ENCODEManual S REV Load Calcs
2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Manual S Compliance Report Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor: 20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 Cooling Equipment Design Conditions °F75.5Entering coil DB:Btuh30707Sensible gain:°F91.2Outdoor design DB: °F63.3Entering coil WB:Btuh7048Latent gain:°F77.1Outdoor design WB: Btuh37754Total gain:°F75.0Indoor design DB: cfm1200Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 4TTR6042J1+TEM6A0C42H41++TDRModel:TraneManufacturer: cfm1200Actual airflow: % of load101Btuh30946Sensible capacity: % of load108Btuh7605Latent capacity: %80SHR:% of load102Btuh38552Total capacity: Heating Equipment Design Conditions °F69.3Entering coil DB:Btuh39065Heat loss:°F36.6Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: BAYHTR1510BRKCModel:TraneManufacturer: cfm497Actual airflow: °F62Temp. rise:% of load87kW10.0Output capacity: Meets all requirements of ACCA Manual S. 2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Building Analysis Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor: 20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1633Design TD (°F)ft26Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:53.629.3Moisture difference (gr/lb)CoolingHeating Infiltration:9137Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 2323 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 36.1141006.0Walls 4.919107.0Glazing 2.183020.0Doors 8.733891.2Ceilings 21.885133.13.1Floors 16.865712.5Infiltration 9.63752Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.039065Total Cooling Walls Glazing Doors Ceilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 28.687823.7Walls 28.5875532.1Glazing 2.474818.1Doors 7.322480.8Ceilings 000Floors 5.817740.7Infiltration 10.63250Ducts 00Ventilation 16.85150Internal gains 00Blower 0Adjustments 100.030707Total Latent Cooling Load = 7048 Btuh Overall U-value = 0.228 Btuh/ft²-°F Data entries checked. Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Load Short Form Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor: 20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 Design Information InfiltrationClgHtg Blower doorMethod9137Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 2323 cfmPressure / AVF1633Design TD (°F) L-Daily range 5050Inside humidity (%) 5429Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade Trane Trade TRANE Model BAYHTR1510BRKC Cond 4TTR6042J1 AHRI ref Coil TEM6A0C42H41++TDR AHRI ref 8628154 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW10.0 Sensible cooling Btuh32400 Heating output Btuh34121 Latent cooling Btuh7600 Temperature rise °F62 Total cooling Btuh40000 Actual air flow cfm497 Actual air flow cfm1200 Air flow factor cfm/Btuh0.013 Air flow factor cfm/Btuh0.039 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.81 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Sitting Room 176 3822 3086 49 121 Master Bedroom 269 2427 1962 31 77 WC 28 759 268 10 10 Master Bath 141 2898 1278 37 50 Master Closet 125 1825 908 23 35 Office 117 156 309 2 12 Entry 72 1149 735 15 29 Playroom 162 1812 918 23 36 Bedroom 3 181 3870 1623 49 63 Pantry 18 0 0 0 0 Bath 3 65 87 266 1 10 Laundry 129 2071 1490 26 58 Hall 57 76 260 1 10 Bedroom 2 172 3792 2046 48 80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 2 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Bath 2 55 796 291 10 11 Great Room 455 8831 9738 112 381 Bedroom 4 159 1879 941 24 37 Kitchen 340 2815 4588 36 179 Entire House 2720 39065 30707 497 1200 Other equip loads 0 0 Equip. @ 1.00 RSM 30707 Latent cooling 7048 TOTALS 2720 39065 37754 497 1200 2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Component Constructions Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor: 20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1633Design TD (°F)ft26Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:53.629.3Moisture difference (gr/lb)CoolingHeating Infiltration:9137Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 2323 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block Foam Fill R-9 15253.8424256.119.00.183397ne 28493.8445316.119.00.183741se 15293.8424326.119.00.183398sw 20963.8433336.119.00.183545nw 79983.84127216.119.00.1832081all Block Wall 4-1 1622.932875.184.10.15555ne 122.93215.184.10.1554se 1262.932225.184.10.15543sw 4432.937835.184.10.155151nw 7432.9313125.184.10.155254all 2 x 6 R-19 411.43662.2719.00.06829se Partitions (none) Windows Double Pane, Low-E, Vinyl: Double Pane, Low-E, Vinyl; NFRC rated (SHGC=0.30); 50% blinds 45°, medium; foreground = new concrete (0.32); 10 ft overhang (4 ft window ht, 2.5 ft sep.); 25.3 ft head ht 18218.2707.0100.21010se Double Pane, Low-E, Vinyl: Double Pane, Low-E, Vinyl; NFRC rated (SHGC=0.30); 50% blinds 45°, medium; foreground = new concrete (0.32); 12 ft overhang (5.25 ft window ht, 2.5 ft sep.); 6.8 ft head ht 147118.25687.0100.21081se 150130.93417.0100.21049nw 297223.09087.0100.210130all Double Pane, Low-E, Vinyl: Double Pane, Low-E, Vinyl; NFRC rated (SHGC=0.30); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (5.25 ft window ht, 2.5 ft sep.); 6.8 ft head ht 69521.52277.0100.21032sw Double Pane, Low-E, Vinyl: Double Pane, Low-E, Vinyl; NFRC rated (SHGC=0.30); 50% blinds 45°, medium; foreground = new concrete (0.32); 12 ft overhang (6.7 ft window ht, 2.5 ft sep.); 6.8 ft head ht 124330.92827.0100.21040nw 186430.94237.0100.21060nw 310630.97057.0100.210101all Doors 2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 2 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Door, mtl fbrgl type 37918.142120.06.30.60021ne 36818.140920.06.30.60020se 74818.183020.06.30.60041all Ceilings Attic, asphalt, r-30, 1/2" gyp 1021.72631.0730.00.03259 Attic, mtl, r-38, 1/2" gyp 910.781411.218.00.405117 20550.7831841.2138.00.4052634 21460.7833261.218.00.4052751all Floors Slab on grade 00851339.401.180216 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Project Summary Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor:20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 Westerberg Architecture 8196 25th St Vero Beach, FL 32866 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F37 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F33 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb54 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh35313 Structure Btuh27457 Ducts Btuh3752 Ducts Btuh3250Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh39065 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh30707 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 2323 cfmPressure / AVF Structure Btuh4629 Ducts Btuh2418Central vent (0 cfm) Btuh0 CoolingHeating (none)27202720Area (ft²) Equipment latent load Btuh7048 2787227872Volume (ft³)Air changes/hour 0.210.39 Equipment Total Load (Sen+Lat)Btuh37754 Equiv. AVF (cfm) 100179 Req. total capacity at 0.81 SHR ton3.2 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTrade Trane Trade TRANE Model BAYHTR1510BRKC Cond 4TTR6042J1AHRI ref Coil TEM6A0C42H41++TDR AHRI ref 8628154Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW10.0 Sensible cooling Btuh32400Heating output Btuh34121 Latent cooling Btuh7600 Temperature rise °F62 Total cooling Btuh40000Actual air flow cfm497 Actual air flow cfm1200 Air flow factor cfm/Btuh0.013 Air flow factor cfm/Btuh0.039Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.81 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Entire House Sitting Room 2 Exposed wall 216.0 ft 27.0 ft 3 Room height 10.2 ft 9.3 heat/coolft 4 Room dimensions ft11.0x16.0 5 Room area 2720.0 ft²176.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 418 397 2425 1525 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 21 21 421 379 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 55 55 287 162 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 39 29 66 41 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 10 20 70 182 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 843 741 4531 2849 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 81 162 568 1471 0 0 0 0 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 20 20 409 368 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 4 4 21 12 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 430 398 2432 1529 103 103 627 394 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 32 9 227 695 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 43 43 222 126 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 694 545 3333 2096 149 109 667 419 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 49 0 341 1501 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 40 0 282 1243 40 0 282 1243 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 60 0 423 1864 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 151 151 783 443 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 59 59 63 102 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 117 117 141 91 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 2634 2634 3184 2055 176 176 213 137 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 2720 216 8513 0 176 27 1064 0 6 c) AED excursion 1800 481 Envelope loss/gain 28742 20533 2853 2674 12 a) Infiltration 6571 1774 618 167 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 4000 0 Subtotal (lines 6 to 13)35313 27457 3471 2841 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 35313 27457 3471 2841 15 Duct loads 11%12%3752 3250 10%9%351 245 Total room load 39065 30707 3822 3086 Air required (cfm)Air required (cfm)497 1200 49 121 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 2...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Master Bedroom WC 2 Exposed wall 15.5 ft 5.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft269.0x1.0 ft5.5x5.0 5 Room area 269.0 ft²27.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 0 0 0 0 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 145 112 686 431 51 51 314 197 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 32 5 227 695 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 269 269 325 210 28 28 33 21 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 269 16 611 0 28 6 217 0 6 c) AED excursion 374 -6 Envelope loss/gain 1849 1710 564 213 12 a) Infiltration 355 96 126 34 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2204 1806 690 247 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2204 1806 690 247 15 Duct loads 10%9%223 156 10%9%70 21 Total room load 2427 1962 759 268 Air required (cfm)Air required (cfm)31 77 10 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 3...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Master Bath Master Closet 2 Exposed wall 20.5 ft 12.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft141.3x1.0 ft125.3x1.0 5 Room area 141.3 ft²125.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 0 0 0 0 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 117 100 614 386 117 100 614 386 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 16 16 114 294 16 16 114 294 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 75 75 456 287 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 141 141 171 110 125 125 151 98 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 141 21 808 0 125 13 493 0 6 c) AED excursion -28 -20 Envelope loss/gain 2162 1049 1371 758 12 a) Infiltration 469 127 286 77 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2632 1176 1658 835 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2632 1176 1658 835 15 Duct loads 10%9%266 102 10%9%167 72 Total room load 2898 1278 1825 908 Air required (cfm)Air required (cfm)37 50 23 35 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 4...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Office Entry 2 Exposed wall 0 ft 6.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft13.0x9.0 ft11.0x6.5 5 Room area 117.0 ft²71.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 0 0 0 0 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 39 29 66 41 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 10 10 70 182 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 0 0 0 0 22 1 8 5 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 20 20 409 368 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 117 117 141 91 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 72 72 86 56 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 117 0 0 0 72 7 256 0 6 c) AED excursion -7 -16 Envelope loss/gain 141 85 895 636 12 a) Infiltration 0 0 149 40 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 200 0 Subtotal (lines 6 to 13)141 285 1044 676 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 141 285 1044 676 15 Duct loads 10%9%14 25 10%9%105 58 Total room load 156 309 1149 735 Air required (cfm)Air required (cfm)2 12 15 29 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 5...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Playroom Bedroom 3 2 Exposed wall 12.0 ft 27.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft13.5x12.0 ft181.0x1.0 5 Room area 162.0 ft²181.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 0 0 0 0 145 145 884 556 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 112 96 585 368 112 96 585 368 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 16 16 114 294 16 16 114 294 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 162 162 196 126 181 181 219 141 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 162 12 473 0 181 28 1084 0 6 c) AED excursion -20 -35 Envelope loss/gain 1368 769 2885 1324 12 a) Infiltration 275 74 630 170 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1642 843 3515 1494 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 3 2 0 0 14 Subtotal 1646 845 3515 1494 15 Duct loads 10%9%166 73 10%9%355 129 Total room load 1812 918 3870 1623 Air required (cfm)Air required (cfm)23 36 49 63 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 6...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Pantry Bath 3 2 Exposed wall 0 ft 0 ft 3 Room height 10.8 heat/coolft 9.3 heat/coolft 4 Room dimensions ft4.5x4.0 ft65.3x1.0 5 Room area 18.0 ft²65.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 0 0 0 0 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 19 19 23 15 65 65 79 51 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 18 0 0 0 65 0 0 0 6 c) AED excursion 0 -6 Envelope loss/gain 23 14 79 45 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 200 Subtotal (lines 6 to 13)23 14 79 245 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -23 -14 0 0 14 Subtotal 0 0 79 245 15 Duct loads 10%9%0 0 10%9%8 21 Total room load 0 0 87 266 Air required (cfm)Air required (cfm)0 0 1 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 7...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Laundry Hall 2 Exposed wall 12.0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft129.3x1.0 ft57.1x1.0 5 Room area 129.3 ft²57.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 112 91 556 350 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 21 21 421 379 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 129 129 156 101 57 57 69 45 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 129 12 473 0 57 0 0 0 6 c) AED excursion -32 -6 Envelope loss/gain 1606 797 69 39 12 a) Infiltration 275 74 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 200 Subtotal (lines 6 to 13)1881 1371 69 239 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1881 1371 69 239 15 Duct loads 10%9%190 118 10%9%7 21 Total room load 2071 1490 76 260 Air required (cfm)Air required (cfm)26 58 1 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 8...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Bedroom 2 Bath 2 2 Exposed wall 27.0 ft 5.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft171.9x1.0 ft10.0x5.5 5 Room area 171.9 ft²55.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 117 117 713 448 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 135 119 728 458 51 51 314 197 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 16 0 114 500 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 172 172 208 134 55 55 66 43 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 172 27 1064 0 55 6 217 0 6 c) AED excursion 176 -6 Envelope loss/gain 2826 1716 597 234 12 a) Infiltration 618 167 126 34 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3444 1883 723 268 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3444 1883 723 268 15 Duct loads 10%9%348 163 10%9%73 23 Total room load 3792 2046 796 291 Air required (cfm)Air required (cfm)48 80 10 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 9...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Great Room Bedroom 4 2 Exposed wall 32.0 ft 12.5 ft 3 Room height 12.7 heat/coolft 9.3 heat/coolft 4 Room dimensions ft454.5x1.0 ft158.8x1.0 5 Room area 454.5 ft²158.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nene 6.116.11 3.843.84 45 45 272 171 0 0 0 0 .DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 nene 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 .WW Block Wall 4-1Block Wall 4-1 0.1550.155 nene 5.185.18 2.932.93 0 0 0 0 0 0 0 0 .WW 2 x 6 R-192 x 6 R-19 0.0680.068 sese 2.272.27 1.431.43 0 0 0 0 0 0 0 0 11 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 sese 6.116.11 3.843.84 247 247 1511 950 117 100 614 386 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 sese 7.017.01 18.1818.18 0 0 0 0 16 16 114 294 DD Door, mtl fbrgl type 0.600Door, mtl fbrgl type 0.600 sese 20.0420.04 18.0618.06 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 sese 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 swsw 6.116.11 3.843.84 57 57 349 219 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 swsw 7.017.01 21.4621.46 0 0 0 0 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 swsw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 WW Block Foam Fill R-9 0.183Block Foam Fill R-9 0.183 nwnw 6.116.11 3.843.84 359 266 1625 1022 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 32 0 227 1001 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 0 0 0 0 0 0 0 0 GG Double Pane, Low-E, 0.210Double Pane, Low-E, 0.210 nwnw 7.017.01 30.9130.91 60 0 423 1864 0 0 0 0 WW Block Wall 4-1Block Wall 4-1 0.1550.155 nwnw 5.185.18 2.932.93 0 0 0 0 0 0 0 0 CC Attic, asphalt, r-30 0.032Attic, asphalt, r-30 0.032 --1.071.07 1.721.72 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 0 0 0 0 0 0 0 0 CC Attic, mtl, r-38, 1/ 0.405Attic, mtl, r-38, 1/ 0.405 --1.211.21 0.780.78 510 510 616 398 159 159 192 124 FF Slab on gradeSlab on grade 1.1801.180 --39.4139.41 0.000.00 455 32 1261 0 159 13 493 0 6 c) AED excursion 1051 -20 Envelope loss/gain 6284 6676 1412 784 12 a) Infiltration 1736 469 286 77 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)8020 8964 1698 861 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 9 6 14 Subtotal 8020 8964 1707 867 15 Duct loads 10%9%810 774 10%9%172 75 Total room load 8831 9738 1879 941 Air required (cfm)Air required (cfm)112 381 24 37 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-09 09:49:34Right-Suite® Universal 2019 19.0.18 RSU27939 Page 10...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Right-J® Worksheet Apr 9th, 2020Date:Entire House Marissa EllerBy:ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Kitchen 2 Exposed wall 0 ft 3 Room height 12.1 heat/coolft 4 Room dimensions ft339.8x1.0 5 Room area 339.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Block Foam Fill R-9 0.183 ne 6.11 3.84 0 0 0 0 .D Door, mtl fbrgl type 0.600 ne 20.04 18.06 0 0 0 0 .W Block Wall 4-1 0.155 ne 5.18 2.93 55 55 287 162 .W 2 x 6 R-19 0.068 se 2.27 1.43 0 0 0 0 11 G Double Pane, Low-E, 0.210 se 7.01 18.18 0 0 0 0 W Block Foam Fill R-9 0.183 se 6.11 3.84 0 0 0 0 G Double Pane, Low-E, 0.210 se 7.01 18.18 0 0 0 0 D Door, mtl fbrgl type 0.600 se 20.04 18.06 0 0 0 0 W Block Wall 4-1 0.155 se 5.18 2.93 4 4 21 12 W Block Foam Fill R-9 0.183 sw 6.11 3.84 0 0 0 0 G Double Pane, Low-E, 0.210 sw 7.01 21.46 0 0 0 0 W Block Wall 4-1 0.155 sw 5.18 2.93 43 43 222 126 W Block Foam Fill R-9 0.183 nw 6.11 3.84 0 0 0 0 G Double Pane, Low-E, 0.210 nw 7.01 30.91 0 0 0 0 G Double Pane, Low-E, 0.210 nw 7.01 30.91 0 0 0 0 G Double Pane, Low-E, 0.210 nw 7.01 30.91 0 0 0 0 W Block Wall 4-1 0.155 nw 5.18 2.93 151 151 783 443 C Attic, asphalt, r-30 0.032 -1.07 1.72 59 59 63 102 C Attic, mtl, r-38, 1/ 0.405 -1.21 0.78 0 0 0 0 C Attic, mtl, r-38, 1/ 0.405 -1.21 0.78 315 315 381 246 F Slab on grade 1.180 -39.41 0.00 340 0 0 0 6 c) AED excursion -80 Envelope loss/gain 1756 1010 12 a) Infiltration 622 168 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 1 230 Appliances/other 2000 Subtotal (lines 6 to 13)2379 3408 Less external load 0 0 Less transfer 0 0 Redistribution 11 7 14 Subtotal 2389 3414 15 Duct loads 18%34%426 1174 Total room load 2815 4588 Air required (cfm)36 179 2020-Apr-09 09:50:16 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Duct System Summary Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor: 20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.31in H2O0.24 Available static pressure in H2O0.39in H2O0.46 Supply / return available pressure 0.273 / 0.187 in H2O in H2O0.231 / 0.159 Lowest friction rate in/100ft0.066in/100ft0.078 Actual air flow cfm1200cfm497 Total effective length (TEL) ft591 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st1110.016.5VlFx0x04.00.183110291cBath 2 st2A135.021.5VlFx0x04.00.148100266cBath 3 75.05.5VlFx0x05.00.2878002046cBedroom 2 st2A165.014.8VlFx0x05.00.1296301623cBedroom 3 st2B150.038.5VlFx0x04.00.123370941cBedroom 4 st2B165.047.7VlFx0x04.00.109290735cEntry st1A150.044.7VlFx0x06.00.1199502435cGreat Room st1A110.039.0VlFx0x06.00.1559502435cGreat Room-A st1130.029.2VlFx0x06.00.1459502435cGreat Room-B st190.023.5VlFx0x06.00.2049502435cGreat Room-C st1110.010.0VlFx0x04.00.193100260cHall st2B155.047.5VlFx0x06.00.1149002294cKitchen st2A120.033.5VlFx0x06.00.1519002294cKitchen-A st290.07.5VlFx0x05.00.2375801490cLaundry st2E250.072.5VlFx0x04.00.0725001278cMaster Bath st2D215.063.0VlFx0x06.00.0837701962cMaster Bedroom st2C210.056.5VlFx0x04.00.087350908cMaster Closet st2C220.053.0VlFx0x04.00.085120309cOffice-A st2A130.024.0VlFx0x04.00.150360918cPlayroom st1B145.059.0VlFx0x06.00.11312103086cSitting Room st2E275.075.8VlFx0x04.00.066100268cWC 2020-Apr-09 09:50:16 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 2 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2C Peak AVF 0 185 0.066 554 8.4 6x8 RectFbg st2B st2B Peak AVF 0 340 0.066 764 10.2 8x8 RectFbg st2A st2E Peak AVF 0 60 0.066 544 8.4 4x4 RectFbg st2D st2A Peak AVF 0 539 0.066 809 12.5 12x8 RectFbg st2 st1B Peak AVF 0 121 0.113 724 6.9 4x6 RectFbg st1A st1A Peak AVF 0 311 0.113 700 8.8 8x8 RectFbg st1 st1 Peak AVF 0 523 0.113 784 11.1 12x8 RectFbg st2 Peak AVF 0 597 0.066 768 13.0 14x8 RectFbg st2D Peak AVF 0 137 0.066 617 8.4 4x8 RectFbg st2C Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb8 0x 00 12 185.0 0.086 62 6.0 x0 0 VlFx rt2A rb5 0x 00 80 89.0 0.178 407 6.0 x0 0 VlFx rt2 rb2 0x 00 121 231.1 0.069 451 7.0 x0 0 VlFx rt2A rb1 0x 00 173 226.5 0.070 220 12.0 x0 0 VlFx rt2A rb7 0x 00 309 240.5 0.066 393 12.0 x0 0 VlFx rt2A rb6 0x 00 406 114.0 0.139 380 14.0 x0 0 VlFx rt2 rb3 0x 00 37 167.0 0.095 270 5.0 x0 0 VlFx rt2A rb4 0x 00 63 105.0 0.151 465 5.0 x0 0 VlFx rt2 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 0 1200 0.066 686 16.9 14x18 RectFbg rrs1 rt2A Peak AVF 0 651 0.066 521 13.4 10x18 RectFbg rt2 rrs1 Peak AVF 0 1200 0.066 617 16.9 14x20 RectFbg rt1 rt1 Peak AVF 0 1200 0.066 533 16.1 18x18 RectFbg 2020-Apr-09 09:50:16 Right-Suite® Universal 2019 19.0.18 RSU27939 Page 1 ...inals\Current\Buchmeyer Residence REV Final.rup Calc = MJ8 Front Door faces: SE Buchmeyer ResidenceJob:Static Pressure and Friction Rate Apr 9th, 2020Date:Entire House Marissa EllerBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Project Information Buchmeyer ResidenceFor: 20806 Glades Cut Off Rd, Port St Lucie, FL 34987 Phone: 772-696-3296 Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.700.70External static pressure Pressure losses 0.070Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 0.150.15Filter 00Humidifier 0.030.03Balancing damper 00Other device 0.390.46Available static pressure Total Effective Length ReturnSupply (ft)(ft) 1113Measured length of run-out 4563Measured length of trunk 185275Equivalent length of fittings 241351Total length 591Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.066OK0.078Supply Ducts OK0.066OK0.078Return Ducts Fitting Equivalent Length Details 4W=35, 2A0=35, 11G=5, 11G=5, 11G=5, 11G=5, 11G=5, 12H1=20, 12H1=20, 2A0=35, 12H1=20, 12H1=20, USR1=65: TotalEL=275 Supply 6O=10, 6C2=30, 6CB=25, 6CA=10, 6CA=10, 12H1=20, 6CA=10, 6C1=10, 8E=10, 8E=10, 5A=40: TotalEL=185Return