HomeMy WebLinkAboutsigned and sealed calculations (2) electricaliG G.F. CONSULVUHR E[MOUNEENS, dirac. STRUCTURAL ENGINEERING • THRESHOLD & SPECIAL INSPECTION • SBCCI CERTIFIED PLAINS EXAMINERS r LICENSES_ ALABAMA, COLORADO, FLORIDA, GEORGIA, NEW MEXICO, NORTH CAROLINA, SOUTH CAROLINA. CO 9129 Structural Calculations FOR Amazon Miami DVB1 Warehouse Chiller Replacement. 7410 Commercial Circle. Ft. Pierce, Florida 34951 FLORIDA BUILDING CODE 2017, 6"' Edition Fresnel E Digitally signed by Fresnel E Hernand Hernandez Date: 2020.05.08 ez 10:53:28-04'00' Fresnel E. Hernandez P.E./S,L/P.X, PE# 46618 NOTE: This set of calculations was prepared under my direct supervision, including the results of computer software generated results, to the extent indicated on this set of calculations. 13170 SW 128TH Street, #204 Miami, FL 33186 • Phone #: 305-97 1 -GFCE(4323) . FAX: 305-971-4332 www.gfce.net E-MAIL GFCE@GFCE.NET COS IJ O LURE Il o MR]RUMM a239 0tmo PROJECTNAME: dmz�oN P b 4 PROJECT #: DATE: ENG: SHEET: OF oil r7 0 IN MEN an ol on 0 no ME z ME ME 0 ME so ME I E MEMO 4/27/2020 L`I C Hazards by Location ATC Hazards by Location Search Information Address: 7410 Commercial Cir Fort Pierce, FL 34951 Coordinates: Elevation: Tlmestamp: Hazard Type: ASCE 7-16 MRI 10-Year MRI 25-Year MRI 50-Year MRI 100-Year Risk Category I Risk Category II 27.475719,-80.4064465 16ff 2020A4-27T19:33:13.278Z Wind ASCE 7-10 87 mph MRI 10-Year 105 mph MRI 25-Year 118 mph MRI 50-Year 129 mph 145 mph ® 157 mph rec P.:.hcme debris reyior,. Risk Category III b 168 mph It the structure under eansideration Is a haallheare facility and you are also sviiLln 1 mile or the coastal mean high vrtter Ilna, you arc in a s6�d-Lorne �ehi;s reyio n. IF �,lher �a� ut�ancy, u� e. he Risk Cateyciy II hasic wind speed contours e deleimine R you aro in a ss�nd-ix:ms debris region. Risk Category IV � 179 mph You aro in a xtind-borne debris r,-;rlinn. MRI 100-Year Risk Category I Risk Category II Sebo tog Go gle t, 16 ft,_,h twt �Plerce Bk�chahee Port So. Lucte o 87 mph 105 mph 118 mph 129 mph 145 mph is 157 mph Vo. .1�P.'n a':V 1<� failJ�01t5 reyln�. Risk Category III -IV li 188 mph If the stmctura under cansidarat3al Is a healtl>^ara facility and you aro also �ahlhin t mile of the coastal main high water Ilne, you are in a wind-Inorne debris reylcn. II other occupancy, use the Ri.x Coteyary II 5asic svind spend contours Ic detomsire If you are in a ��.ind-bane rlehris region, .Map data ��2020 GcogIe,INEGI ASCE 7.05 ASCE 7-05 Wind Speed ii 137 mph `!ou are in a svind-borne deh�is reyian. The results indicated here DO NOT reflect any state or local amendments fo the values or any delineation lines made during the building code adoption process. Users should confirm any output obtained from this tool wrfh the focal Authority Having Jurisdiction before proceeding with design. Disclaimer Hazard loads are interpolated from data provided in ASCE 7 and rounded up to the nearest whole integer. Per ASCE 7, islands and coastal areas outside the last contour should use the Iasi wind speed contour of the coastal area — in some cases, this website will extrapolate past the last wind speed contour and therefore, provide a wind speed That is slighgy higher. NOTE: For queries near wind-borne debris region boundaries, the resulting determination Is sensitive to rounding which may affect whether or not it is considered to he within a wind-borne debris region. Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions. While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility or liability for its accumcy. The material presented in the report should not be used or relied upon for any specific application without competent examination and veriflcalion of Its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does not intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the standard of care required of such professionals in interpreling and applying the results of the report provided by this website. Users of the Information from This website assume all liability arising from such use. Use o(the output o1 this website does not Imply approval by the governing building code bodies responsible for building code approval and interpretation for the building site described by latitude/longitude location in the report. hltps:Uhazards.atcounciLorglftAvind?tat=27.47571981ng=-80.4064465&address=7410 Commercial Cir Fort Pierce % 2C FL 34951 1/2 CHAPTER 29 WIND LOADS ON OTHER STRUCTURES AND BUILDING APPURTENANCES-bIWFRS Height above E. posure ground level, z B D ft (m) 0-15 0-4.6 0.57 0.85 1.03 20 6.1) 0.62 0.90 1.08 25 7.6) 0.66 0.94 1.12 30 (9.1 0.70 0.98 1.16 40 12.2 0.76 1.04 1.22 50 . (15.2 0.81 1.09 1.27 60 (18) 0.85 1.13 1.31 70 (21.3 0.89 1.17 1.34 80 24.4 0.93 1.21 1.38 90 27.4 0.96 1.24 1.40 100 (30.5) 0.99 1.26 1.43 120 (36.6) L04 1.31 1.48 140 42.7 1.09 1.36 1.52 160 48.8 1.13 1.39 1.55 180 54.9) 1.17 1.43 1.58 200 61. 1.20 1.46 1.61 250 76.2) 1.28 1.53 1.68 300 (91.4 1.35 1.59 1.73 350 106.7 1.41 1.64 1.78 400 121.9 1.47 1.69 1.82 450 137.2 1.52 1.73 1.86 500 (152.4) 1.56 1.77 1.89 Notes: 1. The velocity pressure exposure coefficient Kz may be determined from the following formula: For 15ft.Sz<_zg For z<15ft. Kz = 2.01 (7Jz8)2/a Kz = 2.01 (15/zg)1 2. tx and zg are tabulated in Table 26.9.1. 3. Linear interpolation for intermediate values of height z is acceptable. 4. Exposure categories are defined in Section 26.7. 310 d CivY ap yM1t Amewan SaoelyFsgineeis gar Cwp rofPPPV per admaYsOawrl3i1050]IC6. Msar-GARATE OIEGO Pra.MeE Oy IF✓5 under se MN A6LE HareP"oEuctipn w neMwkirg pe�ma�eE vnVwu� ucenze Irom IRS !W tweResaie.0]tlE20100]:d6:]9 MOi Notes: 1. The velocity pressure exposure coefficient Kz may be determined from the following formula: For 15ft.Sz<_zg For z<15ft. Kz = 2.01 (7Jz8)2/a Kz = 2.01 (15/zg)1 2. tx and zg are tabulated in Table 26.9.1. 3. Linear interpolation for intermediate values of height z is acceptable. 4. Exposure categories are defined in Section 26.7. 310 d CivY ap yM1t Amewan SaoelyFsgineeis gar Cwp rofPPPV per admaYsOawrl3i1050]IC6. Msar-GARATE OIEGO Pra.MeE Oy IF✓5 under se MN A6LE HareP"oEuctipn w neMwkirg pe�ma�eE vnVwu� ucenze Irom IRS !W tweResaie.0]tlE20100]:d6:]9 MOi AHRI STANDARD 1310-201 Table 2. Terrain Exposure Constants Exposure Category u Zg, ft B TO 1200 C 9.5 900 D 11.5 700 6,10 Gas! -Effect Factor. The gust -effect factor, G, shall be taken as 0.85. Where conr�ined gust -effect and force coefficient factors are used, the gust -effect factor shall not be applied separately. 6.11 1velocity Pressare. The velocity pressure, 9., evaluated at height z shall be calculated using Equation 10: q. = 0.00256•K,K.,•K�•Kr V s 10 6.12 Design 1Vind Pressure jar EFRS and EAP. The design wind pressures for EFRS and EAP shall be determined in accordance with this section. The calculated design wind pressures shall be assumed to act on the full vertical and horizontal projected areas of Equipment without reduction for openings, such as air inlets and outlets, in the direction being considered. 6.12.1 Ground b-Iounled Equipment. The horizontal design wind pressure, pn, shall be calculated using Equation I1 and shall be assumed to act parallel to the wind direction: ph = 9; G•C/ Concurrent vertical uplift pressure, p„ shall be calculated using Equation 12. p„ = 0.80 'Ph 11 12 The velocity pressure, q„ shall be evaluated at the centroid height of the Equipment vertical projected area. The force coefficient, C� shall be detem�ined from Table 3. Linear interpolation shall be permitted for h/d values other tlian shown. Table 3. Force Coefficients C! Equipment Cross Section Type of Surface d/d 1 7 25 Rectangular wind normal to face All 13 IA 2.0 Rectangular wind along diagonal All 1.0 1.1 L5 Hexagonal or Octagonal All 1.0 L2 IA Round, d qz > 2.5 Moderately smooth 0.5 0.6 0.7 Rough d'/d= 0.02 0.7 0.8 0.9 Very Rough d'ld = 0.08 0.8 1.0 1.2 Round, d qZ <_ 2.5 All 0.7 0.8 1.2 6.12.2 Rooj1founled Egaipmenl. The horizontal design wind pressure, ph, shall be calculated using Equation 13: 13 The combined horizontal gust -effect and force coefficient factor, (CC,)h, shall be taken as 1.9. Where the vertical projected area of Equipment is greater than 10 % of [he vertical projected area of the Building on which [he Equipment is located, a reduction of the (GC,)h factor shall be permitted to be determined in accordance with Section 29.4.1 of ASCE/SEl 7. The vertical uplift design wind pressure, y,., shall be calculated using Equation 14: STANDARD 1310=2019 6.3.1 Risk category per IBC Table 1604.5 for the Building on which the Equipment is located. 6.3.2 Risk category per IBC Table 1604.5 for the Building(s) to which the Equipment provides an HVACR service. 6A Basic IVind Speed The basic wind speed, V, shall be equal to the value provided in Inc wind load design data or shall be determined from Figures 26.5-1 A, B, C, D, and Figures 26.5-2A, B, C, D of ASCE/SEI 7 at the Equipment location and for the risk category determined in accordance with Section 6.3. For locations identified in ASCE/SEI 7 as special wind regions, basic wind speed values shall be obtained from the authority having jurisdiction. Alternatively, the basic wind speed shall be permitted to be determined using the ASCE/SEI 7 Hazard Tool provided by tre American Society of Civil Engineers or the ATC Hazards by Location tool provided by the Applied Technology Council. The wind shall be assumed to come from any horizontal direction. 6.5 Wind Directionality Factor. The wind directionality factor, Kd, shall be determined from Table I . Table 1. Wind Directionality Factor (Kd) Equipment Mounting Location Equipment Shape Equipment Force -Resisting System(Kd) Directionality Factor Ground Square All 0.90 Ground Hexagonal All 0,95 Ground Octagonal Axis mmetric 1,00 Ground Octagonal Nonaxis mmetric 0,95 Ground Round Axis mmetric 1,00 Ground Round Nonaxis mnhetric 0,95 Building Roof All All 0,85 Where growrd mounted Equipment is composed of parts with different shapes, tare wind directionality factor used in design of Structural Elements shall be equal to the greater of the factors for each pail. 6.6 Exposure Category. The exposure category shall be equal to the value provided in the wind load design data or shall be determined in accordance with Section 26.7 of ASCE/SEI 7 at the Equipment location for each wind direction considered. 6.7 Topographic Factor. The topographic factor, K.r, shall be determined in accordance with Section 26.8 of ASCE/SEI 7 at the Equipment location for each wind direction considered. 6.8 Ground Elevation Factor. The ground elevation factor, K., shall be calculated using the Equation 7 where zg, is the ground elevation above sea level at the Equipment location: Ke = C 0.0000362•Zg, Ke shall be permitted to be taken as LO in all cases. 6.9 Velocity Pressure Exposure Coefficient. The velocity pressure exposure coefficient, K., shall be calculated using the Equations 8 and 9 where the height, z, is determined in accordance with Section 6.12. The a and zz terrain exposure constants shall be determined from Table 2. 6.9.1 For lSfl<_z5zs 6.9.2 Forz<ISR, C- 2� C°aOc� �UITUI I� [EIJU ICIEU209 Huff( 0 PROJECT NAME: PROJECT #: DATE: ENG: SHEET: OF ffIIC- (21F ( (mmoulLMI N PROJECT NAME: PROJECT#: DATE: llllll ENG: SHEET: OF CW co)[M)MUM PROJECT NAME: PROJECT#: DATE: ENG: SHEET: OF �r Low PROJECT NAME: PROJECT #: DATE: ENG: SHEET: OF N MEN In MEN 0 0 No MEN 0 NONE ME MEN MENEM 0 IS 11 MEN 0 IN 977 MO Anchor DesignerTM r Software Version 2.8.7094.0 1.Proiect Information Customer company: Customer contact name Customer e-mail: Comment: 2. Inout Data 8 Anchor Parameters General Design melhod:ACI 318-14 Units: Imperial units Anchor Information: Anchor type: Bonded anchor Material: F1554 Grade 36 Diameter (Inch): 0,500 Effective Embedment depth, her (Inch): 4.000 Code report: ICC-ES ESR-2508 Anchor category: - Anchor ductility: Yes hn (inch): 6,50 GB (inch): 8.76 Cmm (inch): 1.75 S,,,„, (Inch): 3.00 Recommended Anchor Anchor Name: SET-XP®-SET-XP w! 1!2"G F1554 Gr. 38 Code Report: ICC-ES ESR-2508 1i Lim , 6f 1 Company: Date: 4/2712020 Engineer: Page: 1/6 Project: Address: Phone: E-mail: Project description: Location: Fastening description: Base Material Concrete: Normal -weight Concrete thickness, h (inch): 6,50 Slate: Cracked Compressive strength, PB (psi): 2500 Wo,v: 1.0 Reinforcement condition: A tension, A shear Supplemental reinforcement: Not applicable Reinforcement provided at comers: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Hole condition: Dry concrete Inspection: Continuous Temperature range, Short/Long: 110175BF Ignore Edo requirement: Not applicable Build-up grout pad: No Input data and results must he checked for agreement vnth the existing Grcumstances, the standards and guidelines must be checked for plausibility. s�mnsen Strong -Tie ,umpari� Inc. 595fi W Las Positas Boulevard Pleasanton, CA 945a8 Phone: 925.560.9000 Fax: 925.847.3a71 www.sUongde.com Anchor DesignerTM Software Version 2.8.7094.0 Load and Geometry Load factor source: Act 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustalned tension: No Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: N�. (Ibj: 1040 Via. jibj: 0 Vun pbj:-985 <Figure U x Z Company: Date: 4I2712020 Engineer: Page: 216 Project: Address: Phone: E-mail: u Input data and results must be checked far agreement wiN the existing Urcumstances, the standards and guidelines must be checked for plausibility. S�mps:;n :�t�enr..-I'_ rony,:ry In:;. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3877 wwur.strongtie.com E7Ir/ Anchor DesignerTM Software Version 2.8.7094.0 <Figure 2> ,.,s— 6.00 Company: Date: 4/27/2020 Engineer: Page: 3/6 Project: Address: Phone: E-mail: Input data and results must be checked for agreement with the existing Grcumstances, Neslandards and guidelines must be checked (or plausihlliry. 5 n,ps n Slmnr, Tie :'.onil�ar:y 1��::. 5956 W Las Positas 9outevard Pleasanton, CA 94568 Phone: 925.560.9060 Fax: 925.847.3677 www.sUongtie.com Eill'1 Anchor DesignerTM r r , Software Version 2.8.7094.0 w Company: Date: 4/27/2020 Engineer: Page: 4/6 Project: Address: Phone: E-mail: 3. Resultina Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, NUM (lb) Vuar (lb) Way (lb) V(Vu,.)'+(Vu,y)' (lb) 1 1040.0 0.0 -985.0 985.0 0.0 -985.0 985.0 Maximum cenaele compression skain (%o): 0.00 Maximum concrete compression stress (psi): 0 Resultant tension force (lb): 1040 Resultant compression force (lb): 0 Eccentricity of resultant tension forces In x-axis, e'Na (inch): 0.00 Eccentricity of resultant tension forces In y-axis, e'ey (Inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'vx (inch): 0,00 Eccentricity of resultant shear forces in y-axis, e'vy (inch): 0.00 4. Steel Strength of Anchor in Tension (Sec. 17.4.11 N,a (lb) 4 pNsa (Ib) 8235 0.75 6176 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2) Nb = koMfIcher" (Eq. 17.4.2.2a) ke Aa PC (psi) hat (In) Nb (lb) 17.0 1.00 2500 4,000 6800 pNab = 4 Ottcl ANra) P.N %,N P.NNb (Sec. 17.3.1 & Eq. 17.4.2.1 a) ANc (in2) ANw (in2) camo (in) v'aaN WCN 'Pra,N Nb (lb) 0 QNo (lb) 144,00 144.00 6.00 1,000 1,00 1.000 6800 0.75 5100 6. Adhesive Strength of Anchor in Tension ISec. 17.4.5 na, = rka.fmrc+armKaaz n,o (Psi) C.nao-rerm War rta, (Psi) 984 1,00 1.00 984 Nos = Aar xdaher(Eq. 17.4.5.2) Aa r (psi) da(in) hot (in) Nba(lb) 1.00 984 0,50 4,000 6183 4Na=0(A ANa ma/ Awl �%d xaWaN.Nb, (Sec. (fn2) AN,o (in2) cNa (in) 17.3.1&Eq, 17.4.5.1a) cam„ (in) v4 x, 'Na,N. 186.15 201.82 7,10 6,00 0.963 1.000 6183 0,65 3534 Input data and results must be checked for agreement with the existing circumstances, the slandartls and gultlelines must be checked for plausibility. Simpsarr Stmny-7iz Coi�pzny Inr.. 5956 W. Las Posilas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.sUongtie.com Anchor Designer TM Software Version 2.8.7094.0 Company: 1 Dale: 1412712020 Engineer: Page: 6/6 Project: Address: Phone: E-mall: 84 . 17.5.11 Vsa (lb) ,jp a„ q OWo Oysa (lb) 4940 1.0 0,65 3211 9 Concrete Breakout Strength of Anchor in Shear ISec 17.5.21 Shear perpendicular to edge In y-direction: Vsr = minj7(1./d,)03�d,J.,Jrtcar'4; s.>aJr<ca,r°1 la (in) da (in) da (Eq. 17.5.2.2a ro (psi) & Eq. 17.5.2.2b) cat (in) Vey (lb) 4.00 0,500 1.00 2500 6,00 6613 ¢V wy =d (Avo/Av)P a.v'PavT.vV°r (Sec. 17.3.1 & Eq. 17.5.2.1 a) A� (In') Avo(In2) V4gV KV %V Ver(Ib) 4 4Vscr(lb) 117,00 162.00 1,000 1.000 1,177 5513 0,75 3514 10 Concrete Pryout Strength of Anchor in Shear ISec 17 5 31 QVop = 0minjk^; kcpNm( = pminjkop(ANa/ANao)W.&a V'op,NaNea; kcp(Ara/AN) .N'Tew V'opNNnj (Sec. 17.3.1 & Eq. 17.5.3.1a) kcp ANa (in') ANa° (inr) W4 Na V4pNa Me (lb) Na (Ib) 2.0 186,15 201.82 0,953 1,000 6183 5437 Ara (inp) ANw (in') V'aN V'ov �p,N Ne (Ib) Nm (Ib) 0 dV�p (Ib) 144.00 144.00 1.000 1.000 1.000 6800 6800 0.70 7612 11. Results Interaction of Tensile and Shear Forces ISec. 17.6a Tension Factored Load, N.a (Ib) Design Strength, eNn (Ib) Ratio Status Steel 1040 6176 0,17 Pass Concrete breakout 1040 5100 0.20 Pass Shear Factored Load, Vpo (Ib) Design Strength, eVp (lb) Ratio Status Steal 985 3211 0.31 Pass (Governs) T Concrete breakout y- 985 3514 0.28 Pass Interaction check Nna/gNp Vs/gVn Combined Ratio Permissible Status Sec. 17.6..2 0.00 0.31 30.7 % 1.0 Pass SET-XP wl 112"0 F7554 Gr. 36 with hef = 4.000 inch meets the selected design criteria. Input data and results must be checked ror agreement with the exis8ng urwmslances, the standards and guidelines must be checked far plausihiliry. � ::n Strang-7ia r;empzn� Inc. 5956 W. las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.a47.3871 wxN.sVongtie.com Anchor DesignerTM Software Version 2.8.7094.0 m Company: Date: 4/27/2020 Engineer: Page: 616 Project: Address: Phone: E-mail: 12. Warninos - When cracked concrete is selected, concrete compressive strength used in concrete breakout strength in tension, adhesive strength In tension and concrete pryout strength in shear for SET-XP adhesive anchor is limited to 21500 psi per ICC-ES ESR-2508 Section 5.3. - This temperature range is currently outside the scope of ACI 318-141-11 and ACI 355.4, Designer must exercise judgement to determine If this design is suitable. - Minimum spacing and edge distance requirement of 6da per ACI 318 Sections 17.7.1 and 17.7.2 for torqued cast -in -place anchor Is waived per designer option. - Designer must exercise own judgement to determine if this design is suitable. - Refer to manufaclurers product literature for hole cleaning and installation instructions. Input data antl results must be checked for agreement with fhe existing dreemslances, the standards and guidelines must be checked for plausibility. S�mFscn Strorc-Te Gnmpar/Inc. 5986 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3877 www.sVon9lie.com ®' Anchor DesignerTm ft Software - Version 2.8.7094.0 1.Prolecf Information Customer company: Customer contact name Customer e-mail: Comment: 2. Inout Data &Anchor Parameters General Design method:ACI 318-14 Units: Imperial units Anchor Information: Anchor type: Bonded anchor Material: A193 Grade B6 (410SS) Diameter (inch): 0.500 Effective Embedment depth, her (Inch): 4.000 Code report: ICC-ES ESR-2508 Anchor category: - Anchor ductility: Yes h, (inch): 6.50 c&e (inch): 8,76 C� (Inch): 1,75 S„„„ (Inch): 3.00 Company: Dale: 4/27/2020 Engineer: Page: 1/6 Project: Address: Phone: E-mail: Recommended Anchor Anchor Name: SET-XP®-SET-XP w/ 1/2"0 A193 Gr. BB (410SS) Code Report: ICC-ES ESR-2508 I� W if f a?�FEiII Project description: Location: Fastening description: Base Material Concrete: Normal -weight Concrete thickness, h (inch): 6,50 Slate: Cracked Compressive strength, fc (psi): 2500 We,v: 1.0 Reinforcement condition: A tension, A shear Supplemental reinforcement: Not applicable Reinforcement provided at comers: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Hoia condition: Dry concrete Inspection: Continuous Temperature range, Shorf/Long: 110l75°F Ignore Edo requirement: Not applicable Build-up grout pad: No Input data antl results must be checked rar agreement with the existing Urcumstances, the standards and guldellnes must he checked for plausibility. 5'-mpsan Sl�eny-Tie faml�eny Inc. 5956 W Las Posilas eaulevald Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 wvrw.sUongge.com Anchor Designer TM Software Version 2.8.7094.0 a Load and Geemelry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: No Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: N�, (IbJ: 1040 Wax jib]: 0 Vuay Jib]: -985 <Figwe 1> X Company: Dale: 4/27/2020 Engineer: Ii Page: 216 Project: Address: Phone: E-mall: �99516 Input data and results must be checked for agreement with the existing Urwmstances, the standartls and guidelines must be checked for plausibility. S.r.:pscn Slmnc-rt, ro,++p;.ny b+::. 5958 W. Las Positas 0oulevard Pleasanton, CA 94598 Phone: 925.560.9000 Fax: 925.847.3871 vNrw.sVongtie.com F711'i Anchor DesignerTM Software Version 2.8.7094.0 «figure 2> 6.00 Company: Dale: 127/2020 Engineer: Page: 3!6 Project: Address: Phone: E-mail: Input data and results must be checked for agreement with the existing cirwmstances, the standartls and guidelines must be checked for plausibllily. S:mrysnn Strang -Tie ConlpGm) h.�. 595fi W. La5 Posilas Boulevard Pleasanton, CA 94588 Phane: 925.56o.9a00 Fax: 925.847.3877 wunv.SVongue.cam Anchor DesignerTM 4-/ I i TO Software Version 2,8.7094.0 Company: I Date: 4/27/2020 Engineer: I Page: 1416 Project: Address: Phone: E-mail: 3. Resulting Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, We (lb) Vuaa (lb) V„sy (lb) d(Vua.)'4(Vuv)' (lb) 1 1040.0 0.0 -985,0 985.0 Sum 1040,0 0.0 -985.0 985.0 Maximum cenuete compression sUain (%o): 0.00 Maximum concrete compression stress (psi): 0 Resultant tension force (lb): 1040 Resultant compression force (lb): 0 Eccentricity of resultant tension forces In x-axis, e'm (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'ry (inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'w (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'W (Inch): 0,00 4. Steel Strength of Anchor in Tension ISec. 17.4.11 Nu (lb) d ¢Nsa (lb) 15620 0.75 11715 5. Concrete Breakout Strength of Anchor In Tension ISec. 17.4.21 Nn = "VPrher'(Eq, 17.4.2.2a) ka ) rc (psi) haf (in) Nb (lb) 17.0 1,00 2500 4.000 6800 gNrb = 4 (Ant/AN )'Fs UV'aHYw,NNb (Sec. 17.3.1 & Eq. 17.421 a) Art (in') Arco (In') cam„, (in) w N v'ON TCC.N Nn (lb) 4 gNm (lb) 144.00 144,00 6,00 1.000 1,00 1.000 6800 0.75 5100 6. Adhesive Strength of Anchor In Tension ISec. 17.4.51 na(psi) &064arm K.t mcr(psi) Nba = Aarr.rrdah.r(Eq. 17.4.5.2) 1.00 984 0.50 4,000 6183 QNa = 4 (ANa/ANao)W..Na'Yn.Naka (Sec. 17.11 & Eq. 17.4.5.1a) ANa (in') ANao (in2) cNa (in) camm (in) v'sa Na 44, Na Nba (lb) 0 ¢Na (lb) 186,15 201,82 7.10 6,00 0,953 1.000 6183 0,65 3534 Input data and results must be checked for agreement with Ne existing circumstances, the standards and guidelines must be checked far plausibility. Simps ;n Su,.n-Tia Co.npary in::. 5956 W. Las Positas Boulevard Pleasanton, CA 9458a Phone: 925.580.9000 Fax: 925.847.387[ vrww.suongtie.com E71rl Anchor Designer TM t Software Version 2.8.7094,0 Company: Date: 4/27/2020 Engineer: Page: 516 Project: Address: Phone: E-mail: 9. Steel Strength of Anchor in Shear lSec. 1715.11 V, (lb) drat d 09mi0Vsa (lb) 9370 1,0 0,65 6091 9 Concrete Breakout Strength of Anchor in Shear lSec. 17.5.21 Shear perpendicular to edge In y-direction: U°y=mini7(la/da)01Jdaa.Jl'acar'0; 9.iaJfacar1d) (Eq. 17.5.2.2a & Eq. 17.5.2,2b) /a (in) da (In) da fc (psi) cal (in) Vcy (lb) 4,00 0,500 1,00 2500 6.00 5513 dVmy =d (Avc/AvwMdvP4vP.vV°y (Sec. 17.3.1 & Eq. 17.5.2.1a) Avc(W) Avw ins) T4V TFv %..v Vey(lb) d dVauy(lb) 117,00 162,00 1,000 1,000 1.177 5513 0,75 3514 10 Concrete Prvout Strength of Anchor in Shear (Sec. 17.5.31 dl ep = 0min)kgNa; kcpNani = 0 minikay(ANa/A,v,o) VjN.Na T6NaNea: kw(Axa/Arraa) T4 m'P.NV .NMJ (Sec. 17.3.1 & Eq. 17.5.31a) kcp ANa(W) ANao(In2) %axa V<p.Na Nna(lb) Na (lb) 2.0 186.15 201,82 0,953 1,000 6183 5437 ANa (ins) ANap (Ins) � x Yc,N Y'ap.N Ne (Ib) Nm (Ib) d dVw (Ib) 144.00 144.00 7.000 1.000 1.000 6800 6800 0.70 7612 11. Results Interaction of Tensile and Shear Forces ISec. 17.6.1 Tension Factored Load, Nua (lb) Design Strength, eNn (lb) Ratio Status Steel 1040 11715 0.09 Pass Concrete breakout 1040 5100 0.20 Pass Shear Factored Load, Vva (Ib) Design Strength, oVn (lb) Ratio Status Steel 985 609t 0.16 Pass T Concrete breakout y- 985 3514 0,28 Pass (Governs) Pryout 985 7612 0.13 Pass Interaction check N„a/dNn Vpa/dV� Combined Ratio Permissible Slalus Sec. 17.6..1 0.29 0.00 29.4% 1.0 Pass SET-XP wl 1l2"0 A193 Or. B6 (410SS) with het = 4.000 Inch meets the selected design criteria. Input tleta antl results must be checked for agreement with Ne existing cirwmstances, the standards and guidelines must he rhecked !or plausihility. Simpson St:enc-Tie Campany Inc. 5956 W Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 wvrN.stron9lie.com �711'i Anchor DesignerM t Software Version 2.8,7094.0 Company: Date: 4/27/2020 Engineer: Page: 616 Project: Address: Phone: E-mail: 12. Warnings - when cracked concrete Is selected, concrete compressive strength used in concrete breakout strength in tension, adhesive strength In tension and concrete pryout strength in shear for SET-XP adhesive anchor is limited to 2,500 psi per ICC-ES ESR-2508 Section 5.3, - This temperature range is currently outside the scope of ACI 318-14/-11 and ACI 355.4. Designer must exercise judgement to determine if this design is suitable. - Minimum spacing and edge distance requirement of 6da per ACI 318 Sections 17.7.1 and 17.7.2 for torqued cast -in -place anchor is waived per designer option. - Designer must exercise own judgement to determine if this design is suitable. - Refer to manufacturers product literature for hole cleaning and installation Instructions. Input data and results must he checked for agreement with the existing circumstances, the stantlards and guidelines must he checked for plausihiliry. 5ir�;psrn Streng-P,e C�mPany Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 wvnv.sVongGe.com ti711'l Anchor DesignerTM L.,sYr.t Software Version 2.8.7094.0 1.Prolect Information Customer company: Customer contact name Customer e-mail: Comment: 2. Inout Data &Anchor Parameters General Design melhod:ACI 318-14 Units: Imperial units Anchor Information: Anchor type: Cast -in -place Material: F1554 Grade 36 Diameter (Inch): 0.625 Effective Embedment depth, h<f (inch): 8.000 Anchor category: - Anchor ductility: Yes hm (inch): 9,38 Cm (Inch): 0,81 Smm (Inch): 2.50 Recommended Anchor Anchor Name: J- or L-Boll - 5/8"(d J- or L-Boll, F1554 Gr. 36 Company: Dale: 4127/2020 Engineer. Page: 116 Project: Address: Phone: E-mail: Project description: Location: Fastening description: Base Material Concrete: Normal -weight Concrete thickness, h (inch): 16.00 State: Cracked Compressive strength, fc (psi): 2500 v: 1.0 Reinforcement condition: B tension, B shear Supplemental reinforcement: Not applicable Reinforcement provided at comers: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear. No Ignore 6do requirement: Yes Build-up grout pad: No Input data and results must be checked for agreement wiN the exisgng circumstances, the standards and guWellnes must be checked for plausibility. o � on Sb�,ng-Tie Comyan, I.c. 595fi W. Las Positas Boulevartl Pleasanton, CA 945fle Phone: 925.560.9000 Fax: 925.847.3871 www.slrongtie.wm F�II'l Anchor DesignerTM Software Version 2.8.7094.0 Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: Not applicable Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: N�. (Ibj: 1040 Vu.. [Ibj: 958 tuw (lb]: 0 <Figure U Company: Date: 4/27/2020 Engineer: Page: 2/6 Project: Address: Phone: E-mail: 10401b 0Ib Input dale and results must be checked for agreement with the existing circumstances, the slantlards and guldellnes must be checked for plausibility. Simp�:rn �Imne,-Tie Compenj Inc. 5e56 W. Las Positas Boulevard Pleasanton, CA a45a8 Phone: 925.560.ed00 Fax: 925.847.3871 w,vw.svongde.com Anchor DesignerTM Software Version 2.6.7094.0 0 <Figure 2> Company: Dale: 4I2712020 Engineer: I Page: 316 Project: Address: Phone: E-mail: C•:J Input data and results must be checked for agreement with the existing cirwmstances, the stantlards antl guidelines must be checketl for plausibility. .. � .v. 5956 W Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.Sfie.9699 Fax: 925.847.3871 wwur.sVongtie.com ®' Anchor DesignerTM 4 r Software Version 2.8.7094.0 Company: Date: 4/27/2020 Engineer: Page: 4/6 Project: Address: Phone: E-mail: 3. Resulting Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, Nva (lb) Vuaw (lb) Way (lb) \I(Vuax)'+(V:,ay)' (Ib) 1 1040.0 958.0 0.0 958.0 Sum 1040.0 958.0 0.0 958,0 Maximum wncrete compression skein (%a): 0.00 Maximum concrete compression stress (psi): 0 Resultant tension force (lb): 1040 Resultant compression force (lb): 0 Eccentricity of resultant tension forces in x-axis, e'ra (inch): 0,00 Eccentricity of resultant tension forces in y-axis, e'Ny (Inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'va (Inch): 0,00 Eccentricity of resultant shear forces in y-axis, e4* (Inch): 0.00 4. Steel Strength of Anchor in Tension (Sec. 17.4.11 Nsa (lb) 4 QNsa (lb) 13100 0.75 9825 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2) Na = kJ dP<her's (Eq. 17.4.2.2a) ka Aa rc(psi) har(in) Nn(lb) 24.0 1.00 2500 5,333 14780 QNxe = 4(Ati</Arxv)Y'ea.ry Y,xT� xNe (Sec. 17.3.1 & Eq. 17.4.2.1a) Arvv (in') Axw (in'j ca,M. (in) Y'aary ry a.ry Ne (Ib) 4 QNm (Ib) 256,00 256,00 8,00 1,000 1.00 1.000 14780 0,70 10346 6. Pullout Strength of Anchor in Tension ISec. 17.4.3) fNva = fY=vNv = fY�,v0.9Psend. (Sec. 17.3.1, Eq. 17.4.3.1 & 17.4.3.5) YfOv ra (psi) da (in) en=3da (in) 4 pNvn (lb) 1'0 2500 0,63 1,88 0.70 1846 Input data and results must be checked for agreement with the existing cirwmstances, the standards and guidelines must be checked for plausibility. S�mpsan Stranc-Tie Company I:�c. 5956 W Las Positas Boulevard Pleasanton, CA 9456a Phone: 925.560.9000 Fax: 925.647.3871 ww✓,.sVongtie,com 1+11t'I Anchor DesignerTM Software Version 2.8.7094.0 8. Steel Strength of Anchor in Shear (Sec. 17.5.1) Vsa (lb) dvra,e d Ogro ^a (lb) 7865 1.0 0.65 5112 Company: Date: 4/27/2020 Engineer: Page: 516 Project: Address: Phone: E-mail: 9. Concrete Breakout Strength of Anchor in Shear [Sec. 17.5 21 Shear perpendicular to edge in x-direction: Vex = minj7(la/da)01Jd,.1,Jr<c,P'; 9.1,Jr c„'-') le (in) da (in) .ta (Eq. 17.5.2.2a Pa (psi) & Eq. 17.5.2,2b) c„ (In) Vex (lb) 5.00 0,625 1.00 2500 8,00 9490 01/ ax=d(Ava/Avw)V'd.v' ,v%vVnx (Sec. 17.3.1 $ Eq. 17.5.2.1a) Avg (In2) Avm (in2) P ,V W4,v ',v Vnx (lb) d dV ax (lb) 240,00 288.00 0.900 1.000 1.000 9490 0.70 4982 Shear parallel to edge in x-direction: Ver = min(7(la/da)0.24da1 Jflcca,l-s; 9Mf4cn' 51 (Eq, 17.5.2.2a & Eq. 17.5.2.2b) /e (In) da (In) As rc (psi) Ca, (in) Var (lb) 5,00 0,625 1.00 2500 8.00 9490 dVmx Avg (in2) =d (2)(Av,/Avoa)Y'6v Y,vY'n.vVer (Sec. Avm (in2) '' 'v 17.3.1, 17.5.2.1 'P.v (c) & Eq. rn.v 17.5.2.1a) Ver (Ib) d ry x (Ib) 192,00 288,00 1,000 1.000 1.000 9490 0,70 8857 10. Concrete Pryout Strength of Anchor In Shear lSec. 17.5 31 dU=QkcaN<a=dk�(ANc/Ane,)Wa,N'P xY�,,,NNo (Sec. 17.3.1$Eq. 17.5.3.1a) kcc ANC (in2) Ar.eo (in2) Y'ae,N 'V a Y4o,N Ne (lb) d dVw (lb) 2.0 256.00 256.00 1,000 1,000 1,000 14780 0,70 20692 11. Results Interaction of Tensile and Shear Forces Sec. 17.6a Tension Factored Load, Nua (lb) Design Strength, eNn (Ib) Ratio Status Concrete breakout 1040 Pullout 1040 10346 0.10 Pass 1846 0.56 Pass (Governs) Shear FactorsdDesign Strength, aV° (lb) Ratio Status Steel 958 5112 0.19 Pass T Concrete breakout x+ 958 4982 0.19 Pass (Governs) ii Concrete breakout y+ 958 8857 0411 Pass (Governs) Pryout 958 20692 0,05 Pass Interaction check Naa/dN° Vua/dU Combined Ratio Permissible Status Sec. 17.6..1 0.56 0.00 56.3% 1.0 Pass 518110 J- or L-Bolt, F1554 Gr. 36 with hef = 8,000 inch meets the selected design criteria. Input date and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson suer; iie C_mNzm; Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925,847,3871 vnnv.sUanglie.com Anchor DesignerTM t r Software Version 2.8.7094.0 Company: Date: 4/27/2020 Engineer: Page: 6!6 Project: Address: Phone: E-mail: 12. Warnfnos - Minimum spacing and edge distance requirement of 6da per Act 318 Sections 17,71 and 17.7,2 for torqued cast -in -place anchor is waived per designer option. Designer must exercise own jutlgemenl to determine if this design is suitable. Input data and results must be checked (or agreement wiN Ne existing Grwmslances, Ne standards and guidelines must be checked for plausibility. .�inip::ori 3tren,-T�, +;,-.nyzn� Inc 5958 W. las Positas 9oulevard Pleasanton, CA 9459a Phone: 925.560.9000 Fax: 925.a47.3a77 www.strongtie.com Anchor DesignerTM Software Version 2.8.7094.2 1.Praiect Information Customer company: Customer contact name Customer e-mail: Comment: 2. Inout Data R Anchor Parameters General Design melhod:ACI 318-14 Units: Imperial units Anchor Information: Anchor type: Bonded anchor Material: A193 Grade B6 (410SS) Diameter (inch): 0.500 Effective Embedment depth, her (Inch): 4,000 Code report: [CC -ES ESR-2508 Anchor category: - Anchor ductility: Yes to (inch): 6.50 c, (Inch): 7,82 Cm (Inch): 1,75 S„ a, (inch): 3.00 Company: Date: 4/27/2020 Engineer: Page: 1/5 Project: Address: Phone: E-mail: Recommended Anchor Anchor Name: SET-XP®-SET-XP w/ 1/2"Pi A793 Gr. BO (410SS) Code Report: IMES ESR-2508 Project description: Location: Fastening description: Base Material Concrete: Normal -weight Concrete thickness, h (inch): 6.50 State: Cracked Compressive strength, fe (psi): 2500 Wav: 1.0 Reinforcement condition: B tension, B shear Supplemental reinforcement: Not applicable Reinforcement provided at comers: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Hole condition: Dry concrete Inspection: Continuous Temperature range, Short/Long: 1501110°F Ignore Edo requirement: Not applicable Build-up grout pad: No Input data and resuns must be checked for agreement vriN the existing dreumstances, the standards and guidelines must be checketl far plausihility. ,. ,,,. 5956 W Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.Sfi0.9000 Fax: 925.847.3871 wurw.strongtie.com ,IIVIY,VN a M - OM � r• Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: No Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: N�, [IbJ: 1220 Vu,. (Ibj: 1560 Vuay [Ibj: 0 <Figure 1> I56011 Company: Dale: 4/27/2020 Engineer: Page: 2/5 Project: Address: Phone: E-mail: oro Input data and results must be checked for agreement with tha epsting Urcumsfances, the stantlards and guidelines must be checked for plausibility. S�npson Sl�eng-Tie company In:; 5956 W. Las Posilas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.647.3a77 wanv.sVonglie.com Anchor DesignerTM t t Software Version 2.8.7094.2 <Figure 2> Company: Date: 4/27/2020 Engineer: Page: 3/5 Project: Address: Phone: E-mail: Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. S;mp,en Stror.�-Tie +;oniNeny Inc. 5956 W Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3877 www.sVon9lie.mm Anchor DesignerTM tl 1 t Software Version 2.8.7094.2 Company: Date: 4/27/2020 Engineer: Page: If 416 Project: Address: Phone: E-mail: 3. Resulting Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, Nua (Ib) War (lb) Way (lb) d(Vuax)'+(Vuay)' (lb) 1 1220.0 1560.0 0.0 1560.0 Sum t22o.a Maximum cencrele compression strain (%b): 0.00 Maximum concrete compression stress (psi): 0 Resultant tension force (Ib): 1220 Resultant compression force (lb): 0 Eccentricity of resultant tension forces in x-axis, e're (Inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'W (Inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'vx (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'uy (Inch): 0,00 4. Steel Strength of Anchor in Tension ISec 17.4.11 Naa (Ib) 4 QNsa (Ib) 15620 0,75 11715 1560.0 5 Concrete Breakout Strength of Anchor in Tension ISec. 17.4.21 Nb = kc4vfchet' s (Eq, 17.4.2.2a) kb b ra (psi) hat (in) Nb (lb) 17.0 1.00 2500 4.000 6800 QNae = 4 (Ark/Arkb) 'Tod a WC. N PCA. NNb (Sec. 17.3.1 8 Eq. 17.4.2.1 a) Ark (in') ANab (in') ca,n (in) y'e4N vjC N �a N Nb (Ib) 4 QNm (lb) 144,00 144.00 - 1.000 1,00 1.000 6800 0.65 4420 6. Adhesive Strength of Anchor in Tension ISec. 17.4.5 nc�= n«d:nan,�,mK:az ntr/(psi) 1.00 � K'00 510 i) 510 1.00 1.00 510 Nba = Aar yrdah,r(Eq. 17.4.5.2) A a r„ (psi) do (In) hat (in) Nba (lb) 1,00 510 0,50 4.000 3204 QNa = Q (AN,/ANao) y'.e,Na'Yw.NaNba (Sec. 17,11 8 Eq. 17.4.5.1 a) ANa (in') AN.o (in') c.v. (in) ca,., (in) y'ea,Na Y4p N. Nba (Ib) 4 QNa (Ib) 104.55 104,55 6,11 - 1.000 1.000 3204 0.65 2083 Input data antl results must be checked ror agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Situps-�n S��enc-Tie ::anuan•; I"c. 595fi w. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3877 vyww.stronBlle.com 6 0 1 Anchor DesignerTM MAX) .b.= Software Version 2.8.7094.2 Company: Date: 4/27/2020 Engineer: Page: 1515 Project: Address: Phone: E-mail: 8. Steel Strength V (lb) of Anchor boravr in Shear 4 (Sec 17 5 11 49�4ysa (to) 9370 1.0 0,65 6091 10 Concrete Prvout Strength of Anchor in Shear lSec 17 5 31 4Vn = 4minIkr,,Na; krpNml = 4minikep(ANa/ANao)Tb,,,va44p,NaNba; kw(Am1ANaa)VJ .v'Yc,NWgi NNbj (Sec. 17.3.1 & Eq. 17.5.3.1 a) kw ANa (Inv) ANao (Inv) T wa 'P..Na Nba (lb) Na (lb) 2.0 104,55 104,55 1,000 1.000 3204 3204 Arx (Inv) ANoa (inv) 5 ayN '/psv %'�p,N Nb (Ib) Nw (Ib) 4 pVp (Ib) 144,00 144,00 1.000 1.000 1,000 6800 6800 0.70 4486 11. Results araction of Tensile and Shear Forces (Sec 17 6 1 Tension Factored Load, Nua (Ib) Design Strength, eN„ (Ib) Ratio Status Steel 1220 11715 0.10 Pass Concrete breakout 1220 4420 0.28 Pass Adhesive 1220 2083 0,59 Pass (Governs) Shear Factored Load, V„a (lb) Design Strength, eVa (Ib) Ratio Status Steel 1560 6091 0,26 Pass Pryout 156 0 0.35 Pass (Governs) Interaction check Naa/QN„ U ✓4Va Combined Ratio Permissible Slalus Sec. 17.6..1 0.59 0.00 58.6% 1.0 Pass SET-XP wl 1I2"0 A193 Gr. BB (41055) with hef = 4.000 Inch meets the selected design criteria. 72, Warnings - When cracked concrete is selected, concrete compressive strength used in concrete breakout s0engih in tension, adhesive strength in tension and concrete pryoul strength in shear for SET-XP adhesive anchor is limited to 2,500 psi per [CC -ES ESR-2508 Section 5.3. - Minimum spacing and edge distance requirement of 6da per ACI 318 Sections 17.7.1 and 17.7.2 for torqued cast -in -place anchor is waived per designer option. - Designer must exercise own judgement to determine if this design is suitable. - Refer to manufacturers product literature for hole cleaning and installation inshactions. Input dale and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. S�mpssn Strere-T.e Ca�i�panJ Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.647.3871 wurvr.strongde.com cbflam?: a.mazen lA£Pswcvral nes5n lln:t rag: CGAt,413e . .,,. -.in Duel . eo By: OuanGry.t �Llidittatl�l(t,..14 Chiller Model CGAM Unit Nominal Tonnage 130 tons Refrigeration Capacity 126.1 tons Cooling Efficiency 10.31 EER (BtuAN-h) IPLV.IP 16.55 EER (Blu/W-h) NPLV.IP 16.55 EER (BtwW-h) Elevation 0.000 it Unit Frequency 60. hertz Unit Voltage 460. volt 3 phases Refrigerant Type R410A Number of compressor 6 Number of circuits 2 Number of capacity steps 6 Agency Listing UUCUL Evaporator Application Sid cooling Fluid Temperatures Flow Rate j Evaporator Leaving 44.00 F Design Flow 301.8 gpm Freeze protection With freeze protection Evaporator Entering 53.98 F Min Flow 146.9 gpm Fouling factor 0.000100 000100 hr-sq ft-deBtu Fluid Properties Fluid Pressure Drop ' Fluid Type Water Total PD evap+strainer 21.3 ft H2O Flow switch set point Flow switch set point 60 cm/sFreeze Point 32.00 F Design Evap PD 14.8 it H2O Water connection size 4.000 in Min PD 4.87 ftH2O Unit Application High ambient Fin Material Lanced aluminum Ambient Air Temp. 95.0 F Total airflow 91332 cfm Number of Fans 10 Unit � I RLA �. LRA , Compressor Starter Across the line Incoming Power Line Conn. Type Single point Compressor A 33.00 A 215.00 A Total Power 146.8 kW Circuit Gorryp fault rated Pressor B 33.00 A 215,00 A Compressor Power 134.4 kW Power Line Conn. Type breaker -high Compressor ressor C 41.90 A 260.00 A Fan Power 12.22 kW Short Circuit Current Option High Compressor D 41.90 A 260.00 A Total Fan FLA 33.00A Short Circuit Current Rating 65000A Compressor 33.00A 215.00A Single Point Power MCA 261 A Compressor F 33.00 A 215.00 A Single Point Power MOP 300 A - 1 111sie I h iu,i-nett Ii _. Dimensions Weights Refrigerant Charge Oil Charge Length 202 in Operating Weight 7900 lb Circuit 1 112.0 lb 5.81 gal Width 89 in Shipping Weight 7753 lb Circuit 2 112.0 lb 5.81 gal Height 92 in 4441ghted -I Sound PowerSound Pressure' Unit Sound Package o.--_____ i 100% 95 dBA 67 dBA Super quiet Note: In Accordance with AHRI 370 'Note: at 30 feet in free field Standard Warranty 2020-04.2316:07:05Z Page 1 of 17 lrb NaPe'�maxe�lAEP BWctural Ues gn Ur.t Tag:CG3fA-130 a azw BV81 Prepared By: Cuantiry:l F h 'v K F Qw wZ jo 00 w wz z0 W Q� 0 O w� a0 wW m4 ffl a OO mmm Grt F z K W 202R04-23 16:0]:062 Page 3 of 1� �S'ia�-L� ..'cb Name: ?rnJz cn l,tEP Structural Cex�gn Unit Tag: CG.11.1-130 M Amazcn OVB1 Prepared ay: ovantityi 0 0 0 O O O ZCal zozo-w-za ts.otosz aaya a a n r= Jcb Name: Amazon PAEV Suederai Oe=.,3n Una Tag: CGAPA-130 Amazcn ovsl Praparea Sr. CUanutr. I C 2020-04-23 100�:062 vase 6 d 1i J TRMjE ob N-m. irn A a ltEP GwcWral Qestyn Unit Tay:CGAf,t-13G m Nsn DAi Prepared By: Oudnmy: I MOUNTING LOCATIONSA UNR POINT LOADMIGHTS TOTALOPERATTIG SIZE MIGHT 1 2 3 4 5 6 7 8 130 1,2M 1,2]2 910 1229 WI 952 %9 A26 ],A990 AfOUNHNG MOLE DIAFffTER 3'4' CONTROL PANEL f3aL'T WL �63F TOP VIEW DIMENSIONS ARE REFERENCED FROM THE ENDAtID SIDE GF THE UNR BASE 202604-2316:0]:O6Z Paga 13 d 1] OPU}Q ,a M�dy Jrh Na e'?.mazcn;AEP SwV..ural Oergn Um T.:CGAK.134 '✓ PraFary 8Y: CuanYry:1 ao o z0 ?9 as° owo Woo w60 .o 00 no do v� �m om op Zo v y o- m f lu v� �m M d O a <n oW oa <I � 1(111(F0439 f6:OT.06Z Page to a n f 2 MTV 5 ups, 2 1/!' 1'-S'(SA (VfNHG I'-1 I/e Y-] 1/2' B 1/2' 8• 7-10'@A aPR) J' Yd ro b O - O l iji i � Mill IlLl I � � I � I I I VAO PLAN VIEW ol.l 3/4'Z1•-0• b b 1 OA IBA'G p r_--------- I?W NqA I -sun I I I 101 I I im O I I , I I 1 I I Y-11/2 I I I I I I m I (opal) l 17 I I I I I I I I I I > b I Jii e I I I I I I b I I I I I I I � I AVG(1YP.) kk y M 000 lr1 12 G i-.WI 12 G t-bl SS Y2 M1aa OPAvI SS qLW FM MTCflWttl (IYY.) 122F. a ]) = ELEVATION