HomeMy WebLinkAboutProject Informationwrightsoft Project SummaryJob: Date: May ta, 2020 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORTPIERCE, FL 34946 Phone: 77246"799 Fas 772-466-6796 Email: DUICKCALCS@AOL.COM For. WIENCKE RESIDENCE LOTA3 VENTURE HARBOR, JENSEN BEACH, FL Notes: Weather. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19522 Btuh Structure 15697 Btuh Ducts 4585 Btuh Ducts 6717 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24107 Btuh Use manufacturer's data n Ratelswingg multiplier Equipmentsensible load 0.95 21293 Btuh Infiltration Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3306 Btuh Ducts 1795 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coolingg (none) Area (ft� 1699 1699 Equipment latent load 5101 Btuh Volume (fit) 16561 16561 Air changesthour 0.38 0.20 Equipment Total Load (Ser Lot) 26395 Btuh Equiv. AVF (cfm) 105 55 Req. total capacity at 0.70 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Ruud Trade Trade RUUD Model Cond RA1630AJlNA AHRI ref Coil RH1T3621MTANAA AHRI ref 7941344 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 6.2 kW Sensible cooling 21000 Btuh Heating output 21119 Btuh latent cooling 9000 Btuh Temperature rise 19 OF Total cooling 30000 Btuh Actual air flow 1000 cfm Actual air flow 1000 cfm Air flow factor 0.041 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed �. -rk- wrlghlGsoH- 202 -May-1410:11:35 •�^• ta^ ft RlghtSuite® Universal 2019 19.0.08 RSU08101 Page 1 ACCKE:\DocurmetsMdghtso9 HVAC\WIENCKE RESIDENCE.rup Calc=MJ8 Front Door races: W wrightsoft Right-J® Worksheet Job: Entire House Date: May 14, 2020 QUICK CALCS, INC, By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466E799 Fax 772-466-6796 Email: OUICKCALCS@AOL.COM 1 2 3 4 5 Room name F)posed wall Room height Room dimensions Room area Entire House 157.4 ft 9.7 ft 1699.0 ft' MASTER BEDROOM 31.0 ft 9.3 ft heattood 1.0 x 284.0 It 254.0 ft- Ty Construction number U-value (BtulVtVVF) Or HTM Arm (ftj or perimeter (ft) Load (Btuh) Area (fn or perimeter (ft) Load (Bluh) Heat Cad Gross WP/S Heat Cod Gross WRIS Heat Cod 6 11 ..._P 11U I-� _ 134-Socs 2 glazing, clr lcwe 2 glazgg, grlcwe_ 13A-5= 2 glazing, clr low-e 2 glazing, or 1 2 plazmp,'clf IowE� taASocs 2 glazing, dr luw-e 2 glazing, dr IOwe 2 gluing, dr 117w-e 2glazing,clrlcw-e_._ 13A-50ns 2plazinq cirlaq-e. __ 2 glazing, dr to -e 2 glazing, dr Icwc 2 glazing, dr lcw_e__ _ 13A-5ocs 2plwinq, clr love 18X19-0md_- _ - 0.125 0.400 0.400 �__0.125 0.400 0A00 0.400 0.125 0.400 0.400 0.400 .. ..0.400_.s_..._...11.20 0.125 ____0.400 0.125 0.400 a.400 . __0.4DD 0.125 0.400 b.408 ___1.358 n n -a a a _e_ s s 5 s sw _sw w w w --w-. m rmr _-�, = 3.50 11.20 1120 ,--e 3.60 11.20 11.20 11.20 3.50 11.20 11.20 11.20 3.50 _11.20 3.50 11.20 11.20 __ .11.20 350 11.20 _ 1.59 ' 38.02 1.91 10.19 _ 1.0.19 1.91 24.14 24.32 _ 20.24 1.91 10.19 10.19 10.19 __._8.81 1.91 _ 15.05 `� 1.91 24.14 24.54 _,„.,24.54 1.91 ^19.70 _ __1.37 _0.00 �_�972 • 6 _ 8 409 30 36 64 446 6 30 24 ..._.._...24..._._.._24_____.ffi9....211:.0 39 14 --198 20 11 ,._ _.___20 39 _ 14 __. 1699 _,_,1699 _ 41�u_38U 0 _ _ 0 ' �Z79 2 2 _ 3 362 .6 30 24 25 7 -- -147 1 0 -._.._.1 25 0 _ _1899 . _157 �1280 67 67 ' -�- 977 336 403 _ 717 1268 67 336 269 89 _ _159 516 224 119 _.� 224 89 159 _ _,2694 5986 �.. 689 61 61 _ -- 5M 724 875 _1295 693 61 306 245 48 213 -�282 483 262 401 48 Z79 __ 2325 0 -_-140 0 _ _ 0 ' 149 30 0 0 -, ------0 0 0 0 0 0 ---0 0 0 _0 0 __ _ 0 -284 ____284 ____'4O 0 0 __--119 2 0 A. ._ _0 0 0 0 0 0 0 - --0 0 0 �.._.... _0 0 _ 0 "_264 31 _,. -486 0 0 - -_416 338 0 0 .. __. ._0 0 0 0 .__.....__0 0 0 ---- --0 0 0 _ _M __ 0 0 _ 0 _-, 410 _1179 _ ___267 0 _ 0 227 724 0 0 --O 0 0 0 ._0 0 0 -- ' -0 0 0 �.__ 0 0 _ 0 ,_ _367 0 VVNN I--G �L---GG _ IW _ W L-G I--G IL----GG IN �G C ____ 6 c)AED excursion 0 -149 Emelope loss/gain 16294 10187 2837 1430 12 a) Infiltration b) Room ventilation 3228 0 910 0 618 0 174 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 4500 0 0 1300 Subtotal pines 6 to 13) 19M 15697 3456 2904 14 15 Less exdemal load Less transfer Redistribution Subtotal Duct loads 23°/, 43% 0 0 0 19522 4585 0 0 0 15697 6717 23% 43% 0 0 0 3456 812 0 0 0 29M 1243 Total room load Air required (cfm) 24107 1000 22414 1000 4267 177 4147 185 Calculations approved bvACCA to meet all reauiremerlts of Manual J 8th Ed c �}:- wrlgh6o6Tt- 2020-May-14 10.11:35 RlghtSuiteO Universal 201919.0.08 RSLP08101 Page 1 EADocurmelslWdghtsoft WAC\WIENCKE RESIDENCE.rup Cate -MJ8 Front Door faces: W F�+wrightsoft Right-JO Worksheet Job: Entire House Date: May 14, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466-6796 Email: OUICKCALCWOL.COM 1 2 3 4 5 Room name Famed wall Room height Room dimensions Room area M WIC 6.0 ft 9.3 ft heat/cool 9.0 x 6.0 ft 54.0 ft' M TOILET 3.0 ft 9.3 It heal/cool 10.0 x 3.0 It 30.0 W Ty Construction number U-value (B1ulVWF) Or HTM (Biuh/ftj Area (ftj a perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Hwt Cod Gross WP/S Heat Cod Gross WP/S Heat cod 6 11 l(V-- 13A'.roc..S.J_-.. . 2glazing, dr lox-e 2 glazing,dr laze^ 134-50cs 2 glazing, clr lave 2 glazing, clr lave 2glazin0. clr lavee_. 134ocs 5 2 glazing,clr lave 2 glazing, c1r lows 2 glazing, clr lave 2 glazing, ciclave.__.._ 13A-5ocs alazin9.clr l0W.6-_,___0:400_sw_,- 13A-Socs 2 glazing,,dr bwe 2 lazir clr lave 2 glazing, clr.ldvre_._ 2 glazinq, dr low-e____0.400 16X19-0md. _ 22a-td1___'"-_......__1.358 _0.-125 0.400 _ 0.400 0.125 0.400 0.400 _.-_-_0.400 0.125 0.400 0.400 0.400 ..0.400 0.125 0.125 0.400 0.400 _.__.:0.400 _0.408_.�1.59_7.37 _ n d n a a a _e_ s s s s _ s.. sw w w w _w.. rnv _mv_ - .___3.50 11.20 _ _ 11.20 3,50 11.20 11.20 w11.20 3.50 11.20 11.20 11.20 -11.20 3.50 11.20__75.05_. 3.50 11.20 11.20 ___11.20 11.20_ 38.02 .1.91 10.19 _._ 10.19 1.91 24.14 24.32 __20.24 1.91 10.19 10.19 10.19 , _8.81 1.91 1.91 24.14 24.54 _._ 24.54 1.9 19.70 0.00..._._..54. fib 0 0 0 0 0 __. 0 0 0 0 0 _..- _0 0 0 0 0 .,._,.,,__0 0 0 _`___54 -56 0 _ 0 0 0 0 0 0 0 0 0 __ ___0 0 0 0 0 __...._._-._O 0 - ' 105 0 0 0 0 0 ._ .._ 0 0 0 0 .0 0. 0 0 0 0 ....... -0 0 __.._. _ _6 �. _ 86 107 0 _ 0 0 0 0 _____0 0 0 0 0 _ _-0 0 ___ 0-�..0 0 0 0 ......0:._._........_0--- 0 ._ _ . _ 0 74 28 0 _ __ __6 0 0 0 ..._- ._ 0 0 0 0 0 _.__ . _0 0 0 0 0 0 0 -_30 - ___22 0 _ _. _, _ 0 0 0 0 ._ 0 0 0 0 0 _ -_ _ 0 0 0 0'-_�--0 0 0 _,------ 0 0 .� 0 _ 30 r.�._._3.-_._.114 _.----- 77 0 _ _ , 67 6 0 0 ._.. 0 0 0 0 0 __ __..__0 0 00 0 0 ._._.____0 0 0 _ ._48 ----42 0 . . _ 61. O 0 0 _ _0 0 0 0 0 _ _ ..0 0 0 0 0 _..__..._0 0 O _ _...__,.41 0 II--GG <W II-G W ... _. _ W .L-G.2 W - I--G IF---CG L-G F __�0 __.,_v 54 ----- -._6._.._.__228_..._.,._'030 6 c)AED exursion -13 -10 Fnnelope loss/gam 509 168 305 134 12 a) Infiltration b) Room watilation 120 0 34 0 60 0 17 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 O 0 0 0 Subtotal Pines 6 to 13) 629 201 365 151 14 15 Less eodernal load Less transfer Redistribution Subtotal Duct loads 239/6 43% 0 0 0 629 148 0 0 0 201 86 2334 43% 0 0 0 365 86 0 0 0 151 65 Total room load Air required (crm) 776 32 288 13 451 19 216 10 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -W o.R- 2020-May-1410:11:35 �c Right -Suite® Unhersal 2019 19.0.08 RSW8101 Page 2 E:1DocurmetslWrightsoft HVAC1WIENCKE RESIDENCE.rup Care =MJB Front Door faces: W wrightsofr RighW@ Worksheet Job: Entire House Date: May 14, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: OUICKCALCS@AOL.COM 1 Room name M BATH LAUNDRY 2 Exposed wail 10.0 ft 0 fit 3 Room height 9.3 ft heat/cod 9.3 It heattcod 4 5 Roonl dimensions Room area 1.0 x 124.0 ft 124.0 ft- 1.0 x 5B.0 ft 58.0 ft2 Ty Construction number U-value (Btuh/WF) Or HTM (Btuwftl Area (ft2) a pefteter (ft) Load (Btuh) Area lit a perimeter (ft) Load (Btuh) Heat I Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 l4IJ--G � ___ 19A-5o'cs -_ 0.125 - n -_ 3.50 1.91 --93 ----^ 87 i305 ___ 165 _� 0 0 0 0 2 glazing, cir lowe 2gluig, cir lowe0.400 0.400 n _n 11.20 1120 10.19 6 __...._._00 0 67 0 61 _ 0.,.,_...___ 0 0 0 ___.. 0 0 00 0 VN�G 11 13A-50cs 2 glazing, dr low-e 0.125 0.400 a a 3.50 11.20 _.-10.19 1.91 24.14 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �G �G 2 glazing, cir love 2 plazirq, clr.low-e 0.400 0.400 a 11.20 11.20 24.32 20.24 0 U 0 0 0 .__ _ _0 0 _ -o 0 _0 0 -�. 0 0 ___ 0 -- _ 13A6as 0.400 _e_ 8 3.. --- _ 0 - _U - �` 0 _- _. __0 0 0 0 0 0- 0 2 glazing, cir low-e 0.4D0 s 11.2020 100.1919 0 0 0 0 0 0 0 0 2 glazing, cir lave 0.400 is 11.20 10.19 0 0 0 0 0 D o 0 2 glazing, cir lowe 291azing,:clrlowe.._ 0.4D0 _____0.40D s _s. 11.20 __11.20 10.19 .8.81'._ 0 ------ 0___._0____0-__._0._._.-0.._. 0 0 0 0 0 ____..0 0 _____0_ 0 _. __.0 IW 13A-5ocs 0.125 sw 3.50 1.91 0 0 0 0 0 0 0 0 - . w 2 glazing, clr lov-e�. 13A-5ots 2 glazing, cir lowe 2 glazing, cir lowe ____._0.40D 0.125 0.400 0.400 sw_ . w w w ._-_11.20 -3.50 11.20 11.20 _ 15.05 1.91 24.14 24.54 , __ - _-_0 , 0 0 0 v_ -0 0 0 0 _ d0 0 0 0 0 0 0 0 0 0� 0 0 _ _ 0 � 0 0 0 ... 0 0 0 _ _ _ 0 0 0 2glazirg,drlmve_.-. _.0.400_w..__11.20_24.54 --- _---- .0_..____0_._.__0._____0 .._..___0 _.__._0,- __0 -._ 0 ._... lM �G 13A-5ocs 2 glazirq, clr lc a 16X19;0md 0.125 0.400 _ 0.40B rnv my _ 3.50 11.20 ,_.._ 1.59 1.91 19.70 1.37.,._724 0 0_ 0 0 ___.124 0 0 197 0 0 _._170 0 0 -_.__58 0 0 ... -_58 0 0 ----92 0 0 _. _79 F _. 22A-tbh __1.358 __._ _._.38.02 0.00 124 70 380 _--0 `� --.._0 _-_ _-0 _- 0 6 c)AED excursion -43 47 Envelope loss/galn 949 355 92 32 12 a) Lnfltmtion 199 56 0 0 b) Rcom ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 250 700 Subtotal Qines 6 to 13) 1148 w 92 732 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1148 661 92 732 15 Duct loads 23% 43% 270 283 23% 43% 22 313 Trial room load 1418 944 114 1046 Air required (cfm) 59 42 6 47 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. r -rw wrlghboft� 2020-May-1410:11;35 Right -Suite® Universal 2019 19.0.08 RSU08101 Page 3 AcAE;lDocurmetslWdghtsod WACwMENCKERESIDENCE.mp Calc=MJB Fmnt Doorfaces: W +++ wrightsoft Right-JO Worksheet Job: Entire House Date: May 14, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Roan name Exposed wall Roan height ROan dimensions Roan area FOYER &0 It 14.3 It heat/cool 1.0 x 152.0 It 152.0 ft' IQTCHEN 0 R 9.3 It healfcod 16.0 x 11.0 It 176.0 ft- Ty Construction number U-value (BtulJftz`F) Or HTM (Btuh/ft2) Area (ftj or perimeter (ft) load (Btuh) Area or perimeter (ft) Load (Btuh) Heat I Cod Gross WP/S Heat Cod Gross WP/S Heat Cool 6 11 ISJ -- 13A-5ocs _-_ 2 glazing, clr lows 2.glazing,clr love 2 glazing, dr loves 2glazi g, 2 glazing, dr IoHe 2 glazing. dr lav-e__. 13A-50cs 2 glazing, clr 10 2 glazing, clr lave 2 glazing, clr lows 2glazing,.dclavc_ 13ASacs 2 glazing, clr low-e - 18A-5ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 gluig,clrlowe_._ 13A50cs 2 plazinq, clr low-e .._.._0.408 22A-toh_--____- _._ 1.91 10.19 4.14 24.32 24.32 _20.24 1.91 10A9 10.19 10.19 . __8.81 1.91 15.05 1.91 24.14 24.54 __.24.54 1.91 19.70 _� 1.37 _ Q00 _-O 0 _._._�0 0 0 0 •_ _ _0 0 0 0 0 . _-__._0.__.-0 0 _ ___ 0 114 0 11 __-_-_20 0 _0 152:--.-_152 _,_752 0 0 0 0 0 _ ___0 0 0 0 0 0 0 ��84 0 0 1 0 _, 0 __. 8 0 0 ._.._..A_ 0 0 0 _- �0 0 0 0 0 _.,_-__ 0-- 0 0 293 0 119 _.._....224 .... 0 0 __ �241 ___3(A , O 0 0 -. 0 0 0 _ Q 0 0 0 0 __ a-,- 0 0 - 160 0 262 -_,._ 491 0 0 _ _-_.0 0 _ -_O 0 0 0 _--. 0 0- 0 0 0 _0 0 0 _.__0 0 0 .._. _.Q 0 0 '_-176 - 176 ____ O 0 ___._..-0 0 0 0 --__ _ _0 0 0 D 0 _.-_-.0 0 0 _.__-0 0 0 __0 0 0 T 176 _ 0 _-0 0 ..- -0 0 0 0 _ _ - 0 0 0 0 0 _ _._. __0 0 0 _-__0 0 0 _.__..0 0 _--_� 0 _ _ _279 --_0 .Y__ 0 0 _0 0 0 0 _ _ 0 0 0 0 0 _ _ _ __.0 0 0 .-_-_0 0 0 .___.._O 0 0 241 -, 0 - 0.125 0.400 0.400 0.400 0.400 0.400 .__,__0.400 0.125 0.400 0.400 0.400 -.__0.400 0.125 _ 0.400 -0.125 0.400 0.400 __._._0.400 0.125 _ o.400 _..._1.358 n n -_p_ a a a _ e_ S s s s _a, sw sw w w w ._w_ w _ray_ 3.50 11.20 __...1110.__.10.19.._-... 1.20 11.20 11.20 __-11.20 3.60 11.20 11.20 11.20 _ _11.20 3.50 11.20 --3.50 11.20 11.20 _._11.20 3.50 11.20 1.59 38.02 II----GG ..___ N/ �G {L-GG W. _ I--c; IW �--(s W- I--G ._ IF---tiG kJ I--_C. F_ _ _-.-_-208 _ -.-a ___ - ------------ 8 c)AED excursion 271 -99 Ermlope loss/gain 1182 1392 279 142 12 a) Infiltration b) Room ventilatim 245 0 69 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 1400 Subtotal Qin es 6 to 13) 1427 1461 279 1542 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 23% 43% 0 0 18 1446 340 0 0 15 1476. 632 23% 43% 0 01 0 279 66 0 0 0 1542 660 Total roan load Alr required (cfm) 1785 74 2108 94 345 14 2201 98 Calculations approved byACCA to meet all requirements of Manual J Sth Ed. t -rW wrlgh oT- 2020-May-1410:11:35 RighlSuile4D Unimrsal 2019 19.0.08 RSW8101 Page 4 EADocurmets\Wrightsoft WAC1WIENCKE RESIDENCE.rup Calc-MJ8 Front Door faces: W wrightsoft• Right-J® Worksheet Job: Entire House Date: May 14, 2020 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466-6796 Email: OUCKCALCS@AOL.COM 1 2 3 4 5 Room name Flposed wall Roan height Room dimensions Raxn area DINING ROOM 23.0 ft 9.3 It teat/cool 15.0 x 15.0 It 225.0 W LMNG ROOM 28.0 ft 9.3 ft heal/cool 1.0 x 211.0 ft 211.0 fN Ty Construction number U-value (BtuIvWF) Or HTM (BtuhRl� Area (ftj or peruneter (ft) load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross WP/S Heat Cod Gross WP/S Heat Cod e 11 IWIF �. ... 13A-5ocs 2 glazing, cir Irnve 2glazing,glrlWrc. _ 13A-50cs 2 glazing, cir Iowe _ 2 glazing, dr lowe 2 clazinq, cir low:ey, 13A-5ocs - 2 glazing, cir Iw 2 glazing, cir lave 2 glazing, cir lowe 2 glazng,:clr 13A-5ocs 2 glazin➢. clrlowe__ 13450cs 2 glazing, cir Iowe 2 glazing, cir Im-e 2 glazing, cir Iow:e 134-5ocs 2 glazirq, ctr loves _ _ 22P,4Dh__._ _ 0._ 125 0.400 _0.400 0.125 0.400 0.400 _ 0.400 ~0.125 0.400 0400 0.400 ---_0.4g0 0.125 _ 0.400 0 0.400 0.400 0.400 0.125 0.400 ___ _ 0.408 __1.358 _ n n .n_._._71.20 a a a -_a.- s s s s _s_ sw _sw_ w w _ w_ w3.50 _nw = _ _ ._. -_ - 3. 50 11.20 3.50 11.20 11.20 - 11.20 350 11.20 1120 11.20 .__71.20 3.50 �11.20 11.20 11.20 -__11.20 __11.20 _ 1.59 _.__38.02 ^ 1.91 10.19 10.19 1.41 24.14 24.32 __ 20.24 1.91 10.19 10.19 10.19 .___8.81 1.91 __ 15.05 24.14 24.64 24.54 1.91 19.70 _1.37 0.00 R �0 0 .. 0 140 0 36 0 _ 0 0 _ 0 -- - 164 0 2 0 50 0 0 24 _......._.. 0 0 0 0 0 _. 0 0 0 �_225 23 ._.. __..0 0 .0 362 0 403 _ 0 -176 0 0 269 -.0 0 ._ _ 0 0 0 _ 0 0 0 _�__357 -__875 _ _.__ 0 0 0____.0_ 198 0 875 0 96 0 0 245 __..-. _0._ 0 _ _._0 0 0 .._ _....._0 0 __ 0 _._ _308 0 __.... O.__..._...__0 0 121 0 0 64 ��- 140 0 0 0 __ 24 0 _ _.._.0 0 0 ; ..... _. 0 0 ___ 0 211 211 0 0. 57 0 0 3 116 0 0 0 .-_._24 0 __.._ 0 .0 0 0 .-- _0 0 _ 0 _ _211---335 r. .28 .._.___O 0 0 - 199 0 0 -___717 404 0 0 0 .-_ .. _269 0 _ ._ _ 0 0- 0 0 . ---0 0 0 _. _ 1065 ,�0 0 0 -- -109 0 0 _ _ _1295 221 0 0 0 _._....211 0 I� IIVlVVSSSN��!!!!! . -74 0 0 24 s_..,._.0 0 _0 0 0 -.. _,- o 0 0 �_ 225 _ __225 _ W I--G W .�0 0 0 0 _ __...._0 0 _ 0 _._289 _ . ____ 0 W T-G E _ _ 8 c)AED emiusion -112 -14 Envelope loss/gain 2442 1610 2988 2111 12 a) Infittmtim b) Room ventilation 459 0 129 0 559 0 157 0 13 Internal gains: Occupants @ 230 Appliances/otter 0 0 0 0 0 0 Subtotal Qines 6 to 13) 2901 1740 3547 2268 14 15 Less eMemal load Less transfer Redistribution Subtotal Duct loads 23% 43% 0 0 0 2901 681 0 0 0 1740 744 23% 43% 0 0 0 3547 833 0 0 0 2288 971 Total mom load Air required (bfm) 3582 149 2484 111 • 4380 182 3239 145 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -rid- wrl9hboft- 2020-May-1410:11:35 RightSuileO tlnlhersal 2019 19.0.08 RSW8101 Page 5 E:1Dmurmets%Wdghtsofl WAC1WIENCKERESIDENCE.mp Calc=MJB Front Doorfaces: W + wrightsoft' Right-M Worksheet Job: Entire House Date: May 14, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax772466-6796 Emil: QUICKCALCS@rAOL.COM 1 2 3 4 5 Room name Egyosed wall Room hefght Room dimensions Room arm BEDROOM 2 11.0 It 9.3 It heath000l 15.0 x 11.0 It 165.0 ft2 CLST 2 2.0 It 9.3 ft heat/cod 11.0 x 2.0 ft 220 ft' Ty construction number U-value (BtuIVWF) Or HTM (Btuwft5 Area ffl or perimeter (ft) Load (Btuh) Area (ft� a perimeter (ft) Lid (Btuh) Heat I Cord Gross WP/S Heat Cod Gross NIP/S Heat Cod 6 1 t ...._ IN 13A5ocs 2 glazing, dr low-e 2 gla_zitg, clr lowe- _"_ 13A-Socs 2 glazing, dr lave 2 glazing, dr Im-e 2 glazuq.drlawe� 13A-5bes 2 glazing, dr lowe 2 glazing; dr lowe 2 glazing, dr lave 2glazing,.c1clowe_____0.400_s_.-_11.20_- 1aA-5ocs 2 glazirp. dr lov-e�_ 13A-5ocs glazing, 2 glazing,clrjowv ._... 13A-5= 2 glazirq, drlow_e� 16X19-0Rld .. _ 22A-tgh_-._-_____ -_ 0.400 0.400 __ 13. 00 0.125 0.400 0.400 0.400 0.125 0.400 0.400 0,400 0.125 .400 0.125 ..__,,..0.400 0.125 0.400 _ _�0.40B _._1.35B _____ n n _p._ a a a e_ s s a s sw sw_ w w__.__11.20___24.Si. nw _-- ___ 3.20 11.20 ___11.20 3.50 11.20 11.20 _71.20 3.50 11.20 11.20 11.20 3.50 11.20 3.60 _ 11.20 1.9 38.02 ._..r__..__- 1.91 10.99 __. 10.19 1.91 24.14 24.32 __20.24 1.91 10.19 10.19 10.19 8.81 1.91 ___15.05 1.91 19.70 _ -J.37 _ 0.0D 0 0 __0 0 0 0 0-- 102 0 30 0 >.____0 0 ._0 0 0,.____._0 0 _..�� 165 765 0- 0 0 0 0 0 0 72 0 30 0 ______0 0 - _0 0 _ 0 __ 165 11 _-. 0 0 __ __._0 0 0 0 _ 0._.__0 253 0 336 0 __ __0 0 __0 0 _.Y-_ �0..._...._.._:0 _ 0 ___..262 ._ 418 ----o '0 0 -_...__ 0 0 0 0 138 0 306 0 -r._0. 0 0__�0 0 "0 0 0 0 0 ___.__ 0 19 0 0 0 _.-_0_ 0 0 0�__._.....,_0 ___ 0 ..__ _ 22 0 0 -0 0 0 0 ___._ 0 19 0 0 0 -0 0 ____0, 0 __ 0 V ___ 22 0 0, _. --__.0 0 0 0 .__. 0 - 65 0 0 0 --- _ .0 0 0 0 0 ,._. _ __ _ 0 0 0 0 _ 0 - -36 0 0 0 ___ ...0 0 _0 o _ 0 ,._ __ 0 ____0 _- _30 _0 L�---GG _T. I�SVV I-G ---GG ltY t_G W- 0 _ 0 .�_226 0 0 -00-_ 0 _= _ice _-__ 7.6 _ . "C ___. F-,__ -2 6 c)AED erxursion -90 -5 Envelope loss/gain 1269 580 176 61 12 a) Infiltration b) Rcom ventilation 219 0 62 0 40 0 11 0 13 Internal gains: Occupants @ 230 Appliarges/other 0 0 750 0 0 0 Subtotal pines 6 to 13) 1488 1392 216 72 14 15 Less external load Less transfer Redistribution Subtotal Dud loads 23% 43% 0 0 117 1606 377 0 0 44 1436 614 230/6 43% 0 0 -216 0 0 0 0 -72 0 0 Total room load Air required (cfm) 1983 82 2050 91 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. C -FW wrlg-htso6R- 202U-May-1410:11:35 Right -Suite® Universal 2019 19.0.08 RSUD8101 Page 6 AlErnE:LDocurmets\Wdghtsoft FB/AC%WIENCKERESIDENCE.mp Calc=MJB Front Doorfaces: W IF wrightsoft Right -A) Worksheet Job: Entire House pate: May 14, zozo By: QUICK CALCS, INC. 317 STLUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fay 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Roan name BATH 2 DEN 2 EKposed wall 6.0 ft 29.4 ft 3 Room height 9.3 ft heat/cool 9.3 It heat/cool 4 Roan dimensions 11.0 x 6.0 ft 1.0 x 120.0 ft 5 Room area 66.0 ft' 120.0 ft' Ty Construction number U-value (BtulVft'--°F) Or HTM (Btuh/ftl Arm (ft0 a perimeter (ft) Load (Btuh) Area (ftj or perimeter (ft) Lead (Btuh) HIM Cad Gross WP/S Heat Cod Gross WP/S Heat Cad 6 -15/ - -- IL---GG 2 glazing, clr low-e 2 glazing, 2_glazing, clr low_e 3.50 11.20 _ 11.20 10.19 0.19 10.19 0 0 0 0 0 0 0 0 -_- 0 0 0 . _-_ 50 0 0 56 0 _ 0 .__- 195 0 . 100 0 _-_ __.,0 -- o.125 0.400 .__ _ 0.400 n - n n _ _' 2 0.400 . a 3.20 1.14 0 A_ _0 0 _ _ 0 0 0 0 _0 0 0 11 2 glazing, dr loxe glazing, 0.400 a 11.20 24.14 0 0 0 0 0 0 0 0 2 glazing, clr lave 0.400 a 11.20 24.32 0 0 0 0 0 0 0 0 glazing, clr-love- 0.400 0 0 0--- _0 ___o �...2 1W 134-5ocs 0.126 _a_ 5 __71.20 3.60 `20.24 1.91 56 ._.�0 50 ._.,- 174 --0 95 __--.-0 56 _�.__ , 66 195 _.�_ 107 2 glazing,clr luxe 0.400 s 11.20 10.19 6. 6 67 61 0 0 0 0 2 glazing, clr lave 0.400 s 11.20 10.19 0 0 0 0 0 0 0 0 2 glazing, clr lore 0.400 s. 11.20 10.19 0 0 0 0 0 0 0 0 2glazing,.clr.lovae___ -0.400 a- ___11.20 _,8,81 -0 _ __ ._.0 __ __,..0 _ ----0 .__ -_. 0 IW �-_-G W - --- _.--_0 39 W __14 84 25 _.. 7 64 -0 89 _ _ 159 223 13475ocs 291azirq. clrbw e _ 13A-5ocs 0.125 __ _._0W .4 0.125 sw _w_ w 3.50 __ 11.20 3.50 1.91 __,_ 15.05 1.91 0 _--__0 0 0 0 0 ___0 0 0 .__0 0 48 __ __ 213 122 0 2 glazing, clr low-e 2 glazing„ clr low-e 0.400 0.400 w w 11.20 11.20 24.14 24.54 0 0 0 0 '0 0 0 0 20 0 1 0 224 0 483 0 2glazirg, cIrlow,e._.d ____0.400 --w_. .... 11.20 _24.54 .._ _.,.,0 0 0 __..__ 0._-,,. _0 _.___..._0 _ __0 --,---0 l4J 13A-5ocs 0.125 w3.50 1.91 0 0 0 0 39 25 89 48 l--G C__.__. 2 glazing, clrfowe_ '16X19flmd_.. _ 0.400 _..__. 0.408 rnv_ 11.20 __1.59 19.70 �.._ 1.37 --_ 0 ._.._66 0 .... 66 _ 0 _...�_105 _ 0_�14-_0 _._ 90 -�.,_120 120 ..__ -_159 _,_ _190 -_ 279 ..._. 164 F_._._ 22A-toh.__-_ 1.358 _ 38.02 0.0066_T62280, 120__- 2911190 6 c)AEO excursion -17 330 Envelope loss/gain 574 230 2641 1901 12 a) Infiltration 120 34 ISM 166 b) Room ventlation 0 0 0 0 13 Internal gains: Occupants ® 230 0 0 0 0 Appliances/other 0 200 Subtotal (litres 6 to 13) 694 264 3229 2267 Less eMenlal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 122 47 9 7 14 Subtotal 816 311 3238 2274 15 Dud loads 23% 430/0 192 133 23% 43% 761 973 Trial roan lead 1007 444 3999 3248 Air required (cfm) 42 20 166 145 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -rW wYrYghCso�it- 2020-May-1410:11:35 A RlghtSuiteO Universal 2019 19.0.08 RSW8101 Page 7 E:1Docu mets\WrightsoB WAGMENCKE RESIDENCE.rop Cale= MJ8 Front Door faces: W wrightsofr Right-J® Worksheet Job: Entire House Date: May 14, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466.6799 Fas 772-4666796 Error: DUICKCALCS(o]AOLCOM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area HALL 0 ft 9.3 ft heat/cool 4.0 x B.0 ft 32.0 ft' Ty Construction number U-value (BtuNft;`F) Or HTM (Btu vft� Area or perimeter (ft) (Btuh) or Load Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 11 U�V� 1345ocs -- glazing, df aw-e glazing, cl_rlay-e 1345ocs 2 glazing, dr lov-e 2 glazing, dr Iow-e 2n1azvxr, drloa_e__ 2 glazing, clr lows 2 glazing,clr Iowa 2 glazing, clr lave g rg,.clr.low-e_._ 13A6ocs 2glmh1q, or lw✓-e0.400 13A-Sots _ 2glazing, dr lowe 2 glazing, clr lave 2glazing„c1,1ow;e 13A-5ocs 2 glazirq, clr low e^ 22A-tvh __. 0.125 I 0.40g ____0.400, 0.125 0.400 0.400 __0.400 0.400 0.400 0.400' ..--0.400 0.125 _ _0.125 0.400 0.400 _,.,,..-,0.400 0.125 0.400 --1.358 n In n a a a _a_ s s s _s_ sw sw_ w w w ._w_ nvv rnv -__ _ 350 11.20 _1120__1019 3.50 11.20 11.20 __11.20 11.20 11.20 11.20 __11.20 3.50 _ 11.20 3.50 11.20 11.20 -s 11.20 3.50 11.20 .- 3B.02 1.91 10.19 1.91 24.14 24.32 _20.24 10.19 10:19 10.19 ..__..8.81 1.91 --__ 15.05 1.91 2414 24.54 __24.54 1.91 _. 19.70 _,. _0.00 0 0 ,0 0 0 0 0 --0 0 __�0 0 0 0 0 --0 0 0 0 0 _ 0 0 0 0 ___0 0 0 `__.._.O 0' 0 0___,0 '0 0 0 0 - i0--�0 0 0D 0 0 ____ 0 0 0 0 .-.._....._O 0 0 _'___0 0 0 0 0 0 0 0 0 0 _ � 0 �0 0 0 ,0 0 _- 0 , - -- ------- --� ---- - ^- -- --C"2 .2 MM11 I---G It---GG _ I�-�-i IWI � C--G WI _ IttF-��� I� _.-1�,GGGG. W L-G, C___,16)C19-0riid.__--0.408__.1.59,_,__7.37___._32_.____32!_51___44 F. -. _ 0 0 0 0 0 0 0 0 _____.0 0 _ 0 ._ __. __- 32 6 c)AED excursion -3 Envelope loss/gain 51 41 12 a) Infilbation _ b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 Subtotal (lines 6 to 13) 51 41 14 15 Less edemal load Less transfer Redistribution-51 Subtotal Duct loads 23% 430% 0 0 0 0 0 0 -11 0 0 Trial mom load Air required (cfm) 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -W wr`gf=boH- 2020-May-14 10:11:35 A&K Right -Suite® Universal 2019 19.0.08 RSU08101 Page 8 EMocurmets\Wrightsoft WAC1WIENCKE RESIDENCE.rup Calc=MJ8 Front Door faces: W wrightsoftDuct System Summary Entire House QUICK CALCS, INC. 317 STLUCIE LANE, FORT PIERCE, FL 34946 Phone: 77246&6799 Fax 772466-6796 Email: OUICKCALCS@AOL.COM Project• • For. WIENCKE RESIDENCE LOTA3 VENTURE HARBOR, JENSEN BEACH, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length [TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1000 cfm Job: Date: May 14, 2020 By: Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1000 cfm 167 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (In) H x W (In) Duct Mall Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 1007 42 20 1.000 5.0 Ox0 VIFx 27.7 115.0 st2 BEDROOM 2 c 2050 82 91 1.000 7.0 Ox0 VIFx 30.8 115.0 st2 DEN h 3999 166 145 1.000 8.0 Ox0 VIFx 32.6 115.0 st2 DINING ROOM h 3582 149 111 1.000 7.0 Ox0 VIFx 31.4 135.0 st3 FOYER c 2108 74 94 1.000 7.0 Ox0 VIFx 27.8 116.0 st2 KITCHEN c 2201 14 98 1.000 7.0 Ox0 VIFx 21.2 115.0 st1 LAUNDRY c 1046 5 47 1.000 6.0 Ox0 VIFx 3.6 95.0 LIVING ROOM h 4380 182 145 1.000 8.0 Ox0 VIFx 33.5 115.0 st2 M BATH h 1418 59 42 1.000 6.0 Ox0 VIFx 17.2 115.0 st1 M TOILET h 451 19 10 1.000 4.0 Ox 0 VIFx 19.1 115.0 st1 M wlc h 776 32 13 1.000 4.0 Ox 0 VIFx 19.3 115.0 st1 MASTER BEDROOM c 2074 89 93 1.000 7.0 Ox 0 VIFx 32.3 135.0 st3 MASTER BEDROOM -A I o 2074 1 89 93 1 1.000 1 7.0 Ox 0 I VIFx 1 32.3 135.0 st3 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (In) Material Trunk st2 Peak AVF 546 495 1.000 695 12.0 0 x 0 VInIFIx st3 Peak AVF 326 296 1.000 737 9.0 0 x 0 VinIFIX st1 st1 Peak AVF 450 459 1.000 584 12.0 0 x 0 VinIFIX Aff- wrightsoft- 2028-May-14 10:11:41 RlghtSuite® Universal 2019 19.0.08 RSU08101 Page 1 AEADwurmetslWrightsoft WAC1WIENCKE RESIDENCE.rup Calc=MJ8 Front Door faces: W Return Branch Detail Table Name Grille Size (in) Htg (cfm) clg (cfm) TEL (It) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat] Trunk rb1 0x0 1000 1000 0 0 0 0 Ox 0 VIFx wrightsoft- 2020-May-14 10:11:41 Rt. •du �.�.-na.�+ Right -Suite® Universal 201919.0.08 RV.10MI pa o 2 9 �AEADocuwets\Wrighlsofl tWACtWIENCKE RESIDENCE.rup Colo =MJ8 Front Door faces: W B�GK ;ZAFT DEBION EERVICEB, LLC DESIGN I DRAFTING 1 CONSULTING WIENCKE RESIDENCE u LOT A3 VENTURE HARBOR ST. LUCIE COUTNY, FLORIDA 2017 EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 98 The lower the Energy Performance Index, the more efficient the home. 1. New home or, addition 1. New (From Plans) 12. Ducts, location & insulation level a) Supply ducts R 6.0 2. Single-family or multiple -family 2. Single-family b) Return ducts R 6.0 c) AHU location Attic 3. No. of units (if multiple -family) 3. 1 4. Number of bedrooms 4. 2 13. Cooling system: Capacity 30.0 a) Split system SEER 16.0 5. Is this a worst case? (yes/no) 5. No b) Single package SEER c) Ground/water source SEER/COP 6. Conditioned floor area (sq. ft.) 6. 1699 d) Room unit/PTAC EER e) Other 7. Windows, type and area a) U-factor:(weighted average) 7a. 0.400 b) Solar Heat Gain Coefficient (SHGC) 7b. 0.200 14. Heating system: Capacity 27.0 c) Area 7c. 305.0 a) Split system heat pump HSPF b) Single package heat pump HSPF 8. Skylights c) Electric resistance COP 1.0 a) U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE b) Solar Heat Gain Coefficient (SHGC) 8b. NA e) Gas furnace, LPG AFUE f) Other 9. Floor type, insulation level: a) Slab -on -grade (R-value) 9a. 0.0 b) Wood, raised (R-value) 9b. 15. Water heating system c) Concrete, raised (R-value) 9c. a) Electric resistance EF 0.99 b) Gas fired, natural gas EF 10. Wall type and insulation: c) Gas fired, LPG EF A. Exterior: d) Solar system with tank EF 1. Wood frame (Insulation R-value) 10A1. e) Dedicated heat pump with tank EF_ 2. Masonry (Insulation R-value) 10A2. 5.0 f) Heat recovery unit HeatRec% B. Adjacent: g) Other 1. Wood frame (Insulation R-value) 10B1. 11.0 2. Masonry (Insulation R-value) 10132. 16. HVAC credits claimed (Performance Method) 11. Ceiling type and Insulation level a) Ceiling fans a) Under attic 11a. 0.0 b) Cross ventilation No b) Single assembly 11b. c) Whole house fan No c) Knee walls/skylight walls 11c. d) Multizone cooling credit d) Radiant barrier installed 11d. No e) Multizone heating credit f) Programmable thermostat No *Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be complet based on installed code compliant features. p Builder Signature: Date: Address of New Home: LOT A3 VENTURE HARBOR City/FL Zip: JENSEN BEACH. FL 5/14/2020 11:03:23 AM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: WIENCKE RESIDENCE Builder Name: Street: LOT A3 VENTURE HARBOR Permit Office: ST LUCIE COUNTY City, Slate, Zip: JENSEN BEACH, FL, Permit Number: Owner: Jurisdiction: ST LUCIE COUNTY 2 Design Location: FL, Fort Pierce O COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air bander shall be installed in the building envelope. Air -permeable Insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the The insulation in any dropped ceiling/soffit insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers or frame walls The junction of the top plate and the tap of exterior walls shall be sealed. shall be insulated by completely filling the cavity with a Knee walls shall be sealed. material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be Installed to (Including - maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation shall and cantilevered floors) be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the botto to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with a Where provided instead of floor insulation, Insulation Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall Recessed light fixtures installed in the building be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring a plumbing In exterior walls, or insulation that on ' installation readily conforms to available space shall extend behind piping and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to shavers and tubs shall be on exterior wall tubs shall separate them from the showers and tubs. insulated. Electricallphone box on The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sealed sprinklers in a manner that is recommended bythe manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ratings. a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. 5/1412020 11:03 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1