HomeMy WebLinkAboutapproved Plans; Electrical & HVAC e1-m1DATE I ELECTRICAL SPECIFICATIONS I 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, N.F.P.A., LOCAL CODES, ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. 2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST-CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB- CONTRACT. 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. 6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 7, ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTINGS. 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. 10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL BE 12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS 10 AWG AND SMALLER MAY BE SOLID; ALL THOSE 8 AWG AND LARGER TO BE STRANDED. 11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3 4" GALVANIZED RIGID STEEL CONDUIT UNLESS WHERE OTHERWISE NOTED ON PLANS. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. 12. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. 13. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE THOSE MANUFACTURED BY EITHER BUSSMAN OR LITTLEFUSE. THE CONTRACTOR SHALL FURNISH TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL BE CLASS L. 14. ALL GENERAL PURPOSE RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND PLATES SHALL BE WHITE UNLESS DICTATED OTHERWISE BY ARCHITECT/OWNER. - COVER PLATES: 15. A SEPARATE, GREEN TYPE THWN COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250-122 OF THE N.E.C. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. 16. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. 17. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. 18. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SQUARE "D"; HOWEVER, COMPARABLE EQUIPMENT BY EATON & SIEMENS ONLY WILL BE ACCEPTABLE. TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. 19. PROVIDE IDENTIFICATION FOR ALL PANELS, CABINETS, ENCLOSURES, DISCONNECTS & TRANSFORMERS USING ENGRAVED NAMEPLATES, WHITE LETTERING ON A BLACK BACKGROUND. NAMEPLATES SHALL IDENTIFY PANEL DESIGNATION (NAME,) VOLTAGE, PHASE & WIRE CONFIGURATION. PROVIDE TYPEWRITTEN DIRECTORIES UNDER PLASTIC COVER FOR ALL PANEL BRANCH CIRCUITS, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CKT PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED. 20. ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING PANEL NAME, VOLTAGE AND AMPERAGE. 21. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL SECTIONS AT SLAB PENETRA11ONS WHERE SUBJECT TO POSSIBLE DAMAGE. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST -RESISTANT SITUMASTIC PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. 22. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL COORDINATE ALL RELATED WORK WITH THE UTILITY COMPANY S RESPONSIBILITIES TO MEET THE OWNER'S SCHEDULE. 23. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, RIGID GALVANIZED CONDUIT OR SCHEDULE 40 P.V.C. THERE SHALL BE NO TYPE 'NM', ELECTRICAL NON-METALLIC TUBING, & FLEXIBLE METAL CONDUIT USED FOR BRANCH CIRCUITING. MAXIMUM NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). "MC" TYPE CABLE SHALL NOT BE USED AS HOME RUNS. THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL. 24. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: 208V SYSTEM 240V (HIGH ) SYSTEM 480V SYSTEM PHASE SEQUENCE NEUTRAL - WHITE NEUTRAL -WHITE NEUTRAL - WHITE/STRIPE ABC, TOP TO BOTTOM PHASE A - BLACK PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT, FRONT PHASE B - RED PHASE B - ORANGE PHASE B - PURPLE TO BACK PHASE C - BLUE PHASE C - BLUE PHASE C - YELLOW GRD.CON - GREEN GRD.CON - GREEN GRD.CON - GREEN 25. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L. ASSEMBLY STANDARDS. 26. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO BE MARKED WHEN INSTALLED. USE GREEN TO INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE RUQ TO INDICATE FIELD CHANGES. UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ELECTRICAL ENGINEER. 27. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN HIS OPINION FINDS OMISSIONS OR ERRORS ON ELECTRICAL DOCUMENTS, IT IS HIS RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF THE ELECTRICAL ENGINEER IMMEDIATELY, IF ELECTRICAL CONTRACTOR PROCEEDS WITH ANY CHANGES TO THE CONTRACT DOCUMENTS, WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER, CONTRACTOR WILL NOT BE COMPENSATED. MDP EXISTING Rated Voltage: 2771480V 3PH 3W: Manufacture: EASTING Mounting: Surface Rated Amps: ICU bus) 225A SPACES: 30 Location: SEE PLAN Type: NEMA1 Main: MLO Project No. 20190011.00 A.I.C. 10 KAIC KVA KVA CIRCUIT DESIGNATION O.C.P. AWG/COND. RCPT CONT. LOAD MOTOR PH RCPT CONT. LOAD MOTOR AWOICOND. _ O.C.P. CIRCUIT DESIGNATION 1 NEW PANEL'1T" VIA.25KVA TX 70/2 SEE RISER 3.66 0.00 1.44 A 1 2011 SPACE 2 3 3.48 0.30 1.44 B SPACE 4 5 SPACE C SPACE 6 7 SPACE A SPACE $ 9 SPACE B i SPACE 10 11 SPACE SPACE 12 13 SPACE JA SPACE 14 SPACE SPACE 16 17 SPACE SPACE 18 19 O COOLING TOWER *3 '104114 ' 2.10 A SPACE 20 21 2.10 B SPACE 22 23 2.10 C SPACE 24 25 ELEVATOR - + 7013 4-1" 9.42 A SPACE 26 27 9.42 B SPACE 28 29 9.42 C ! SPACE 30 31 SPACE A SPACE 32 33 SPACE 13 SPACE 34 361 SPACE C SPACE 36 SUBTOTAL CONNECTED LOADf 7.1 0.3 37.4 0.0 0.0 0.0 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 16.6 CONTINUOUS & LARGEST MOTOR @ 25%: 0.1 note 1 verify max, O.C.P.D. With nameplate CONNECTED LOAD PHASE, 8: 16.7 CONNECT MOTOR LOADS @ 100%: 37.4 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 11b CONNECTED CONTINUOUS LOAD @100%: 0.300 note 3 non -concurrent bad TOTAL CONNECTED LOAD: 44.9 RECEPTACLE COMPUTED LOAD: 7A note 4 G.F.C.I. type circuit breaker RECEPT CONNECTED LOAD: 7A note 5 photo cell controlled TOTAL COMPUTED LOAD: 45 KVA note 6 tune switch controlled 54 AMPS note 7 mecharicaly hell lighting contactor NEW "IT" ROOM NEW 100A MANUAL PANEL XFER SW. IT, -- N L 0 125A E MLO 120/240V 10,3W NEMA 3R NEMA 1 GENERAL PLUG 3-3 AWG ,1-8 CU EG. IN 2" EMT EXISTING ELECTRICAL ROOM PENTHOUSE EG. IN 2" EMT EXISTING PANEL MDP" 225A MLO 480V 30,4W NEMA 1 EXISTING 3-1 AL, 1-6 CU EG. IN 2" EMT APPROXIMATE LOCATION OF PROPOSED "IT" ROOM 3-3 AWG ,1-8 CU 2-4 AWG,1-8 CU EG. IN 1" EMT VENTILATED 25 KVA TRANSFORMER 480V TO 240/120 V DRY TYPE NEMA 1 PANEL "IT" NEW Rated Voltage: 120I240V 1 PH, 3V/ Manufacture: SQUARE-D QOD Mounting: Surface Rated Amps (Cu bus) 125A SPACES: 30 Location: SEE PLAN Type: NEMA 1 Main: MILO Project No. 20190011.00 A.I -C. 10 KAIC KVA KVA CIRCUIT DESIGNATION O.C.P. AWOICOND. RCPT CONT. LOAD MOTOR PH RCPT CONT. LOAD MOTOR AWGJCOND. O.C.P. CIRCUIT DESIGNATION 1 MINI SPLIT UNIT (AHU-1/CU-1) 2.3KW 2012 12-112" 1'4 A 2011 SPARE 2 1.44 B 2011 SPARE 4 3 5 TWIST LOCK RECEPTACLE (L630) 30A 3012 10-112" 0'� - A 2011 SPARE 6 7 0.60 B 2011 SPARE 8 9 TWIST LOCK RECEPTACLE (L630) 30A 3012 10-fir 0'60 A 20/1 SPARE 10 0.60 B 2011 SPARE 12 11 13 TWIST LOCK RECEPTACLE (LS-20) 30A 3011 104tr 0.60 A 20/1 SPARE 14 15 TWIST LOCK RECEPTACLE (L5-20) 30A 3011 10-wr 0.60 B SPACE 16 17 RECEPTACLE 2011 12-1/2" 1.08 A SPACE 18 19 RECEPTACLE 2011 12-11r 1.08 B SPACE 20 TWIST LOCK RECETACLE (L5-20) 30A 3011 10412" 0.60 A 21 SPACE 22 23 TWIST LOCK RECETACLE IL5-20) 30A 3011 1041r 0.60 g SPACE 24 25 CONVIENIENCE RECEPTACLE 2011 12-112" 0.18 A SPACE 26 27 LIGHTING 2011 12-1/2" 0.300 B SPACE 28 29 SPACE A SPACE 30 SUBTOTAL CONNECTED LOAD, 7.1 0.3 2.9 0.0 0.0 0.0 SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 3.9 CONTINUOUS & LARGEST MOTOR @ 250A: 0.1 note 1 verify nuX. ORC,P.D. with nameplate CONNECTED LOAD PHASE B: 3.5 CONNECT MOTOR LOADS @ 100%: 2.9 note 2 lockable circuit breaker CONNECTED CONTINUOUS LOAD @100%: 0.300 note 3 non -concurrent bad TOTAL CONNECTED LOAD: 7.4 RECEPTACLE COMPUTED LOAD: 7.1 note 4 G.F.C.1. type circuit breaker RECEPT CONNECTED LOAD: 7.1 note 5 photo cell controlled TOTAL COMPUTED LOAD: 10 KVA note 6 time switch controlled 43 AMPS note 7 mechanically held fighting contactor LOCATION MAP ®® SCALE: NTS DISC SW. 21 ODA 1ODA 120/240V 1P,3W TO ELECTRICAL RM. LOWER FLOOR. - 1" FMC 8 AWG 2" FMC CU GND ELECTRICAL RISER SCALE: NTS PROPOSED CONDENSING UNIT. EXACT LOCATION TO BE DETERMINED IN THE FIELD CU-1 PROPOSED SPLIT UNIT. DISCONNECT SWITCH FOR PROPOSED ONDENSING UNIT. EXACT LOCATION TO BE �- FDETERMINED IN THE FIELD. Il M.W.CCONVENIENCE RECEPTACLE TO BE LOCATED 0X36 EAR FINAL LOCATION OF CONDENSING IT-1/3 I \220A1 UNIT. I IT-2/ L J dhWP/GFCI PKUV ED IT-9/1' "IT" OOM IT-5/7 IT-23 j IT-21 M.W.0 SIT-15 30X36" NIT-13 I "IT" ''IT-19 L � JIT-17 FLOOIR PLAIII 4� GENE AL NOTES 1. CONTRACTOR TO UPDATE PANEL DIRECTORY PER NEC ARTICLE 408.4 2. ALL RECEPTACLES IN NEW "IT" ROOM SHALL BE MOUNTED 7' ABOVE FINISH FLOOR. 3. RECEPTACLE SPACING IN NEW "IT" ROOM SHALL BE VERIFIED WITH OWNER BEFORE INSTALLATION. SCOPE OF WO SCOPE OF WORK IS NEW SERVICE TO NEW "IT" ROOM. am__ SCALE: 1/4 )) =1 -0, GENERIC L E GEND SYMBOL _ DESCRIPTION II 20A DUPLEX RECEPT. (SEE GENERAL NOTES FOR MOUNTING REQUIREMENT SPECIAL PURPOSE RECEPT.(SEE GENERAL NOTES FOR MOUNTING REQUIREMENT.SEE PANEL SCHEDULE FOR RATING) ® SURFACE MOUNTED LIGHT FIXTURE 2 LAMP, T5HO W/ ELECTRONIC BALLAST. LITHONIA DMW-54T5HO MVOLT 1/3 GEB10PS90 OR EQUAL M.W.0 MINIMUM WORK CLEARANCE LIGHT SWITCH (+48" A.F.F, TO TOP. U.N.D) (D HP RATED DISCONNECT (+60"O.C. A.F.F, U.N.D) NEMA 3R FOR EXTERIOR AND 'NEMA 1 FOR INTERIOR. PANELBOARD (+60" A.F.F O.0 OF PNL, U.N.D) PHASE INDICATES CIRCUIT LINE NEUTRAL eft INDICATES INDICATES HOMERUN LINE ISOLATED GND. " -CIRCUIT NUMBER OFUSE SIZE --iI WIRE' IN FREE AIR SUPPORTED FRAME SIZE TO BLDG. STRUCTURE NUMBER OF POLES AVAILf §LE FAULT CURRENT AFC 110`7•Olt34.ii COPYRIGHT O 2019 BY TMW CONSULTING ENGINEERS. ALL IDEAS, DESIGNS, ARRANGEMENTS, AND PLANS REPRESENTED BY THESE DRAWINGS ARE OWNED BY, AND THE PROPERTY OF TMW CONSULTING ENGINEERS AND WERE CREATED, EVOLVED, AND DEVELOPED FOR USE ON, AND IN CONNECTION ONLY WITH THIS SPECIFIC PROJECT. NONE OF SUCH IDEAS, DESIGNS, ARRANGEMENTS, OR PLANS SHALL BE USED BY, OR DISCLOSED TO ANY PERSON, FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER WITHOUT PRIOR WRITTEN PERMISSION FROM 1MW CONSULTING ENGINEERS. Fi Z a) 14 0�UMr Cn _> Z °' O O� L" U o OO H I W F., - C7 M C) N a A S14 ELT E * I 1 OF 1 SHEET 1 HVAC GENERAL NOTES # I REVISION I DATE scale: 1/4" = 1'-0" 1. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS: A. 2017 FLORIDA BUILDING CODE - MECHANICAL B. NFPA 90A C. SMACNA HVAC DUCT CONSTRUCTION STANDARDS D. ANSI/ASME B31.9 - CODE FOR BUILDING SERVICE PIPING E. ANSI/ASHRAE 15 F. THE NATIONAL ELECTRIC CODE G. THE FLORIDA ENERGY EFFICIENCY CODE 2. COORDINATE INSTALLATION OF WORK WITH BUILDING STRUCTURE AND WORK OF OTHER TRADES. DRAWINGS ARE SCHEMATIC; ALL PIPING AND DUCTWORK OFFSETS ARE NOT NECESSARILY SHOWN. 3. PIPING A. CONDENSATE DRAIN PIPING SHALL BE ASTM B88 TYPE L COPPER WITH BRAZED JOINTS. B. REFRIGERANT PIPING SHALL BE ASTM B280 TYPE ACR COPPER WITH BRAZED JOINTS. C. INSTALL REFRIGERANT PIPING SPECIALTIES IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. D. PROVIDE HANGARS AND SUPPORTS IN ACCORDANCE WITH ASME B31.5 AND MSS SP- 69. E. CHARGE AND PURGE ALL REFRIGERANT SYSTEMS IN ACCORDANCE WITH ASHRAE 15. F. SEAL ALL PENETRATIONS OF FIRE RATED ASSEMBLIES WITH A UL APPROVED SEALANT. INSTALLATION SHALL MAINTAIN RATING OF ASSEMBLY. G. SLEEVE ALL PIPING PENETRATIONS THROUGH WALL WITH SCHEDULE 10 GALVANIZED PIPE SLEEVES. SEAL PENETRATION WITH FLEXIBLE SEALANT. H. INSULATE CONDENSATE DRAIN AND REFRIGERANT SUCTION PIPING WITH 3/4" ARMAFLEX 2000 INSULATION. FINISH WITH MANUFACTURER'S APPROVED WEATHER RESISTANT FINISH. 4. PROVIDE ALL HVAC EQUIPMENT CONTROLS COMPLETE. ALL WIRING IN WALLS SHALL BE INSTALLED IN GRS CONDUIT. CONTROL WIRING IN RETURN AIR PLENUMS SHALL BE UL RATED FOR THAT USE AND BE INDEPENDENTLY BUNDLED AND SUPPORTED FROM THE STRUCTURE. MOUNT ALL WALL MOUNTED THERMOSTATS OR SENSORS AT 60 INCHES ABOVE THE FINISHED FLOOR UNLESS NOTED OTHERWISE. 5. COORDINATE CUTTING AND PATCHING WITH WORK OF OTHER TRADES. RESTORE ALL FINISHES TO MATCH EXISTING. '6. PERFORM A COMPLETE TEST AND BALANCE OF ALL DEVICES IN WORK AREA. USE STANDARD FORMS OF AABC, NEEB, OR SMACNA. SUBMIT RESULTS TO ENGINEER FOR APPROVAL. 1. MAINTAIN MANUFACTURER'S REQUIRED SERVICE AND OPERATING CLEARANCE. VERIFY PRIOR TO INSTALLATION. II - 2. REFRIGERANT PIPING FROM SLAB MOUNTED CONDENSING UNIT. INSTALL PIPING ON SUPPORTS SHORTEST DISTANCE TO BUILDING. RISE TIGHT TO WALL ABOVE OFFICE SPACE. SLEEVE THRU EXTERIOR AND INSTALL OVER TO AHU. SIZE PIPING AS RECOMMENDED BY MANUFACTURER. 3. 1" CONDENSATE DRAIN FROM AIR HANDLING UNIT TO EXTERIOR SPLASH BLOCK. -10 S C� S p k I "I SPLIT SY TEM E L!IPMENT CNEDULE CONDENING UNIT CU MAN. &MODEL # N.TONS CAP STAGES SEER RILFRIG LIQ/'SUCT'` FAN F A COMP. RLA VOLT/PHASE MCA/MOCP CU-1 MINI SPLIT CU 2.0 1 15 410-A 3/8�5/8 0.93 12.9 120/240-1 17.1/20 AIR HANDLER AH MAN. &MODEL # TC (MBH) SC (MBH) TOTAL CFM E6P("W.G.) FAN HP/FLA H R KW TH (MBH) VOLT/PHASE MCA/MOCP AHU-1 MINI SPLIT AHU 22.5 - 628 1/8-0365 - - 120/240-1 17.1/20 NOTES: 1. UNITS SHALL BE DUCTLESS SPLIT SYSTEM. PROVIDE SPECIFIED .MANUFACTURER OR APPROVED EQUAL 2. PROVIDE FACTORY PROGRAMMABLE THERMOSTAT TO MATCH CAPACITY i ,I STAGES. I Y LJ L I Y J I I Y V V I Y 1 1 STAINLESS STEEL AIRCRAFT CABLE FOR HURRICANE TIEDOWN ANCHOR UNIT TO PLATFORM WITH 1 /4" DIA. BOLTS &NEOPRENE PAD (TYPICAL FOR 4) SUCTION &LIQUID REFRIGERANT LINES 4"x4"x4"x2" ANGLE � WELDED FRAME 6" SQ.x2" STEEL PLATE ANCHORED TO WALL WITH STEEL NUTS, BOLTS AND WASHERS. (TYPICAL) CONDENSING UNIT PLATFORM L_ EXTERIOR WALL OF IT ROOM AIR COOLED CONDENSING UNIT NOT TO SCALE COPYRIGHT ®2017 Y �JIMMIE FERRYMAN PE ALL DEpS, jDE51GN5 ARRANGEM NTS (AND PLANS REPRESENTED BY TNES� DRAWINGS ARE OWNED BY, AND THE PpiOPERTY OF �JIMMIE FERRYMAN A D IWERE CREATED EVOLVED. ANp DEVE O ED FOR USE ON; gm'E IONOILY WITH THIS NOVJE OFSUCH ARPoANGEMENTS, OR UEDIBY,ORY �EPoSON FIRM-0R �CCORPORATION FOR '�NY PURPOSE jWHATSOEVER WITHO T ICRIOR WRITTEN � ERMISSION FROM JIMMIE FERRYMAN PE. rr w M N wp-wo� ¢N � 0 N