HomeMy WebLinkAboutFL10626_R17_AE_2019_12_FINAL_ER_GAF_UNDERLAYMENTS_FL10626-R17
NEMO|etc.
Certificate of Authorization #32455
353 Christian Street, Unit #13
Oxford, CT 06478
(203) 262-9245
ENGINEER EVALUATE TEST CONSULT CERTIFY
EVALUATION REPORT
GAF
1Campus Drive
Parsippany, NJ 07054
(800) 766-3411
Evaluation Report 01506.04.08-R17
FL10626-R17
Date of Issuance: 04/25/2008
Revision 17: 12/13/2019
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products
described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION: GAF Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until the named product(s) changes, the referenced Quality
Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). NEMO|etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words “NEMO|etc. Evaluated” may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 11.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 12/13/2019. This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire, or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing produ cts for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO|etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project
on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically
for that purpose.
©2019 NEMO ETC, LLC
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 2 of 11
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: GAF Roof Underlayments, as produced by GAF, have demonstrated compliance with the
following sections of the Florida Building Code through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind Uplift FM 4474 2011
1507.1.1, R905.1.1 Exception Unrolling, Breaking Strength, Pliability ASTM D226 2009
1507.1.1, R905.1.1 Exception Tear Strength ASTM D4533 2015
1507.2.3 / 1507.1.1 Physical Properties ASTM D6757 2016
1507.2.4 / 1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015
1507.3.3, R905.3.3 Physical properties FRSA/TRI April 2012 (04-12) 2012
1507.11.2 Physical Properties ASTM D6164 2011
3. REFERENCES:
Entity Examination Reference Date
ERD (TST 6049) Physical Properties R3360.02.07-2-R1 03/13/2007
ERD (TST 6049) Physical Properties G12110.12.08 12/02/2008
ERD (TST 6049) FRSA/TRI April 2012 (Slippage) G34150.08.11 11/14/2011
ERD (TST 6049) ASTM D6164 G40630.01.14-2B 01/07/2014
ERD (TST 6049) ASTM D6164 G46160.09.14-3A 09/09/2014
ERD (TST 6049) ASTM D1970 GAF-SC13285.03.17-3 03/01/2017
ERD (TST 6049) ASTM D1970 GAF-SC13285.03.17-4 03/01/2017
PRI (TST 5878) Physical properties BRY-003-02-01 03/19/2002
PRI (TST 5878) ASTM D1970 GAF-026-02-01 03/26/2002
PRI (TST 5878) ASTM D1970 GAF-027-02-01 03/26/2002
PRI (TST 5878) Physical properties GAF-042-02-01 06/03/2005
PRI (TST 5878) Physical properties GAF-224-02-01 07/27/2009
PRI (TST 5878) ASTM D1970 GAF-238-02-01 03/03/2010
PRI (TST 5878) ASTM D1970 GAF-275-02-01 11/11/2010
PRI (TST 5878) Physical properties GAF-349-02-01 07/03/2012
PRI (TST 5878) Wind Uplift GAF-434-02-01 09/16/2013
PRI (TST 5878) Wind Uplift GAF-434-02-03 09/16/2013
PRI (TST 5878) Wind Uplift GAF-434-02-04 09/16/2013
PRI (TST 5878) FBC 1507.1.1 (Exception) GAF-818-02-01 12/05/2017
PRI (TST 5878) FBC 1507.1.1 (Exception) GAF-826-02-01 06/04/2018
PRI (TST 5878) FBC 1507.1.1 (Exception) GAF-847-02-01 06/04/2018
PRI (TST 5878) FBC 1507.1.1 (Exception) GAF-914-02-01 04/10/2019
PRI (TST 5878) FBC 1507.1.1 (Exception) 376T0012 07/15/2019
PRI (TST 5878) FBC 1507.1.1 (Exception) 376T0018 x 2 07/31/2019
PRI (TST 5878) ASTM D1970 376T0032 10/22/2019
UL (TST 1740) Physical properties 02NK22569 06/04/2002
UL (TST 1740) ASTM D6757 10NK11990 05/18/2011
Miami-Dade (CER 1592) HVHZ compliance 16-1216.02 02/02/2017
Miami-Dade (CER 1592) HVHZ compliance 18-0119.15 02/22/2018
ICC-ES (EVL2396) IBC/IRC compliance ESR-2053 07/01/2017
ICC-ES (EVL2396) IBC/IRC compliance ESR-2808 07/01/2017
ICC-ES (EVL2396) IBC/IRC compliance ESR-1322 01/01/2018
ICC-ES (EVL2396) IBC/IRC compliance ESR-3286 02/01/2018
UL, LLC (QUA 9625) Quality Control Service Confirmation 12/17/2018
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 3 of 11
4. PRODUCT DESCRIPTION:
Product Specification Plant(s) Description
4.1 Liberty™ SBS Self-Adhering
Base/Ply Sheet
ASTM D1970 Mt. Vernon, IN smooth-surfaced, fiberglass-reinforced, self-
adhering SBS modified bitumen roof
underlayment
4.2 StormGuard® Film Surfaced
Leak Barrier
ASTM D1970 Mt. Vernon, IN
Savannah, GA
film-surfaced, fiberglass-reinforced, self-
adhering SBS modified bitumen roof
underlayment; also used as a secondary
water barrier to seal roof decks
4.3 WeatherWatch® Mineral
Surfaced Leak Barrier
ASTM D1970 Mt. Vernon, IN
Savannah, GA
Arkadelphia, AR
mineral-surfaced, fiberglass-reinforced, self-
adhering SBS modified bitumen roof
underlayment; also used as a secondary
water barrier to seal roof decks
4.4 Deck-Armor™ Premium
Breathable Roof Deck
Protection
FBC 1507.1.1 &
R905.1.1
(Exception)
North Bay, ON
Dadra, India
non-woven, spun-bonded polypropylene
laminated polyethylene scrim sheet roof
underlayment
4.5 FeltBuster® High-Traction
Synthetic Roofing Felt
FBC 1507.1.1 &
R905.1.1
(Exception)
Richmond, VA non-asphaltic, polypropylene roofing
underlayment
4.6 Shingle-Mate® Roof Deck
Protection
FBC 1507.1.1 &
R905.1.1
(Exception)
Pryor, OK fiberglass reinforced, asphaltic roof
underlayment
4.7 StormSafe™ Anchor Sheet FBC 1507.1.1 &
R905.1.1
(Exception)
North Bay, ON polypropylene woven fabric which serves as
an anchor sheet in two-ply roof
underlayment systems
4.8 Tiger Paw™ Roof Deck
Protection
FBC 1507.1.1 &
R905.1.1
(Exception)
Dadra, India
North Bay, ON
Parzai, India
Umerkui Kilvani,
India
non-woven, polypropylene reinforced,
polymer coated roof underlayment
4.9 RoofPro™ SBS-Modified All-
Purpose Underlayment
AC165 Fontana, CA fiberglass-reinforced, SBS modified bitumen
roof underlayment
4.10 VersaShield® Fire-Resistant
Roof Deck Protection
ASTM D6757
(physicals)
Conover, NC non-asphaltic, fiberglass-based roof
underlayment and/or fire barrier
4.11 Ruberoid® Mop Granule ASTM D6164 Savannah, GA granule-surfaced, polyester-reinforced,
asphalt-applied SBS modified bitumen roof
underlayment
4.12 Ruberoid® Mop Granule FR ASTM D6164 Savannah, GA granule-surfaced, polyester-reinforced,
asphalt-applied SBS modified bitumen roof
underlayment
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 4 of 11
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory or test
report from accredited testing agency for fire ratings of this product.
5.4 GAF Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval
based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
Underlayment Asphalt
Shingles Nail-On Tile Foam-On
Tile Metal
Wood
Shakes &
Shingles
Slate or
Simulated
Slate
Liberty™ SBS Self-Adhering Base/Ply
Sheet Yes No No No No No
StormGuard® Film Surfaced Leak
Barrier Yes No No Yes No No
WeatherWatch® Mineral Surfaced
Leak Barrier Yes No No No No No
Deck-Armor™ Premium Breathable
Roof Deck Protection Yes No No Contact
GAF
Contact
GAF
Contact
GAF
FeltBuster® High-Traction Synthetic
Roofing Felt Yes No No No No No
Shingle-Mate® Roof Deck Protection Yes No No No No No
Tiger Paw™ Roof Deck Protection Yes No No Contact
GAF
Contact
GAF
Contact
GAF
RoofPro™ SBS-Modified All-Purpose
Underlayment Yes No No No Yes Yes
VersaShield® Fire-Resistant Roof Deck
Protection Yes No No No No No
Ruberoid® Mop Granule Yes Yes Yes
See 5.5.1 No Yes Yes
Ruberoid® Mop Granule FR Yes Yes Yes
See 5.5.1 No Yes Yes
5.5.1 “Foam-On Tile” is limited to use of the following Approved tile adhesives / underlayment combinations.
TABLE 1A: ALLOWABLE TILE ADHESIVE / UNDERLAYMENT COMBINATIONS1
Adhesive Florida Product Approval Underlayments
DuPont TileBond™ FL22525 Ruberoid® Mop Granule; Ruberoid® Mop Granule FR
1 Refer to Tile Manufacturer’s or Adhesive Manufacturer’s Florida Product Approval for Overturning Moment Resistance Performance.
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 5 of 11
5.6 Allowable Substrates:
TABLE 2: SUBSTRATE OPTIONS FOR ADHERED UNDERLAYMENTS
Underlayment Application Primer Substrates
Liberty™ SBS Self-Adhering Base/Ply Sheet
self-adhering (Optional)
ASTM D41 plywood StormGuard® Film Surfaced Leak Barrier
Weather Watch® Mineral Surfaced Leak Barrier
Liberty™ SBS Self-Adhering Base/Ply Sheet
self-adhering None ASTM D226 felt StormGuard® Film Surfaced Leak Barrier
Weather Watch® Mineral Surfaced Leak Barrier
Liberty™ SBS Self-Adhering Base/Ply Sheet
self-adhering ASTM D41 metal (flashing metal, valley metal, etc.) StormGuard® Film Surfaced Leak Barrier
Weather Watch® Mineral Surfaced Leak Barrier
Ruberoid® Mop Granule hot asphalt ASTM D41 structural concrete Ruberoid® Mop Granule FR
Ruberoid® Mop Granule hot asphalt None GAFGLAS® #80 Ultima™ Base Sheet or
Ruberoid® 20 Smooth Ruberoid® Mop Granule FR
5.6.1 Wind Resistance for Underlayment Systems in Foam-On Tile Applications:
The following wind uplift limitations apply to underlayment systems that are not prescriptively addressed in
FRSA/TRI April 2012 (04-12) and are used in foam-on or mortar-set tile applications. Maximum Design Pressure is
the result of testing for wind load resistance based on allowable wind loads and reflects the ultimate passing
pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April
2012 (04-12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure = -45 psf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: GAFGLAS® #80 Ultima™ Base Sheet or Ruberoid® 20 Smooth mechanically attached with 12 ga., min.
1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 9-inch o.c. at the
min. 4-inch wide side laps and 9-inch o.c. at two (2), equally spaced, staggered center rows in the field
of the sheet.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 lbs/square.
#2 Maximum Design Pressure = -75 psf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: GAFGLAS® #80 Ultima™ Base Sheet or Ruberoid® 20 Smooth mechanically attached with 12 ga., min.
1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 8-inch o.c. at the
min. 4-inch wide side laps and 8-inch o.c. at three (3), equally spaced, staggered center rows in the
field of the sheet.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 lbs/square.
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 6 of 11
#3 Maximum Design Pressure = -97.5 psf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: GAFGLAS® #80 Ultima™ Base Sheet or Ruberoid® 20 Smooth mechanically attached with 11 ga., min.
1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 4-inch o.c. at the
min. 2-inch wide side laps and 4-inch o.c. at four (4), equally spaced center rows in the field of the
sheet.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 lbs/square.
#4 Maximum Design Pressure = -442.5 psf.
Deck: Min. 2,500 psi structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction
Base Sheet: GAFGLAS #75 Base Sheet, Tri-Ply #75 Base Sheet, GAFGLAS #80 Ultima Base Sheet, GAFGLAS Ply 4,
Tri-Ply Ply 4 or GAFGLAS Flex Ply 6 applied in full mopping of ASTM D312, Type IV hot asphalt at 20 to
25 lbs/square.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 lbs/square.
5.6.1.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or
exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies
marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29
(January 2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
TABLE 3: EXPOSURE LIMITATIONS
Underlayment Maximum
Exposure (days)
Deck-Armor™ Premium Breathable Roof Deck Protection, FeltBuster® High-Traction Synthetic Roofing Felt,
Shingle-Mate® Roof Deck Protection, StormSafe™ Anchor Sheet, Tiger Paw™ Roof Deck Protection,
RoofPro™ SBS-Modified All-Purpose Underlayment, Liberty™ SBS Self-Adhering Base/Ply Sheet,
StormGuard® Film Surfaced Leak Barrier and WeatherWatch® Mineral Surfaced Leak Barrier
30
VersaShield® Fire-Resistant Roof Deck Protection, Ruberoid® Mop Granule and Ruberoid® Mop Granule FR 180
5.8 Tile Slippage Limitations (TAS 103 per FRSA/TRI April 2012 (04-12)):
When loading roof tiles on the underlayment in direct-deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
TABLE 4: TILE SLIPPAGE LIMITATIONS FOR DIRECT-DECK TILE INSTALLATIONS
Underlayment Tile Profile Staging Method Maximum
Slope
Ruberoid® Mop Granule
Flat Max. 10-tile stack 4:12
Flat Max. 6-tile stack (4 over 2) 5:12
Lugged Max. 10-tile stack 5:12
Ruberoid® Mop Granule FR Flat or Lugged Max. 6-tile stack (4 over 2) 5:12
Lugged Max. 10-tile stack 4:12
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 7 of 11
6. INSTALLATION:
6.1 GAF Roof Underlayments shall be installed in accordance with GAF published installation instructions subject to
the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application and prime the substrate (if applicable).
6.3 Install self-adhering underlayments when ambient temperatures are minimum 45°F and rising.
6.4 All metal surfaces shall be primed with Matrix™ 307 Premium Asphalt Primer or alternate GAF accepted ASTM
D41 primer prior to application of self-adhering membranes.
6.5 Deck-Armor™ Premium Breathable Roof Deck Protection:
6.5.1 Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC Table
1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed, considering the wider sheet-width for
double-layer applications.
6.5.2 Fasteners:
Minimum fasteners shall be 1-inch diameter plastic-capped corrosion resistant nails or 1-inch diameter plastic-
capped, corrosion resistant staples, unless restricted by Code.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: “…except metal cap nails shall
be required where the ultimate design wind speed, Vault, equals or exceeds 150 mph.”
6.5.3 Slopes of 4:12 or greater:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches. End (vertical)
laps shall be offset from course to course not less than 6 feet.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. Secure end laps 6-inch o.c.
When batten systems are to be installed atop the underlayment, the underlayment need only be preliminarily
attached pending attachment of the battens.
6.5.4 Slopes of 2:12 to less than 4:12:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 28.5-inches (for 54-inch
wide rolls) or minimum 25.5-inches (for 48-inch wide rolls). End (vertical) laps shall be offset from course to course
not less than 6 feet.
Begin by fastening a full-width along the eaves or install full-width leak barrier. Place a full-width sheet over the
starter, completely overlapping the starter course. Continue upslope, maintaining minimum 28.5-inch side laps
(for 54-inch wide rolls) or minimum 25.5-inch side laps (for 48-inch wide rolls), resulting in a double-layer
application.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. Secure end laps 6-inch o.c.
When batten systems are to be installed atop the underlayment, the underlayment need only be preliminarily
attached pending attachment of the battens.
6.5.3 Optional, or if required by the Authority Having Jurisdiction: Install a leak barrier of Liberty™ SBS Self-Adhering
Base/Ply Sheet; StormGuard® Film Surfaced Leak Barrier or WeatherWatch® Mineral Surfaced Leak Barrier at
vulnerable leak areas, including but not limited to eaves, valleys, rakes, skylights and dormers. At eaves and valleys,
install the leak barrier prior to installation of the underlayment. Along the rake, install the underlayment, leaving
6 to 8-inch of the deck exposed, and then install the leak barrier over the underlayment and exposed decking. At
other areas, install the leak barrier over the underlayment.
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 8 of 11
6.6 FeltBuster® High-Traction Synthetic Roofing Felt or Tiger Paw™ Roof Deck Protection:
6.6.1 Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC Table
1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed, considering the wider sheet-width for
double-layer applications.
6.6.2 Fasteners:
Minimum fasteners shall be 1-inch diameter plastic-capped corrosion resistant nails or 1-inch diameter plastic-
capped, corrosion resistant staples, unless restricted by Code.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: “…except metal cap nails shall
be required where the ultimate design wind speed, Vault, equals or exceeds 150 mph.”
6.6.3 Slopes of 4:12 or greater:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches. End (vertical)
laps shall be offset from course to course not less than 6 feet.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. Secure end laps 6-inch o.c.
When batten systems are to be installed atop the underlayment, the underlayment need only be preliminarily
attached pending attachment of the battens.
6.6.4 Slopes of 2:12 to less than 4:12:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 25.5-inches. End
(vertical) laps shall be offset from course to course not less than 6 feet.
Begin by fastening a full-width along the eaves or install full-width leak barrier. Place a full-width sheet over the
starter, completely overlapping the starter course. Continue upslope, maintaining minimum 25.5-inch side laps,
resulting in a double-layer application.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. Secure end laps 6-inch o.c.
When batten systems are to be installed atop the underlayment, the underlayment need only be preliminarily
attached pending attachment of the battens.
6.6.5 Optional, or if required by the Authority Having Jurisdiction: Install a leak barrier of Liberty™ SBS Self-Adhering
Base/Ply Sheet; StormGuard® Film Surfaced Leak Barrier or WeatherWatch® Mineral Surfaced Leak Barrier at
vulnerable leak areas, including but not limited to eaves, valleys, rakes, skylights and dormers. At eaves and valleys,
install the leak barrier prior to installation of the underlayment. Along the rake, install the underlayment, leaving
6 to 8-inch of the deck exposed, and then install the leak barrier over the underlayment and exposed decking. At
other areas, install the leak barrier over the underlayment.
6.7 StormSafe™ Anchor Sheet:
6.7.1 StormSafe™ Anchor Sheet is limited to use as a mechanically attached base layer in 2-ply underlayment systems.
6.7.2 Fasteners:
Minimum fasteners shall be 1-inch diameter plastic- or steel-capped corrosion resistant nails; corrosion-resistant
nails & 1-5/8-inch tin-caps; or Drill-Tec screws and plates, unless restricted by Code.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: “…except metal cap nails shall
be required where the ultimate design wind speed, Vault, equals or exceeds 150 mph.”
6.7.3 Starting at the eave, fasten the eave edge and 6-inch wide end-laps 6-inch o.c. Fasten in the field of the roll 12-inch
o.c. in two, equally spaced, staggered center rows.
Continue upslope in a similar manner, maintaining minimum 3-inch side-laps and minimum 6-inch end-laps. Fasten
6-inch o.c. in the laps and 12-inch o.c. in two, equally spaced, staggered center rows in the field. Ensure all end
laps are staggered at least 3-feet apart.
One the same day, install Liberty™ SBS Self-Adhering Base/Ply; StormGuard® Film Surfaced Leak Barrier or
WeatherWatch® Mineral Surfaced Leak Barrier over the StormSafe™ Anchor Sheet.
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 9 of 11
6.8 RoofPro™ SBS-Modified All-Purpose Underlayment and Shingle-Mate® Roof Deck Protection:
6.8.1 Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC Table
1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed.
6.8.2 Fasteners:
As required in FBC Table 1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed. No hammer
tacks or staples are permitted.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: “…except metal cap nails shall
be required where the ultimate design wind speed, Vault, equals or exceeds 150 mph.”
6.8.3 Optional, or if required by the Authority Having Jurisdiction: Install a leak barrier of Liberty™ SBS Self-Adhering
Base/Ply Sheet; StormGuard® Film Surfaced Leak Barrier or WeatherWatch® Mineral Surfaced Leak Barrier at
vulnerable leak areas, including but not limited to eaves, valleys, rakes, skylights and dormers. At eaves and valleys,
install the leak barrier prior to installation of the underlayment. Along the rake, install the underlayment, leaving
6 to 8-inch of the deck exposed, and then install the leak barrier over the underlayment and exposed decking. At
other areas, install the leak barrier over the underlayment.
6.9 VersaShield® Fire-Resistant Roof Deck Protection:
6.9.1 Shall be installed in compliance with the codified requirements for ASTM D6757 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.9.2 Fasteners:
Minimum fasteners shall be 1-inch diameter plastic-capped or metal-capped corrosion resistant nails or 1-inch
diameter plastic-capped, corrosion resistant staples, unless restricted by Code.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: “…except metal cap nails shall
be required where the ultimate design wind speed, Vault, equals or exceeds 150 mph.”
6.9.3 Slopes of 4:12 or greater:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches. End (vertical)
laps shall be offset from course to course not less than 6 feet.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. Secure end laps 6-inch o.c.
When batten systems are to be installed atop the underlayment, the underlayment need only be preliminarily
attached pending attachment of the battens.
6.9.4 Slopes of 2:12 to less than 4:12:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 22-inches. End (vertical)
laps shall be offset from course to course not less than 6 feet.
Begin by fastening a half-width starter strip along the eaves or install full-width leak barrier. Place a full-width sheet
over the starter, completely overlapping the starter course. Continue upslope, maintaining minimum 22-inch side
laps, resulting in a double-layer application.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. Secure end laps 6-inch o.c.
When batten systems are to be installed atop the underlayment, the underlayment need only be preliminarily
attached pending attachment of the battens.
6.9.5 Optional, or if required by the Authority Having Jurisdiction: Install a leak barrier of Liberty™ SBS Self-Adhering
Base/Ply Sheet; StormGuard® Film Surfaced Leak Barrier or WeatherWatch® Mineral Surfaced at vulnerable leak
areas, including but not limited to eaves, valleys, rakes, skylights and dormers. At eaves and valleys, install the leak
barrier prior to installation of the underlayment. Along the rake, install the underlayment, leaving 6 to 8-inch of
the deck exposed, and then install the leak barrier over the underlayment and exposed decking. At other areas,
install the leak barrier over the underlayment.
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 10 of 11
6.10 Liberty™ SBS Self-Adhering Base/Ply Sheet:
6.10.1 Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.10.2 The minimum and maximum roof slopes are ½:12 and 6:12, respectively. Back-nailing is required when slope is
1:12 or greater. Back-nailing shall consist of minimum 1-inch square or round cap nails spaced 18” o.c.
encapsulated within min. 3-inch side laps.
6.10.3 Non-Tile Applications:
Shall be fully self-adhered to the substrates noted in Section 5.6. For direct-bond to deck applications plywood
shall be primed with Matrix™ 307 Premium Asphalt Primer or alternate GAF accepted ASTM D41 primer at ½ to
¾ gallon per square.
Prior to removal of release film, align sheets properly starting at the low-point of the roof (eave) with the selvage
edge upslope and for minimum 2-inch overhang at eaves and rakes. Roll out sheet and allow to ‘relax’ for min. 30
minutes. Remove the lower piece of release film and bond to substrate and fold the overhanging 2-inch over the
eave and nail into place 12” o.c. Remove the top piece of release film and bond to substrate. Install primed drip
edge and fasten to meet FBC Chapter 16 wind load requirements. Install 1/8-inch troweling of Matrix™ 201
Premium SBS Flashing Cement over drip edge.
Continue upslope in a similar manner, maintaining minimum 3-inch side-laps and minimum 6-inch end-laps. Ensure
all end laps are staggered at least 18-inch apart.
Use a weighted lawn or linoleum roller to ensure complete adhesion to the substrate. Use a hand roller to firmly
bond side and end laps.
6.11 StormGuard® Film Surfaced Leak Barrier:
6.11.1 Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.11.2 Back-nailing is required. Back-nailing shall consist of minimum 1-inch square or round cap nails spaced 18” o.c.
encapsulated within min. 3-inch side laps.
6.11.3 Non-Tile Applications:
Shall be fully self-adhered to the substrates noted in Section 5.6. Prior to removal of release film, align sheets
properly starting at the low-point of the roof (eave) with the selvage edge upslope and for minimum 2-inch
overhang at eaves and rakes. Remove the lower piece of release film and bond to substrate and fold the
overhanging 2-inch over the eave and nail into place 12” o.c. Remove the top piece of release film and bond to
substrate. Install primed drip edge and fasten to meet FBC Chapter 16 wind load requirements. Install 1/8-inch
troweling of Matrix™ 201 Premium SBS Flashing Cement over drip edge.
Continue upslope in a similar manner, maintaining minimum 3-inch side-laps and minimum 6-inch end-laps. Ensure
all end laps are staggered at least 18-inch apart.
Use a hand roller to firmly bond side and end laps.
6.12 WeatherWatch® Mineral Surfaced Leak Barrier:
6.12.1 Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.12.2 WeatherWatch® Mineral Surfaced Leak Barrier may be installed as a secondary water barrier using minimum 4-
inch wide rolls to seal plywood deck joints prior to installation of the primary underlayment system.
6.12.3 Back-nailing is required. Back-nailing shall consist of minimum 1-inch square or round cap nails spaced 18” o.c.
encapsulated within min. 4-inch side laps.
NEMO|etc.
NEMO ETC, LLC Evaluation Report 01506.04.08-R17
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL10626-R17
GAF Roof Underlayments; (800) 766-3411 Revision 17: 12/13/2019
Page 11 of 11
6.12.4 Non-Tile Applications:
Shall be fully self-adhered to the substrates noted in Section 5.6. Prior to removal of release film, align sheets
properly starting at the low-point of the roof (eave) with the selvage edge upslope and for minimum 2-inch
overhang at eaves and rakes. Remove the lower piece of release film and bond to substrate and fold the
overhanging 2-inch over the eave and nail into place 12” o.c. Remove the top piece of release film and bond to
substrate. Install primed drip edge and fasten to meet FBC Chapter 16 wind load requirements. Install 1/8-inch
troweling of Matrix™ 201 Premium SBS Flashing Cement over drip edge.
Continue upslope in a similar manner, maintaining minimum 3-inch side-laps and minimum 6-inch end-laps. Ensure
all end laps are staggered at least 18-feet apart.
Use a hand roller to firmly bond side and end laps.
6.13 Ruberoid® Mop Granule; Ruberoid® Mop Granule FR:
6.13.1 Ruberoid® Mop Granule or Ruberoid® Mop Granule FR shall be installed in compliance with current GAF published
installation requirements.
6.13.2 For use in tile applications, Ruberoid® Mop Granule or Ruberoid® Mop Granule FR are for use as an alternate to
“Mineral Surface Roll Roofing” (ASTM D6380, Class M) in the “Single Ply System” from FRSA/TRI April 2012 (04-12)
beneath mechanically fastened tile roof systems or the Hot Asphalt applied “Cap Sheet” in the “Two Ply System”
from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems.
6.13.3 Fully adhere in ASTM D312, Type IV hot-asphalt to the substrates noted in Section 5.6. Side laps shall be minimum
4-inch and end-laps minimum 6-inch wide, and offset end-laps minimum 3-feet from course to course. Side and
end-laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-
inch beyond the lap edge.
6.13.4 Consult GAF instructions regarding back-nailing requirements.
6.14 Tile Staging (Ruberoid® Mop Granule; Ruberoid® Mop Granule FR):
6.14.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer
to Table 4 herein, and GAF published requirements for tile staging.
6.14.2 Battens and/or Counter-battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be
used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of bat tens or
nail-boards, to prevent tile sliding and/or damage to the underlayment during the loading process.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this
product.
8. MANUFACTURING PLANTS:
Contact the manufacturer or the named QA entity for plants covered under Rule 61G20-3 QA requirements. Refer
to Section 4 herein for product & production locations having met codified physical properties specifications.
9. QUALITY ASSURANCE ENTITY:
UL, LLC. – QUA9625; (847) 664-3281
- END OF EVALUATION REPORT -