HomeMy WebLinkAbout7- Tile Adhesive for Perimiter OnlyTRINITY ERD
EVALUATION REPORT
ICP Adhesives and Sealants, Inc.
12505 NW 44th Street
Coral Springs, FL 33065
(888)774-1419
EXTERIOR RESEARCH & DESIGN, I.I.C.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT 13
OXFORD, CT 06478
(203) 262-9245
Evaluation Report 02768.03.06-118
FL6332-R8
Date of Issuance: 08/08/2008
Revision 8: 10/12/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: ICP Adhesives Polyset® AH -160
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity I ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 9.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/12/2017 This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinitvl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
ROOFING COMPONENT EVALUATION;
1.
\I TRINITY ERD
SCOPE:
Product Category: Roofing
Sub -Category: Roof Tile Adhesives
Compliance Statement: ICP Adhesives Polyset® AH -160, as produced by ICP Adhesives and Sealants, Inc., has
demonstrated compliance with the 6th Edition (2017) Florida Building Code through testing in accordance with the
Standards set forth herein. Compliance is subject to the Installation Requirements and Limitations / Conditions of
Use set forth herein.
2. STANDARDS:
Sections
1504.2.1.1
3. REFERENCES:
Entity
ERD (TST 6049)
ERD (TST 6049)
ICC-ES(EVL2396)
Miami -Dade (CER 1592)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
UL LLC (QUA 9625)
4. PRODUCT DESCRIPTION:
Property
Overturning resistance
Examination
Static Uplift —SSTD 11
Static Uplift—SSTD 11
2012 IBC Compliance
HVHZ compliance
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift — SSTD 11
Static Uplift—SSTD 11
Static Uplift—SSTD 11
Static Uplift — SSTD 11
Static Uplift — SSTD 11
Static Uplift—SSTD 11
Static Uplift — SSTD 11
Quality Assurance
Standard
SSTD 11
Reference
P39740.02.12
P39740.11.13 -R1
ESR -1709
17-0322.03
ECM -001-02-01
PFI -006-02-01
PFI -006-02-02
PFI -007-02-01
PFI -008-02-04
PFI -009-02-03
TG R I-001-02-03
TG RI -001-02-03
PFPI-010-02-01
PFPI-011-02-01
PFPI-012-02-01
PFPI-013-02-01
PFPI-014-02-01
ECM -003-02-01
ECM -004-02-01
ECM -005-02-01
ECM -006-02-01
ECM -007-02-01
ECM -008-02-01
Service Confirmation
Year
1997
Date
02/20/2012
01/02/2015
12/01/2016
04/27/2017
09/21/2001
05/09/2005
05/09/2005
10/11/2005
02/21/2006
02/21/2006
10/30/2006
10/30/2006
12/07/2006
12/07/2006
12/07/2006
12/07/2006
12/07/2006
06/13/2008
06/13/2008
06/13/2008
06/13/2008
06/13/2008
06/13/2008
Exp. 06/05/2018
4.1 ICP Adhesives Polyset® AH -160 is a two -component expanding polyurethane roof tile adhesive that is mixed
and dispensed from a dispensing system provided by ICP Adhesives and Sealants, Inc. The components are
available in refillable tanks or disposable cylinders (ICP Adhesives ProPack° 30 & 100).
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for
permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-R8
Certificate of Authorization #9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset° AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 2 of 9
rT�INITi ERD
5.3 Fire classification is not part of this evaluation. Refer to a current Roofing Materials Directory for fire ratings
of this product and FBC 1505.2.
5.4 ICP Adhesives Polyset' AH -160 can be used with flat, low and high profile tiles or any rigid, discontinuous roof
assembly having a current Florida Statewide Product Approval or approved on a local -level by the Authority
Having Jurisdiction.
5.5 Minimum underlayment shall be per FRSA/TRI April 2012 (04-12) or having a current Florida Statewide
Product Approval or approved on a local -level by the Authority Having Jurisdiction for use with ICP Adhesives
Polyset® AH -160.
5.6 Field tiles, meeting the limitations of FBC 1609.5.3, using ICP Adhesives Polyset® AH -160 are limited to
projects having an Aerodynamic Uplift Moment (MJ, determined in accordance with FBC 1609.5.3 or Tables
2A and 2B of FRSA/TRI April 2012 (04-12), not greater than the following Allowable Overturning Moment
values. Refer to Section 10 and ICP Adhesives and Sealants, Inc. published installation instructions for
Adhesive Paddy Placement details.
TABLE 1: FIELD TILES IN ICP ADHESIVES POLYSETO AH -160
ALLOWABLE OVERTURNING MOMENT PERFORMANCE DATA
2 TO 1 MARGIN OF SAFETY ALREADYAPPLIED FOR INDEPENDENT (SINGLE OR CONTINUOUS PADDY) PLACEMENT
4 -To 1 MARGIN OFSAFETYALREADY APPLIED FOR INTERDEPENDENT (TWO PADDY) PLACEMENT
Tile (FBC 1609.5.3)
Allowable
Adhesive Paddy Placement overturning
Type
Profile
Moment (ft-lbf)
Independent; Single Paddy, Medium (2x7 -inch, -30 gram) 60
Clay
Flat
Independent; Single Paddy, Large (2x10 -inch, -45 gram) 112
Concrete
Interdependent; Two Paddy (4x4 -inch on underlayment, 2x4 -inch at tile overlap) 54
'
Independent; Single Paddy, Medium (20 -inch, -30 gram) 39
Clay or-_
Low/
Independent; Single Paddy, Large (2x10 -inch, -54 gram) 67
Concrete
Medium)
Interdependent; Two Paddy (4x4 -inch on underlayment, 2x4 -inch at tile overlap) 58
Clay
High
Independent; Single Paddy, Large (2x10 -inch, -45 gram) 134
Independent; Single Paddy, Medium (2x7 -inch, "30 gram) 65
Concrete Clay
High
Independent; Single Paddy, Large (2x10 -inch, -63 gram) 109
Interdependent; Two Paddy (4x4 -inch on underlayment, 2x4 -inch at tile overlap) 40
Clay
Barrel
2x10 -inch x -35 gram for pans; 2 @ 1x10 -inch x -17 gram for cap 147
Concrete
Barrel
2x10 -inch x -35 gram for pans; 2 @ 1x10 -inch x -17 gram for cap 107
Clay
Cap atop 2x
Independent: Continuous Paddy (-34 gram/ft) 135
stringer
Concrete
Cap atop 2x
Independent: Continuous Paddy (^' 34 gram/ft) 116
stringer
ClayCap
atop 2x
Interdependent: 105
stringer
Head: One (1) #10 x 2'/2" screw; Overlap: 1 x 6 inch (^'10.5 gram)
Concrete
Cap atop 2x
Interdependent: 76
stringer
Head: One (1) #10 x 2'/2" screw; Overlap: 1 x 6 inch (^'10.5 gram)
5.6.1 Data in Table 1 relates to installation over a '30/90' underlayment system, as detailed in the FRSA/TRI April
2012 (04-12). Alternate underlayment systems include those having a current Florida Statewide Product
Approval and/or approved on a local -level by the Authority Having Jurisdiction specifically for use with ICP
Adhesives Polyset® AH -160.
5.6.2 Tile roof systems using tile types or profiles other than those listed above acquiring acceptance for use with
ICP Adhesives Polyset® AH -160 shall be tested in accordance with SSTD 11 or Testing Application Standard
TAS 101. For the interdependent two -paddy method, an additional 2 -to -1 margin above that specified in
SSTD it or Testing Application Standard TAS 101 shall be applied in determining the 'allowable overturning
moment'.
Exterior Research and Design, LLC. Evaluation Report 02768.03.06-R8
Certificate o/Authorization #9503 6T" EDITION (2017) FBG NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset° AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 3 of 9
VT RINITY I ERD
5.7 Hip and ridge tiles using ICP Adhesives Polyset® AH -160 are limited to projects having hip/ridge design pressure
requirements, determined in accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater than the
following values. Refer to ICP Adhesives and Sealants, Inc. published installation instructions for Adhesive
Paddy Placement details.
TABLE 2: HIP & RIDGE TILES IN ICP ADHESIVES POLYSETO AH -160
ALLOWABLE UPLIFT RESISTANCE PERFORMANCE DATA
1 TO 1 MARGIN OFSAFETYALREADYAPPLIED FOR INDEPENDENT (CONTINUOUS PADDY) PLACEMENT
4 TO 1 MARGIN OF SAFETYALREADY APPLIED FOR INTERDEPENDENT PLACEMENT
Allowable
Tile
Substrate
Attachment Method
Design Pressure
Ipsf)
Clay
2x PT ridge board
Independent: Continuous Paddy ("34 gram/ft)
116
Concrete
2x PT ridge board
Independent: Continuous Paddy (" 34 gram/ft)
107
Clay
2x PT ridge board
Interdependent: Head: One (1) #10 x 2'/" screw;
90
Overlap: 1 x 6 inch ("10.5 gram)
Interdependent: Head: One (1) #10 x 2'/2" screw;
Concrete
2x PT ridge board
Overlap: 1 x 6 inch ("10.5 gram)
56
Clay or
Hip & Ridge Channel Metal (FL5374)
Independent: Continuous Paddy ("34 gram/ft)
169
ncrete
galvanized only
Clay or
Trim Lock TM (FL5374): aluminum,
Independent: Continuous Paddy ("34 gram/ft)
173
Concrete
galvanized, Galvalume® or stainless steel
Clay or
Trim Lock'"" Plus (FLS374): aluminum,
Independent: Continuous Paddy (" 34 gram/ft)
178
Concrete
galvanized, Galvalume° or stainless steel
Clay
Top Notch (FL8095)
Independent: Continuous Paddy (" 32 gram/ft)
125
Concrete
Top Notch (FL8095)
Independent: Continuous Paddy ( 32 gram/ft)
146
6. INSTALLATION:
6.1 ICP Adhesives Polyset® AH -160 and the tile roof assembly shall be installed in accordance with FRSA/TRI
April 2012 (04-12) and ICP Adhesives and Sealants, Inc. published installation instructions, subject to the
limitations outlined in Section 5.
6.2 Hip and ridge boards or hip/ridge metal shall be installed in accordance with the FRSA/TRI April 2012 (04-12).
Proprietary hip and ridge metal shall be installed in accordance with the manufacturer's Florida Product
Approval.
6.3 Installation shall be performed by applicators who hold a valid Qualified Applicator Card presented by ICP
Adhesives and Sealants, Inc.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the
installation of this product.
8. MANUFACTURING PLANTS:
Tomball, TX
9. QUALITY ASSURANCE ENTITY:
UL, LLC. — QUA9625; (847) 664-3623; LeAnna.Gradecki@ul.com
Exterior Research and Design, U.C. Evaluation Report 02768.03.06-R8
Certificate o/Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-118
ICP Adhesives Polyset® AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 4 of 9
TRINITY ERD
10. PADDY PLACEMENT DETAILS (FROM ICP ADHESIVES AND SEALANTS, INC. PUBLISHED LITERATURE):
10.1 Independent, Medium Paddv:
N.,il though plastic cement
(when rec;iri re d}
Underlayment o,i`�
G '. G
1
1\ 7 in. 2 in. N'1�
Battens optional °
Eave Course
0
a 101n.
�i
Paddy (Beneath Tile)
1
Flat/Low Profile Tile
Nall through plastic cement
(when required)
s
Underlayment \,/
Battensoptional
Eave
In.
rr Paddy (Beneath Tlle)
n.
Eave Closure
Fascia
Medium Profile Tile
Nall through plastic cement-, paddy (Beneath Tile)
(when required)
Undedayment
7In.
2 In.
Battens optiona l 'j
`tc
r Eave Course-._ `` Fascla
Weephole
loin. Z in. Eave closure
Drip edge
High Profile Tile
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-118
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page S of 9
10.2 Independent, Large Paddy:
Nail through plastic cement
(when required)
Underlayment °
O
I\ 10 ink
Battens optional
O FF!?'14
4'` Mti
2i
Paddy 18eneeth Tile)
Flat/Low Profile Tile
��l TRINITY ERD
Nall through plastic cement
(when required)
Paddy (Beneath Tile)
4
Underlayment
loin ri`.��
2 in.wide1
Battens optional c �`
�1.
1�. mac, 2in.
Eave Closure
Eave Course .'— Fascia
Medium Profile Tile
Nall through plasticce
(when requl red) Paddy (BeneathTlle)
Underlayment
. 2 in.wide
Battensty
optional "rt"
Eave Course - _ Fascia
a
Weephole
10 in. 2in.
Eave closure
►' Drip edge
High Profile Tile
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-118
Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVH2 EVALUATION FL6332-118
ICP Adhesives Polyset° AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 6 of 9
10.3 Interdependent, Two Paddy:
Nail through plastic cement
When requiredl
Battens optional °
n
Singlepeddy
on top of the
x4in.
on underlayment 2 x 4 in.
0
loin S
v
Flat/Low Profile Tile
Exterior Research and Design, I.I.C.
Certificate ofAuthorization #9503
(between tiles)
Pedcly (undertile)
Eave Closure
�'l I RINITY ERD
Nall through plastic cement Single paddy under tile
(when required)
Paddy (between tiles)
Battens Paddy (under tile)
optional
a`
Singl• paddy
on top of the .;
`r
4x411n. 2x41n.
Single paddy on
underlayment
10 in 4 tin.
Eave Closure
Eave Course Fascia
Medium Profile Tile
Nail through plastICce
Single paddy under tile
(when required)
Paddy (between tiles)
Battens °
aptioizal
ct, y
Paddy (under tile)
r Singlepaddy
�onunderlaymen[
r`
y
x4 in.�
Singla 2x 4 in
paddyan
~`^
topoftlle—
Eave Course --
''# Fascia
Weephole
loin tin.
Eaveclosure
Drip edge
High Profile Tile
Evaluation Report 02768.03.06-R8
6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 7 of 9
10.4
10.5
Two Piece Barrel (Cap & Pan) Tile:
1) plica enough adhesive to achieve 65 to 70 sq, In. Steap plich applications
In contact with the pan tile, when required)
21 Tum Coven opalde down. Place adheaWc
1121n.101 "-h in from gilt-lifeedge o} sever tile.
Install cover tile.
Ereaure 2e to 215 sq, 10, contpot oma cn
each aide of .aver 1He.
1Ir1nderlayment
3'
r,^.'f ,•'`fr Sheathing
Eaveclssura t'
(motor shown)
weephole FastIs Beard
Remove top portion of the save course cover tile. Abut to second course of
pan tiles. Ensure save end of pan and cover tiles are flush at save line.
Two Piece Barrel - High Profile Tile
Hip and Ridge (independent placement):
A bead of ICP PolysedbAH-166 may be applied above the field To attach hipindge tiles, a bead of 1CP Polyeel»AH-160 may
file surface ou both sides of the Wpltldge board or golviolzed be applied down the center of the hq»ridge board or galvvdzed
metal frame to provide weatherblockurg. frame.
�l I RINITY ERD
hr gnlled * he fill lrn�lr of rhe kle ra. AAq• ! awhea r;chrliar 7 Wil- mr
the — and .f ids
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-R8
Certificate ofAuthorization 119503 6TH EDITION (2017) FEIC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 8 of 9
10.6
�I TRINITY IERD
Hip and Ridge (interdependent placement):
- END OF EVALUATION REPORT -
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-R8
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH -160; (888) 774-1419 Revision 8: 10/12/2017
Page 9 of 9