HomeMy WebLinkAboutAir System Sizing SummaryAir System Sizing'Summary for AHU-1/CU-1
Project Name: HUTCHINSON ISLAND CONDO CLUB 06/24/2019
Prepared bv:. 06:29PM
Air System Information
Air System Name .._....... _ ........ .......... ........._... AHU-11CU-1
Equipment Class ................................................... SPLT AHU
Air System Type _ ----------------------------------------------------------- SZCAV
Sizing Calculation Information
Calculation Months .............................................. Jan to Dec
Sizing Data ...................... ......Calculated
Central Cooling Coil Sizing Data
Number of zones ................................. _...... _................................. 1
FloorArea................................................................................ 120.0 ft'
Location ........................................ West Palm Beach, Florida
Zone CFM Sizing ..................... Sum of space airflow rates
Space CFM Sizing ................ Individual peak space loads
Total coil load.........................................................................
2.0
Tons
Load occurs at.....
Jul 1700
Total coil load.......
.. 24.1
MBH
CA DB / WB.............................................. _----------
_----- 89.7177.7
°F
Sensible coil load...............................................................
24.1
MBH
Entering IDS / WB..................................... _.._.............
76.4146.6
°F
Coil CFM at Jul 1700.......................................................
1265
CFM
Leaving DB / WB .........................................................
58.7137.6
"F
Max block CFM ..................................................................
1265
CFM
Coil ADP ._._......................
... 66.7
°F
Sum of peak zone CFM .................... _............................
1266
CFM
Bypass Factor ..... _............ ----------------------------------------------------
0.100
Sensible heat ratio ............... _.... _....................................
1.000
Resulting RH..._--...--...-.---....-.._.-..........................................
0
%
ft'/Ton........ .................... .-------------------------- .---------------------------
59.7
Design supply temp ................................................................
58.0
°F
BTU/(hr-ft�......................._._--------...................................
200.9
Zone T-stat Check ................................................................
1 of 1
OK
Water Flow @ 10.0 °F rise ................................................
NIA
Max zone temperature deviation ..._-.----
---------------------------- 0.0
°F
Supply Fan Sizing Data
Actual max CFM ----------------------------------------------------------------
1265
CFM
Fan motor BHP...--..--..--......_-....---...-....-......-.......-.....
0.00
BHP
Standard CFM ................................... ___._....._—_._.._.
1264
CFM
Fan motor kW .............................. _.... ._...... .................
......... 0.00
kW
Actual max CFM/ft'..........................................................
10.64
CFM/ft'
Fan static ... _...............................................................................
0.00
in wg
Outdoor Ventilation Air Data
Design airflow CFM............................... -----
------- ----------- 0
CFM
CFM/person .............................. ....... ................
............. 0.00
CFM/person
CFM/ft'... -..............................................................................
0.00
CFM/ft'
Hourly Analysis Program v4.91 Page 1 of 3
Zone Sizing Summary for AHU-1/CU-1
Project Name: HUTCHINSON ISLAND CONDO CLUB 06/2412019
Prepared by:. 06:29PM
Air System Information
Air System Name ............................................... AHU-1/CU-1
Equipment Class ..... ...................._. SPILT AHU
Air System Type SZCAV
Sizing Calculation Information
Calculation Months .............................................. Jan to Dec
Sizing Data .............................................................. Calculated
Zone Terminal Sizing Data
Number of zones............................................................................1
Floor Area--..............--...............................:.-------------------.. 120.0 ft'
Location ........................................ West Palm Beach, Florida
Zone CFM Sizing ..................... Sum of space airflow rates
Space CFM Sizing ................Individual peak space loads
Reheat
Zone
Zone -
Design
Minimum
Reheat
Coil
Htg Unit
' Htg Unit
Mixing
Supply
Supply
Coil
Water
Coil
Water
Box Fan
Airflow
Airflow
Zone
Load
gpm
Load
gpm
Airflow
Zone Name _ _
CFM
CFM
CFM/ft'
MBH
20.0 °F
(MBHI
20.0 °F
CFM
Zone 1
1265
1265
10.54
0.0
-
0.0
-
0
Zone Peak Sensible Loads
Zone
-Zone
Zone
Cooling
Time of
Heating
Floor
Sensible.
Peak Sensible
Load'
Area
Zone Name
(MBH)
Cooling Load
(MBH)
(it')
Zone 1
23.21
Jul 1700
0.6
120.0
Space Loads and Airflows
- -
--
- -
Time of
Cooling
Peak
Air
Heating
Floor
Zone.Name/
'Sensible
Sensible
Flow
Load
Area
Space
Space Name
Mult.
MBH
.Load
CFM
MBH
ft'
CFM/ft'
Zonal
IT BUILDING
1
23.2
Jul 1700
1265
0.6
120.0
10.54
Hourly Analysis Program v4.91 Page 2 of 3
Air System Design Load Summary for AHU-1/CU-1
Project Name: HUTCHINSON ISLAND CONDO CLUB 06/2412019
Prepared by:. 06:29PM
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
COOLING OADB / WB 89.7 °F / 77:7 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 43.0 °F 136.1 °F
_ -
ZONE LOADS _
Details
- Sensible
(BTU/hr)
Latent
_ (BTU/hr)
_ _
. Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
0 ft2
0
-
0 ft2
-
-
Wall Transmission
493 ft2
466
-
493 ft2
524
Roof Transmission
120 ft2
163
-
120 ft2
79
-
Window Transmission
0 ft2
0
-
0 ft2
0
-
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Loads
0 ft2
0
0 ft2
0
-
Floor Transmission
120 ft2l
0
120 ft2
0'
-
Partitions
0 ft2
0
-
0 ft2
0
-
Ceiling
0 ft2
0
-
0 ft2
0
Overhead Lighting
240 W
0
0
0
-
Task Lighting
0 W
0
0
0
-
Electric Equipment
6000 W
20472
-
0
0
-
People
0
0
0
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
10%/ 0%
2110
0
0%
0
0
>> Total Zone Loads -
- - -
33210
_ - - 0
-
603
0
Zone Conditioning
-
23284
0
-
67
0
Plenum Wall Load
0%
0
0
0
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
100%
819
-
0
0
-
Return Fan Load
1265 CFM
0
-
1265 CFM
0
-
Ventilation Load
0 CFM
0
0
0 CFM
0
0
Supply Fan Load
1265 CFM
0
-
1265 CFM
0
-
Space Fan Coil Fans
-
0
-
NO
-
0
-
Duct Heat Gain / Loss
0%
0
-
0%
0
-
Total System Loads
24103
0
67
0
Central Cooling Coil
-
24103
0
-
0
0
>> Total Conditioning
-
24103
- - -
-- _ 0
0
Key:
'Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
'Negative values are clg loads
Hourly Analysis Program v4.91 Page 3 of 3
AHU-1/CU-1 Input Data
Project Name: HUTCHINSON ISLAND CONDO CLUB O6/24/2019
Prepared by:. 06:29PM
1. General Details:
Air System Name ._....._........__.....__.._........_.....__.... AHU-11CU-1
Equipment Type . ................ Split AHU
Air System Type .......................... .... _...... _.--...................................... Single Zone CAV
Number of zones ------------------------------------- --- --- ---------------------------------- 1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control................................................................
Constant Ventilation Airflow
Ventilation Sizing Method...............................................Sum
of Space OA Airflows
Unocc. Damper Position
.............................................. Closed
DamperLeak Rate ..........................................................................................................
....... 0 %
Outdoor Air CO2 Level -------------- __._------- -----------
----------------------------------------------------------- 400 ppm
Central Cooling Data:
Supply Air Temperature
................................................................ 58.0 °F
CoilBypass Factor .................................................................................................
__... 0.100
Cooling Source .........................................................................................
... Air -Cooled DX
Schedule ........ ._....... _..... _.._..............................................................
JFMAMJJASOND
Capacity Control ..........._ ..........................._._
Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ........................................................ __... _....... _... __................... Forward Curved
Configuration....-.......-...._........._....._........_.....__.._........... Draw-thru
Fan Performance .....-........ .......................... _. .........0.00 in wg
OverallEfficiency..............................................................----.._...._...........__..._............... 54
Fan Control............................................................ 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain.......
Duct Leakage _......_
Return Duct or Plenum Data:
Return Air Via......................................................................................
Return Air Plenum
Wall Heat Gain to Plenum ......_...
___..................................... ....._......._..0 %
Roof Heat Gain to Plenum...............................................................................:_.......-----....
0 %
Lighting Heat Gain to Plenum ...... _....................................
_._...................................... 100 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
IT BUILDING
xt
Thermostats and Zone Data:
Zone............._-.--.._.-........_._._.................-...........................-----------.............................
All
CoolingT-stat: Occ..........................................................................................................
75.0
°F
CoolingT-stat: Unocc...................... .................................... --.......................................
80.0
°F
Heating T-stat: Occ._.._..................................................
_.__...... 70.0
°F
Heating T-stat: Unocc.--------------- ....................................................................................
65.0
'F
T-stat Throttling Range -------------------------------------------------------------------------------------
°F
DiversityFactor ....................................................................................................
..._......_.. 100
%
Direct Exhaust Airflow--------------------------------------------------------- _..__----------
_-------------------------- 0.0
CFM
Direct Exhaust Fan kW.................._................._.............................................................
0.0
kW
Thermostat Schedule ...............................................................................................
TSTAT
Unoccupied Cooling is .......................... ..............._.............._........Available
Supply Terminals Data:
Zone........------------------...------..........................................-----------_........................__.. All
TerminalType..........................._........................._....----------------------............ Diffuser
MinimumAirOow........................................................................................................... .. 0.00 CFM/person
Zone Heating Units:
Zone................................................................................................. __........__......_................ All
Zone Heating Unit Type ................................................ ............................... ........___.. None
Zone Unit Heat Source...................................................................Electric Resistance
Zone Heating Unit Schedule ......... _..................................................JFMAMJJASOND
Hourly Analysis Program v4.91
AHU-1/CU-1 Input Data
Project Name: HUTCHINSON ISLAND CONDO CLUB 06/2412019
Prepared by: . 06:29PM
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
oF
Su
1
CFM
Ventilation Airflow ...............................................................................................
----ou'
opm
Hydronic Sizing Specifications:
Chilled Water Delta-T
10.0
*F
Hot Water De|ta-T....................................................................................................
...... 2n.0
^F
Safety
Cooling Sensible ..... —'
------'.—.'--.-------10
%
Cooling Latent
0
m
Heating........................................................... ......
—.... ............... ................................. 0
%
Zone Sizing Data:
Zone Airflow Sizing Method ..........................................
Sum oyspace airflow rates
Zone
SupplyAirnow
Zone Htg Unit
Reheat Coll