This —la ie based only upon pemmaters ah.n, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at venfy the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss weband/or chord members only. Additional temporary and permanent bracing MiTek'
s always requi,d /o, staGlity and to prevent collapse with possible personal injury antl propedy damage. For general gu,d.— regartling the
fabdcatron, atmage, delivery, erection and bracing of Wasea and trues syatema, see ANS-11 quality Criteria, OSB-89 antl BCSf Building Component g9oq Para East BIM.
.4, lnsafm seda, available from Tmss Puts I-axa, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
T20150977
1
6cals=1:60.8
4.6 = 3x4 = 3x4 II 3xe = 3.4 = 4.6 = 3x4 = 4x6 =
1 17 18 2 3 19 4 20 5 6 7 21 22 8
16 15 14 13 12 11 10 9
3x6 3x8 = 3.6 = .10 = 416 = 3x4 = 3x8 = 3x6
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) War L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.65
Vert(LL) -0.23 11-13 -999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.48
Vert(CT) -0.45 11-13 >953 240
BCLL 0.0
Rep Stress Incr YES
WB 0.98
Horz(CT) 0.07 9 n/a We
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Wind(LL) 0.34 11-13 >999 240
Weight: 194 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 3-11-13 oc pudins,
BOT CHORD 2x4 SP M 30 except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied
or 4-11-5 oc bracing.
WEBS 1 Row at midpt
1-15, 8-10
REACTIONS. (size) 16=Mechanical, 9=Mechanical
Max up, 16=-816(LC 12), 9=-816(LC 12)
Max Grav 16=1309(LC 1), 9=1309(LC 1)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (Ib) Or less except when shown.
TOP CHORD 1-1 6=-1 243/1025,1-2=-2039/1530, 2-3=-2998/2232, 3-5=-2998/2232, 5-7=-2999/2232,
7-8=-2038/1530, 8-9=-124311025
BOT CHORD 11-13=-2232/2999, 10-11=-1530/2038
113-15=-1530/2039,
WEBS -15=-1703/2274,2-15=-927/857,2-13=-811/1089,3-13=-375/423, 5-11=-376/425,
7-11=-812/1090, 7-10=-927/857,8-10=-1703/2274
NOTES.
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf, h=15ft; B=45ft; L=36ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-1-12 to 3-8-9, Intedor(1) 3-8-9 to 35-6-4 zone;C-C for
members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Provide adequate drainage to prevent water ponding.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
This item has been
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100lb uplift atjoint(s) except Ql=lb)
electronically signed and
16=816,9=816.
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 6634
9904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
,&WARNING.v=dty Wspnrwramemrs antl READ NOTES ON TNIS AND INCLUDEON1TEx RE—ENCEPAGENIA]/73— 10Poarzp15 BEFOREUSE. ��-
Daslgn valid for use only— MITek®wnnectsm. This —la is basetl only upon parameters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer must verify the applicability or tlesi9n parameters antl pro dy Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always reguiretl kr shGlily antl to prevent wllapse with possible pe,sonal injury antl Drapery tlama9e. For general guidance rega d, the
fabdcatron, ammge, delivery, erection and bracing of lasses antl trues systems, see ANSI PIl quality CNNria, OSB-89 and BCS1 Building Component g9Dq Parke East BIM.
.4, rnyolmadon available from Truss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
'-'
Lumber design values are in accordance with ANSI/TPI 1 section 6.3
These truss designs rely on lumber values established by others.
i�lYs
MiTek'
RE: 76703-
MiTek USA, Inc.
Site Information:
6904 Parke East Blvd.
Customer Info: FAT ROBASSON
Project Name: PHILLIPE Model: Tampa, FL 33610-4115
Lot/Block:
Subdivision:
Address: UNKNOWN
City: FORT PIERCE
State: FL
Name Address and License # of Structural Engineer of Record, If there is one, for the building.
Name: License #:
Address:
City: State:
General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special
Loading Conditions):
Design Code: FBC2017/TP12014 Design Program: MiTek 20/20 8.3
Wind Code: ASCE 7-10 Wind Speed: 170 mph
Roof Load: 37.0 psf Floor Load: N/A psf
This package includes 59 individual, Truss Design Drawings and 0 Additional Drawings.
With my seal affixed to this sheet, I hereby certify that I am the Truss Design Engineer and this index sheet
conforms to 61 G15-31.003, section 5 of the Florida Board of Professional Engineers Rules.
No.
Seal# Truss Name
Date
No.
Seal# Truss Name
Date
1
T20150962 A
516/20
15
T20150976 B5
5/6/2(
2
T20150963 Al
5/6/20
16
T20150977 B6
5/6/2(
3
T20150964 A2
516/20
17
T20150978 C
5/6/2(
4
T20150965 A3
516/20
18
T20150979 C1
5/6/2(
5
T20150966 A4
516/20
19
T20150980 D
5/6/2(
6
T20150967 A5
5/6/20
20
T20150981 D1
5/6/2(
7
T20150968 A6
5/6/20
21
T20150982 E
5/6/2(
8
T20150969 A7
5/6/20
22
T20150983 G
5/6/2(
9
T20150970 A8
516/20
23
T20150984 GRA
5/6/2(
10
T20150971 ATA
5/6/20
24
T20150985 GRB
5/6/2(
11
T20150972 B1
5/6/20
25
T20150986 GRC
5/6/2(
12
T20150973 B2
516/20
26
T20150987 GRID
5/6/2(
13
T20150974 B3
516/20
27
T20150988 GRE
5/6/2(
14
T20150975 B4
516/20
28
T20150989 GRG
5/6/2(
This item has been electronically signed and sealed by Lee, Julius, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies
The truss drawing(s) referenced above have been prepared by
MiTek USA, Inc. under my direct supervision based on the parameters
provided by Chambers Truss.
Truss Design Engineer's Name: Lee, Julius
My license renewal date for the state of Florida is February 28, 2021.
IMPORTANT NOTE: The seal on these truss component designs is a certification
that the engineer named is licensed in the jurisdiction(s) identified and that the
designs comply with ANSI/TPI 1. These designs are based upon parameters
shown (e.g., loads, supports, dimensions, shapes and design codes), which were
given to MiTek or TRENCO. Any project specific information included is for MiTek's or
TRENCO's customers file reference purpose only, and was not taken into account in the
preparation of these designs. MiTek or TRENCO has not independently verified the
applicability of the design parameters or the designs for any particular building. Before use,
the building designer should verify applicability of design parameters and properly
incorporate these designs into the overall building design per ANSI/TPI 1, Chapter 2.
�, ��O E N 3F . , 41
No 34869
'a .9STATE OF •4/Z
1'0� 'A, o R Q P N���
FSS,ONA; E���%
Julius Lee PE No.34869
MiTek USA, Inc. FL Cen 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
May 6,2020
Lee, Julius 1 of 2
1
T20150978
i
4.4 =
4
6Y11`1131 fB
3x6 =
4x4 = 3z8 — 4.4 =
LOADING (par) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DO L 1.25 TC 0.31 Vert(LL) -0.13 7-11 >999 360 MT20 244/190
TCDL TO Lumber DOL 1.25 BC 0.51 Vert(CT) -0.29 7-11 >824 240
BCLL 0.0 Rep Stress ]nor YES WB 0.26 Hom(CT) 0.03 6 n/a n/a
BCDL 10.0 Code FBC2017ITPI2014 Matdx-MS Wind(LL) 0.14 7-11 >999 240 Weight: 80 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-10-11 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 7-9-1 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 6=0-8-0, 2=0-8-0
Max H— 2=162(LC 11)
Max Uplift 6=-048(LC 12), 2=-553(LC 12)
Max Grav 6=723(LC 1), 2=789(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1315/1026, 3-4=-1041/834, 4-5=-1042/857, 5-6=-1320/1038
BOT CHORD 2-7=-854/1183, 6-7=-838/1188
WEBS 4-7=-521/696, 5-7=-385/441, 3-7=-378/434
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vu11=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf, h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exledor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 9-9-8, Exledor(2) 9-9-8 to
13-1-1, Interior(1) 13-1-1 to 19-7-0 zone;C-C for members and forces S MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) This truss has been designed for a 10.0 par bottom chord live load nonconcurrent with any other live loads.
4) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at -lb)
6=448,2=553.
i$
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,39
MiTak USA, Inc. FL Cart 6634
6604 Parke East BNd. Tampa FL 33610
pate:
May 6,2020
A wARN1N0-vedq—is. pare — and READ NOTES ON nvis ANO INCLUDED N1TEfr REFERENCE PAGE Nl4T/73-14-015 BEFORE USE. ��-
Daslgn valid for use only— MITek®wnnectom. This design is based only upon parameters shown, and is for an Individual building component, not
I truss system. Before use, the budding designer ,at vebfy the applicability of design pammat— antl pro dy Incorporate thls design into the overall
builtling design. Bradng indirated is to prevent bulling of individual truss web and/or chord memb—nly. Adda—alta.,omary and permanent bracing MiTek'
s always required bo, staGlity and to prevent collapse with possible pe,sonal injury antl Dropan, damage. For general guxance raga d, the
labdcatron, ammge, delivery, erection antl bracing of lasses and trues systems, see ANS-11 Qualify Criteria, OSB-89 antl Bcs!Building Component 6904 Parke East BIM.
.4, lnyofmadon available from Truss Plate In58Me, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
1
T20150979
4.4 =
4
a
FY�1r-SIKFfa
3x5 = 3x6 — 3x4 = 3.4 = 3x5 =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) Vdefl
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.24
Vert(LL)
-0.12 10-14 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.40
Vert(CT)
-0.25 10A4 >933
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.13
HOrz(CT)
0.03 7 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Wind(LL)
0.08 10-14 1999
240
Weight: 871b FT=201
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly
applied or 5-11-13 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD Rigid ceiling directly
applied
or 7-6-10 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 7=0-8-0
Max Horz 2=152(LC 11)
Max Uplift 2=-550(LC 12), 7=-550(LC 12)
Max Grav 2=788(LC 1), 7=788(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-1357/1126, 3-4=-1076/899, 4-5=-957/868, 5-6=-1076/899, 6-7=-1357/1126
BOT CHORD 2-10=-914/1229, 9-10=-561/957, 7-9=-931/1229
WEBS 3-10=-375/452, 4-10=-201/300, 5-9=201/300, 6-9=-376/452
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 1-10-0, Intenor(1) 1-10-0 to 9-0-0, Exterior(2) 9-0-0 to
14-9-15. Interior(1) 14-9-15 to 20-9-0 wne;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at=lb)
2=550, 7=550.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9934
9964 Parke East BNd. Tampa FL 33910
Data:
May 6,2020
'&WARNING-vedq—is. Parameters and READ NOTES ON TNIs ANO INCLUDED AdmEK REFERENCE PAGE Nl4T/73— 1gPo3rzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT- nnec— This d-la is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at vebfy the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always rep—dfix stalblity and to prevent collapse with possible personal injury antl propedy damage. For general gux.—regartling the
fabdcatron, atmage, delivery, erection and bracing of Wawa and truss systama, see ANS-11 quality criteria, OSB-89 antl Bcsf Building Component 8904 Parke East BIM.
.4, lnyolmadon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa. FL M610
Sd 8
&1-15, 7-16.0.7 Is" 11-11-0
1-2-0 d-&9 056 2 Od61-2-0
0.2-9
Scale=1:21.3
4x4 =
3
T1
3.4 =
6
2x3
3x4 =
6-0-7
1D
4$-9
0.7-15 0.7-15
4-8-9
LOADING (par)
SPACING-
2-0-0
CSI.
DEFL.
in (too) I/deb
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DO L
1.25
TC 0.25
Vert(LL)
-0.02 6-12 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.18
Vert(CT)
-0.04 6-12 >999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.09
HOR(CT)
0.01 4 n/a
We
BCDL 10.0
Code FBC2017/IP12014
Matrix -MS
Wind(L-)
0.04 6-12 >999
240
Weight: 40 lb FT=20%
LUMBER-
BRACING.
TO CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 4=0-&0
Max H— 2=-95(LC 10)
Max Uplift 2=-346(LC 12), 4=346(LC 12)
Max Grav 2=461(LC 1), 4=461(LC 1)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-633/587, 3-4=-633/587
BOT CHORD 2-6=-374/547, 4-6=-374/547
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; save=oft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 1-10-0, Interior(1) 1-10-0 to 54-8, Extenor(2) 54-8 to
9-7-7, Interior(1) 9-7-7 to 11-11-0 mne;C-C for members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ql=lb)
2=346,4=346.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
,&WARNING- verily Wspn paramemrs antl READ NOTES ON T— ANO INCLUDED NITEIr REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Daslgn valid for use only wdh Mmek®wnnectom. This —la is based only upon parameters shown, and is for an Individual building component, not
I wss system. Before use, the budding designer ,at vebfy the applicability of design parameters and popery Incorporate this design into the overall
building design. Bramg indicated is to prevent b-ling of individual truss web and/or chord memb—nly. Adda—al—,omary and permanent bracing MiTek'
s always required bo, staGlity antl to prevent collapse with possible persona aq, antl property damage. For general guxance regarding the
labdcatron, smmge, delivery, erection and bracing of lasses and trues systems, see ANS-11 Qualify CNhria, OSB-89 antl Bcsf Building Component g90q Parke Esat BIM.
.4, an/ormetlon available from Tmss Plate InstiMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
F?s1.'SP3�0
4.4 =
3
e
zx3 II
3x4 =
3x4 =
SJ 6
10-0-0
64-8
5d-0
LOADING (par)
SPACING-
2-0-0
CSL
DEFL.
in (I-) Udell
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.23
Vert(LL)
-0.02 6-12 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.18
Vert(CT)
-0.04 6-12 >999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.09
HOR(CT)
0.01 4 n/a
We
BCDL 10.0
Code FBC2017/IP12014
Matrix -MS
Wind(L-)
0.04 6-12 >999
240
Weight: 40 lb FT=20%
LUMBER-
BRACING.
TO CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 4=0-&0
Max H— 2=-97(LC 10)
Max Uplift 2=-346(LC 12), 4=346(LC 12)
Max Grav 2=461(LC 1), 4=461(LC 1)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-619/545, 3-4=-619/545
BOT CHORD 2-6=-346/529, 4-6=-346/529
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 1-10-0, Interior(1) 1-10-0 to 54-8, Extenor(2) 5-4-8 to
8-4-8, Interior(1) 8-4-8 to 11-11-0—;C-C for members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ql=lb)
2=346,4=346.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 9634
9904 Parke East BNd. Tampa FL 33610
Den:
May 6,2020
,&WARNING-va",Wspn paramemrs antl READ NOTES ON T— ANO INCLUDED N1TEfr REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Dealgn valid for use only wdh Mmek®wnneclom. This —la ie based only upon parameters ah.n, and is for an Individual building component, not
I tmss system. Before use, the budding designer ,at vebfy the applicability of design parameters and popery Incorporate this design into the overall
building design. Bramg indicated is to prevent b-ling of individual truss web and/or chord membe,sonly. Adda—al—,omary and permanent bracing MiTek'
s always raquiredfo, staGlity and to prevent collapse with possible pe,sona aq, antl properly damage. For general guxance regarding the
labdcatron, atomge, delivery, erection and bracing of Wasea and trues system., aee ANS-11 Qualify CNhria, OSB-89 antl Bcsf Building Component g90q Parke Esal BIM.
.4, lnyormadon available from Tmss Plate InsgMe, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
4x5 =
3
3M = as 11
Emu
I¢
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) Vdefl
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.35
Vert(LL) 0.09
6-16 >999
240
MT20 2441110
TCDL 7.0
Lumber DOL
1.25
BC 0.21
Vert(CT) -0.04
6-11 >999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.12
Hom(CT) -0.01
4 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matdx-MS
Weight: 50 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 6-0-0 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied
or 6-9-8 oc bracing.
WEBS 2x4 SP No.3
WEDGE
Left: 2x4 SP No.3 , Right: 2x4 SP No.3
REACTIONS. (size) 2=0-3-0, 4=0-3-0
Max Horz 2=-114(LC 10)
Max Uplift 2=-681(LC 12), 4=-681(LC 12)
Max Grav 2=544(LC 1), 4=544(LC 1)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (I c) or less except when shown.
TOP CHORD 2-3=-605/1337, 3-4=-605/1337
BOTCHORD 2-6=-1061/509, 4-6=-1061/509
WEBS 3-6=-622/242
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 6-6-0, Exterior(2) 6-0-0 to
9-6-0, Intedor(1) 9-6-0 to 14-2-0 zone; cantilever left and right exposed ; porch left and right exposed;C-C for members and forces 8
MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100111 uplift at joints) except at -lb)
2=681,4=681.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9904 Parke East BNd. Tampa FL 33910
Data:
May 6,2020
'&WARNING-vedq—is. parameters antl READ NOTES ON T-t ANO INCLUDED NITEa REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT— nett This deagn is based only upon parameters ah.n, and is for an Individual building component, not
I tmss system. Before use, the budding designer ,at vanfy the applicability of design parameters antl propery Incorporate this design into the overall
building design. Bracing indicated is to prevent b—ing of individual truss web and/or chord membe,sonly. Adda—altemporary and permanent bracing MiTek'
s always n paired fo, stalblity and to prevent collapse with possible personal injury antl property damage. For general gux.— regartling the
fabdcatron, atmage, delivery, erection and bracing of Wsaea and truss systama, see ANS-11 Qualify CNhria, OSB-89 antl BCS1 Building Component 6904 parka East BIM.
.4, lnssmsadon available from Tmss Plate I-adta, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
1
T20150983
4.4 = 4x4 —
4 5
kR117110liw1*1
3x5 = sad = 4x8 = ass = sae =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) Vdefl
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.25
Vert(LL)
-0.12 9-17 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.40
Vert(CT)
-0.27 9-17 >907
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.14
HOrz(CT)
0.03 7 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Wind(LL)
0.09 9-17 1999
240
Weight: 891b FT=201
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 5-9-15 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied
or 7-3-12 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 7=0-8-0
Max Horz 2=152(LC 11)
Max Uplift 2=-567(LC 12), 7=-567(LC 12)
Max Grav 2=815(LC 1), 7=815(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1425/1194, 3-4=-1144/964, 4-5=-1020/929, 5-6=-1144/964, 6-7=-1425/1194
BOT CHORD 2-11=-976/1291, 9-11=-623/1020, 7-9=-99W1291
WEBS 3-11=-381/454, 4-11=-194/311, 5-9=194/311, 6-9=-381/454
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 1-10-0, Intenor(1) 1-10-0 to 9-0-0, Exterior(2) 9-0-0 to
15-6-15.
Interior(1) 15-6-15 to 21-6-0 wne;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any Other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at=lb)
2=567.7=567.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING -verify —is. Mra — and READ NOTES ON TNIs AND INCLUDED NITEx REFERENCE PAGE Nl4T/73— 10Poarzp15 BEFORE USE. ��-
Daslgn valid for use only— MITek®wnnec— This d-la ie based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding Designer ,at vebfy the applicability of design ps—a —antl propery Incorporate this design into the overall
building design. Braung indicated is to prevent b—ing of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always roq—d fo, stalbsty antl to prevent collapse with possible personal injury antl properly Damage. For general gux.— regartling the
fabdcatron, atorege, delivery, erection and bracing of Wsaea and truss systama, see ANS-11 Duality criteria, OSB-89 antl Bcsf Building Component 8904 Perke East BIM.
.4, lnyolma8on available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
1-2A 2-&0 SO-0 9-10-0 14-BA 19-11-14 2S2A 304-2 3S&0
-2-0 2-&0 2-1-0 4-10-0 4-10A 53-14 52-2 52-2 53-14
Sces =1:63.1
5x8 =
5 m 12 5.8 = 3x4 11 4x5 = 3x6 = 3x4 11 3x4 = 4x5 =
4 25 26 27 5 28 29 30 6 31 32 7 8 M U 35 36 9 37 38 39 10 4041 42 11
3 cpcp
21�2od3 M 19 45 46
7x10 MT18HB i 4xg = 17 47 48 16 49 50 15 51 14 13 5253 54 12
4.4 _ _ 3x6
3x6 � 3x4 6x6 _3.10 = 3.6 = dxd =
4.00 12 7.10 MT18HS =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) I/defl L/d
PLATES
GRIP
TCLL 20.0
Plate Grip DC1L
1.25
TC 0.46
Vert(LL) -0.61
18 >700 360
MT20
244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.88
V=' CT1 -1.15
18 >370 240
MT18HS
244/190
BCLL 0.0
Rep Stress Incr
NO
WB 0.92
Hom(CT) 0.29
12 n/a n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Wind(LL) 1.02
18 >417 240
Weight: 545111
FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 6-0-0 oc
puriins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied
or 10-0-0 oc bracing, Except:
8-11-3 oc bracing: 18-19.
REACTIONS. (size) 12=Mechanical, 2=0-8-0
Max Horz 2=172(LC 8)
Max Uplift 12=-1537(LC 8), 2=-1580(LC 8)
Max Grav 12=2224(LC 1), 2=2270(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-9948/6792, 3-4=-7473/5096, 4-5=-11322/7772, 5-6=11322/7772, 6-7=-13648/9448.
7-9=-7894/5460,9-10=-7894/5460,10-11=-4806/3329,11-12=-2125/1523
BOT CHORD 20-21=-5790/8345, 19-20=-4888/7118, 18-19=-10186/14752, 6-18=-315/637,
16-17=-1537/2255,15-16=-6557/9482,13-15=-3329/4806,2-21=-6376/9204
WEBS 4-20=-524/873,4-19=-3012/4425,5-19=-357/347,6-19=-3582/2512,16-18=-5000/7219,
7-18=-3059/4385,7-16=-934/797,7-15=-1728/1194,9-15=-375/397, 10-15=-2304/3339,
10-13=-1735/1354,11-13=-3531/5099,3-21=-1479/2178,3-20=-1348/978
NOTES
1) 3-ply truss to be connected together with 10d (0.131"x3") nails as follows:
Top chards connected as follows: 2x4 - 1 row at 0-9-0-
Bottom chords connected as follows: 2x4 - 1 row at 0-9-0 oc.
Webs connected as follows: 2x4 - 1 row at 0-4-0 oc, Except member 194 2x4 - 1 row at 0-9-0 or, member 5-19 2x4 - 1 row at 0-9-0
member 19-6 2x4 - 1 row, at 0-9-0 oc, member 16-18 2x4 - 1 row at 0-9-0 oc, member 18-7 2x4 - 1 row at 0-9-0 oc, member 7-16
2x4 - 1 row at 0-9-0 oc, member 15-7 2x4 - 1 row at 0-9-0 oc, member 9-15 2x4 - 1 now at 0-9-0 oc, member 15-10 2x4 - 1 row at
0-9-0 oc, member 10-13 2x4 - 1 row at 0-9-0 oc, member 11-13 2x4 - 1 row at 0-9-0 oc, member 21-3 2x4 -1 row at 0-9-0 oc,
ember 3-20 2x4 - 1 row at 0-9-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front IF) or back (B) face in the LOAD CASE(S) section. Ply to
ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
3) Unbalanced roof live loads have been considered for this design.
4) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=36ft; eave=5ft; Cat.
11; Exp C; Eliot, GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
5) Provide adequate drainage to prevent water ponding.
6) All plates are MT20 plates unless otherwise indicated.
7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
8) ` This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
9) Refer to girder(s) for truss to truss connections.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 6634
6906 Parke East BNd. Tampa FL 33610
Data:
IU) Hearing at lolnt(s) 2 considers parallel to grain value using ANSI/ I PI 1 angle to grain tormula. building designer should verity May 6,2f
capacity of bearing surface.
'&WARNING -Vera, -is. pa_antl READ NOTES ON TNIs AND INCLUDED hisma REFERENCE PAGE Nl47/73- 10Po4rzp15 BEFORE USE. ��-
Dealgn valid for use only- MIT-nnectom. This -la is based only upon parameters shown, and is for en ,ndividual bu,idi,g component, not
I truss system. Before use, the assaing designer ,at verify the applicability of design parameters antl pmpedy dwrpo,ate this design into the overall
building design. Braung indicated is b prevent b-ing of individual truss web and/or chord membemonly. Additionaltemporaryandpermanentbmcing MiTek'
s always reguired for staGlily and to prevent collapse with possible pe,sonal injury antl Droperry damage. For general guidance regard, the
fabdcatron, ammge, delivery, erection antl bracing of Wasea and truss systama, see ANS-11 Quality Criteria, OSB-89 antl BCV Building Component g90q Parke East BIM.
.4, lnss matlon available from Truss Plate InsdMe, 218 N. Lee Street, suite 312, N ddlm, VA 22314. Tampa. FL M610
NOTES-
11) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at -lb) 12=1537, 2=1580.
12) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 273 lb down and 271 lb up at 5-0-0, 117lb down and 108 lb up at
7-0-12, 117 lb down and 108 lb up at 9-0-12, 1171b down and 1081b up at 11-0-12, 1171b down and 108 Ib up at 13-0-12, 122 Ib down and 135 Ib up at 15-0-12, 122 It,down and 135 lb up at 15-10-4, 122 lb dawn and 135 lb up at 17-10-0, 122 lb down and 135 lb up at 19-10-4, 122 lb down and 135 lb up at 21-10-0, 122 lb down and
1351b up at 23-10-4, 122 lb down and 135 lb up at 25-10-4, 122 lb down and 135 lb up at 27-10-4, 122 It, down and 135 lb up at 29-10-4, and 122 lb down and 135 lb
up at 31-104, and 122 Ib down and 13516 up at 33-104 on top chord, and 90 lb down and 65 lb up at 5-0-0, 63 lb down and 52 Ito up at 5-0-12, 63 lb down and 52 lb
up at 7-0-12, 63 lb dawn and 52 lb up at 9-0-12, 63 lb down and 52 lb up at 11-0-12, 63 Ib down and 52 lb up at 13-0-12. 48 lb down and 24 lb up at 14-9-12, 48 lb
down and 24 lb up at 15-104. 48 lb down and 24 lb up at 17-104, 48 lb down and 24 lb up at 19-10-4, 48 It, down and 24 lb up at 21-104, 48 lb down and 24 lb up at
23-10-4, 48 lb down and 24 lb up at 25-10-4, 48 lb down and 24 lb up at 27-10-4, 48 lb down and 24 lb up at 29-104, and 48 It, down and 24 lb up at 31-104, and 48 lb
down and 24 lb up at 33-104 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increa-1.25
Uniform Loads (plf)
Vert: 14=-54,4-11=-54, 18-21=-20, 12-17=-20, 21-22=-20
Concentrated Loads (lb)
Vert: 4=-110A 6=-60(F) 14=-01(F) 20=-142(F=-63) 16=-41(F) 18=-41(F) 26=-46(F) 27=-46(F) 28=-46(F) 29=-46(F) 31=-60(F) 32=-60(F) 33=-60(F) 35=-60(F)
36=-60(F) 37=-60(F) 38=-60(F) 40=-60(F) 41=-60(F) 42=-60(F) 43=-63(F) 44=-63(F) 45=63(F) 46=-63(F) 47=41(F) 48=41(F) 49=41(F) 50=41(F) 51=41(F)
52=41(F) 53=41(F) 54=41(F)
'&WARNING-.", Wsige parameters antl READ NOTES ON T ANO INCLUDED N1TEx REFERENCE PAGE Nl4T/73-14-015 BEFORE USE. M�'
Deagn valid for use only 01, Mrek®wnnec- This tleagn is based only upon parameters ahown, and is for en Intlivitlual builtling component, not
a buss system. Before use, the builtling designer must verify the applicability of design parameters antl propery Incorporate this design into the overall
builtlingd ign. Bradngindiratetlistopreventbullingofintlivitlualtrussw¢band/orchordmembersonly. Additional temporary andpermanentbracing MiTek'
s always reguired for-ity and to prevent collapse with possible personal injury antl property damage. For general gu,d.- rega d, the
fabdcatron, atorege, delivery, erection antl bracing of Wsaea antl trues syatema, see ANS-11 Qualify Criteria, OSB-89 antl BCSi Building Component g9Dq Parke East BIM.
Safay lnyolm - available from Truss Piste I -Me, 218 N. Lee Street, Suite 312, -a-, VA 22314. Tamps, FL M610
Type
T20150985
FRI!�HQ: OIB
3.4 II
4.8 = 4.4 = 3.4 = 4.6 = 3.4 = 3x4 = 4x6 = 4x4 = 4.8 =
1 21 22 2 23 24 325 26 4 5 27 28 ' 6 W 31 7 32 a 33 934 M 36 10
20 11
M 11 37 38 19 39 18 17 4041 42 1643 44 45 15 d8 14 13 4] 48 49 12 50 51 3x6 11
4x8 = 3x8 = 414 3.8 = 3x4 = 5.6 = 4.4 = 4x6
LOADING (pal)
SPACING-
2-0-0
CSI.
DEFL.
in 111 War L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TIC 0.46
Vert(LL)
0.59 15-16 >719 240
11-0 2441110
TCDL 7.0
Lumber DOL
1.25
BC 0.70
Vert(CT) -0.65
15-16 >653 240
BCLL 0.0
Rep Stress Incr
NO
WB 0.94
Hom(CT)
0.11 11 n/a n/a
BCDL 10.0
Code FBC20177rP12014
Matrix -Ms
Weight: 3891b FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 5-1-8 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied
or 6-5-2 oc bracing.
REACTIONS. (size) 20=Mechanical, 11=Mechani
Max Uplift 20=-2021(LC 8), 11=2018(LC 8)
Max Grev 20=2818(LC 1), 11=2815(LC 1)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (Ib) Or less except when shown.
TOP CHORD 1-20=-2708/2006, 1-2=-4316/3102, 2-3=-7100/51003-5=-8507/6114, 5-6=-8507/6114,
6-7=-8510/6116,7-9=-7103/5107,9-10=-4315/3101:10-11=-27072004
BOT CHORD 17-19=-3102/4316, 16-17=-5lOOf71OO, 15-16=-6116/8510, 13-15=-510777103,
12-13=-3101/4315
WEBS 1-19=-3544/4932,2-19=-2220/1787,2-17=-2316/3227,3-17=-1362/1150,
3-16=-1175/1631, 5-16=-556/578, 6-15=553/574, 7-15=-117011631, 7-13=-137011156,
9-13=-2325/3231,9-12=-2217/1786,10-12=-3543/4931
NOTES-
1) 2-ply truss to be connected together with 1 Old III 131'x3") nails as follows:
Top chords connected as follows: 2.4 - 1 row at 0-9-0 oc.
Bottom chards connected as follows: 2.4 - 1 now at 0-9-0 oc.
Webs connected as follows: 2. - 1 row at 0-9-0 x.
2) All loads are considered equally applied to all plies, except If noted as front (F) or back (13) face in the LOAD CASE(S) section. Ply to
ply connections have been provided to distribute only loads noted as (F) Or (B), unless otherwise indicated.
3) Wind: ASCE 7-10; VUI1=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=36ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 par bottom chord live load nonconcurrent with any other live loads.
6) - This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will Fit between the bottom chord and any Other members.
7) Refer to girder(s) for truss to truss connections.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1001b uplift at joint(s) except at -lb)
20=2021,11=2018.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 6634
6604 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
Aidwa" G-Vergy Wsign Para -and READ NOTES ON TN AND INCLUDED NITEx REFERENCE PAGE Nl4T/73n 10Poarzp15 BEFORE USE. ��-
Das valid for use only v, h MITek®wnneclam. This deagn is based only upon parameters shown, and is for en ddivid.al la. lding component, not
.Was system. Before use, me builCing designer must vedy the applicability or tlesi9n parameters antl properly Incorporate tl,ls design into the overall
building design. Bracing indicated is to prevent-lids&individual truss web and/or chord membe,sonly. Adda-altemp r, and permanent bracing MiTek'
s always regui,ed lo, stalblity and to prevent collapse with possible personal injury and pmpe,ry damage. For general gu,da . regartling the
fabd.dt ammge, delivery, erection and bracing of Wawa and W sa syatema, see ANSI PIl quality CdNria, OSB-89 and BCS1 Building Component - Parke East BIM.
Salaty rnyolm rid available /ram Tmss Plate Insdads 218 N. Lee Street, Suite 312, Nexa , VA 22314. Tampa, FL M610
NOTES-
9) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 152 lb down and 190 lb up at 1-9-12, 152 lb down and 190 lb up at
3-9-12, 152 lb down and 190 lb up at 5-9-12, 152 lb down and 190 lb up at 7-9-12, 152 Ito down and 190 It, up at 9-9-12, 152 lb down and 190 lb up at 11-9-12, 1521b
down and 190 lb up at 13-9-12, 152 It, down and 19011, up at 15-9-12, 152 lb down and 190 It, up at 17-9-12, 152 lb down and 190 lb up at 19-9-12, 152 lb down and 190
Ib up at 21-9-12, 152 lb down and 1901b up at 23-9-12, 152 lb down and 190 lb up at 25-9-12, 152 lb dawn and 190 lb up at 27-9-12, 1521b down and 1901b up at
29-9-12, and 152 lb down and 190 lb up at 31-9-12, and 152 lb down and 190 lb up at 33-9-12 on lop chord, and 85 lb down and 33 It, up at 1-9-12, 85 lb down and 33 It,
up at 3-9-12, 851b down and 33 lb up at 5-9-12, 85 lb down and 331b up at 7-9-12, 85 Ito down and 33 lb up at 9-9-12, 85 lb down and 33 Ito up at 11-9-12, 85 lb down
and 33 lb up at 13-9-12, 851b down and 33 lb up at 15-9-12, 85 Ito down and 33 lb up at 17-9-12, 85 Ito down and 33 lb up at 19-9-12, 85 lb down and 331b up at 21-9-12
, 85 lb down and 33 lb up at 23-9-12, 85 lb down and 331b up at 25-9-12, 85 lb down and 331b up at 27-9-12, 85 lb down and 33 lb up at 29-9-12, and 85 lb down and 33
Ib up at 31-9-12, and 851b down and 33 lb up at 33-9-12 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (pit)
Vert: 1-10=54, 11-20=-20
Concentrated Loads (lb)
Vert: 4=-111(F) 18=-67(F) 8=-111(F) 14=67(1`) 21=111(F) 22=-111(F) 23=-111(F) 24=111(F) 25=-111(F) 26=-111(F) 27=111(F) 28=-111(F) 29=-111(F)
30=-111(F)31=-111(F)32=-111(F)33=-111(F)35=-111(F)36=-111(F)37=-67(F) 38=-67(F)39=-67(F)40=67(F)41=-67(F)42=-67(F)43=-67(F)44=-67(F)
45=-67(F) 46=-67(F) 47=-67(F) 48=-67(F) 49=-67(F) 50=-67(F) 51=-67(F)
'&WARNING -Verily Wsige parameters antl READ NOTES ON T ANO INCLUDED NITEN REFERENCE PAGE Nl4]/73-14-015 BEFORE USE. ��'
Dasgn valid for use only- MITak® connectors. This deagn is based only upon parameters shown, and is for an Individual building component, not
a tN55 system. Before use, the building designer must verify the applicability of design parameters antl properly Incorporate thls design into the overall
building design. Braung indicated is b prevent b-mg of individual truss weband/or chord membarsonly. Additionaltemporaryandperrnane.t bracing MiTek'
s always repaired for stadlity and to prevent collapse with possible personal injury antl property damage. For general guu.-regartling the
fabdcatron, storage, delivery, erection and bracing of Wasea and truss syatema, see ANS-11 Oaalify Cr-, OSB-89 antl Bc3/Bui/dme Component g90q parka East BIM.
Safay lnyo7madon available from Tmss -te In-, 218 N. Lee Street, Suite 312, Nea -, VA 22314. Tampa, FL M610
SM0
iTiFEs
MiTek'
RE: 76703 -
Site Information:
Customer Info: FAT ROBASSON Project Name: PHILLIPE Model:
Lot/Block: Subdivision:
Address: UNKNOWN
City: FORT PIERCE State: FL
No. Seal# Truss Name Date
29 T20150990
GRH
5/6/20
30 T20150991
GIRL
5/6/20
31 T20150992
GRR
516/20
32 T20150993
J1
5/6/20
33 T20150994
J3
5/6/20
34 T20150995
J5
5/6/20
35 T20150996
J5C
516/20
36 T20150997
J7
516/20
37 T20150998
JA
5/6/20
38 T20150999
JB
5/6/20
39 T20151000
JC
5/6/20
40 T20151001
JC3
5/6/20
41 T20151002
JD
5/6/20
42 T20151003
JE5
516/20
43 T20151004
KJ5
516/20
44 T20151005
KJ7
5/6/20
45 T20151006
KJA
5/6/20
46 T20151007
KJB
5/6/20
47 T20151008
KJC
5/6/20
48 T20151009
KJD
5/6/20
49 T20151010
MV2
5/6/20
50 T20151011
MV4
5/6/20
51 T20151012
MV6
5/6/20
52 T20151013
MV8
5/6/20
53 T20151014
V4
5/6/20
54 T20151015
V8
516/20
55 T20151016
V12
516/20
56 T20151017
VA
5/6/20
57 T20151018
VB
5/6/20
58 T20151019
VC
5/6/20
59 T20151020
VD
516/20
2 of 2
MiTek USA, Inc.
6904 Parke East Blvd.
Tampa, FL 33610-4115
T20150986
Girder 11 1
8.330 s Me
ID:170y9y4e_wm9VIH6C
9-9-8 12-7-0
2-9-8 ~ 2-" ~
Sx6 =
3x4 = 5.0 =
3 17 4 18 5
3z5 = sad =ax6 = =� 3.5 =
FY�1r-SlkFfa
Ig
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) War
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.55
Vert(LL)
0.19 8-10 >999
240
MT20 2441110
TCDL 7.0
Lumber DOL
1.25
BC 0.60
Vert(CT) -0.22
8-10 >999
240
BCLL 0.0
Rep Stress Incr
NO
WB 0.30
Hom(CT)
0.07 6 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matnx-MS
Weight: 83 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 3-6-13 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied
or 5-2-1 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 6=0-8-0
Max Horz 2=122(LC 7)
Max Uplift 2=-1107(LC 8), 6=1108(LC 8)
Max Grav 2=1502(LC 1), 6=1502(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3149/2211, 3-4=-2881/2128, 4-5=-2882/2128, 5-6=-3149/2211
BOT CHORD 2-10=-1886/2945, 8-10=-2029/2999, 6-8=-1886/2845
WEBS 3-10=-420/791, 4-10=-274/29614-8=274/296, 5-8=420f791
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Can.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load noncencument with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joints) except at -lb)
2=1107,6=1108.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 211 Ib down and 339 Ib up at
7-0_0 152 It, down and 190 lb up at 9-0-12, and 152 It, down and 190 It, up at 10-6-4, and 211 lb down and 339lb up at 12-7-0 on
top chord, and 400 lb down and 2871b up at 7-0-0, 85 Ib dawn and 33 lb up at 9-0-12, and 85 Ib dawn and 331b up at 10-6-0, and
400 It, down and 287 It, up at 12-64 on bottom chord. The design/selection of such connection device(s) is the responsibility of
others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back fie.
LOAD CASE(S) Standard
11 Dead + Roof Live (balanced): Lumber Increas-1.25, Plate Increa-1.25
Uniform Loads (p1f)
Vert: 1-3=-54, 3-5=-54, 5-7=-54, 11-14=-20
Concentrated Loads (Ib)
Vert: 3=-137(F)5=-137(F) 10=-400(F)8=400(F) 17=-111(F) 18=-111(F) 19=-67(F)20=-67(F)
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq—is. Parameters and READ NOTES ON T-t ANO INCLUDED NITEK REFERENCE PAGE Nl4T/73— 10Poarzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT—radeclom. This —la is based only upon parameters shown, and is for en Individual building component, not
I truss system. Before use, the building designer ,at vebfy the applicability of design parameters antl pro dy Incorporate this design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord membemonly. Adddionaltemporary and permanent bracing MiTek'
s always required rid, starblity and to prevent collapse with possible personal injury antl properly damage. For general gux.—regartling the
fabdcatron, smmge, delivery, erection and bracing of Wawa and truss systems, see ANS-11 Qualify Criteria, OSB-89 antl Bc8/Buifding Component 6904 Perke East BIM.
.4, lnyolmadon available from Truss Plate In58Me, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
Girder 1 1 I T20150987
3.19 12 4x4 =
4xa =
4 20 21 22 5 23
l
FTs1:�SPYlO
Ia
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) War
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.11
Vert(LL) -0.02
10 -999
360
MT20 2-110
TCDL 7.0
Lumber DOL
1.25
BC 0.15
Vert(CT) -0.03
10 >999
240
BCLL 0.0
Rep Stress Incr
NO
WB 0.07
H..X 0.01
7 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Wind(LL) 0.03
10-11 >999
240
Weight: 48 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 6-0-0 oc pur ins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied
or 10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 7=0-8-0
Max Horz 2=-50(LC 6)
Max Uplift 2=-379(LC 8), 7=-379(LC 8)
Max Grav 2=519(LC 36), 7=519(LC 37)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-945/493, 3-4=-987/578, 4-5=-954/579, 5-6=-987/578, 6-7=-945/493
BOT CHORD 2-12=-387/870, 11-12=-375/875, 10-11=462/961, 9-10=-369/877, 7-9=-384/873
NOTES-
1 ) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vu11=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf, h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ql=lb)
2=379, 7=379.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 154 lb down and 2416 up at
1-2-2, 33 lb down and 52 lb up at 3-0-0, 1021b down and 80 lb up at 4-0-6, 97 It
down and 73 lb up at 5-4-8, 102 Ib down and 80 lb
up at 6-8-10, and 33 lb down and 52 Ib up at 7-9-0, and 154 lb down and 241b up at 9-6-14 on top chord, and 31 Ib down and 7 Ib
up at 1-2-2, 23 lb down and 8 It, up at 3-0-0, 42 lb down and 12 lb up at 4-0-6, 2716 down and 12 lb up at 54-8, 4216 down and
12 lb up at 6-8-10, and 23 lb down and 8 lb up at 7-9-0, and 31 Ib down and 7 It, up at M-14 on bottom chord. The
design/selection of such connection device(s) is the responsibility of others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increa-1.25, Plate Increa-1.25
Uniform Loads (plf)
Vert: 1-3=-54, 3-4=-54,4-5=-54, 5-6=-54, 6-8=-54, 13-16=-20
Concentrated Loads (lb)
Vert: 4=-9(F) 5=-9(F) 12=5(F) 11=-15(F) 10=-15(F)9=5(F)21=-8(F)24=-4(F)25=-14(F)26=4(F)
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq—is. Parameters and READ NOTES ON T ANO INCLUDED AUMEK REFERENCE PAGE Nl4]/73— 10PoIrzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT—radectom. This —la is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the building designer ,at vebfy the applicability of design parameters antl pro dy Incorporate this design into the overall
building design. Bracing indicated is to prevent b-ling of individual truss web and/or chord memb—nly. Adddionaltemporary and permanent bracing MiTek'
s always requirod fo, starblity and to prevent collapse with possible personal injury antl Dropedy damage For general guxance raga d, the
fabdcatron, smmge, delivery, erection and bracing of lasses and trues systems, see ANS-11 quality criteria, OSB-89 antl Bc8/Buifding Component g90q Perks East BIM.
.4, lnyolmadon available from Tmss Plate InstiMe, 218 N. Lee Street, Suite 312, A —chid,, VA 22314. Tampa, FL M610
1
T20150988
3.29 12
4x4
5x10 % 21 22 4 23 24 5 5.10
3x4 =
3x8 II
FY'1r.SP1-X8
Id
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) War L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.28
Vert(LL) 0.07
9 >999 240
MT20 2441110
TCDL 7.0
Lumber DOL
1.25
BC 0.21
Vert(CT) 0.06
9 >999 180
BCLL 0.0
Rep Stress Incr
NO
WB 0.09
Hom(CT) -0.02
6 n/a n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MS
Weight: 62 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 6-0-0 oc pur ins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied
or 6-0-7 oc bracing.
WEBS
2x4 SP No.3
WEDGE
Left: 2x4 SP No.3 , Right: 2x4 SP No.3
REACTIONS.
(size) 2=0-3-0, 6=0-3-0
Max Horz 2=96(LC 24)
Max Uplift 2=-995(LC 8), 6=-995(LC 8)
Max Gmv 2=766(LC 17), 6=766(LC 18)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown
TOP CHORD
2-3=-1137/1537, 3-4=-1079/1579, 4-5=-1079/1579, 5-6=-1137/1537
BOT CHORD
2-10=-1419/1007, 9-10=-1418/1008, 8-9=-1390/1008, 6-8=-1392/1007
WEBS
4-9=-263/235
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); cantilever left and right exposed ; porch left and right exposed; Lumber DOL=1.60
plate grip DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ql=lb)
2=995, 6=995.
6) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 631b down and 14216 up at
4-7-14, 85 lb down and 153 lb up at 5-6-8, 97 It, down and 161 lb up at 6-0-0, 78 lb down and 152 lb up at 6-6-0, 97 Ib down and
161 Ib up at 7-0-0, and 85 Ib down and 153 lb up at 7-5-8, and 63 lb down and 142 Ib up at 8-4-2 on top chord, and 26lb down and
4 lb up at 4-7-14, 36 lb down and 44 It,up at 5-6-8, 53 lb down and 6716 up at 6-0-0, 43 lb down and 61 It,up at 6-6-0, 53 lb down
and 67 lb up at 7-0-0, and 36 lb down and 44 Ib up at 7-5-8, and 26 Ib down and 4 lb up at 8-4-2 on bottom chord. The
design/selection of such connection device(s) is the responsibility of others.
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead+ Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=-54, 3-4=-54,4-5=-64, 5-7=-54, 11-16=-20
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9904 Parke East BNd. Tampa FL 33910
Data:
May 6,2020
,&WARNING -welly Wsi9n Parameters antl READ NOTES ON nvis ANO INCLUDED NITEx REFERENCE PAGE Nl4]/73— 1pPoarzpl5 BEFORE USE. ��-
Dealgn valid for use only— MIT- wnneclom. This d-la is based only upon peramstars shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl propery Incorporate this design into the overall
building design. Brarmgiadicated is b prevent b—irs of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always ropairedfo, stalblity and to prevent collapse with possible personal injury antl properly damage. For general gux.—rega,tling the
fabdcatron, atmage, delivery, erection and bracing of Wawa and truss systama, see ANS-11 Quality CrlNna, OSB-89 and Bcsf Building Component 8904 Perks East BIM.
.4, lnrormatron available from Truss Plate InsdMe, 218 N. Lee Street, Suite 312, Nex —, VA 22314. Tampa, FL M610
LOAD CASE(S) Standard
Concentrated Loads (Ib)
Vert: 4=-58(F) 10=0(F) 9=-34(F)8=0(F)21=-38(F)22=-64(F)23=-64(F)24=38(F)25=-21(F)26=-30(F)27=-30(F)28=-21(F)
,&WARNING-Verey—is. paramemrs antl READ NOTES ON TNIS ANO INCLUDED NITEN REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��'
Desgn valid for use only— MIT— nett This deagn is based only upon parameters shown, and is for an Individual building component, not
a buss system. Before use, the building designer must verify the applicability of design parameters antl properly Incorporate thls design into the overall
building design. B.drg indicated is to prevent b-ling of individual truss weband/or chord membersonly. Additionaltemporaryandpermanentbracing MiTek'
s always repaired for staGlity and to prevent collapse with possible personal injury antl pmpedy damage. For general gu,d.— raga d, the
fabdcatron, —a., delivery, erection and bracing of Wasea and truss syatema, see ANS-11 Duality criteria, OSB-89 antl Bcsf Building Component g9Oq parka Eest BIM.
Safay lnyolm — available from Tmss -te I -Me, 218 N. Lee Street, Suite 312, NeR —, VA 22314. Tampa, FL M610
T20150989
Girder 11
1
8.330 a Mar:
ID:170y9y4e wm9yIH6Dt(c7L
10-2-0 13.4-0
3-2-0 3-2-0
Sze 2.3 II 5x8 =
3 18 4 19 5
4.6 = 2.3 11 4z6 3x8 = 2.3 II 4x5 =
kR1171101iwlC ]
I�
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) War L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.60
Vert(LL) 0.21
9 >999 240
MT20 2441110
TCDL 7.0
Lumber DOL
1.25
BC 0.64
Vert(CT) -0.23
9 >999 240
BCLL 0.0
Rep Stress Incr
NO
WB 0.24
Hom(CT) 0.08
6 n/a n/a
BCDL 10.0
Code FBC2017rrP12014
Matnx-MS
Weight: 90 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 34-5 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied
or 4-10-15 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 6=0-8-0
Max Ho 2=122(LC 24)
Max Uplift 2=-1196(LC 8), 6=-1196(LC 8)
Max Grav 2=1619(LC 1), 6=1619(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-3437/2438, 3-4=-3429/2556, 4-5=-3429/2556, 5-6=-3437/2438
BOT CHORD 2-11=-2094/3111, 9-11=-2107/3139, 8-9=-2107/3139, 6-8=-2094/3111
WEBS 3-11=-266/626, 3-9=-507/508, 4-9=-430/476, 5-9=-508/508, 5-8=-266/626
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; VUlt=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; save=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonooncurrent with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joints) except at -lb)
2=1196,6=1196.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 211 Ib down and 339 Ib up at
7-0_0 152 It, down and 1901b up at 9-0-12, 152 Ib down and 190 Ib up at 10-2-0, and 1521b down and 1901b up at 11-3-4, and
211 lb down and 3391b up at 13-4-0 on tap chord, and 400 lb down and 287 lb up at 7-0-0, 85 lb down and 33 lb up at 9-0-12, 85
lb down and 33 It, up at 10-2-0. and 85 It, down and 33 lb up at 11-34, and 400 lb down and 287 Ib up at 13-34 on bottom chord.
The design/selection of such connection device(s) is the responsibility of others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increa-1.25, Plate Increa-1.25
Uniform Loads (p1f)
Vert: 1-3=-54, 3-5=-54, 5-7=-54, 12-15=-20
Concentrated Loads (lb)
Vert: 3=-137(B)5=-137(B)11=300(B)9=-67(B)4=-111(B)8=-400(B)18=-111(B)19=-111(B)20=-67(B)21=-67(B)
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 6634
g904 Padre East Blvd. Tampa FL 33610
pare:
May 6,2020
A wARN1NG-verily—is. pa ram antl NEAO NOTES ON TNIS AND INCLUDED N1TEx REFERENCE PAGE Nl4]/73—la-2015 BEFORE USE. ��-
Deagn valid for use only— MIT—nneclom. This tleagn ie based only upon parameters shown, and is for en Individual building component, not
I itsystem. Before use, the budding designer must vebfy the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to preventb-ling of individual truss web and/or chord memb—nly. Additionaltemporary and permanent bracing MiTek'
s always repaired fo, starblity and to prevent wllapse with possible personal injury antl properly damage. For general gux.— rega d, the
fabdcatron, atomge, delivery, erection and bracing of Wasea and truss syatema, see ANS-11 Qualify CNhria, DSB-89 and Bcal Building Component g9pq Perks East BIM.
.4, In/ormetlon available from Truss Piste In—, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
GIRDER
T20150990
3
4M II
0
3.10 11 -"- — """"" 7.8 = 3.10 11 HUS26
THD26-2 HUS26 HUS26
&Y' 7Ig1x14k1
Ig
LOADING (psf)
SPACING-
2-0-0
CS1.
DEFL.
in (loc) I/deft
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.58
Vert(LL)
0.26 7-12 >924
240
MT20 2441190
TCDL 7.0
Lumber DOL
1.25
BC 0.98
Vert(CT) -0.31
7-12 >779
240
BCLL 0.0
Rep Stress Incr
NO
WB 0.92
Hom(CT)
0.08 6 n/a
n/a
BCDL 10.0
Code FBC2017/rP12014
Matrix -MS
Weight: 3221b FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 6-0-0 oc puriins.
BOT CHORD 2x6 SP No.2
*Except'
BOT CHORD
Rigid ceiling directly
applied
or 10-0-0 oc bracing.
6-9: 2x6 SP 240OF 2.0E
WEBS 2x4 SP No.3
REACTIONS. (size) 6=0-8-0, 2=0-B-0
Max Horz 2=167(LC 24)
Max Uplift 6=-4621(LC 8), 2=-3408(LC 8)
Max Grav 6=7134(LC 1), 2=5019(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-12552/8394, 3-0=-9695/6474, 4-5=-9726/6490, 5-6=1366618914
BOT CHORD 2-10=-7641/11541, 8-10=-7641/11541, 7-8=-8153/12615, 6-7=-8153/12615
WEBS 4-8=4840/7279, 5-8=-4694/3050, 5-7=-2471/4018, 3-8=-3327/2398, 3-1 0=-1 985/2924
NOTES
1) 3-ply truss to be connected together with 1 Old (0.131"x3") nails as follows:
Top chords connected as follows: 2x4 - 1 row at 0-9-0ac.
Bottom chords connected as follows: 2x6 - 3 rows staggered at 0-4-0 oc.
Webs connected as follows: 2x4 - 1 row, at 0-9-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to
Ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
3) Unbalanced roof live loads have been considered for this design.
4) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=4511; L=24ft; save=oft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
6) - This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at -lb)
6=4621, 2=3408.
8) Use USP THD26-2 (With 18-16d nails into Girder 8 12-1 Old nails into Truss) or equivalent at 7-1-8 from the left end to connect
truss(es) to front face of bottom chord.
9) Use USP HUS26 (With 14-16d nails into Girder 8 6-16d nails into Truss) or equivalent spaced at 2-0-0 oc max. starting at 9-0-12
from the left end to 19-0-12 to connect truss(es) to front face of bottom chord.
10) Fill all nail holes where hanger is in contact with lumber.
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Incmase=1.25, Plate Increase=1.25
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL cart 6634
6604 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
AWARNING-vedq—is. Parameters and READ NOTES ON T-t AND INCLUDED MITEK REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Design valid for use only— MITek®wnnec— This deagn is based only upon parameters ah.n, and is for en Individual building component, not
I tmss system. Before use, the building designer ,at vebfy the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always required fo, stalblity and to prevent collapse with possible personal injury antl propedy damage. For general gu,d.— regartling the
fabdcatron, atorage, delivery, erection and bracing of Wawa and truss systama, see ANS-11 Quality CNhria, OSB-89 antl Bcsf Buffdsdg Component 6904 Perks East BIM.
.4, lnyolmadon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
LOAD CASE(S) Standard
Uniform Loads (pif)
Vert: 1-4=-54, 4-6=-54, 2-6=-20
Concentrated Loads (Ib)
Vert: 12=-1300(F) 15=-2798(F) 16=-1289(F) 17=-1300(F) 18=-1300(F) 19=-1300(F) 20=-1300(F)
,&WARNING-.",Wsi3e paramemrs antl REAR N0TE30N TNIS AND—L—D NITEN REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��'
Dasgn valid for use only— MIT— nn.ld- Thia desgn is based only upon parameters ah.n, and is for en Individual building component, not
a tmss system. Before use, the building designer must verify the applicability of design parameters antl properly Incorporate thls design into the overall
building design. Braung indicated is to prevent b—ing of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always re —,! for staGlity and to prevent collapse with possible personal injury antl pmpedy damage. For general gu,d.— raga d, the
fabdcatron, —a., delivery, erection and bracing of Wows and trues syatema, see ANS-11 Qualify CNhria, OSB-89 antl BCs!Building Component g91M Parke East BIM.
Safay lnyolm — available from Tmss -te In,—, 218 N. Lee Street, Suite 312, NeR —, VA 22314. Tampa, FL M610
&R' 1$Relil
Ing
Ia
5.6 = THDH26-3 54 =
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr NO
Code FBC2017rrP12014
CSI.
TC 0.39
BC 0.58
WB 0.76
Matnx-MS
DEFL. in (loc) "deftL/d
Vert(LL) 0.14 S7 >929 240
Vert(CT) -0.16 S7 >786 240
Hom(CT) 0.03 4 n/a n/a
PLATES GRIP
MT20 244/190
Weight: 95 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structuralwood sheathing directly
applied or 6-0-0 oc puffins.
BOT CHORD 2x6 SP 240OF 2.0E BOT CHORD Rigid ceiling directly applied or
10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 4=0-8-0, 2=0-8.0
Max Horz 2=96(LC 24)
Max Uplift 4=-2254(LC 8), 2=-1538(LC 8)
Max Grav 4=3444(LC 1), 2=2215(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-5667/3767, 3-4=-5623/3741
BOT CHORD 2-5=-3390/5191, 4-5=-3390/5191
WEBS 3-5=-2601/3979
NOTES-
1) 2-ply truss to be connected together with 1 Old (0.131"x3") nails as follows:
Top chords connected as follows: 2x4 - 1 row, at 0-9-0..
Bottom chards connected as follows: 2x6 - 2 rows staggered at 0-7-0 oc.
Webs connected as follows: 2x4 - 1 row at 0-4-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to
Plyconnections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
3) Unbalanced roof live loads have been considered for this design.
4) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
This item has been
5) This truss has been designed for a 10.0 pef bottom chord live load nonconcument with any other live loads.
electronically Signed and
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
sealed b Lee, Julius, PE
y
will fit between the bottom chord and any Other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100lb uplift atjoint(s) except Ql=lb)
using a Digital Signature.
4=2254, 2=1538.
Printed copies of this
8) Use USP THDH26-3 (With 20-16d nails into Girder 8 8-16d nails into Truss) or equivalent at 5-2-4 from the left end to connect
document are not considered
truss(es) to back face of bottom chord.
signed and sealed and the
SI g
9) Use USP HUS26 (With 14-16d nails into Girder 8 6-16d nails into Truss) or equivalent spaced at 2-0-0 oc max. starting at 7-0-12
from the left end to 9-0-12 to conned truss(es) to back face of bottom chord.
signature must be Verified
10) Fill all nail holes where hanger is in contact with lumber.
On any electronic Copies.
LOAD CASE(S) Standard
Julius Lee PE No. 34809
1) Dead + Roof Live (balanced): Lumber Increa-1.25, Plate Increa-1.25
MiTak USA, Inc. FL Cart 9634
9964 Pane East Blvd. Tampa FL 33610
Uniform Loads (plf)
Date:
Vert: 1-3=-54, 3-4=-54, 2d=20
May 6,2020
AWARNING-w4f, sl9n pare 1 antl READ NOTES ON TNIs AND INCLUDED NITEK REFERENCE PAGE Nl4T/73n 10Poarzpf5 BEFORE USE. ��-
Dasign valid for use only with MITek®wnneclom. This dasgn is based only upon parameters shown, and is for en Individual building component, not
I itsystem. Before use, the building designer must verify the applicability of design parameters antl propery Incorporate thls design into the overall
building design. Bradng indicated is b prevent budling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always reps d fo, shlliry and to prevent collapse with possible personal injury antl properly damage. For general guxtl . regarding the
fabncatron, smmge, delivery, erection antl bracing d Wawa antl trues syatema, see ANS-1 qualify CrlNria, OSB-89 antl Bcs!Building Component g9Dq Perks Easl BIM.
.4, In/olmetlon available from Tmss Plele Ins , 218 N. Lee Street, Suite 312, Neea , VA 22314. Tampa, FL M610
LOAD CASE(S) Standard
Concentrated Loads (lb)
Vert: 5=-2204(B) 10=-1299(B) 1 1=-1299(B)
,&WARNING-Verey—is. paramemrs antl READ NOTES ON TNIS ANO INCLUDED NITEN REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��'
Desgn valid for use only— MIT— nett This deagn is based only upon parameters shown, and is for an Individual building component, not
a buss system. Before use, the building designer must verify the applicability of design parameters antl properly Incorporate thls design into the overall
building design. B.drg indicated is to prevent bulling of individual truss weband/or chord membersonly. Additionaltemporaryandpermanentbracing MiTek'
s always repaired for staGlity and to prevent collapse with possible personal injury antl pmpedy damage. For general gu,d.— raga d, the
fabdcatron, —a., delivery, erection and bracing of Wasea and truss syatema, see ANS-11 Duality cn—, OSB-89 antl Bcsf Building Component g9Oq parka Eest BIM.
Safay lnyolm — available from Tmss -te I -Me, 218 N. Lee Street, Suite 312, NeR —, VA 22314. Tampa, FL M610
fl
6-1-14 9-" 1&b2 19-7-0
1-2-0 6-1-14 3-7-10 3-7-10 6.1-14
Sple = 133.3
4.4
300 II - - '---- 7.8 = "---- 3.10 II ---- '----
THD26-2 HUS26
ii
LOADING (psf)
SPACING- 2-0.0
CSI.
DEFL.
in (loc) I/defl
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.44
Vert(LL)
0.21 7-12 >999
240
MT20 2441110
TCDL 7.0
Lumber DOL 1.25
BC 0.60
Ven(CT) -0.25
7-12 >932
240
BCLL 0.0
Rep Stress Incr NO
WB 0.89
Hom(CT)
0.06 6 n/a
n/a
BCDL 10.0
Code FBC2017/rP12014
Matnx-MS
Weight: 310 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 6-0-0 oc purlins.
BOT CHORD 2x6 SP 240OF 2.0E
BOT CHORD
Rigid ceiling directly
applied
or 10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 6=0-8-0, 2=0-8.0
Max Horz 2=162(LC 7)
Max Uplift 6=-3946(LC 8), 2=-3217(LC 8)
Max Grav 6=6069(LC 1), 2=4725(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-11877/7953, 34=-9369/6271, 4-5=-9393/6282, 5-6=13125/8579
BOT CHORD 2-10=-7240/10908, 8-10=-7240/10908, 7-8=-7844/12113, 6-7=-7844/12113
WEBS 4-8=4645/6983, 5-8=4241/2748, 5-7=-2145/3510, 3-8=-2774/2013, 3-1 0=-1
584/2336
NOTES-
1) 3-ply truss to be connected together with 1 Old (0.131"x3") nails as follows:
Top chords connected as follows: 2x4 - 1 row, at 0-9-0..
Bottom chards connected as follows: 2x6 - 3 rows staggered at 04-0 oc.
Webs connected as follows: 2x4 - 1 row at 0-9-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to
Plyconnections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
3) Unbalanced roof live loads have been considered for this design.
4) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate gnp DOL=1.60
This item has been
5) This truss has been designed for a 10.0 pef bottom chord live load nonconcument with any other live loads.
electronically Signed and
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
sealed b Lee, Julius, PE
y
will fit between the bottom chord and any Other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100lb uplift atjoint(s) except Ql=lb)
using a Digital Signature.
6=3946, 2=3217.
Printed Copies of this
8) Use USP THD26-2 (With 18-16d nails into Girder 8 12-10d nails into Truss) Or equivalent at 7-1-8 from the left end to connect
document are not considered
truss(es) to back face of bottom chord.
signed and sealed and the
SI g
9) Use USP HUS26 (With 14-16d nails into Girder 8 6-16d nails into Truss) or equivalent spaced at 2-0-0 oc max. starting at 9-0-12
from the left end to 17-0-12 to connect truss(es) to back face of bottom chord.
Signature must be Verified
10) Fill all nail holes where hanger is in contact with lumber.
On any electronic Copies.
L)Dead+OAD Standard
Julius Lee PE No. 34809
Roof
1) Dead +Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
MiTak USA, Inc. FL Cart 9634
9964 Pane EeR Blvd. Tampa FL 33610
Uniform Loads (00
Date:
Van: 14=-54, 4-6=-54, 2-6=-20
May 6,2020
AWARNING-Vergy Wsige pare 1 antl READ NOTES ON TNIs AND INCLUDED NITEK REFERENCE PAGE Nl4T/73n 10Poarzpf5 BEFORE USE. ��-
Design valid for use only w9h MITek®wnnectom. This desgn is ba-d only upon parameters shown, and is for en Individual building component, not
I itsystem. Before use, the building designer must verify the applicability of design parameters antl propery Incorporate thls design into the overall
building design. Bradng indicated is b prevent budling of individual truss web and/or chord members only. Add,r.nal temporary and permanent bracing MiTek'
s always reps dfo,shlliry and to prevent collapse with possible personal injury antl property damage. For general guxance regarding the
fabncatron, smmge, delivery, erection antl bracing of Wsses antl trues syatema, see ANS-1 qualify criteria, OSB-89 antl Bcs!Building Component g9Dq Perks Eest BIM.
.4, In/olmetlon available from Tmss Piste Ins , 218 N. Lee Street, Suite 312, Neea , VA 22314. Tampa, FL M610
1
T20150962
3x5 =
Cd' 19
Ida =
6
14
3x4 = 3.6 = 3x8 = 3x6 = 3x4 =
FY'118R3rk:
LOADING (pat)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) I/de6
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.37
Vert(LL) -0.16
14 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.56
Vert(CT) -0.34
12-14 >999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.83
Hom(CT) 0.11
10 n/a
n/a
BCDL 10.0
Code FBC2017/rP12014
Matnx-MS
Wind(LL) 0.24
14 >999
240
Weight 1751b FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 4-0-13 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied
or 5-6-3 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Ho, 2=-324(LC 10)
Max Uplift 2=-921(LC 12), 10=-921(LC 12)
Max Grav 2=1383(LC 1), 10=1383(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-2848/2027, 3-5=-2589/1869, 5-6=-1795/1436, 6-7=-1795/1436, 7-9=-2589/1869,
9-10=-2848/2027
BOT CHORD 2-16=-1717/2617, 14-16=-1290/2094, 12-14=-1321/2094, 10-12=-1733/2598
WEBS 6-14=-739/1045, 7-14=-743/619, 7-12=-256/527, 9-12=-402/403, 5-14=-742/619,
5-16=-256/527, 3-16=402/403
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=36ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extenor(2)-1-2-0 to 2-4-13, Interior(1) 24-13 to 17-10-0, Exterior(2)
17-10-0 to 214-13, 1ntenor(1) 214-13 to 36-10-0 zone;C-C for members and forces 8 MWFRS for reactions shown; Lumber
DOL=1.60 plate grip DOL=1.60
3) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
4) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100111 uplift at joinf(s) except at -lb)
2=921. 10=921.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34N6
MiTak USA, Inc. FL Cart 6634
6604 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq—is. parameters antl READ NOTES ON TNrs ANO INCLUDED NITEx REFERENCE PAGE Nl4T/73— 1gPoarzpl5 BEFORE USE. ��-
Dealgn valid for use only— MIT— nett This design ie based only upon parameters ah.n, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at verify the applicability of design parameters antl pro dy Incorporate this design into the overall
building design. Bracing indicated is to prevent bulling of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always reps d fo, stalblity and to prevent collapse with possible pe,sonal injury antl property damage. For general gu,d.— regartling the
fabncatron, ato,age, delivery, erection antl bracing of Wsaes and truss syatema, see ANS-11 Duality criteria, OSB-89 antl BcS1 Building Component g9Oq parka East BIM.
.4, lnfolmas— available /ram Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nex —, VA 22314. Tampa, FL M610
LOAD CASE(S) Standard
Concentrated Loads (lb)
Vert: 15=-2795(B) 16=-1289(B) 17=-1300(B) 18=-1300(B) 19=-1300(B) 20=-1300(B)
,&WARNING-Verey—is. paramemrs antl READ NOTES ON TNIS ANO INCLUDED NITEN REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��'
Desgn valid for use only— MIT— nett This deagn is based only upon parameters shown, and is for an Individual building component, not
a buss system. Before use, the building designer must verify the applicability of design parameters antl properly Incorporate thls design into the overall
building design. B.drg indicated is to prevent bulling of individual truss weband/or chord membersonly. Additionaltemporaryandpermanentbracing MiTek'
s always repaired for staGlity and to prevent collapse with possible personal injury antl pmpedy damage. For general gu,d.— raga d, the
fabdcatron, —a., delivery, erection and bracing of Wasea and truss syatema, see ANS-11 Duality cn—, OSB-89 antl Bcsf Building Component g90q parka Eest BIM.
Safay lnyolm — available from Tmss -te I -Me, 218 N. Lee Street, Suite 312, NeR —, VA 22314. Tampa, FL M610
a-alrsaaa
91'CE
LOADING (par)
SPACING- 2-0-0
CSI.
DEFL.
in (too) War
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DO L 1.25
TC 0.27
Vert(LL)
0.00 5 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.04
Vert(CT)
0.00 5 >999
240
BCLL 0.0
Rep Stress ]nor YES
WB 0.00
Horz(CT)
0.00 4 n/a
We
BCDL 10.0
Code FBC2017ITP12014
Matrix -MP
Wind(LL) -0.00 5 -999
240
Weight: 5lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood
sheathing directly applied or 1-0-0 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly
applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=70(LC 12)
Max Uplift 3=A(LC 9), 2=183(LC 12), 4=-5(LC 1)
Max Grav 3=11(LC 13), 2=137(LC 1), 4=29(LC 12)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 par bottom chord live load —concurrent with any other live loads.
3) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 4 except at=lb)
2=183.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
'&WARNING-vedq Ws;9n pare — antl READ NOTES ON T— ANO INCLUDED M1Tisa REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deagn valid for use only— MITek®wnnec— This dasgn is based only upon parameters shown, and is for an Individual building component, not
I Vuss system. Before use, the budding designer ,at vebfy the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b—ire of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always roguirod bo, atxGlity antl to preventcollapae with possible pe,sonal injury antl property damage. For general guitlance regartling the
labdcatron, aroma., delivery, erection and bracing of Wasas and truss sya ama, see ANS-11 Qualify Criteria, OSB-89 antl Bcs!Building Component g90q Parke East BIM.
.4, lnrofinerlon available from Tmss -te InsgMe, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
T20150994
-1-J3
1ack-0pen
9
1
Job Reference (optional)
Chambers Truss, Inc.,
Fart Pierce, FL
8.330 6 Mar 23 2020 MiTek Industries, Inc. Wad May 6 14:42:53 2020 Page 1
ID:I?Oy9y4e wm9YIH6Dtfc7UzSVDS-jNG3CBZusNV_S?W3DGfausJmPC
PKu7Oi6uoDMzJBZO
-1-2-0
3-0-0
2-0
3."
5.00 12
8
Scale = 1:10.8
3
2
1
4
3x4 =
3-0-0
3-0-0
LOADING (par)
SPACING- 2-0-0
CSI.
DEFL. in
(too) I/deb L/d
PLATES GRIP
TCLL 20.0
Plata Grip DOL 1.25
TC 0.27
Vert(LL) -0.00
4-7 >999 360
MT20 244/190
TCDL T'o
Lumber DOL 1.25
BC 0.18
Vert(CT) -0.01
4-7 >999 240
BCLL 0.0
Rep Stress ]nor YES
WB 0.00
Hom(CT) -0.00
3 n/a n/a
BCDL 10.0
Code FBC2017ITP12014
Matdx-MP
Wlnd(LL) 0.01
4-7 -999 240
Weight: ll lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 3-0-0 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3-Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=119(LC 12)
Max Uplift 3=-61(LC 12), 2=-172(LC 12), 4=-3(LC 9)
Max Grav 3=67(LC 17), 2=184(LC 1), 4=50(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; 3=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 1-10-0, Interior(1) 1-10-0 to 2-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
3) ` This truss has been designed for alive load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1001b uplift at joint(s) 3, 4 except at=lb)
2=172.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,39
MiTek USA, Inc. FL Cart 6634
11904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
IAWARNING- vedq Ws;9e paramam —READ NOTES ON T—AND INCLUDE- MITEX REFERENCE PAGE Nl4T/73— 10Poarzp15 BEFORE USE. ��-
Desgn valid for use only— MIT—nadectom. This —la is based only upon parameters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the appfcability of design parameters antl pro dy Incorporate thls design into me overall
building design. Braung indicated is to prevent b-ling of individual truss web and/or chord membera-ly. Adda—altemporary and permanent brecing MiTek'
s always reguiretl for shGlily antl to prevent collapse with possible personal injury antl Drapery tlama9e. For general guitlance raga d, the
labdcatron, storage, del- , erection and bracing of Wsses and W as systems, see ANS-11 Qualify Criteria, OSB-89 antl Bcal Building Component g9oq Parke East BIM.
.4, lnyofmadon available from Truss -te I-adc, 218 N. Lee Street, Suite 312, Nexe—, VA 22314. Tampa, FL M610
T20150995
6Y11r$REIV3
3.4 =
LOADING (par)
SPACING- 2-0-0
CS'DEFL.
in
(too) Well
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.85
Vert(LL) -0.03
4-7 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.74
Vert(CT) -0.06
4-7 >999
240
BCLL 0.0
Rep Stress ]nor YES
WB 0.00
Hom(CT) -0.00
3 n/a
We
BCDL 10.0
Code FBC2017ITP12014
Matrix -MP
Wind(LL) 0.07
4-7 >832
240
Weight: 18 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood
sheathing directly applied or 2-2-14 oc pudins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly
applied or 10-0-0 oc bracing.
REACTIONS. (size) 3-Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=170(LC 12)
Max Uplift 3=-119(LC 12), 2=-199(LC 12), 4=-8(LC 12)
Max Grav 3=121(LC 17), 2=253(LC 1), 4=88(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 4-11-4 zone;C-C for
members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
3) ` This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except (jt=lb)
3=119,2=199.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
,&WARNING-verey Ws;9n pa ram antl READ NOTES ON TN AND INCLUDED M1TEfr REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deasn valid for use only wdh MIT—nnectom. This —la is based only upon parameters ah.n, and is for en Individual building component, not
I tmsa system. Before use, the budding designer ,at verify the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord membe,sonly. Adda—al—,omary and permanent bracing MiTek'
s always raq—dbo, ataGlity and to prevent collapae with possible pe,sonal injury antl property damage. For general guxance regarding the
labdcatron, ammge, delivery, erection and bracing of Wawa and trues syxiama, aee ANS-11 Qualify criteria, OSB-89 antl Bcs!Building Component g9pq Parke East BIM.
.4, an/ofinetlon available from Truss P to InsdMe, 218 N. Lee Street, Suite 312, Naea—, VA 22314. Tampa, FL M610
6Y11r$REIF3
Emm
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) War L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.47
Vert(LL) -0.02 6 -999 360
MT20 2-110
TCDL 7.0
Lumber DOL 1.25
BC 0.72
Vert(CT1 -0.05 5-6 >999 240
BCLL 0.0 `
Rep Stress Incr YES
WB 0.00
Hom(CT) -0.02 5 n/a n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MR
Wind(LL) 0.06 5-6 >999 240
Weight: 20 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly
applied or 5-0-0 oc pudins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied
or 9-2-11 oc brecing.
REACTIONS. (size) 4=Mechanical, 2=0-8-0, 5=Mechanical
Max Ho 2=170(LC 12)
Max Uplift 4=-92(LC 12), 2=-195(LC 12), 5=-33(LC 12)
Max Grav 4=105(LC 17), 2=265(LC 1), 5=95(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 3-9=-265/213
BOT CHORD 2-7=-357/297, 3-6=-297/357
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2)-1-2-0 to 1-6-10, Interior(1) 1-6-10 to 4-11-4 zone;C-C for
members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4, 5 except gt=lb)
2=195.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33910
Data:
May 6,2020
'&WARNING-vedq—is. Parameters antl READ NOTES ON T-t AND INCLUDED NITEK REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Dasgn valid for use only— MITek®wnnec— This deagn is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at verify the applicability of design parameters antl popery Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always repaired fo, stalblity and to prevent collapse with possible personal injury antl properly damage. For general gux.—regartling the
fabdcatron, atmage, delivery, erection and bracing of Wawa and truss systama, see ANS-11 Qualify CNhria, OSB-89 antl Bc8/Buffding Component 8904 Parke East BIM.
.4, lnyolmadon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nea —, VA 22314. Tampa. FL M610
T20150997
i
FY'1r-- RP1B
3.4 = 4
LOADING (pat) SPACING- 2-0-0 CSI. DEFL. in (loc) Well L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.54 Vert(LL) -0.08 4-7 >999 360 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.40 Vert(CT) -0.18 4-7 >459 240
BCLL 0.0 Rep Stress Inc" YES WB 0.00 Hom(CT) -0.00 3 n/a n/a
BCDL 10.0 Code FBC2017rrP12014 Matnx-MP Wind(LL) 0.17 4-7 >494 240 Weight: 24 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pur ins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3-Mechanical, 2=0-8-0, 4=Mechanical
Max Ho 2=220(LC 12)
Max Uplift 3=-175(LC 12), 2=231(LC 12), 4=-13(LC 12)
Max Grev 3=173(LC 17), 2=325(LC 1), 4=125(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exlenor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-010 6-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will 8t between the bottom chord and any other members.
4) Refer to girder(.) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except Qt=lb)
3=175,2=231.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 6e34
g904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-verey—is. parameters antl READ NOTES ON TR/S Asadav UDEONITEfr REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT—nnectom. This design is based only upon parameters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl properly Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always required fo, stalblity and to prevent collapse with possible pe,sonal injury antl property damage. For general guitlance raga d, the
fabdcatron, storage, delivery, erection antl bracing of lasses and trues systems, see ANS-11 Qualify criteria, OSB-89 antl BcS1 Buffdfng Component g9pq parka East BIM.
.4, lnsdam s— available from Truss Plate la—, 218 N. Lee Street, Suite 312, Neea , VA 22314. Tampa, FL M610
T20150998
11
PTM
FY 1r$RF18
LOADING (par) SPACING- 2-0-0 CS'DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.40 Vert(LL) 0.11 4-8 >577 240 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.35 Vert(CT) -0.04 4-8 >999 240
BCLL 0.0 Rep Stress ]nor YES WB 0.00 Hom(CT) -0.02 3 n/a n/a
BCDL 10.0 Code FBC2017ITP12014 Matrix -MP Weight: 19 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5813 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3-Mechanical, 2=0-3-0, 4=Mechanical
Max Hom 2=174(LC 12)
Max Uplift 3=-132(LC 12), 2=480(1-C 12), 4=-91(LC 9)
Max Grav 3=1141(LC 1), 2=312(LC 1), 4=88(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Corner(3) -1-3-0 to 2-11-15, Exterior(2) 2-11-15 to 5-6-1 zone; cantilever
left exposed ; porch left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate gnp
DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except Qt=lb)
3=132,2=380.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
11904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
,&WARNING-vedq Ws;9n pare — antl READ NOTES ON TNIS ANO INCLUDED M1Tisa REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deasn valid for use only— MITek®wnneclom. This —la is based only upon parameters ah.n, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design pammat— antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord membe,sonly. Adda—al—,omary and permanent bracing MiTek'
s always required bo, alxGlity and to prevent collapse with possible pe,sonal injury antl properly damage. For general gux.—regartling the
labdcatron, aroma., delivery, erection and bracing of Wasea and trues syxiama, see ANS-11 Qualify CNhria, OSB-89 antl Bcsi Building Component g90q Parke East BIM.
.4, In/ofinetlon available from Truss -t, InsgMe, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
'sR1r4El1iIR1V4
3.4 -
LOADING (pat)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) War
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.56
Vert(LL) -0.00
7 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.12
Vert(CT) -0.00
7 >999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Hom(CT) -0.00
3 n/a
n/a
BCDL 10.0
Code FBC2017rrP12014
Matdx-MP
Wind(LL) -0.00
7 >999
240
Weight: 10 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly
applied or 2-6-6 oc pudins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly
applied
or 10-0-0 oc bracing.
REACTIONS. (size) 3-Mechanical, 2=0-8-0, 4=Mechanical
Max Ho 2=101(LC 12)
Max Uplift 3=41(LC 12), 2=-187(LC 12), 4--2(LC 9)
Max Grav 3=49(LC 17), 2=179(LC 1), 4=40(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=411; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Comer(3) zone;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will 8t between the bottom chord and any other members.
4) Rafer to girder(.) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 4 except 0t=l1b)
2=187.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
,&WARNING-vedq—is. parameters antl READ NOTES ON TR ANO INCLUDED NITEX REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Dealgn valid for use only— MITak®wnnect This d-la is basetl only upon parameters ah.n, and is for an Individual building component, not
I fmss system. Before use, the budding designer ,at verify the applicability of design parameters antl popery Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always n paired fo, stalblity and fo prevent collapse with possible personal injury antl property damage For general guitlance rag d, the
fabdcatron, atmage, delivery, erection and bracing of Wawa and trues syatema, see ANS-11 Duality Criteria, OSB-89 antl Bc8/Buifding Component g90q parka East BIM.
.4, lnsdam s— available from Truss Plate la—, 218 N. Lee Street, Suite 312, Nea —, VA 22314. Tampa, FL M610
T20151000
r:mr4alplu
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017rrP12014
CSI.
TC 0.27
BC 0.34
WB 0.00
Matrix -MP
DEFL. in (loc) War L/d
Vert(LL) -0.00 5 -999 360
Vert(CT) -0.00 5 >999 240
Horz(CT) 0.00 3 n/a n/a
Wind(LL) 0.00 5 >999 240
PLATES GRIP
MT20 2-110
Weight: 11 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly
applied or 2-4-12 oc pudins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or
10-0-0 oc bracing.
WEDGE
Left: 2x4 SP No.3
REACTIONS. (size) 3-Mechanical, 2=0-3-0, 4=Mechanical
Max Ho' 2=104(LC 12)
Max Uplift 3=-27(LC 9), 2=-284(LC 12), 4=-26(LC 9)
Man Grav 3=17(LC 1), 2=215(LC 1), 4=22(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extenor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 2-4-0 zone; cantilever left
exposed ; porch left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate gnp
DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) - This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 4 except 0t=l1b)
2=284.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33910
Data:
May 6,2020
'&WARNING-vedq—is. parameters antl READ NOTES ON T-t AND INCLUDED NITEK REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT—nnectom. This —la is based only upon pemmeters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemp r, and permanent bracing MiTek'
s always repaired for stalblity and to prevent collapse with possible personal injury antl Dropedy damage. For general guxance rag d, the
fabdcatron, smmge, delivery, erection and bracing of lasses and truss systems, see ANS-11 Duality Criteria, OSB-89 antl BCSf Buflding Component 8904 Parke Eeat BIM.
.4, lnyolmadon available from Truss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa. FL M610
L Job Reference (optional) T20151001
-1-JC3 Jack-0pen 2 1
Chambers Truss, Inc., Fart Pierce, FL 8.330 a Mar 23 2020 MiTek Industries, Inc. Wad May 6 14:42:58 2020 Page 1
ID:17Oygy4e wm9YIH6Dtfc7UzSVDB-4K3yFrdOhv7GYnOlOgFlbvOadRfo7BMIrObZtzZJBYx
-1-2-0 249 0 3-0-0
1-2-0 2-8-0 0.4.0
Scale = 1:10.8
4
5.110 12
3
3x4 =
2
5 Q
1 a
3x4 =
LOADING (par) SPACING- 2-0-0 CSI. DEFL. in (too) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.43 Vert(LL) -0.04 6 >973 360 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.29 V.'(CT) -0.08 6 >464 240
BCLL 0.0 Rep Stress ]nor YES WB 0.00 Hom(CT) 0.01 5 n/a We
BCDL 10.0 Code FBC201771P12014 Matrix -MP Wlnd(LL) 0.03 6 -999 240 Weight: 13 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 3-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 4-Mechanical, 2=0-8-0, 5=Mechanical
Max 11— 2=119(LC 12)
Max Uplift 4=-36(LC 12), 2=-171(LC 12), 5=-20(LC 12)
Max Grav 4=60(LC 17), 2=191(LC 1), 5=62(LC 3)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 1-6-10, Interior(1) 1-6-10 to 2-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
3) ` This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1001b uplift at joint(s) 4, 5 except at=lb)
2=171.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,39
MiTek USA, Inc. FL Cart 6634
11904 Parke East BNd. Tampa FL 33610
Date:
May 6,2020
'&WARNING-verey—is. parameters antl READ NOTES ON TNIS AND INCLUDED haTEfr REFERENCE PAGE Nl4T/73-14-2015 BEFORE USE. ��-
Deagn valid for use only— MITI®wnneclom. This deagn is based only upon paramaUx shown, and is for an Individual building component, not
I tmsa system. Before lad, the budding designer must vedfy the applicability of design parameters antl properly Incorporate thls design into the overall
building design. Bradng indicated is to prevent bulling of individual truss web and/or chord membe—rly. Addd—altemporary and permanent bracing MiTek'
s always repaired bo, etadlity and to prevent collapse with possible personal injury antl properly damage. For general gux.— raga d, the
labdcatron, ato,age, delivery, aredion and bracing of —ea and truss syalama, aee ANS-11 Qualify criteria, OSB-89 antl Bcs!Building Component g9oq parka Ees[ BIM.
Safay lnPofmadon available from Truss -t, lr—, 218 N. Lee Street, Suite 312, Neaa—, VA 22314. Tampa, FL M610
i'
Type OIY Ply
ipec al 3
8.330 a Me
ID:170y9y4e wm9YIH6l
17-10-0 18- 238-3
4&11 1 5-03
5.6 =
5.00 1112
7 8
T20150963
FY'1lcR3r[I
7.14 MT18HS = 4x8 = 19 16 15 " 13
5.8 = 6x8 = 3.6 = 3A _
302 1.00 12
LOADING (pat) SPACING- 2-0-0 CSI. DEFL. in (loc) War L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.16 ,art(LL) -0.45 20-21 -933 360 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.81 Vert(CT) -1.05 20-21 >404 240 MT18HS 244/190
BCLL 0.0 ' Rep Stress Incr YES WB 0.89 Hom(CT) 0.32 12 We n/a
BCDL 10.0 Code FBC2017rrP12014 Matrix -MS Wind(LL) 0.6220-21 >687 240 Weight: 205lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30'Except' TOP CHORD Structural wood sheathing directly applied or 2-2-0 oc pudins.
1-5: 2.4 SP M 31 BOT CHORD Rigid ceiling directly applied or 3-1 t-0 oc bracing. Except:
BOT CHORD 2x4 SP M 30'Except' 6-0-0 oc bracing: 8-16
2-21: 2x4 SP M 31, 8-16: 2x4 SP No.3 WEBS i Row at midpt 7-20
WEBS 2x4 SP No.3 *Except*
3-21: 2x6 SP No.2
WEDGE
Right: 2x4 SP No.3
REACTIONS. (size) 12=0-4-0, 2=0-8-0
Max Herz 2=316(LC 11)
Max Uplift 12=-814(LC 12), 2=-915(LC 12)
Max Grav 12=1306(LC 1), 2=1371(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-6212/4073, 3-4=-5749/3912, 4-6=-2567/1855, 6-7=-2545/2012, 7-8=1940/1661,
8-9=-1990/1579,9-11=-2276/1734, 11-12=-2683/1925
BOT CHORD 20-21=-2152/3242, 18-20=-971/1696, 17-18=-971/1696, 15-16=-157/321,
13-15=-1633/24D4,12-13=-1633/2404,2-21=-3747/5999,8-17=-185/288
WEBS 6-20=-283/370, 15-17=-1157/1747, 9-17=-431/343, 11-15=-509/425, 3-21=-250/627,
7-17=-645/829, 7-20=-810/1160, 4-21=-1544/2581, 4-20=9861790
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vul1=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsh, h=15ft; B=45ft; L=35ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 2-4-6, Inte6oKl) 2-4-6 to 17-10-0, Exterior(2) 17-10-0
to 21-4-6, Interior(1) 21-4-6 to 35-4-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) All plates are MT20 plates unless otherwise indicated.
4) All plates are 3x4 MT20 unless otherwise indicated.
5) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
6) ' This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
7) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at--lb)
12=814,2=9IS
'fin 1�
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 6634
6604 Parke East BNd. Tampa FL 33610
D6ta:
May 6,2020
'&WARNING-verey—is. parameters and READ NOTES ON TNrs Asse N UDE0 N1TEx REFERENCE PAGE Nl47/73-14-2015 BEFORE USE. ��-
Daslgn valid for use only— MITek®wnnec— This d-la is based only upon parameters shown, and is for en ddividual building mmp..m not
I tmss system. Before use, the budding designer ,at venfy the applicability of design parameters antl po dy Incorporate this design into the overall
building design. Bradng indirated is to prevent b—ing&individual truss web and/or chord membe,sonly. Adddenaltemporary and permanent bracing MiTek'
s always reguiredfo, staGlity and to prevent collapse with possible personal injury antl properly damage. For general guxi.—regartling the
fabdcatron, storage, delivery, erection antl bracing of Wows and truss syatema, see ANS-11 Qualify Criteria, OSB-89 antl Bc8/Buifding Component g9pq Parke East BIM.
.4, lnsdamas— available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Neea , VA 22314. Tampa, FL M610
Y�108RA'�
3M =
LOADING (par)
SPACING- 2-0-0
CS'DEFL.
in (loc) Udell
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.27
Vert(LL) -0.00 7 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.06
Vert(CT) -0.00 7 >999
240
BCLL 0.0
Rep Stress ]nor YES
WB 0.00
Hom(CT) 0.00 4 n/a
n/a
BCDL 10.0
Code FBC2017ITP12014
Matrix -MP
Wind(LL) -0.00 7 >999
240
Weight: 7lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD Structural wood
sheathing directly applied or 1-7-4 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD Rigid ceiling directly
applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=85(LC 12)
Max Uplift 3=-18(LC 9), 2=A68(LC 12)
Max Grav 3=28(LC 17), 2=145(LC 1), 4=24(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 par bottom chord live load —concurrent with any other live loads.
3) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3 except (jt=lb)
2=168.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
,&WARNING-vamx—is. pare — antl READ NOTES ON T— ANO INCLUDED M1Tisa REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deagn valid for use only wdh MITek®wnnec— This dasgn is based only upon parameters shown, and is for an Individual building component, not
I Vuss system. Before use, the budding designer ,at vebfy the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b—ire of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always raq—d bo, atxGlity antl to prevent collapae with possible pe,sonal injury antl property damage. For general guitlance regartling the
labdcatron, aroma., delivery, erection and bracing of Wasas and truss syatama, see ANS-11 Qualify Criteria, OSB-89 antl BCsi Building Component g90q Parke East BIM.
.4, lnrofinerlon available from Tmss -te InsgMe, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
T20151003
FY?1f- M!sMv
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) War L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.38 Vert(LL) 0.14 4-9 >468 240 MT20 2-110
TCDL 7.0 Lumber DOL 1.25 BC 0.99 Vert CT) -0.05 4-9 >999 240
BCLL 0.0 Rep Stress Incr YES WB 0.00 HocdCT) -0.02 3 n/a n/a
BCDL 10.0 Code FBC2017rrP12014 Matnx-MP Weight: 20 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-6-8 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied.
WEDGE
Left: 2x4 SP No.3
REACTIONS. (size) 3-Mechanical, 2=0-3-0, 4=Mechanical
Max Ho' 2=183(LC 12)
Max Uplift 3=-137(LC 12), 2=-362(LC 12), 4=-91(LC 12)
Man Grav 3=112(LC 1), 2=302(LC 1), 4=83(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 5-5-12 man.; cantilever
left exposed ; porch left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) - This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit
between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except Qt=lb)
3=137.2=362.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9934
9904 Pants East BNd. Tampa FL 33910
Data:
May 6,2020
'&WARNING-vedq—is. parameters antl READ NOTES ON T-t AND INCLUDED NITEK REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Daslgn valid for use only— MITek®wnneclom. This —la is based only upon parameters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl propery Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord membemonly. Adda—altemporary and permanent bracing MiTek'
s always repaired fo, stalblity and to prevent collapse with possible personal injury antl properly damage. For general gu,d.— regartling the
fabdcatron, smmge, delivery, erection antl bracing of Wsses and truss systems, see ANS-11 Duality Criteria, OSB-89 antl BCSf Buflding Component 8904 Parke East BIM.
.4, lnssmsadon available from Truss Plate InsdMe, 218 N. Lee Street, Suite 312, A—ddlna, VA 22314. Tampa. FL M610
Jab Tmss Truss Type OtY Pty
T20151004
7fi703 KJ5 Diagonal Hip Girder 1 1
I23F;2
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr NO
Code FBC20171TP12014
CSI.
TC 0.25
BC S.
WB 0.00
Matrix -MR
DEFL. in (loc) War L/d
Vert(LL) -0.07 5-6 -999 360
Vert(CT) -0.13 5-6 >652 240
H..,T) 0.03 5 n/a n/a
Wind(LL) 0.10 5-6 >811 240
PLATES GRIP
MT20 2-190
MT18HS 244/190
Weight: 25 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Stmdural wood sheathing directly
applied or 6-0-0 oc pudins.
BOT CHORD 274 SP M 30 *Except* BOT CHORD Rigid ceiling directly applied or
10-0-0 oc bracing.
3-7: 2x4 SP NG.3
REACTIONS. (size) 4=Mechanical, 2=0-10-15, 5=Mechanical
Max Hom 2=169(LC 24)
Max Uplift 4=-120(LC 8), 2=-296(LC 8), 5=-41(LC 8)
Max Gray 4=141(LC 28), 2=372(LC 28), 5=119(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-579/170
BOT CHORD 2-7=-238/503
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; save=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) All plates are MT20 plates unless otherwise indicated.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 5 except Qt=lb)
4=120,2=296.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 103 lb down and 201b up at
This item has been
1-6-1, 103 lb down and 20 lb up at 1-6-1, and 1141b down and 77 lb up at 44-0, and 1141b down and 77 lb up at 4-4-0 on top
electronically signed and
chord, and 341b down and 9lb up at 1-6-1, and 341b down and 91b up at 1-6-1 on bottom chord. The design/selection of such
sealed b Lee, Julius, PE
y
connection devices) is the responsibility of others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
using a Digital Signature.
Printed copies of this
LOAD CASE(S) Standard
document are not considered
1) Dead+ Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
signed and sealed and the
Uniform Loads (plf)
Vert: 1-4=-54, 7-8=-20, 5-6=-20
signature must be verified
Concentrated Loads (lb)
on any electronic copies.
Vert: 12=-1(F=-1, B=-1)
Julius Lee PE No. 34469
MiTak USA, Inc. FL Cart 6634
i Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq—is. parameters antl READ NOTES ON THIS AND INCLUDED NITEK REFERENCE PAGE Nl4T/73—laaeor l3 BEFORE USE. ��-
Dealgn valid for use only wdh MIT—radeclom. This —la is based only upon parameters ahown, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at verify the applicability of design parameters antl pro dy Incorporate this design into the overall
building design. Bradng indicated is to prevent r-ling of individual truss web and/or chord memb—nly. Addidonaltemporaryandpermanentbmcing MiTek'
s always reguiredfor stalblity and to prevent collapse with possible personal injury antl properly damage. For general gux.—regartling the
fabdcatron, atorege, del- , erection and bracing of Wasea and truss syatema, see ANS-11 Duality criteria, OSB-89 antl Bcal Building Component g9pq Perks East BIM.
.4, lnsonesson available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
Jab Tmss Truss Type OtY Pty
T20151005
7fi703 KJ7 Diagonal Hip Girder 4 1
I 1
3x4 = n4 II 5
3.4
=
FY-1171EIIW4WA
LOADING (par) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.19 V. ILL) -0.05 7-10 >999 240 MT20 2441190
TCDL 7.0 Lumber DOL 1.25 BC 0.24 Vert(CT) -0.06 7-10 >999 180
BCLL 0.0 Rep Stress ]nor NO WB 0.32 Horz(CT) 0.01 5 We n/a
BCDL 10.0 Code FBC2017/IP12014 Matrix -MS Weight: 41 It, FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 9-10-4 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 4=Mechanical, 2=0-10-15, 5=Mechanical
Max Horz 2=219(LC 24)
Max Uplift 4=-114(LC 8), 2=-394(LC 8), 5=-225(LC 8)
Max Grev 4=103(LC 1), 2=522(LC 28), 5=371(LC 28)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-894/451
BOT CHORD 2-7=-547/798, 6-7=-547/798
WEBS 3-7=-38/293, 3-6=872/599
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=1511; B=4511; L=24ft; save=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) ` This truss has been designed for alive load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will f/ between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 Ib uplift at joint(.) except at -lb)
4=114, 2=394, 5=225.
6) Hanger(s) or other connection d wice(s) shall be provided sufficient to support concentrated load(s) 103 Ib down and 201b up at
1-6-1. 103 Ib down and 20 Ib up at 1-6-1, 114 Ib dawn and 77 Ib up at 4-0-0, 114 Ib down and 77 Ib up at 4-0-0, and 144 It,down
and 143 Ib up at 7-1-15, and 1441b down and 1431b up at 7-1-15 on top chord, and 34 lb down and 9lb up at 1-6-1. 34 lb down
and 9 It, up at 1-6-1, 24 Ib down and 12 Ib up at 4-4-0, 24 It, down and 12 Ib up at 4-4-0, and 45 Ib down and 24 Ib up at 7-1-15,
and 45 Ib down and 24 Ib up at 7-1-15 on bottom chord. The design/selection of such connection device(s) is the responsibility of
others.
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
11 Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-4=-54, 5-8=-20
Concentrated Loads (Ib)
Vert: 12=-l(F=-1, B=-1) 13=-76(F=-38, B=-38) 15=-15(F=-7, B=-7) 16=-65(1`=33, B=33)
1¢
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34819
MiTak USA, Inc. FL Cart 6634
I Parke East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-verfy—is. parameters antl READ NOTES ON T— ANO INCLUDED N1TEIr REFERENCE PAGE Nl4T/73-14-015 BEFORE USE. ��-
Dasgn valid for use only wdh MITek®wnad. m. This deagn is based only upon parameters ah.n, and is for en ddividual building component, not
I truss system. Before use, the budding designer must verify the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent budding of individual truss web and/or chord m.mbe,sonly. Addaenaltemporary and permanent brecing MiTek'
s always required(, staGlity and to prevent collapse with possible personal injury antl preperry damage. For general gux.—regartling the
fabdcatron, atorege, del- , erection and brecing d Imasas and truss syatema, see ANS-11 Qualify Criteria, OSB-89 antl BCSI Building Component g9pq parka Eeat BIM.
.4, an/ormetlon —1—from Tmss -t, InsgMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
3x4 =
LOADING (par)
TCLL 20.0
TCDL T'o
BCLL 0.0
BCDL 10.0
. 0-7-2
SPACING- 2-0-0
Plate Gnp DO L 1.25
Lumber DOL 1.25
Rep Stress ]nor NO
Code FBC2017ITP12014
CSI.
TC 0.22
BC 0.18
WB 0.00
Matrix -MP
57-10
DEFL. in (too) I/deft Ud
Vert(LL) 0.09 4-8 >825 240
Vert(CT) -0.07 4-8 >999 240
HI-0.02 3 n/a We
PLATES GRIP
MT20 244/190
Weight: 21 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanipl, 2=0-3-6, 4=Mechanical
Max Hom 2=183(LC 8)
Max Uplift 3=-144(LC 8), 2=-427(LC 8), 4=-101(LC 5)
Max Grav 3=125(LC 1), 2=345(LC 1), 4=98(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); cantilever left exposed ;porch left and right exposed; Lumbar DOL=1.60 plate
grip DOL=1.60
2) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
3) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100111 uplift at joints) except at-lb)3=144,2=427,
4=101.
6) Hanger(s)or other connection device(s) shall be provided sufficient to support concentrated load(s) 34111 down and 51 Ib up at
2-10-3 on top chord, and 7 Ib up at 2-10-3 on bottom chord. The design/selection of such connection device(s) is the responsibility
of others.
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
This item has been
LOAD CASE(S) Standard
nd
a signed and
electronicallyLee, gned
i) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
sealed yJulius, PE
Uniform Loads (plf)
Vert: 1-3=-54, 4-5=-20
using a Digital Signature.
Concentrated Loads (lb)
Printed copies of this
Vert: 10=5(e)
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348119
MiTak USA, Inc. FL Cart 6634
6604 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
A wARN1N0-vedq—is. paramamrs antl READ NOTES ON TNIS ANO INCLUDED M1TEIr REFERENCE PAGE M167473-14-15 BEFORE USE. ��-
Deagn valid for use only— MITI®wnnec— This deagn is based only upon parameters ah.n, and is for en Individual building component, not
I truss system. Before lad, the budding designer ,at verify the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent bulling of individual truss web and/or chord membersonly. Adda—al—,omary and permanent bracing MiTek'
s always re —d bo, staGlity and to prevent wllapae with possible personal injury antl properly damage. For general gux.— regartling the
labdcatron, aroma., delivery, erection and bracing of Wasea and trues syxiama, see ANS-11 Duality CNhria, OSB-89 antl Bcs'Building Component g90q Parke Eax BIM.
.4, In/ofinetlon available from Truss Plate I-ad1k, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
Type
3NAL HIP GIRDER 22 PIy I T20151007
FY'1r$aEWA
LOADING (par) SPACING- 2-0-0 CSI. DEFL. in (too) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Gnp DOL 1.25 TC 0.31 Vert(LL) 0.06 4-8 >999 240 MT20 2441190
TCDL 7.0 Lumber DOL 1.25 BC 0Ml6 Vert(CT) -0.03 4-8 >999 240
BCLL 0.0 Rep Stress ]nor NO WB 0.00 Horz(CT) -0.01 3 n/a n/a
BCDL 10.0 Code FBC20177fP12014 Matrix -MP Weight: 1816 FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-2-12 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3-Mechanical, 2=0-3-6, 4=Mechanical
Max Horz 2=161(LC 12)
Max Uplift 3=-111(LC 12), 2=-392(LC 12), 4=-79(LC 9)
Max Grav 3=98(LC 1), 2=316(LC 1), 4=78(LC 3)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; 3=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Corner(3)-1-3-12 to 2-11-3, Exterior(2) 2-11-3 to 5-2-0 zone; cantilever
left exposed ; porch left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate gnp
DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for tmss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except Qt=lb)
3=111,2=392.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,39
MiTak USA, Inc. FL Cart 6634
19M Parke East Blvd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq Ws;9e pare — antl READ NOTES ON This ANO INCLUDED M1TEfr REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deasn valid for use only— MITek®wnnectom. This design ie based only upon parameters shown, and is for en Individual building component, not
I tmsa system. Before use, the budding designer ,at verify the applicability of design pammat— antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord membe,sonly. Adda—al—,omary and permanent bracing MiTek'
s always repaired bo, ataGlity and to prevent collapae with possible pe,sonal injury antl property damage. For general gux.—regartling the
iabdcatron, ammge, delivery, erection and bracing of Wasea and trues syxiama, see ANS-11 Qualify CNhria, OSB-89 antl Bcs!B.0ding Component g90q Parke East BIM.
.4, lnyofmadon available from Tmss Plate I-adta, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
Jab Tmss Truss Type Oty Ply
T20151008
7fi703 KJC Diagonal Hip Girder 2 1
Scale =1:10.7
3x4 =
LOADING (par)
SPACING- 2-0-0
CS'DEFL.
in
(too) War
Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.08
Vert(LL) -0.00
4-7 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.05
Vert(CT) -0.01
4-7 >999
240
BCLL 0.0
Rep Stress ]nor NO
WB 0.00
Hom(CT) -0.00
3 n/a
n/a
BCDL 10.0
Code FBC2017ITP12014
Matrix -MP
Wlnd(LL) 0.00
4-7 -999
240
Weight: 1316 FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood
sheathing directly applied or 34-15 cc puriins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-12, 4=Mechanical
Max Horz 2=119(LC 8)
Max Uplift 3=-66(LC 8), 2=-201(LC 8), 4=-3(LC 5)
Max Grav 3=73(LC 25), 2=211(LC 1), 4=58(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 paf bottom chord live load nonconcurrent with any other live loads.
3) " This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will 5t between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1001b uplift at joint(s) 3, 4 except Gt=lb)
2=201.
6) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 113 Ib down and 381b up at
1-11-10 on top chord, and 16111 down and 0111 up at 1-11-10 on bottom chord. The design/selection of such connection device(s) is
the responsibility of others.
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increas-1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=-54,4-5=-20
Concentrated Loads (lb)
Vert: 9=0(B)
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34819
MiTak USA, Inc. FL Cart 6634
I Parke East BNd. Tampa FL 33610
Date:
May 6,2020
A wARN1ND-vedq—is. parameters and READ NOTES ON TNIS AND INCLUDED M1TEx REFERENCE PAGE M167473— 1darV2015 BEFORE USE. ��-
Dasgn valid for use only wdh MITek®wnnectom. This deagn ie based only upon parameters shown, and is for en Individual building component, not
I itsystem. Before use, the budding designer must verify the applicability of design pa aradt—antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is In prevent b-ling of individual truss web and/or chord membemonly. Adddenaltemporary and permanent bracing MiTek'
s always reguiretl for staGlily antl to prevent wllapse with possible pe,sonal injury antl Droperry tlama9e. For general guitlance rega d, the
fabdcatron, atmage, delivery, erection and bracing of Wasea and trues syarama, aee ANS-11 Qualify Criteria, DSB-89 antl BCSr Building Component g9pq Parke Eeat BIM.
.4, Information available from Tmss Plate Hoe, 218 N. Lee Street, suite 312, Nea —, VA 22314. Tampa, FL M610
'' �1r4El1iN*3
3x5 =
LOADING (pat)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) War
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.22
Vert(LL) 0.00
5 >999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.04
Vert CT) -0.00
7 >999
180
BCLL 0.0
Rep Stress Incr
NO
WB 0.00
Hom(CT) 0.00
4 n/a
n/a
BCDL 10.0
Code FBC2017?PI2014
Matdx-MP
Wind(LL) -0.00
5 1999
240
Weight:6 to FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly
applied or 1-3-13 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly
applied
or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-12, 4=Mechanical
Max Horz 2=74(LC 12)
Max Uplift 3=-9(LC 9), 2=202(1C 12)
Max Grav 3=14(LC 17), 2=158(LC 1), 4=26(LC 12)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) Or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24111; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Comer(3) zone;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
3) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will 8t between the bottom chord and any other members.
4) Rafer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3 except Qt=lb)
2=202.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL cart 6e34
g904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
A wARNINO-vedq—is. parameters antl READ NOTES ON T-t AND INCLUDED NITEx REFERENCE PAGE Nl4T/73— 10PoIrzp15 BEFORE USE. ��-
Dealgn valid for use only— MITak®wnd.td- This design ie based only upon parameters shown, and is for an Individual building component, not
I fmss system. Before use, the budding designer ,at verify the applicability of design parameters antl popery Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—alte r, and permanent bracing MiTek'
s always n paired fo, stalblity and fo prevent collapse with possible personal injury antl property damage For general guitlance rag d, the
fabdcatron, atmage, delivery, erection and bracing of Wasea and trues systama, see ANS-11 Duality criteria, OSB-89 antl BcS1 Building Component g9Dq parka East BIM.
.4, lnyolmadon available from Truss Plate la—, 218 N. Lee Street, suite 312, Nea —, VA 22314. Tampa. FL M610
AreR7
'17111/J
'tT �1r K*l
LOADING (par) SPACING- 2-0-0 CSI. DEFL. in (too) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.07 Vert(LL) n/a - n/a 999 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.03 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress ]nor YES WB 0.00 HI-0.00 2 n/a n/a
BCDL 10.0 Code FBC20177IP12014 Matrix-P Weight: 5111 FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 2-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 1=2-0-0, 2=2-0-0, 3=2-0-0
Max Horz 1=32(LC 12)
Max Uplift 1=-23(LC 12), 2=-40(LC 12)
Max Grav 1=47(LC 1), 2=36(LC 17), 3=25(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Gable requires continuous bottom chord bearing.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) " This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Bearing at joint(s) 2 considers parallel to grain value using ANSIrTPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1001b uplift at joint(s) 1, 2.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348119
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
A wARN1N0-verex—is. pare — antl READ NOTES ON T— ANO INCLUDED Admsa REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deagn valid for use only— MITI®wnnec— This dasgn is based only upon parameters shown, and is for an Individual building component, not
I tmsa system. Before use, the budding designer ,at verify the applicability of design pammat— and pro dy Incorporate thls design into the overall
building design. Bramg indicated is to prevent bulling of individual truss web and/or chord memb—nly. Addda—l—,omary and permanent bracing MiTek'
s always mguired/o, atxGlity and to prevent collapae with possible pe,sonal injury antl property damage. For general guxance regarding the
labdcatron, ammge, delivery, erection and bracing of Wasas and trues syxiama, see ANS-11 Duality criteria, OSB-89 antl Bcs!Building Component g90q Parke East BIM.
.4, lnrormetlon available from Tmss Plate la—, 218 N. Lee Street, Suite 312, —a—, VA 22314. Tampa, FL M610
.1
3
3.4 1 3.4 II
6Y11r$Rf9l
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.48 Vert(LL) rile - n/a 999 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.19 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress ]nor YES WB 0.00 Hom(CT) 0.00 n/a n/a
BCDL 10.0 Code FBC2017/TPI2014 Matrix-P Weight: 13 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 4-0-0 oc purlins,
BOT CHORD 2x4 SP No.3 except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 1�-0-0,3=4-0-0
Max Ho¢ 1=79(LC 12)
Max Uplift 1=-56(LC 12), 3=-89(LC 12)
Max Grav 1=116(LC 1), 3=120(LC 17)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
NOTES.
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; save=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exlerior(2) mne;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Gable requires continuous bottom chord bearing.
3) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
4) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 3.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Date:
May 6,2020
,&WARNING-vedq—is. pare — antl READ NOTES ON TN/S Aaadav UDE0 N1TEfr REFERENCE PAGE Nl4T/73-14-015 BEFORE USE. ��-
Deagn valid for use only with MITek®wnnec— This design,. based only upon parameters shown, and is for an Individual building component, not
I tmsa system. Before use, the budding designer ,at verify the applicability of design parameters antl popery Incorporate thls design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord membe,sonly. Adda—al—,omary and permanent bracing MiTek'
s always repaired bo, sterility and to prevent collapae with possible personal injury antl property damage. For general gu,d.— rega,tling the
labdcatron, aroma., delivery, erection and bracing of Wasea and trues sy,dama, see ANS-11 Qualify CNhria, OSB-89 antl Bcs!Building Component 6904 Parke East BIM.
.4, lnrofinerlon available from Tmss -te InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
T
Type Ott' Ply
ipec al 3
8.330 s Me
ID:170y9y4e_wmgYIH6Dtfc
17-10-0 22-7-11
4-9-11 49-11
Sxg =
5.00 12
7
T20150964
6-^=1f1E]IRiF'
Tx14 MT1811S =
dxg = 4.6 = 3z10 = 114MT115- =3x10
2.12 1.00 12
12 18Io
LOADING (psf)
SPACING-
2-0-0
CS'.
DEFL.
in (loc) VdeB L/d
PLATES
GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC
0.91
Vem(LL)
-0.50 14-16 >840 360
MT20
244/190
TCDL 7.0
Lumber DOL
1.25
BC
0.82
Ve11(CT)
-1 12 16-17 >378 240
MT18H5
244/190
BCLL 0.0
Rep Stress Incr
YES
WB
1.00
Hom(CT)
0.46 12 ma n/a
BCDL 10.0
Code FBC20171TP12014
Matdx-MS
Wind(-L)
0.71 16-17 >599 240
Weight: 1961b
FT=20%
LUMBER-
BRACING
TOP CHORD 2x4 SP M 30 `Except'
TOP CHORD
Structural wood sheathing directly applied or 1-10-8 oc
pudins.
1-5: 2x4 SP M 31
BOT CHORD
Rigid ceiling directly applied or 3.10.15 oc bracing.
BOT CHORD 2x4 SP M 30 `Except`
WEBS
1 Row at midpt 7-16
2-17,12-13: 2x4 SP M 31
WEBS 2x4 SP No3'Except.
3-17,11-11 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 12=0-4.0
Max Horz 2=316(LC 11)
Max Uplift 2=-915(LC 12), 12=-814(LC 12)
Max Gov 2=1371(LC 1), 12=1306(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-6306/4083, 3-4=-5839/3920, 4-6=-2562/1849, 6.7=-2540/2008, 7-8=2517/1989,
8-10=-2537/1850, 10-11=-5012/3742, 11-12=-5474/3866
BOT CHORD 16.17=-2149/3318, 14-16=-980/1715, 13-14=-2099/3019, 2-17=-3757/6085,
12-13=-3505/5034
WEBS 3-17=-253/628, 11-13=-235/608,4-17=-1556/2589,4-16=-9877793, 6-16=286/372,
10-13=-1384/1828, 10-14=-855/771,8-14=-295/376,7-16=-785/1212,7-14=759/1155
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7.10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.0psf; h=15ft; B=45ft; L=35ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exledor(2) -1-2-0 to 2-4-6, Interior(1) 2-4-6 to 17-10-0, Exterior(2)17-10-0
to 21-4-6, Inteaor(1) 21-4-6 to 35-4-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
gap DOL=1.60
3) All plates are MT20 plates unless otherwise indicated.
4) All plates :re
3x4 MT20 unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconpument with any other live loads.
6) ' This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-M wide
will St between the bottom chord and any other members, with BCDL = 10.0psf.
7) Bearing at joint(s) 2,12 considers parallel to grain value using ANSITrPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at -lb)
2=915, 12=814.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34899
MiTak USA, Inc. FL Cart 6634
6904 Parde East Blvd. Tampa FL 33610
Dr.:
May 6,2020
A wARN1N0-vedq—is. pare — antl READ NOTES ON TfUs ANO 1NCLUDE0 M1TEx REFERENCE PAGE Ml4T/73-14-015 BEFORE USE. ��-
Dasgn valid for use only— MITek®wnnecld- This deagn is based only upon parameters shown, and is for en Individual building component, not
I itsystem. Before use, the bullding designer must verify the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord memb—nly. Adddenaltemporary and permanent bracing MiTek'
s always reo—d fo, deGlity and to prevent collapse with possible personal injury antl propedy damage. For general gu,d.— rega d, the
fabdcatron, smmge, del- , erection and bracing of lmases and W as syatema, see ANS-11 Quality criteria, OSB-89 and Bcal Building Component g9pq parka East BIM.
Safay lnyolmadon available from Truss -te InsgMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
3.4 II Scale: 3/4-=V
3
5 4
3.4 1 2.3 II 3.4 II
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.27 Vert(LL) rile - n/a 999 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.12 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress ]nor YES WB 0.12 Hom(CT) 0.00 n/a n/a
BCDL 10.0 Code FBC2017/TPI2014 Matrix-P Weight: 21 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP No.3 except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. (size) 1=6-0-0, 4=6-0-0, 5=6-0-0
Max Horz 1=129(LC 12)
Max Uplift 4=-64(LC 12), 5=-183(LC 12)
Max Grav 1=56(LC 1), 4=87(LC 17), 5=249(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
WEBS 2-5=-207/406
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-8-12 to 3-8-12, Interior(i) 3-8-12 to 5-10-4 zone;C-C for
members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Gable requires continuous bottom chord bearing.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except (jt=lb)
5=183.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33910
Date:
May 6,2020
,&WARNING-vedq—is. pa ram antl READ NOTES ON TN ANO INCLUDED N1TEfr REFERENCE PAGE Nl4T/73-14-015 BEFORE USE. ��-
Deagn valid for use only with MITek®wnnec— This deagn is based only upon parameters shown, and is for en ddividual building component, not
I tmss system. Before use, the budding designer ,at vebfy the applicability of design parameters antl propedy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord membe,sonly. Addda—l—,omary and permanent bracing MiTek'
s always required bo, alaGlity and to prevent collapse witle possible personal injury antl propedy damage. For general gux.—rega,tling the
labdcatron, atomge, delivery, erection and bracing of Wasea and trues sy,dama, see ANS-11 Qualify CNhria, OSB-89 antl Bcsf Buffdfng Component 89e4 Parke East BIM.
.4, lnrofinerlon available from Tmss P t, InsdMe, 218 N. Lee Street, Suite 312, Neea , VA 22314. Tampa, FL M610
3.4 II scale =1:20.6
3
5 4
3x4 i 2.3 II 3.4
LOADING (par) SPACING- 2-0-0 CSI. DEFL. in (too) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.45 Vert(LLI rile - rile 999 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.22 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress ]nor YES WB 0.14 Hom(CT) 0.00 n/a n/a
BCDL 10.0 Code FBC2017/IPI2014 Matrix-P Weight: 29 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP No.3 except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. (size) 1=8-0-0, 4=8-0-0, 5=8-0-0
Max Horz 1=180(LC 12)
Max Uplift 4=-86(LC 12), 5=-253(LC 12)
Max Grav 1=85(LC 1), 4=116(LC 17), 5=344(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOPCHORD 1-2=-271/118
WEBS 2-5=-269/459
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; save=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extenor(2) 0-8-12 to 4-0-0, Intenor(1) 4-0-0 to 7-10-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Gable requires continuous bottom chord bearing.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
4) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joints) 4 except Qt=lb)
5=253.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
'&WARNING- vedlr Ws;9n param antl READ NOTES ON TN ANO INCLUDED N1TEfr REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deasn valid for use only with MITek®wnnec— This design,. based only upon parameters shown, and is for an Individual building component, not
I tmsa system. Before use, the building designer ,at verify the applicability of design parameters antl propery Incorporate thls design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord membe,sonly. Adda—al—,omary and permanent bracing MiTek'
s always repaired bo, staGlity and to prevent collapae with possible personal injury antl properly damage. For general gux.—regartling the
labdcatron, ammge, delivery, erection and bracing of Wasea and trues sy,dama, see ANS-11 Qualify CNhria, OSB-89 antl Bcs!Building Component g90q Parke Eesl BIM.
.4, lnrofinerlon available from Tmss P t, InsdMe, 218 N. Lee Street, Suite 312, Neea , VA 22314. Tampa, FL M610
1
T20151014
3x6 =
5.00 12 2
3.4 i 3.4
Y:1r-8fib1
LOADING (pat) SPACING- 2-0-0 CSI. DEFL. in (loc) War L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 0.12 Vert(LL) n/a - n/a 999 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.13 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress Incr YES WB 0.00 Hom(CT) -0.00 3 n/a n/a
BCDL 10.0 Code FBC2017/r"2014 Matrix-P Weight: 10 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 4-0-0 oc puriins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 1�-0-0,3=4-0-0
Max Ho 1=-19(LC 10)
Max Uplift 1=-59(LC 12), 3=-59(LC 12)
Max Grav 1=94(LC 1). 3=94(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vul1=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=151t; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exlenor(2) mne;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate gnp DOL=1.60
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1001b uplift at joint(s) 1, 3.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 9934
9904 Parke East Blvd. Tampa FL 33610
pate:
May 6,2020
,& WARNING-va",—is. parameters antl READ NOTES ON TRrs ANO INCLUDED NITEx REFERENCE PAGE Nl4T/73— 10PoIrz0f5 BEFORE USE. ��-
Daslgn valid for use only— MIT—nneclom. This —la ie based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at venfy the applicability of design parameters antl properly Incorporate this design into the overall
building design. Bracing indirated is to prevent bulling of individual truss web and/or chord membe,sonly. Adda—alte r, and permanent bracing MiTek'
s always repaired fo, stalblity and to prevent collapse with possible personal injury antl properly damage. For general gux.—regartling the
fabncatron, atmage, delivery, erection and bracing of Wawa and trues syatema, see ANS-11 Duality criteria, OSB-89 antl BcS1 Building Component g9Oq parka Essl BIM.
.4, lnyolm s— available /ram Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
6-RP7HRE!&
4" =
2
4
3x4 2x3 II 3.
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC "0 Vert(LL) rile - n/a 999 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.18 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress ]nor YES WB 0.09 Hom(CT) 0.00 3 n/a n/a
BCDL 10.0 Code FBC2017ITPI2014 Matrix-P Weight: 24 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. (size) 1=8-M, 3=8-0-0, 4=8-0-0
Max H— 1=-49(LC 10)
Max Uplift 1=-90(LC 12), 3=-90(LC 12), 4=-122(LC 12)
Max Gray 1=118(LC 1), 3=118(LC 1), 4=248(LC 1)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
WEBS 2-0=-166/286
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extenor(2) zone;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
5) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 3 except at=lb)
4=122.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 9934
9904 Parke East BNd. Tampa FL 33910
Date:
May 6,2020
,&WARNING-vedq—is. pare — antl READ NOTES ON T— ANO INCLUDED N1TEfr REFERENCE PAGE Nl4T/73-14-015 BEFORE USE. ��-
Deagn valid for use only— MITek®wnnec— This dasgn ie based only upon parameters shown, and is for an Individual building component, not
I tmsa system. Before lad, the budding designer ,at verify the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord membe,sonly. Addda—l—,omary and permanent bracing MiTek'
s always required bo, ataGlity and to prevent collapse with possible personal injury antl properly damage. For general gux.—rega,tling the
labdcatron, ammge, delivery, erection and bracing of Wawa and truss sy,dama, see ANS-11 Qualify CNhria, OSB-89 antl Bcs!Building Component 8904 Parke Easl BIM.
.4, an/ofinetlon available from Tmss -t, In58Me, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
T20151016
1
FY'11711MINIM-1
VMS
F1
4
3x4 i 2,3
II 3x0
LOADING (par) SPACING- 2-0-0 CS1. DEFL. in (too) I/deb Ud PLATES GRIP
TCLL 200 Plate Grip DO L 1.25 TC 0.69 Vert(LL) n/a - n/a 999 MT20 244/190
TCDL TO Lumber DOL 1.25 BC 0.45 Vert(CT) n/a - n/a 999
BCLL 0.0 Rep Stress ]nor YES WB 0.11 Hom(CT) 0.00 3 n/a n/a
BCDL 10.0 Code FBC2017ITP12014 Matrix-S Weight: 38 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. (size) 1=12-0-0, 3=12-0-0, 4=12-0-0
Max H— 1=-79(LC 10)
Max Uplift 1=-121(LC 12), 3=121(LC 12), 4=-245(LC 12)
Max Grav 1=175(LC 21), 3=175(LC 22), 4=439(LC 1)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
WEBS 2-0=-288/369
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extenor(2) 0-8-12 to 3-8-12, Interiorf) 3-8-12 to 6-0-0, Extenor(2) 6-0-0
to 9-0-0, Intenor(1) 9-0-0 to 11-34 wne;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Gable requires continuous bottom chard bearing.
4) This truss has been designed for a 10.0 par bottom chord live load nonconcument with any other live loads.
5) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ql=lb)
1=121,3=121,4=245.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348419
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Deta:
May 6,2020
'&WARNING-vedq Ws;9n pare — antl READ NOTES ON T— ANO INCLUDED N1TEx REFERENCE PAGE Nl4T/73-14-15 BEFORE USE. ��-
Deasn valid for use only— Mmek®wnnectom. This —la is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the building designer ,at vanfy the applicability of design parameters antl pro dy Incorporate thls design into the overall
building design. Bradng indicated is to prevent b-ling of individual truss web and/or chord membe,sonly. Adda—al—iomary and permanent bracing MiTek'
s always roguirod bo, ataGlity antl to prevent collapse with possible personal injury antl property damage. For general guitlance regartling the
labncatron, ammge, delivery, erection and bracing of Wsses and trues systems, see ANS-11 Qualify CNhria, OSB-89 antl Bcs!Building Component g90q Parke East BIM.
.4, an/ormetlon available from Tmss -te InsgMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
TYpe 1rnY Ply 1
E T20151017
4.4 =
4
12 11 10 9 84x5
4.5 II era II 2x3 II 2r3 II
FTs1'4�Ik::lt0
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) War Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.63
Vert(LL) 0.00
6 n/r 120
MT20 2-110
TCDL 7.0
Lumber DOL
1.25
BC 0.18
Vert(CT) 0.00
6 n/r 90
BCLL 0.0
Rep Stress Incr
YES
WB 0.10
Hom(CT) -0.00
8 n/a n/a
BCDL 10.0
Code FBC20171TP12014
Matnx-R
Weight: 73 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. All bearings 13-0-0
(lb) - Max Horz 12=-318(LC 10)
Max Uplift All uplift 100111 or less atjoint(s) except 12=-278(LC 12), 8=-278(LC 12), 9=-211(LC 8), 11=-212(LC
9)
Max Grav All reactions 2501b or less at joint(s) 12, 8, 10 except 9=422(LC 18), 11=423(LC 17)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-12=-179/438, 3-4=-125/280, 4-5=-126/280, 6-8=-179/437
WEBS 5-9=-255/351, 3-11=-256/351
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.0psf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exlenor(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 6-6-0, Extenor(2) 6-6-0 to
9-6-0, Interior(1) 9-6-0 to 14-2-0 one; end vertical left and light exposed;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcument with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
6) Provide mechanicel connection (by others) of truss to bearing plate capable of withstanding 2781In uplift at joint 12, 278111 uplift at
joint 8, 211 Ib uplift at joint 9 and 21216 uplift at joint 11.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9904 Parts East BNd. Tampa FL 33610
pate:
May 6,2020
'&WARNING-vedq—is. pa ram antl READ NOTES ON TNIB ANO INCLUDED NITEx REFERENCE PAGE Nl4T/73— 1gPo3rzp15 BEFORE USE. ��-
Deagn valid for use only— MIT- nnec— This deagn is based only upon parameters shown, and is for en Individual building component, not
I tmsa system. Before use, the building designer ,at verify the applicability of design parameters antl propery Incorporate this design into the overall
building design. Bracing indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always rep—d fo, stalblity and to prevent collapae with possible personal injury antl properly damage. For general gu,d.— regartling the
fabdcatron, ammge, delivery, erection and bracing of Wasea and truss systama, see ANS-11 Quality criteria, OSB-89 antl BcBI Building Component g9Oq Parke East BIM.
.4, lnssmsadon available from Tmss Plate I-axa, 218 N. Lee Street, suite 312, Nee —, VA 22314. Tampa, FL M610
-1-2-0 66-0 13-0-0 14-2-0
r I, i 6-fi-0 6.60
4x4 =
4
12 11 10 9 8 3.5 II
3.5 I I 2.3 1 2.3 11 2.3 11
FY1181KiF9
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Ud PLATES GRIP
TCLL 20.0 Plate Grp DOL 1.25 TC 0.50 Vert(LL) 0.00 6 n/r 120 MT20 244/190
TCDL 7.0 Lumber DOL 1.25 BC 0.10 Vert(CT) ().Do 6 n/r 90
BCLL 0.0 Rep Stress ]nor YES WB 0.10 Horz(CT) -0.00 8 n/a n/a
BCDL 10.0 Code FBC2017ITPI2014 Matrix-R Weight: 66 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30 except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. All bearings 13-0-0.
(Ib)- Max Horz 12=259(LC 11)
Max Uplift All uplift 100111 or less at joint(s) except 12=-267(LC 12), 8=-267(LC 12), 9=-190(LC 12).
11=-190(LC 12)
Max Grav All reactions 2501b or less at joint(s) 12, 8, 10 except 9=346(LC 18), 11=347(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-12=-181/418, 3<=-126/266, 4-5=-128/265, 6-8=-181/417
WEBS 5-9=-236/330, 3-11=-237/331
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.0psf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Enc1., GCpi=0.18; MWFRS (directional) and C-C Exteror(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 6-6-0, Exte ior(2) 6-6-0 to
9.6-0. Interior(1) 9-6-0 to 14-2-0 zone; end vertical left and fight exposed;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 par bottom chord live load nonconcurtent with any other live loads.
5) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit be the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 267111 uplift at joint 12, 267111 uplift at
joint 8, 190 lb uplift at joint 9 and 190111 uplift at joint 11.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348119
MiTak USA, Inc. FL Cart 9634
9904 Parke East BNd. Tampa FL 33910
Data:
May 6,2020
,&WARNING-vedq—is. pa ram antl READ NOTES ON TN ANO INCLUDED Almsa REFERENCE PAGE Ml67473— 1gPoarzpl5 BEFORE USE. ��-
Deagn valid for use only with MIT— nnec— This dasgn is based only upon parameters shown, and is for en ddividual building component, not
I tmsa system. Before lad, the budding designer ,at verify the applicability of design parameters antl propery Incorporate thls design into the overall
building design. Bradng indicated is to prevent bulling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
s always repaired for staGlity and to prevent collapse with possible personal injury antl properly damage. For general guxi.—regartling the
iabdcatron, ammge, delivery, erection and bracing of Wasea and truss sy,dama, see ANS-11 Duality CNhria, OSB-89 antl Bcs!Building Component 8904 Parke Easl BIM.
.4, lnyofmatlon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, A —chid,, VA 22314. Tampa, FL M610
Jab Tmss Truss Type Ott' Pty
T20151079
76703 VC GABLE 1 1
Job Reference (optional)
Chambers Truss, Inc., Fart Pierce, FL 8.330 s Mar 23 2020 MiTek Industries, Inc. Wed May 6 14:43:12 2020 Page 1
ID:170y9y4e vnn9YIH6Dtfc7UzSVD8-glvEB.oCuHDwSjgmVlAab U4VnHTMp3Z JNIzJBYj
-1-2.0 6-6-0 13-0-0 14-2-0
1-2-0 6.6.0 S." 1-2-0
4.4 = Scale=1:27.1
4
5"00 12 2x3 II 2x3 II
3 5
td 15
3 16
3x4 3.4
2 g
12 11 10 n 83x5 II
3.5 11 2.3 2x3 I 2x3 I
13-0-0
LOADING (par)
SPACING- 2-0-0
1 CSI.
DEFL. in (too) I/deb Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.41
Vert(LL) 0.00 6 n/r 120
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.06
Vert(CT) -0.00 6 n/r 90
BCLL 0.0
Rep Stress ]nor YES
WB 0.09
Hoc (CT) -0.00 8 n/a n/a
BCDL 10.0
Code FBC2017ITP12014
Matrix-R
Weight: 60 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30 except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or
10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. All bearings 13-0-0.
(Ib) - Max Horz 12=-200(LC 10)
Max Uplift All uplift 1001b or less at joint(s) except 12=-255(LC 12), 8=-255(LC 12), 9=-192(LC 12).
11=-192(LC 12)
Max Grav All reactions 250 It, or less at joint(s) 12, 8, 10 except 9=311(LC 18), 11=313(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-12=-187/404, 3A=-142/259, 4-5=-143/257, 6-8=-187/402
WEBS 5-9=-219/318,3-11=-220/318
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.0paf; h=15ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Enc1., GCpi=0.18; MWFRS (directional) and C-C Exterior(2)-1-2-0 to 1-10-0, Interior(1) 1-10-0 to 6-6-0, Exterior(2) 6-6-0 to
9.6-0. Intedor(1) 9-6-0 to 14-2-0 zone; end vertical left and fight exposed;C-C for members and forces 8 MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 par bottom chord live load nonconcurrent with any other live loads.
5) " This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit be the bottom chord and any other members.
This item has been
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 2551b uplift at joint 12, 2551b uplift at
electronically signed and
joint 8, 1921b uplift at joint 9 and 192 lb uplift at joint 11.
sealed by Lee, Julius, -
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,39
MiTak USA, Inc. FL Cart 6634
1904 Pare East Blvd. Tampa FL 33610
Date:
May 6,2020
IAWARNING-verey-is. parama dd READ NOTES ON TNIa ANO INCLUDED MITEX REFERENCE PAGE Nl4T/73- 10PoIrze15 BEFORE USE. ��-
Deagn valid for use only wdh MI -nnectom. This dasgn ie based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer must vedfy the applicability of design parameters antl propery Incorporate thls design into the overall
buildingdesien. Braung indiratetl isb prevent bulling of intlivitlual truss web andlor chortl members only. Addd-alte.,omery and permanent bracing MiTek'
s always required for dardity and to prevent collapse with possible personal.n and property damage. For generalguxi.-regarding the
labdcatron, atorege, delivery, erection and bracing of -ea and truss sy,dama, aee ANS-11 qualify CrlNria, OSB-89 antl Bcsi Building Component g9pq pare Eaat BIM.
Safay lnfolmadon available from Tmss Plete InsgMe, 218 N. Lee Street, Suite 312, Nee -, VA 22314. Tampa. FL M610
4x4 =
3
FY�1r-SWYi4
10 9 8 7 6
3x5 11 2x3 11 2x3 11 2.3 11
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) War Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.37
Vert(LL)
n/a - n/a 999
MT20 2-110
TCDL 7.0
Lumber DOL
1.25
BC 0.06
Vert(CT)
n/a - n/a 999
BCLL 0.0
Rep Stress Incr
YES
WB 0.10
Hom(CT)
0.00 6 n/a n/a
BCDL 10.0
Code FBC2017/rP12014
Matrix-R
Weight: 50 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc pudins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied Or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. All bearings 13-0-0
(lb) - Max Horz 10=-95(LC 10)
Max Uplift All uplift 100 lb or less atjoint(s) except 10=-111(LC 12), 6=-111(LC 12), 7=-223(LC 12), 9=-223(LC
12)
Max Grav All reactions 250 it, or less at joint(s) 10, 6, 8 except 7=306(LC 18), 9=308(LC 17)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-167/274, 3-4=-167/274
WEBS 4-7=-222/328, 2-9=-222/328
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=15ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exlenor(2) 0-1-12 to 3-1-12, Interior(l) 3-1-12 to 6-6-0, Eztedor(2) 6-6-0
to 9-6-0, Interior(1) 9-6-0 to 12-IOA zone;C-C for members and forces 8 MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 111 Ib uplift at joint 10, 111 lb uplift at
joint 6, 223 Ib uplift at joint 7 and 22316 uplift at joint 9.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 6634
9904 Parke East BNd. Tampa FL 33610
Dat4:
May 6,2020
'&WARNING-vedgWsfgn parameters antl READ NOTES ON TRIS AND INCLUDED AdmEK REFERENCE PAGE Nl4T/73— 10PoIrzd15 BEFORE USE. ��-
Daslgn valid for use only— MIT—nneclom. This —la is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer ,at verify the applicability of design parameters antl propery Incorporate this design into the overall
building design. Bradng indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adda—altemporary and permanent bracing MiTek'
s always n paired fo, stalblity and to prevent collapse with possible personal injury antl properly damage. For general gu,d.— regartling the
fabdcatron, smmge, delivery, erection and bracing of Wawa and truss systems, see ANS-11 Quality cNhria, OSB-89 antl BcSI Bufldfng Component g9Dq parka East BIM.
.4, lnyolmadon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, Nee —, VA 22314. Tampa, FL M610
Vv
n N Z W
(n m > m r N� r Cl)
— D m A m X m .W m
z
N O N I I r a
n v�icmov_z� W m o A'"' n
O
m o:a m,0=a $o. O 1
m
n WOo SON 3�'mm� =°c�a Z ..oF� md• �m� ma0- J1� mDOon Z
3 '� �^ w a m c m c? °' o as 3 m D
N N? o N N '•C• N r N yE. y y A C •� S. N Z
ay'Q 00 �°yma 'U �aQ coN —a ".ma
omgo° mm•< D 'm c ago �o m�ymm O
(nmo_ Fmo v� •� m? m a m ran hm c maj m
0o@3 O °l aoH N'o'�: m'^ oomn z
oo�4.Nd ym — z oc, m v�y�.
o mo.ao 3 m �o. Z.
f° m o y 1O ?' as o = m m J m K m Z
Q o. m c N o m
a
o o = m o
3
-
cx
D �-
xv0
TOP CHORD
m
v"-v
0
41 ti
wA
n O
mz
rcy
ci-e
Z
y
c m
ow
y
mo
my
mzw
:��p
r_
vim
I
O 0m
Z.
mO
.< M'
o a
vm
S p�m
m
O
a
o m<
may.
w�
y
m
mm
cm
p0
v
cr
5m m
s
rnw
yy
m�
O
V
W21
O
N
c
N N N
N �'
��
'a
m
yK
O
1
�.
�■
O
A
w
N
O f
w�
G
T
H e
Z
n
2
m
y
N
p w
,^
""�
�.
m�
N
TFOR
F m
ooi
A
-Dfm
=p
o
N"
u 3
✓V/
m
w
w ��1
D ?
w
N
W
m
z
mm
Q�
° 3
CD
m
zm
w
Oo
c
^
m
z
mo
n i
N
p <Z
m
m
So
mo
N
N C Cl)
. T.
'g
m
o m
TOP CHORD
zo -gip a<c :z �d£2 ay 3 c
�3 m'm u mm h £m 'oN '<� as 3 'mm 3m ncallo u6 N
�-3n 3
Ocm - a- m-�o' - 3m 'm aam� mm`3m - mmJxO T m
O CD
_ _ �_�
a° ag_ mN f 3m d 'w n;=J aN b�"o`°. f
-E oo - m S 3u a`1 "�. mn a om - _ o `o0 CD
m' 3 A 0 3 m 3 w^ - a S m 3 d w 7 �%
3 roo f£ zm� C50
�.a 33 - �CL
.� om� mm �m gm -£" v �2 srwr �� CL
cn
01 xm o. F Q s - F3 an o '3 - £v y3 N3 N y1
m nd S om - - 2vn,'
a 3 �� o
cr 3 Z
= 3 - m
O
.-r
(D
N
1890
18-0-0
,1-2A 24i0 ]-S8 13-0.5 17-0-0 1,718q 22-7-11 z N2 1 2S1b 33AO I 3sd8
11-2-0 2d9 410A SS13 311-11 0.10-d' 3-11-11 2-9-] 2-Ba 4-10-0 2J-0
0 0
0-s-0
4z8 =7x8 =
5.00 12 4x8 =
7z14MT18H$ _ _
3.10 = Iz6 = 3x8 7z14 MT18H5 =3x10
U12 i.00 12
2-8-0 13A-5 17A-0 1 21-8-9 -7-11 2552 33-0-0 351-0
2-8-0 10.4-5 311-1138-9 11- 2-9-7 7-8-14
Plate Offsets (X,Y) -
[2:0-25,Edge], [3:0-2-12,0-1-2], [4:0-3-0,0-1-12], V:0-4-0,0-2-2], [8:0-4-0,0-4-12], [9:0-4-0,0-2-2], [13:0-2-12,0.1-2], [14:0.0.9,0-1-6], [15:0-8-5,Edge),
I19:M-12,Edge1
LOADING (pat)
SPACING- 2-0-0
CS.
DEFL.
in (loc) Udeft
L/d
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.91
Vert IL)
-0.49 18-18 >872
360
MT20
244/190
TCDL 7.0
Lumbar DOL 1.25
BC 0.82
Vert(CT)
-1.12 18-19 >377
240
MT18HS
244/190
BCLL 0.0 '
Rep Stress Incr YES
WB 0.99
Horz(CT)
0.46 14 n/a
n/a
BCDL 10.0
Code FBC2017/TP12014
Matdx-MS
Wind(LL)
0.71 18-19 >597
240
Weight: 196 lb
FT=20%
LUMBER -
TOP CHORD 21
SP M 30'Except`
7-9: 2x6 SP No.2, 1-5: 2.4 SP M 31
BOT CHORD 2x4 SP M 30 *Except*
2-19,14-15: 2x4 SP M 31
WEBS 2x4 SP No.3 `Except*
3-19,13-15: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 14=0-4-0
Max Hoa 2=302(LC 11)
Max Uplift 2=-915(LC 12), 14=-814(LC 12)
Max Grav 2=1371(LC 1). 14=1306(LC 1)
BRACING -
TOP CHORD Structural wood sheathing directly applied or 1-104 oc pudins.
BOT CHORD Rigid ceiling directly applied or 3-9-8 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-6275/4301, 3-4=-5804/4112, 4-6=-2557/1964, 6-7=-2517/2122, 7-8=2215/1961,
8-9=-2194/1930,9-10=-2495/2089,10-12=-2532/1930,12-13=-5006/3851,
13-14=-5471/3991
BOT CHORD 18-19=-2297/3300, 16-18=-1051/1689, 15-16=-2188/3023, 2-19=-3975/6044,
14-15=-3620/5031
WEBS 3-19=-291/631, 13-15=-267/611,8-18=-830/1163,6-18=-227/379,4-18=-1003/817,
4-19=-1610/2562,8-16=-802/1109,10-16=-238/385,12-16=-871/792, 12-15=-139911818
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; VuI1=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsh, h=15ft; B=45ft; L=35ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-2-0 to 2-4-6, Interior(1) 2-4-6 to 17-0-0, Exterior(2) 17-0-0 to
23-7-15, Interior(1) 23-7-15 to 35-4-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) All plates are 3x4 MT20 unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
8) Bearing at joint(s) 2, 14 considers parallel to grain value using ANSUTPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ql=lb)
2=915, 14=814.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 6634
6904 Parke East BNd. Tampa FL 33610
Data:
May 6,2020
,&WARNING-verey—is. parameters antl READ NOTES ON TN ANO INCLUDED M1TEx REFERENCE PAGE Nl4T/73—la-15 BEFORE USE. ��-
Dealgn valid for use only— MITek®wnnec— This deagn is based only upon parameters shown, and is for en ddividual building component, not
I truss system. Before use, the building designer ,at verify the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Braung indicated is to prevent b—ing&individual truss web and/or chord membersonly. Adddionaltemporary and permanent bracing MiTek'
s always rep—d fo, staGlity and to prevent collapse with possible personal injury antl pmpe,ry damage. For general gu,d.— regartling the
fabdcatron, smmge, delivery, erection and bracing of Wawa and truss system., see ANS-11 Duality criteria, OSB-89 antl BcS1 Building Component 6904 Parke East BIM.
.4, lnyo arse, available /ram Truss Ptate In58Me, 218 N. Lee Street, Suite 312, Nex —, VA 22314. Tamps, FL M610
1-2-0 7-&5 15A-0 20-8-0 25-&2 28-0-8 3&0-0 35.8-0 3&10.0
4-2-0I 7-&5 I 7$11 I 541-0 I 4-9-2
Scale: 3/1fi"=1'
Salt
5.00 12 Sx8 = Sx
4 26 275
17 15 14 13
3x4 3.5 4x8 3x8 = 5x6 — 3.4 II 7x14MT18HS —3x12 1
=
4.00 12
LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) War L/d PLATES GRIP
TCLL 20.0 Plate Grip DOL 1.25 TC 1.00 "it" LL) -0.43 1 1 -12 -999 360 MT20 2441190
TCDL 7.0 Lumber Da 1.25 BC 0.77 Ve"(CT) -0.89 11-12 >483 240 MT18HS 244/190
BCLL 0.0 Rep Stress Incr YES WB 0.89 Hom(CT) 0.29 9 n/a n/a
BCDL 10.0 Code FBC2017/rP12014 Matnx-MS Wind(LL) 0.63 11-12 >675 240 Weight: 196 lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied.
BOT CHORD 2x4 SP M 30 *Except* BOT CHORD Rigid ceiling directly applied or 3-8-14 oc bracing.
6-13: 2x4 SP No.3, 9-11: 2x4 SP M 31 WEBS i Row at midpt 3-15, 5-15, 5-12
WEBS 2x4 SP No.3 *Except*
8-11: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 9=0-&O
Max Ho 2=276(LC 11)
Max Uplift 2=-921(LC 12), 9=-921(LC 12)
Max Grav 2=1383(LC 1),9=1383(LC 1)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-2844/2189, 3-4=-2075/1720, 4-5=-1846/1702, 5-6=-2867/2463, 6-7=2936/2365,
7-8=-5618/4277, 8-9=-6034/4426
BOT CHORD 2-17=-1877/2569, 15-17=-1876/2571, 14-15=-1223/1837, 11-12=-2320/3144,
9.11=4041/5599
WEBS 3-17=0/322,3A5=-891/726,4-15=-265/480,12-14=-1125/1750, 5-12=-1031/1230,
&11=-235/552, 7-11=-1687/2311, 7-12=-700/590
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vul1=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsh, h=15ft; B=45ft; L=36ft; eave=511; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2)-1-2-0 to 2-4-13, Interior(1) 24-13 to 15-0-0, Exterior(2) 15-0-0
to 20-0-8, Interior(1) 20-0-8 to 20-8-0, Exterior(2) 20-8-0 to 25-8-8, Interior(l) 25-8-8 to 36-10-0 zone;C-C for members and forces S
MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 pef bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will 6t between the bottom chord and any Other members.
7) Bearing at joint(!) 9 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at --lb)
2=921,9=921.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 34809
MiTak USA, Inc. FL Cart 9634
9964 Pants East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING- vedry Wsfgn Paramamrs READ NOTES ON nvis AND INCLUDED NITER REFERENCE PAGE Nl4]/73— 10Poarzp15 BEFORE USE. ��-
Daslgn valid for use only— MIT—nnectom. This design is based only upon parameters shown, and is for en Individual building component, not
I tmss system. Before use, the budding designer must vebfy the applicability of design parameters antl pro dy Incorporate this design into the overall
building design. Braung indicated is to prevent b—ing of individual truss web and/or chord memb—nly. Adddxnaltempmary and permanent bracing MiTek'
s always reguiretl for staGlily antl to prevent collapse with possible personal injury antl Drapery tlamage. For general guitlance rega d, the
fabdcatron, ammge, delivery, erection antl bracing of Wasea and truss systama, see ANS-11 Duality criteria, OSB-89 antl Bc8/Buffding Component g9Dq parka East BIM.
.4, lnss,s agon available from Tmss Plate InsdMe, 218 N. Lee Street, Suite 312, N ddlm, VA 22314. Tampa, FL M610
T20150967
I
FY'1r.SQ•iA-]
Sx8 3.4 I
5 31 6
3.8 = 5x6 =
32 7 33 34 8
7.14 W18H5 = 3x4 = 19 18 17 16
5x8 = sx8 = 6x8 - 3.4 II 7x14MT18H8 =3x12
3x12 400 12 3.4 II 3.4 II 3.4 11
2 Hi
743-7 ?" i .- 1 18-&0 1
22-8-0 1 W11 nm 1 35-8.0
Plate Offsets (X,Y)-
[2:0-25,Edge], [3:0-2-12,0-1-2], [5:0-5-12,0-2-8], [8:0-3-0,0-2-4], [10:0-2-12,0-1-2], [11:0-25,Edge], [13:05-12,Edge], [15:0-2-8,0-3-0], [20:0-2-12,0-3-0],
f22:0-8-12,Edgel
LOADING (pat)
SPACING- 2-0-0
Cat.
DEFL.
in (loc) Udeft
L/d
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.77
Vert(LL)
-0.50 13-14 >855
360
MT20
244/190
TCDL 7.0
Lumbar DOL 1.25
BC 0.85
Vert(CT)
-1.16 13-14 >367
240
MT18HS
244/190
BCLL 0.0 '
Rep Stress Incr YES
WB 0.89
Horz(CT)
0.51 11 n/a
n/a
BCDL 10.0
Code FBC2017ITP12014
Matrix -MS
Wind(LL)
0.6913-14 >617
240
Weight: 218 lb
FT=20%
LUMBER- BRACING -
TOP CHORD 21
SP M 31 'Except` TOP CHORD
5-8: 2x4 SP M 30 BOT CHORD
BOT CHORD 2x4 SP M 30 *Except*
6-19: 2x4 SP No.3, 2-22,11-13: 2x4 SP M 31
WEBS 2x4 SP No.3 `Except*
3-22,10-13: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 11=0-6-0
Max Horz 2=242(LC 11)
Max Uplift 2=-921(LC 12), 11=-921(LC 12)
Max Gmv 2=1383(LC 1). 11=1383(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-6141/4487, 3-4=-5659/4261, 4-5=-2586/2075, 5-6=-2354/2053, 6-7=2345/2047,
7-8=-2310/1998,8-9=-2593/2091,9-10=-5656/4256, 10-11=-6138/4477
BOT CHORD 21-22=-2433/3167, 20-21 =-1 570/2338, 18-1 9=-1 88/362, 14-15=-2451/3161,
13-14= 2451/3161, 2-22=-0079/5804, 11-13=d084/5699
WEBS 5-21=-395/858,5-20=-258/189,15-17=0/421, 8-15=-530/772, 7-18=673/506,
3-22=-344/627,10-13=-337/637,4-22=-1561/2493,4-21=1003/955, 9-13=-1539/2346,
9-15=-958/946, 18-20=-1324/1814, 15-18=-1451/2040,7-20=-221/396, 7-15=-134/325
Structural wood sheathing directly applied or 2-2-0 oc purlins.
Rigid ceiling directly applied or 3-8-13 oc bracing.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vu11=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsh, h=15ft; B=45ft; L=36ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exlerior(2)-1-2-0 to 2-4-13, Interior(1) 24-13 to 13-0-0, Exterior(2) 13-0-0
to 18-0-8, Interior(1) 18-0-8 to 22-8-0, Extenor(2) 22-8-0 to 27-8-8, Intedor(1) 27-8-8 to 36-10-0 zone;C-C for members and forces &
MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 pat bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Bearing at joint(s) 2, 11 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at --lb)
2=921,11=921.
This item has been
electronically signed and
sealed by Lee, Julius, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Julius Lee PE No. 348,19
MiTak USA, Inc. FL Cart 9634
9904 Pants East BNd. Tampa FL 33610
Data:
May 6,2020
'&WARNING-vedq-is. parameters antl READ NOTES ON nvis ANO INCLUDED N1TEx REFERENCE PAGE Nl4]/73-1a-15 BEFORE USE. ��-
Dealgn valid for use only- MITek®wnnec- This deign is based only upon peramsters shown, and is for en Individual building component, not
I truss system. Before use, the budding designer ,at verify the applicability of design parameters antl propedy Incorporate this design into the overall
building design. Braung indicated is to prevent b-ing of individual truss web and/or chord membersonly. Adda-altemporary and permanent bracing MiTek'
s always repaired fo, staGlity and to prevent collapse with possible personal injury antl propedy damage. For general gu,d.- rega,tling the
fabdcatron, storage, delivery, erection and bracing of Wawa and truss systama, see ANS-11 Quality criteria, OSB-89 antl Bcs!Building Component 6904 Parke East BIM.
.4, lnyo7madon available from Tmss Ptate InsdMe, 218 N. Lee Street, Suite 312, Nex -, VA 22314. Tamps, FL M610