HomeMy WebLinkAboutPopeyes Ft Pierce Test and Balance Report For Popeyes Fort Pierce, FL PROJECT #FL20-049 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 1 Table of Contents GENERAL COMMENTS ........................................................................................................................................... 2 INSTRUMENTATION LIST .................................................................................................................................... 3 INSTRUMENTATION CALIBRATION................................................................................................................. 5 NOMENCLATURE ................................................................................................................................................. 12 FORMULAS USED ON TEST FORMS................................................................................................................ 14 STORE PRESSURIZATION ................................................................................................................................. 15 RTU #1 DATA SHEET .......................................................................................................................................... 16 RTU #1 AIR DISTRIBUTION SHEET ............................................................................................................................. 17 RTU #2 DATA SHEET .......................................................................................................................................... 18 RTU #2 AIR DISTRIBUTION SHEET ............................................................................................................................. 19 RTU #3 DATA SHEET .......................................................................................................................................... 20 RTU #3 AIR DISTRIBUTION SHEET ............................................................................................................................. 21 FAN DATA SHEET ................................................................................................................................................ 22 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 2 GENERAL COMMENTS I. CERTIFICATION STATEMENT A. All data contained in this final report has been compiled from the equipment and systems installed on the job. All values in this report are true and correct as of the date of test and are within the limits of field test error. B. All supply air diffusers, return air and exhaust air registers/grilles were measured with a calibrated flow hood reading directly in cfm. Sidewall diffusers, grilles and exhaust hoods were measured with a direct reading instrument reading in velocity and then converted to cubic feet per minute. With the above in mind, we believe that the following report should be self -explanatory; however, should any questions arise, please do not hesitate to contact us. Regards, Travis Leonard Travis Leonard Leonard’s Air and Energy Service, LLC National Balancing Council #14-137-05 CAC 1816353 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 3 INSTRUMENTATION LIST I. AIRFLOW VOLUME / VELOCITY / STATIC PRESSURE MEASURING INSTRUMENTS 1. HOOK GAUGE BY DWYER .001” – 2.0” 2. MICRO MANOMETER BY DWYER .001” – 2.0” 3. ALNOR VELOMETER 0-300 FPM, 0-1250 FPM, 0-2500 FPM 4. ALNOR MODEL 6461 BALOMETER (DIRECT CFM MEASURING FLOWHOOD) 5. SHORTRIDGE MODEL ADM 870C AIR DATA MULTIMETER 6. SHORTRIDGE FLOWHOOD MODEL 860 7. EXTECH VANE THERMO-ANEMOMETER MODEL 451104 8. ANEMOTHERM 0-8000 FPM 9. PITOT TUBE 1/8” X 12” 10. PITOT TUBE 5/16” X 12” 11. PITOT TUBE 5/16” X 18” 12. PITOT TUBE 5/16” X 24” 13. PITOT TUBE 5/16” X 36” 14. PITOT TUBE 5/16” X 48” 15. PITOT TUBE 5/16” X 60” 16. U-TUBE BY DWYER 0-16” II. WATER FLOW MEASUREMENTS 1. SHORTRIDGE MODEL (HDM-300) HYDRODATA MULTIMETER ELECTRONIC PRESSURE GAUGE 2. DWYER 0-500PSI DIGITAL METER 3. BARCO FLOW METER 0-50” 4. ELLISON FLOW METER 0-50” 5. BELL & GOSSETT FLOW METER 0-25’ 6. BELL & GOSSETT FLOW METER 0-150’ III. TEMPERATURE MEASURING INSTRUMENTS 1. EXTECH RH401 PSYCHROMETER / IR THERMOMETER 2. TAYLOR MERCURY THERMOMETERS 30-120F 1 DEGREE INCREMENTS 3. WEKSLER MERCURY THERMOMETERS 30-120F 1/10 DEGREE INCREMENTS 4. WEKSLER MERCURY THERMOMETERS 0-220F 2 DEGREE INCREMENTS 5. ALNOR PRYOMETER 8 LEADS 0-300F 6. TAYLOR SLING PSYCHROMETER 7. CONTACT PYROMETER BY AMPROBE IV. CURRENT MEASURING DEVICES Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 4 1. AMPROBE AMPS 0-6/15/40/100/300 VOLTS 0-150/300/600 AMPS 2. FIELDPIECE SC-56 3. FLUKE CLAMP METER 4. AMPROBE RECORDER AMPERAGE/VOLTAGE V. ROTATING EQUIPMENT SPEED INDICATORS 1. EXTECH MODEL 461893 NON-CONTACT PHOTO-TACHOMETER 2. JAQUET’S INDICATOR RPM-FPM 3. JOHNSON HAND-HELD STROBE LIGHT Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 5 INSTRUMENTATION CALIBRATION Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 6 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 7 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 8 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 9 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 10 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 11 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 12 NOMENCLATURE 1. AC/HR = ROOM TOTAL AIR VOLUME CHANGES PER HOUR. 2. Ak = GRILLE NET AREA CORRECTION FACTOR, SQUARE FEET. 3. AMPS = MEASURED PUMP OR FAN MOTOR OPERATING CURRENT AT TEST CONDITIONS, AMPS. 4. AMPSNP = PUMP OR FAN MOTOR NAMEPLATE FULL LOAD CURRENT RATING AMPS. 5. BHP = CALCULATED PUMP OR FAN MOTOR BRAKE HORSEPOWER . 6. BTUH = HEATING OR COOLING ENERGY CAPACITY RATE, BRITISH THERMAL UNITS PER HOUR. 7. C = CONE OR FLOWHOOD READING. 8. CFM = AIR FLOW RATE, CUBIC FEET PER MINUTE. 9. CHW = CHILLED WATER. 10. EAT = ENTERING AIR DRY BULB TEMPERATURE, F. 11. EFFm = PUMP OR FAN MOTOR OPERATING EFFICIENCY, PERCENT. 12. ESP = EXTERNAL STATIC PRESSURE, IN.WG. 13. EWB = ENTERING AIR WET BULB TEMPERATURE, F. 14. EWT = ENTERING WATER TEMPERATURE, F. 15. F = TEMPERATURE IN DEGREES FAHRENHEIT. 16. FLA = FULL LOAD AMPERAGE RATING. 17. GPM = WATER FLOW RATE, GALLONS PER MINUTE. 18. HPnp = PUMP OR FAN MOTOR NAMEPLATE HORSEPOWER RATING. 19. HW = HOT WATER. 20. kW = ELECTRICAL ENERGY CAPACITY RATE, KILOWATTS. 21. LAT = LEAVING AIR DRY BULB TEMPERATURE, F. 22. Lf = PUMP OR FAN MOTOR CURRENT LOAD FACTOR. 23. LWB = LEAVING AIR WET BULB TEMPERATURE, F. Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 13 NOMENCLATURE (CONTINUED) 24. LWT = LEAVING WATER TEMPERATURE, F. 25. % LOAD = CURRENT LOADING OF PUMP OR FAN MOTOR AT TEST CONDITIONS , PERCENT. 26. NA = NOT APPLICABLE OR NO ACCESS. 27. NG = NOT GIVEN. 28. NI = NOT INSTALLED. 29. OA = OUTSIDE AIR. 30. PF = PUMP OR FAN MOTOR CURRENT POWER FACTOR. 31. THENT = AIR ENTHALPY (OR TOTAL HEAT) AT COIL ENTERING CONDITIONS, BTU/LB. 32. TP = THERMALLY PROTECTED. 33. TSP = TOTAL STATIC PRESSURE, IN.WG. 34. THLVG = AIR ENTHALPY (OR TOTAL HEAT) AT COIL LEAVING CONDITION, BTU/LB. 35. TONS = REFRIGERATION RATE, 12,000 BTUH FOR COLLING & 15,000 BTUH FOR CONDENSING 36. VAVG = AIR VELOCITY, FEET PER MINUTE. 37. VOLTS = MEASURED PUMP OR FAN MOTOR OPERATING VOLTAGE. 38. VOL. = ROOM TOTAL AIR VOLUME, CUBIC FEET. Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 14 FORMULAS USED ON TEST FORMS A. FOR CALCULATING PUMP/FAN BRAKE HORSEPOWER (THREE PHASE ONLY) 1. BHP = (1.732 X AMPS X VOLTS X EFFM X PF X LF) / (746) NOTE: L F OBTAINED FROM KAHOE FIELD MANUAL, TABLE 6.2 2. FULL LOAD EFFM X PF = (HP X 746) / (1.732 X AMPSNP X VOLTSNP) NOTE: AT FULL LOAD, LF = 1.0. 3. % LOAD = [AMPS – (0.5 X AMPSNP)] / (0.5 X AMPSNP) X [VOLTS /VOLTSNP] B. FOR CALCULATING ELECTRIC HEATER KW (THREE PHASE ONLY). 1. KW = (1.732 X AMPS X VOLTS) / (1000) C. FOR CALCULATING HEATING COIL CAPACITY. 1. BTUH = 1.085 X CFM X (LAT-EAT). D. FOR CALCULATING COOLING COIL CAPACITY. 1. AIRSIDE A. BTUH = 4.5 X CFM X (THENT - THLVG) 2. WATERSIDE A. BTUH = 500 X GPM X (LWT – EWT). A. FOR CALCULATING CHILLER TONNAGE. 1. TONS = [500 X GPM X (LWT – EWT)] / (12,000). F. FOR CALCULATING AIR VOLUME. 1. FROM TRAVERSE. a. CFM = V AVG X ADUCT 2. SIDEWALL GRILLES / UNIT HEATERS CFM = V AVG X Ak Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 15 STORE PRESSURIZATION UNIT # DESIGN O/A (CFM) TEST (CFM) RTU #1 OUTSIDE AIR 875 922 RTU #2 OUTSIDE AIR 875 900 RTU#3 OUTSIDE AIR 875 864 TOTAL OUTSIDE AIR 2625 2686 EF-1 Hood 935 905 EF-2 Hood 935 905 EF-3 Batter 600 632 EF-4 Restroom 150 164 TOTAL EXHAUST AIR 2620 2606 STORE NET PRESSURIZATION +5 +80 Store pressurization should be slightly positive. Most local codes require this pressurization. If the pressurization is not positive as indicated on this sheet, review the data in this report for corrective solutions that will allow adjustments in the HVAC equipment to correct this problem. SUMMARY OF MEASURED SUPPLY AIR UNIT # DESIGN (CFM) TEST (CFM) RTU #1 3400 3332 RTU #2 3400 3312 RTU #3 3400 3207 TOTAL 10200 9851 Based upon 400 cfm per ton of cooling capacity, this total tested supply airflow equates to __25_ tons. Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 16 RTU #1 DATA SHEET MANUFACTURER: Carrier SERIAL: 0520P90288 MODEL: 50HCD09 DATE TESTED: 5/19/20 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 3400 3332 OA AMBIENT RETURN CFM 2525 2410 SUM. DB / WB,F 88/- OUTSIDE CFM 875 922 WINTER DB / WB,F MIXED AP SP, ”wg 0.51” FAN SUCT’N SP, ”wg 0.75” ROOM DB / WB,F 74/- FAN DISCH. SP, ”wg 0.55” ESP / TSP, ”wg 0.75” 1.06”/1.3” DUCT P SET POINT, ”wg - FAN RPM Not Given 768 MOTOR HP COOLING CFM 3332 VOLTS / PHASE EAT DB / WB,F Verified MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB / WB,F Operation ENT TH, BTU/# MOTOR MFR. Marathon LVG TH, BTU/# MOTOR HP / BHP 2.9 TH, BTU/# MOTOR RPM 1725 TOTAL BTUH VOLTAGE / PHASE 208-230/460 211 AMPERAGE 8.4/4.2 5.4 SERVICE FACTOR 1.15 MISC. DATA AHU FIELD DATA HEATER SIZE Thermally Protected HEATING AMPS Verified HEATER RATING Thermally Protected HTG VOLTS /  Operation FAN SHEAVE AFD74x1 # OF STAGES MOTOR SHEAVE VM50x7/8 HEATING kW 12.0/16.0 OT / C to C 4/14 ½ TOTAL BTUH BELTS AX48 NOTES: O/A=5ft2 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 17 RTU #1 AIR DISTRIBUTION SHEET DATE TESTED: 5/19/20 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST # SIZE Ak TYPE/ SIZE NECK RUN- OUT VEL CFM VEL CFM VEL CFM VEL CFM % OF DESIGN Kitchen 1 24x24 12” C 600 680 615 615 Kitchen 2 24x24 12” C 600 640 563 563 Kitchen 3 24x24 12” C 600 635 588 588 Kitchen 4 24x24 12” C 600 650 572 572 Kitchen 5 24x24 12” C 600 720 617 617 Kitchen 6 24x24 12” C 400 123 377 377 Total 3400 3332 NOTES: Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 18 RTU #2 DATA SHEET MANUFACTURER: Carrier SERIAL: 0520P90289 MODEL:50HC-D09E DATE TESTED: 5/19/20 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 3400 3312 OA AMBIENT RETURN CFM 2525 2412 SUM. DB / WB,F 84- OUTSIDE CFM 875 900 WINTER DB / WB,F MIXED AP SP, ”wg 0.52” FAN SUCT’N SP, ”wg 0.65” ROOM DB / WB,F 74/- FAN DISCH. SP, ”wg 0.55” ESP / TSP, ”wg 0.75” 1.07”/1.2” DUCT P SET POINT, ”wg - FAN RPM Not Given 755 MOTOR HP COOLING CFM VOLTS / PHASE EAT DB / WB,F Verified MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB / WB,F Operation ENT TH, BTU/# MOTOR MFR. Marathon LVG TH, BTU/# MOTOR HP / BHP 2.9 TH, BTU/# MOTOR RPM 1725 TOTAL BTUH VOLTAGE / PHASE 208-230/460 208 AMPERAGE 8.4/4.2 5.3 SERVICE FACTOR 1.15 MISC. DATA AHU FIELD DATA HEATER SIZE Thermally Protected HEATING AMPS V/O HEATER RATING Thermally Protected HTG VOLTS /  FAN SHEAVE AFD74x1 # OF STAGES MOTOR SHEAVE VM44x7/8 HEATING kW 12.0/16.0 OT / C to C 4/14 ¼ TOTAL BTUH BELTS AX48 NOTES: O/A=5ft2 Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 19 RTU #2 AIR DISTRIBUTION SHEET DATE TESTED: 5/19/20 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST # SIZE Ak TYPE/ SIZE NECK RUN- OUT VEL CFM VEL CFM VEL CFM VEL CFM % OF DESIGN Kitchen 1 24x24 12” C 600 700 563 563 Kitchen 2 24x24 12” C 600 745 580 580 Kitchen 3 24x24 12” C 600 730 565 565 Kitchen 4 24x24 12” C 600 710 557 557 Kitchen 5 24x24 12” C 500 545 513 513 Kitchen 6 24x24 12” C 500 580 534 534 Total 3400 3312 NOTES: Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 20 RTU #3 DATA SHEET MANUFACTURER: Carrier SERIAL: MODEL:50HC-D09 DATE TESTED: 5/19/19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 3400 3270 OA AMBIENT RETURN CFM 2510 2406 SUM. DB / WB,F 84/- OUTSIDE CFM 875 864 WINTER DB / WB,F MIXED AP SP, ”wg 0.54” FAN SUCT’N SP, ”wg 0.71” ROOM DB / WB,F 75/- FAN DISCH. SP, ”wg 0.57” ESP / TSP, ”wg 0.75” 1.11”/1.28 DUCT P SET POINT, ”wg FAN RPM 769 MOTOR HP COOLING CFM 3270 VOLTS / PHASE EAT DB / WB,F Verified MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB / WB,F Operation ENT TH, BTU/# MOTOR MFR. Marathon LVG TH, BTU/# MOTOR HP / BHP 2.9 TH, BTU/# MOTOR RPM 1725 TOTAL BTUH VOLTAGE / PHASE 208-230/460 AMPERAGE 8.4/4.2 6.2 SERVICE FACTOR 1.15 MISC. DATA AHU FIELD DATA HEATER SIZE Thermally Protected HEATING AMPS V/O HEATER RATING Thermally Protected HTG VOLTS /  FAN SHEAVE AFD74x1 # OF STAGES MOTOR SHEAVE VM44x7/8 HEATING kW 12.0/16.0 OT / C to C 4/14 ¼ TOTAL BTUH BELTS AX48 NOTES: O/A=5ft2. Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 21 RTU #3 AIR DISTRIBUTION SHEET DATE TESTED: 5/19/20 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST # SIZE Ak TYPE/ SIZE NECK RUN- OUT VEL CFM VEL CFM VEL CFM VEL CFM % OF DESIGN Seating 1 24x24 12” C 550 730 587 567 Seating 2 24x24 12” C 550 710 590 540 Seating 3 24x24 12” C 550 320 532 532 Seating 4 24x24 12” C 550 650 540 510 Seating 5 24x24 12” C 400 515 388 368 Seating 6 24x24 12” C 400 380 367 367 Entry 7 24x24 8“ C 150 200 139 139 Entry 8 24x24 8” C 150 235 142 142 RR 9 12x12 C 50 210 55 50 RR 10 12x12 C 50 190 55 55 Total 3400 3270 NOTES: Leonard’s Air and Energy Service Independent Test & Balance Project: Popeyes Date: 5/19/20 Location: Fort Pierce, FL Project #: FL20-049 22 FAN DATA SHEET FAN DATA SPECIFIED DESIGN DATA FAN # EF-1 EF-2 EF-3 EF-4 LOCATION/SERVES Grease Hood Grease Hood Batter Station Restroom CFM 935 935 600 150 STATIC PRESSURE, ”wg 1.25” 1.25” 0.5” 0.375” HP / BHP ¾ ¾ .18 0.08 VOLT / PHASE 115/1 115/1 115/1 115/1 FAN RPM 1276 1276 1688 1395 FIELD TEST DATA DATE TESTED MANUFACTURER Captive Aire Captive Aire Captive Aire Captive Aire MODEL # DU85HFA DU85HFA DU12HFA DR10HFA SERIAL # 4123809 4123809 4123809 4263640 MOTOR MFR HSSA HSSA VERISPEED HSSA MOTOR HP / BHP ¾ ¾ DD N.G. MOTOR RPM 1350 1350 DD 1550 NP AMPERAGE 8.7/4.4 8.7/4.4 DD 1.0 NP VOLTAGE 115/230 115/230 DD 115 SERVICE FACTOR 1.0 1.0 DD Not Given TEST AMPERAGE 3.4 3.3 0.8 0.8 TEST VOLTAGE / PHASE 119 119 119 119 HEATER SIZE Thermally Protected Thermally Protected Thermally Protected Thermally Protected HEATER RATING Thermally Protected Thermally Protected Thermally Protected Thermally Protected FAN SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive MOTOR SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive OT / C to C Direct Drive Direct Drive Direct Drive Direct Drive BELTS Direct Drive Direct Drive Direct Drive Direct Drive FAN RPM Direct Drive Direct Drive Direct Drive Direct Drive FAN CFM 909 905 632 164 NOTES: