HomeMy WebLinkAboutPopeyes Ft Pierce
Test and Balance Report
For
Popeyes
Fort Pierce, FL
PROJECT #FL20-049
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
1
Table of Contents
GENERAL COMMENTS ........................................................................................................................................... 2
INSTRUMENTATION LIST .................................................................................................................................... 3
INSTRUMENTATION CALIBRATION................................................................................................................. 5
NOMENCLATURE ................................................................................................................................................. 12
FORMULAS USED ON TEST FORMS................................................................................................................ 14
STORE PRESSURIZATION ................................................................................................................................. 15
RTU #1 DATA SHEET .......................................................................................................................................... 16
RTU #1 AIR DISTRIBUTION SHEET ............................................................................................................................. 17
RTU #2 DATA SHEET .......................................................................................................................................... 18
RTU #2 AIR DISTRIBUTION SHEET ............................................................................................................................. 19
RTU #3 DATA SHEET .......................................................................................................................................... 20
RTU #3 AIR DISTRIBUTION SHEET ............................................................................................................................. 21
FAN DATA SHEET ................................................................................................................................................ 22
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
2
GENERAL COMMENTS
I. CERTIFICATION STATEMENT
A. All data contained in this final report has been compiled from the equipment and systems
installed on the job. All values in this report are true and correct as of the date of test and
are within the limits of field test error.
B. All supply air diffusers, return air and exhaust air registers/grilles were measured with a
calibrated flow hood reading directly in cfm. Sidewall diffusers, grilles and exhaust hoods
were measured with a direct reading instrument reading in velocity and then converted to
cubic feet per minute.
With the above in mind, we believe that the following report should be self -explanatory; however, should
any questions arise, please do not hesitate to contact us.
Regards,
Travis Leonard
Travis Leonard
Leonard’s Air and Energy Service, LLC
National Balancing Council #14-137-05
CAC 1816353
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
3
INSTRUMENTATION LIST
I. AIRFLOW VOLUME / VELOCITY / STATIC PRESSURE MEASURING INSTRUMENTS
1. HOOK GAUGE BY DWYER .001” – 2.0”
2. MICRO MANOMETER BY DWYER .001” – 2.0”
3. ALNOR VELOMETER 0-300 FPM, 0-1250 FPM, 0-2500 FPM
4. ALNOR MODEL 6461 BALOMETER (DIRECT CFM MEASURING FLOWHOOD)
5. SHORTRIDGE MODEL ADM 870C AIR DATA MULTIMETER
6. SHORTRIDGE FLOWHOOD MODEL 860
7. EXTECH VANE THERMO-ANEMOMETER MODEL 451104
8. ANEMOTHERM 0-8000 FPM
9. PITOT TUBE 1/8” X 12”
10. PITOT TUBE 5/16” X 12”
11. PITOT TUBE 5/16” X 18”
12. PITOT TUBE 5/16” X 24”
13. PITOT TUBE 5/16” X 36”
14. PITOT TUBE 5/16” X 48”
15. PITOT TUBE 5/16” X 60”
16. U-TUBE BY DWYER 0-16”
II. WATER FLOW MEASUREMENTS
1. SHORTRIDGE MODEL (HDM-300) HYDRODATA MULTIMETER ELECTRONIC PRESSURE GAUGE
2. DWYER 0-500PSI DIGITAL METER
3. BARCO FLOW METER 0-50”
4. ELLISON FLOW METER 0-50”
5. BELL & GOSSETT FLOW METER 0-25’
6. BELL & GOSSETT FLOW METER 0-150’
III. TEMPERATURE MEASURING INSTRUMENTS
1. EXTECH RH401 PSYCHROMETER / IR THERMOMETER
2. TAYLOR MERCURY THERMOMETERS 30-120F 1 DEGREE INCREMENTS
3. WEKSLER MERCURY THERMOMETERS 30-120F 1/10 DEGREE INCREMENTS
4. WEKSLER MERCURY THERMOMETERS 0-220F 2 DEGREE INCREMENTS
5. ALNOR PRYOMETER 8 LEADS 0-300F
6. TAYLOR SLING PSYCHROMETER
7. CONTACT PYROMETER BY AMPROBE
IV. CURRENT MEASURING DEVICES
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
4
1. AMPROBE AMPS 0-6/15/40/100/300 VOLTS 0-150/300/600 AMPS
2. FIELDPIECE SC-56
3. FLUKE CLAMP METER
4. AMPROBE RECORDER AMPERAGE/VOLTAGE
V. ROTATING EQUIPMENT SPEED INDICATORS
1. EXTECH MODEL 461893 NON-CONTACT PHOTO-TACHOMETER
2. JAQUET’S INDICATOR RPM-FPM
3. JOHNSON HAND-HELD STROBE LIGHT
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
5
INSTRUMENTATION CALIBRATION
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
6
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
7
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
8
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
9
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
10
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
11
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
12
NOMENCLATURE
1. AC/HR = ROOM TOTAL AIR VOLUME CHANGES PER HOUR.
2. Ak = GRILLE NET AREA CORRECTION FACTOR, SQUARE FEET.
3. AMPS = MEASURED PUMP OR FAN MOTOR OPERATING CURRENT AT TEST
CONDITIONS, AMPS.
4. AMPSNP = PUMP OR FAN MOTOR NAMEPLATE FULL LOAD CURRENT RATING AMPS.
5. BHP = CALCULATED PUMP OR FAN MOTOR BRAKE HORSEPOWER .
6. BTUH = HEATING OR COOLING ENERGY CAPACITY RATE, BRITISH THERMAL
UNITS PER HOUR.
7. C = CONE OR FLOWHOOD READING.
8. CFM = AIR FLOW RATE, CUBIC FEET PER MINUTE.
9. CHW = CHILLED WATER.
10. EAT = ENTERING AIR DRY BULB TEMPERATURE, F.
11. EFFm = PUMP OR FAN MOTOR OPERATING EFFICIENCY, PERCENT.
12. ESP = EXTERNAL STATIC PRESSURE, IN.WG.
13. EWB = ENTERING AIR WET BULB TEMPERATURE, F.
14. EWT = ENTERING WATER TEMPERATURE, F.
15. F = TEMPERATURE IN DEGREES FAHRENHEIT.
16. FLA = FULL LOAD AMPERAGE RATING.
17. GPM = WATER FLOW RATE, GALLONS PER MINUTE.
18. HPnp = PUMP OR FAN MOTOR NAMEPLATE HORSEPOWER RATING.
19. HW = HOT WATER.
20. kW = ELECTRICAL ENERGY CAPACITY RATE, KILOWATTS.
21. LAT = LEAVING AIR DRY BULB TEMPERATURE, F.
22. Lf = PUMP OR FAN MOTOR CURRENT LOAD FACTOR.
23. LWB = LEAVING AIR WET BULB TEMPERATURE, F.
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
13
NOMENCLATURE (CONTINUED)
24. LWT = LEAVING WATER TEMPERATURE, F.
25. % LOAD = CURRENT LOADING OF PUMP OR FAN MOTOR AT TEST CONDITIONS ,
PERCENT.
26. NA = NOT APPLICABLE OR NO ACCESS.
27. NG = NOT GIVEN.
28. NI = NOT INSTALLED.
29. OA = OUTSIDE AIR.
30. PF = PUMP OR FAN MOTOR CURRENT POWER FACTOR.
31. THENT = AIR ENTHALPY (OR TOTAL HEAT) AT COIL ENTERING CONDITIONS,
BTU/LB.
32. TP = THERMALLY PROTECTED.
33. TSP = TOTAL STATIC PRESSURE, IN.WG.
34. THLVG = AIR ENTHALPY (OR TOTAL HEAT) AT COIL LEAVING CONDITION, BTU/LB.
35. TONS = REFRIGERATION RATE, 12,000 BTUH FOR COLLING & 15,000 BTUH FOR CONDENSING
36. VAVG = AIR VELOCITY, FEET PER MINUTE.
37. VOLTS = MEASURED PUMP OR FAN MOTOR OPERATING VOLTAGE.
38. VOL. = ROOM TOTAL AIR VOLUME, CUBIC FEET.
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
14
FORMULAS USED ON TEST FORMS
A. FOR CALCULATING PUMP/FAN BRAKE HORSEPOWER (THREE PHASE ONLY)
1. BHP = (1.732 X AMPS X VOLTS X EFFM X PF X LF) / (746)
NOTE: L F OBTAINED FROM KAHOE FIELD MANUAL, TABLE 6.2
2. FULL LOAD EFFM X PF = (HP X 746) / (1.732 X AMPSNP X VOLTSNP)
NOTE: AT FULL LOAD, LF = 1.0.
3. % LOAD = [AMPS – (0.5 X AMPSNP)] / (0.5 X AMPSNP) X [VOLTS /VOLTSNP]
B. FOR CALCULATING ELECTRIC HEATER KW (THREE PHASE ONLY).
1. KW = (1.732 X AMPS X VOLTS) / (1000)
C. FOR CALCULATING HEATING COIL CAPACITY.
1. BTUH = 1.085 X CFM X (LAT-EAT).
D. FOR CALCULATING COOLING COIL CAPACITY.
1. AIRSIDE
A. BTUH = 4.5 X CFM X (THENT - THLVG)
2. WATERSIDE
A. BTUH = 500 X GPM X (LWT – EWT).
A. FOR CALCULATING CHILLER TONNAGE.
1. TONS = [500 X GPM X (LWT – EWT)] / (12,000).
F. FOR CALCULATING AIR VOLUME.
1. FROM TRAVERSE.
a. CFM = V AVG X ADUCT
2. SIDEWALL GRILLES / UNIT HEATERS
CFM = V AVG X Ak
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
15
STORE PRESSURIZATION
UNIT # DESIGN O/A (CFM) TEST (CFM)
RTU #1 OUTSIDE AIR 875 922
RTU #2 OUTSIDE AIR 875 900
RTU#3 OUTSIDE AIR 875 864
TOTAL OUTSIDE AIR 2625 2686
EF-1 Hood 935 905
EF-2 Hood 935 905
EF-3 Batter 600 632
EF-4 Restroom 150 164
TOTAL EXHAUST AIR 2620 2606
STORE NET PRESSURIZATION +5 +80
Store pressurization should be slightly positive. Most local codes require this pressurization. If the pressurization is
not positive as indicated on this sheet, review the data in this report for corrective solutions that will allow
adjustments in the HVAC equipment to correct this problem.
SUMMARY OF MEASURED SUPPLY AIR
UNIT # DESIGN (CFM) TEST (CFM)
RTU #1 3400 3332
RTU #2 3400 3312
RTU #3 3400 3207
TOTAL 10200 9851
Based upon 400 cfm per ton of cooling capacity, this total tested supply airflow equates to __25_ tons.
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
16
RTU #1 DATA SHEET
MANUFACTURER: Carrier SERIAL: 0520P90288
MODEL: 50HCD09 DATE TESTED: 5/19/20
FAN SECTION COIL SECTION
AHU DATA SPECIFIED
DSN DATA
FIELD TEST
DATA AHU DATA SPECIFIED
DSN DATA
FIELD TEST
DATA
SUPPLY CFM 3400 3332 OA AMBIENT
RETURN CFM 2525 2410 SUM. DB / WB,F 88/-
OUTSIDE CFM 875 922 WINTER DB / WB,F
MIXED AP SP, ”wg 0.51”
FAN SUCT’N SP, ”wg 0.75” ROOM DB / WB,F 74/-
FAN DISCH. SP, ”wg 0.55”
ESP / TSP, ”wg 0.75” 1.06”/1.3”
DUCT P SET POINT, ”wg -
FAN RPM Not Given 768
MOTOR HP COOLING CFM 3332
VOLTS / PHASE EAT DB / WB,F Verified
MOTOR DATA NAMEPLATE
DATA
FIELD TEST
DATA
LAT DB / WB,F Operation
ENT TH, BTU/#
MOTOR MFR. Marathon LVG TH, BTU/#
MOTOR HP / BHP 2.9 TH, BTU/#
MOTOR RPM 1725 TOTAL BTUH
VOLTAGE / PHASE 208-230/460 211
AMPERAGE 8.4/4.2 5.4
SERVICE FACTOR 1.15
MISC. DATA AHU FIELD DATA
HEATER SIZE Thermally Protected HEATING AMPS Verified
HEATER RATING Thermally Protected HTG VOLTS / Operation
FAN SHEAVE AFD74x1 # OF STAGES
MOTOR SHEAVE VM50x7/8 HEATING kW 12.0/16.0
OT / C to C 4/14 ½ TOTAL BTUH
BELTS AX48
NOTES: O/A=5ft2
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
17
RTU #1 AIR DISTRIBUTION SHEET
DATE TESTED: 5/19/20
AREA SERVED
SPECIFIED GRILLE SPECIFIED
DESIGN
PRELIM
FIELD TEST
PRELIM
FIELD TEST FINAL FIELD TEST
#
SIZE
Ak TYPE/
SIZE NECK
RUN-
OUT VEL CFM VEL CFM VEL CFM VEL CFM
% OF
DESIGN
Kitchen 1 24x24 12” C 600 680 615 615
Kitchen 2 24x24 12” C 600 640 563 563
Kitchen 3 24x24 12” C 600 635 588 588
Kitchen 4 24x24 12” C 600 650 572 572
Kitchen 5 24x24 12” C 600 720 617 617
Kitchen 6 24x24 12” C 400 123 377 377
Total 3400 3332
NOTES:
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
18
RTU #2 DATA SHEET
MANUFACTURER: Carrier SERIAL: 0520P90289
MODEL:50HC-D09E DATE TESTED: 5/19/20
FAN SECTION COIL SECTION
AHU DATA SPECIFIED
DSN DATA
FIELD TEST
DATA AHU DATA SPECIFIED
DSN DATA
FIELD TEST
DATA
SUPPLY CFM 3400 3312 OA AMBIENT
RETURN CFM 2525 2412 SUM. DB / WB,F 84-
OUTSIDE CFM 875 900 WINTER DB / WB,F
MIXED AP SP, ”wg 0.52”
FAN SUCT’N SP, ”wg 0.65” ROOM DB / WB,F 74/-
FAN DISCH. SP, ”wg 0.55”
ESP / TSP, ”wg 0.75” 1.07”/1.2”
DUCT P SET POINT, ”wg -
FAN RPM Not Given 755
MOTOR HP COOLING CFM
VOLTS / PHASE EAT DB / WB,F Verified
MOTOR DATA NAMEPLATE
DATA
FIELD TEST
DATA
LAT DB / WB,F Operation
ENT TH, BTU/#
MOTOR MFR. Marathon LVG TH, BTU/#
MOTOR HP / BHP 2.9 TH, BTU/#
MOTOR RPM 1725 TOTAL BTUH
VOLTAGE / PHASE 208-230/460 208
AMPERAGE 8.4/4.2 5.3
SERVICE FACTOR 1.15
MISC. DATA AHU FIELD DATA
HEATER SIZE Thermally Protected HEATING AMPS V/O
HEATER RATING Thermally Protected HTG VOLTS /
FAN SHEAVE AFD74x1 # OF STAGES
MOTOR SHEAVE VM44x7/8 HEATING kW 12.0/16.0
OT / C to C 4/14 ¼ TOTAL BTUH
BELTS AX48
NOTES: O/A=5ft2
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
19
RTU #2 AIR DISTRIBUTION SHEET
DATE TESTED: 5/19/20
AREA SERVED
SPECIFIED GRILLE SPECIFIED
DESIGN
PRELIM
FIELD TEST
PRELIM
FIELD TEST FINAL FIELD TEST
#
SIZE
Ak TYPE/
SIZE NECK
RUN-
OUT VEL CFM VEL CFM VEL CFM VEL CFM
% OF
DESIGN
Kitchen 1 24x24 12” C 600 700 563 563
Kitchen 2 24x24 12” C 600 745 580 580
Kitchen 3 24x24 12” C 600 730 565 565
Kitchen 4 24x24 12” C 600 710 557 557
Kitchen 5 24x24 12” C 500 545 513 513
Kitchen 6 24x24 12” C 500 580 534 534
Total 3400 3312
NOTES:
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
20
RTU #3 DATA SHEET
MANUFACTURER: Carrier SERIAL:
MODEL:50HC-D09 DATE TESTED: 5/19/19
FAN SECTION COIL SECTION
AHU DATA SPECIFIED
DSN DATA
FIELD TEST
DATA AHU DATA SPECIFIED
DSN DATA
FIELD TEST
DATA
SUPPLY CFM 3400 3270 OA AMBIENT
RETURN CFM 2510 2406 SUM. DB / WB,F 84/-
OUTSIDE CFM 875 864 WINTER DB / WB,F
MIXED AP SP, ”wg 0.54”
FAN SUCT’N SP, ”wg 0.71” ROOM DB / WB,F 75/-
FAN DISCH. SP, ”wg 0.57”
ESP / TSP, ”wg 0.75” 1.11”/1.28
DUCT P SET POINT, ”wg
FAN RPM 769
MOTOR HP COOLING CFM 3270
VOLTS / PHASE EAT DB / WB,F Verified
MOTOR DATA NAMEPLATE
DATA
FIELD TEST
DATA
LAT DB / WB,F Operation
ENT TH, BTU/#
MOTOR MFR. Marathon LVG TH, BTU/#
MOTOR HP / BHP 2.9 TH, BTU/#
MOTOR RPM 1725 TOTAL BTUH
VOLTAGE / PHASE 208-230/460
AMPERAGE 8.4/4.2 6.2
SERVICE FACTOR 1.15
MISC. DATA AHU FIELD DATA
HEATER SIZE Thermally Protected HEATING AMPS V/O
HEATER RATING Thermally Protected HTG VOLTS /
FAN SHEAVE AFD74x1 # OF STAGES
MOTOR SHEAVE VM44x7/8 HEATING kW 12.0/16.0
OT / C to C 4/14 ¼ TOTAL BTUH
BELTS AX48
NOTES: O/A=5ft2.
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
21
RTU #3 AIR DISTRIBUTION SHEET
DATE TESTED: 5/19/20
AREA SERVED
SPECIFIED GRILLE SPECIFIED
DESIGN
PRELIM
FIELD TEST
PRELIM
FIELD TEST FINAL FIELD TEST
#
SIZE
Ak TYPE/
SIZE NECK
RUN-
OUT VEL CFM VEL CFM VEL CFM VEL CFM
% OF
DESIGN
Seating 1 24x24 12” C 550 730 587 567
Seating 2 24x24 12” C 550 710 590 540
Seating 3 24x24 12” C 550 320 532 532
Seating 4 24x24 12” C 550 650 540 510
Seating 5 24x24 12” C 400 515 388 368
Seating 6 24x24 12” C 400 380 367 367
Entry 7 24x24 8“ C 150 200 139 139
Entry 8 24x24 8” C 150 235 142 142
RR 9 12x12 C 50 210 55 50
RR 10 12x12 C 50 190 55 55
Total 3400 3270
NOTES:
Leonard’s Air and Energy Service
Independent Test & Balance
Project: Popeyes Date: 5/19/20
Location: Fort Pierce, FL Project #: FL20-049
22
FAN DATA SHEET
FAN DATA SPECIFIED DESIGN DATA
FAN # EF-1 EF-2 EF-3 EF-4
LOCATION/SERVES Grease Hood Grease Hood Batter Station Restroom
CFM 935 935 600 150
STATIC PRESSURE, ”wg 1.25” 1.25” 0.5” 0.375”
HP / BHP ¾ ¾ .18 0.08
VOLT / PHASE 115/1 115/1 115/1 115/1
FAN RPM 1276 1276 1688 1395
FIELD TEST DATA
DATE TESTED
MANUFACTURER Captive Aire Captive Aire Captive Aire Captive Aire
MODEL # DU85HFA DU85HFA DU12HFA DR10HFA
SERIAL # 4123809 4123809 4123809 4263640
MOTOR MFR HSSA HSSA VERISPEED HSSA
MOTOR HP / BHP ¾ ¾ DD N.G.
MOTOR RPM 1350 1350 DD 1550
NP AMPERAGE 8.7/4.4 8.7/4.4 DD 1.0
NP VOLTAGE 115/230 115/230 DD 115
SERVICE FACTOR 1.0 1.0 DD Not Given
TEST AMPERAGE 3.4 3.3 0.8 0.8
TEST VOLTAGE / PHASE 119 119 119 119
HEATER SIZE Thermally Protected Thermally Protected Thermally Protected Thermally Protected
HEATER RATING Thermally Protected Thermally Protected Thermally Protected Thermally Protected
FAN SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive
MOTOR SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive
OT / C to C Direct Drive Direct Drive Direct Drive Direct Drive
BELTS Direct Drive Direct Drive Direct Drive Direct Drive
FAN RPM Direct Drive Direct Drive Direct Drive Direct Drive
FAN CFM 909 905 632 164
NOTES: