HomeMy WebLinkAboutSigned BRADFORD TERRY & DIANE PREVOST - FULL - R0PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
T01
01 VICINITY
02 AERIAL
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
SHEET INDEX
T01COVER
S01LAYOUT
S02FIRE SAFETY
S03ATTACHMENT
E01LINE DIAGRAM
L01LABELS
D01STRUC DATASHEETS
D02STRUC DATASHEETS
D03ELEC DATASHEETS
D04ELEC DATASHEETS
PROJECT INFORMATION
JURISDICTION
DESIGN SPECS
GOVERNING CODES
SYSTEM
BUILDING: ST. LUCIE COUNTY
WIND EXPOSURE: B
WIND SPEED (MPH): 160
BUILDING: FBC 2017
ELECTRICAL: NEC 2014
FIRE: NFPA 2015
SIZE (KWDC): 7.14
# PANELS: 21
PANEL: BLK-G6340
INVERTER(S): SE6000H-US
VOLTAGE (V): 240
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
S01
01 PLAN VIEW 05 RAIL SYSTEM
04 ATTACHMENT SYSTEM
03 BUILDING DATA
02 PANEL DATA
INV -INVERTER
PM -POWER METER
ACD -AC DISCONNECT
MP -MAIN PANEL/DISC
-ZONE 1
-ZONE 2
COUNT 21
MAKE HANWHA QCELLS
MODEL BLK-G6340
DIMS (IN)68.5"x40.5"x1.26"
REAR LOAD: WIND (PSF) 75
MAKE-MODEL IRONRIDGE-FLASHFOOT2
MIN # IF SUPPORTS 24" OC 32
MIN # IF SUPPORTS 16" OC 30
MEAN ROOF HEIGHT, h (FT)<=15'
ROOF PITCH, (DEG)<=27°
ROOF TYPE SHINGLE
SUPPORT SPACING (IN)24" OR 16"
WIND PERIMETER, a (FT)3'
MAKE-MODEL IRONRIDGE-XR100
# RAIL PER PANEL 2
MAX SPAN PER TABLES (IN): Z1, Z2 94" 70"
MAX CANTILEVER (IN), Z1, Z2 37.6" 28"
SPAN IF SUPPORTS 24" OC (IN): Z1, Z2 72" 48"
SPAN IF SUPPORTS 16" OC (IN): Z1, Z2 80" 64"
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
S02
01 FIRE SAFETY OFFSETS
NFPA 1 11.12.2.2.2 FOR RESIDENTIAL HOMES
.1.1 HIP ROOF LAYOUTS:
PHOTOVOLTAIC MODULES SHALL BE LOCATED IN A
MANNER THAT PROVIDES A 3 FT (914 MM) WIDE
CLEAR ACCESS PATHWAY FROM THE EAVE TO THE
RIDGE OF EACH ROOF SLOPE WHERE THE
PHOTOVOLTAIC MODULES ARE LOCATED. THE
ACCESS PATHWAY SHALL BE LOCATED AT A
STRUCTURALLY STRONG LOCATION OF THE
BUILDING, SUCH AS A BEARING WALL.
EXCEPTION: THE REQUIREMENT OF 11.12.2.2.2.1.1
SHALL NOT APPLY WHERE ADJOINING ROOF PLANES
PROVIDE A 3 FT (914 MM) WIDE CLEAR ACCESS
PATHWAY.
.1.2 SINGLE RIDGE LAYOUTS:
PHOTOVOLTAIC MODULES SHALL BE LOCATED IN A
MANNER THAT PROVIDES TWO 3 FT (914 MM) WIDE
ACCESS PATHWAYS FROM THE EAVE TO THE RIDGE
ON EACH ROOF SLOPE WHERE THE MODULES ARE
LOCATED.:
.1.3 HIP AND VALLEY LAYOUTS:
PHOTOVOLTAIC MODULES SHALL BE LOCATED NO
CLOSER THAN 1 1/2 FT (457 MM) TO A HIP OR VALLEY
IF MODULES ARE TO BE PLACED ON BOTH SIDES OF
THE HIP OR VALLEY. WHERE MODULES ARE LOCATED
ON ONLY ONE SIDE OF A HIP OR VALLEY OF EQUAL
LENGTH, THE PHOTOVOLTAIC MODULES SHALL BE
ALLOWED TO BE PLACED DIRECTLY ADJACENT TO
THE HIP OR VALLEY.
.2 RIDGE SETBACK:
PHOTOVOLTAIC MODULES SHALL BE LOCATED NOT
LESS THAN 3 FT (914 MM) BELOW THE RIDGE.
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
S03
BLK-G6340
68.5 IN
40.5 IN
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
E01
01 NOTES
02 MODULE RATINGS 03 OPTIMIZER RATINGS
04 INVERTER RATINGS 05 SYSTEM
06 CONDUCTOR SCHEDULE
07 ELECTRICAL LINE DIAGRAM
MAKE SOLAREDGE
MODEL P340
INPUT POWER (W) 340
MAX INPUT VOLTAGE (V) 48
MAX INPUT CURRENT (A) 13.75
MAX OUTPUT CURRENT (A) 15
MAX STRING POWER (W) 5700-6000
MAKE HANWHA QCELLS
MODEL BLK-G6340
RATED POWER (W) 340
MPP VOLTAGE (V)33.94
MPP CURRENT (A) 10.02
OC VOLTAGE (V)40.66
SC CURRENT (A) 10.52
MAKE SOLAREDGE
MODEL SE6000H-US
MAX INPUT POWER (W) 9300
MAX INPUT VOLTAGE (V) 480
NOM INPUT VOLTAGE (V) 380
MAX INPUT CURRENT (A) 16.5
NOM AC VOLTAGE (V) 240
MAX AC CURRENT (A) 25
NOM AC POWER (W) 6000
ID RUN VOLTAGE(V) CURRENT(A) VD(%) LEN(FT) CONDUCTOR SIZE OHM/KFT CONDUIT MIN SIZE #CCC EGC OCPD(A) TERM(C) TEMP FAC FILL FAC BASE AMP ADJ AMP
A STR-JBOX 380 14.32 1 107 PV WIRE #10 1.24 FREE AIR NA 4 #10 NA 75 0.96 0.8 30 30
B JBOX-INV 380 14.32 1 107 THHN/THWN-2/PV WIRE #10 1.24 PVC/EMT/FMC/NMLT 3/4" 4 #10 NA 75 0.96 0.8 30 30
C INV-DISC 240 25 1 107 THHN/THWN-2 #8 0.778 PVC/EMT/FMC/NMLT 3/4" 3 #10 35 75 0.96 1 50 50
D DISC-PCC 240 25 1 170 THHN/THWN-2 #6 0.491 PVC/EMT/FMC/NMLT 3/4" 3 NA 35 75 0.96 1 65 65
# MODS 21
# INVERTERS 1
STC DC RATING (KW) 7.14
AC OUTPUT RATING (KW) 6
INVERTER 1 SE6000H-US
# STRINGS 2
MIN-MAX STRING SIZE 8-16
DC/AC RATIO 1.19
MPP CURRENT (A) 16.5
GENERAL
1.1 CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH NEC 2014 AND FBC 2017 REQUIREMENTS AND EQUIPMENT INSTALLATION
INSTRUCTIONS NOT SHOWN IN THIS PLAN.
1.2 CONDUCTOR TYPES SHALL MEET THE REQUIREMENTS PER NEC 310.10 BASED ON INSTALLATION LOCATION.
1.3 DIRECT-CURRENT PV SOURCE AND OUTPUT CONDUCTORS INSIDE A BUILDING SHALL BE CONTAINED IN METAL RACEWAYS, 690.31(G).
1.4 ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(D).
1.5 CONDUCTORS ARE SIZED BASED ON RACEWAYS NOT EXPOSED TO DIRECT SUNLIGHT UNLESS STATED OTHERWISE. 10% OF CIRCUIT
LENGTH CAN BE EXPOSED DIRECT SUNLIGHT UP TO 10FT, NEC 310.15(A)(2).
1.6 PV SOURCE AND OUTPUT CIRCUIT CONDUCTORS ARE SIZED TO BE EXPOSED TO DIRECT SUNLIGHT GREATER THAN 10% OF THEIR
LENGTH WHEN INSTALLED IN RACEWAYS ½” OR GREATER ABOVE ROOF. ADJUSTMENTS ARE BASED ON MAX STRING CURRENT OF 15A &
AMBIENT TEMPERATURE OF 35C PER NEC 310.15(B)(2)(A) & 310.15(B)(3)(C).
SYSTEM
2.1 THE OUTPUT VOLTAGE OF THE OPTIMIZERS ARE REGULATED BY THE INVERTER AND ARE NOT IMPACTED BY THE NUMBER OF MODULES IN
THE STRING. THE CONTINUOUS CURRENT OF A SINGLE STRING IS EQUAL TO THE MAXIMUM OUTPUT CURRENT OF THE OPTIMIZER OF 15A.
2.2 THE INVERTER IS EQUIPPED WITH A RAPID SHUTDOWN FEATURE WHICH CONFORMS TO NEC 690.12 (2014).
2.3 THE INVERTER IS NON-ISOLATED AND UNGROUNDED. NEITHER THE NEGATIVE NOR POSITIVE CONDUCTOR IS GROUNDED AND HAS A
COMMON AC AND DC EQUIPMENT GROUNDING TERMINAL THEREFORE NO DC GEC IS REQUIRED.
2.4 UTILITY CONNECTION SHALL BE MADE AS SHOWN BY LINE-SIDE-TAP PER ARTICLE 705.12(A) USING INSULATED, PIERCING CONNECTORS UL
LISTED FOR THIS PURPOSE AND LOCATED WITHIN CODE COMPLIANT ENCLOSURE.
2.5 INTEGRATED DC DISCONNECT AND AFCI IS PROVIDED WITH INVERTER.
GROUNDING
3.1 ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690.
3.2 FRAMED PV MODULES SHALL BE BONDED TOGETHER USING LUGS OR RACKING INTEGRATED GROUNDING CLAMPS.
3.3 EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED PER NEC 250.120(C), SIZED PER 690.45 & BE A MINIMUM OF #6 WHEN
EXPOSED TO DAMAGE.
8-16
8-16
8-16P340
06 CONDUCTOR SCHEDULE
8-16
8-16
8-16P340
35A
150A
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
L01
16.5
380
480
30
240
25
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
D01
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
D02
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
D03
PROJECT ID:
CONTRACTOR:ENGINEER OF RECORD DESCRIPTIONDATEVERBY
PAPER:
ARCHB
SCALE:
NTS
06.19.20 RG 01 INITIAL DESIGN
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
BRADFORD TERRY & DIANE PREVOST
5108 PALM DR, FORT PIERCE, FL 34982, USA
061920-MSS-PREVOST
SOLAR SUN LLC
6090 CENTRAL AVE,
ST.PETERSBURG FL 33707
727-269-5350
I-EC13008840
SPENCER N. ROBINSON
PE81250
D04