REVIEW COMMENTS
DWI ED Page 1
NOV 15 2017 Owner(s):
Bertrand Laidier Jr / Charlotte Almore /
Michael E Bell li
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 7
APPLICATION INFORMATION
Permit Number: 1709-0086 Stones:
Permit Type: BUILDING RESIDENTIAL (SFR UP TO 2 FLOORS)
CONTRACTOR INFORMATION
Contractor Name:
Michael J Miranda
Business Name:
Group One Construction & Dev Inc
Business Addr:
10302 S Federal Hwy Ste 164
City / State / Zip:
Port St Lucie, FI 34952
Review Tvoe
ADDRESSING ASSIGNMENT
Comment:
DOCUMENTS MISSING
9/2012017 Comment:
9/22/2017 Comment:
ENVIRONMENTAL REVIEW
Comment:
FRONT COUNTER REVIEW
Comment:
PE REVIEW COMMENTS (2)
10/2/2017 Comment:
Comment:
10/212017
Comment:
10/2/2017
Block:
Automatic Sprinkler System? No
Fax Number: 772-334-0804
Status Reviewed By Date Started
COMPLETE Lydia Galbraith 912212017
PENDING Lashahna Ingram
VEG PERMIT IN DRAWER UNDER'A" ALMORE. NO FEE
SUB AGREEMENTS FOR MECHANICAL AND ROOF.
COMPLETE Lynn Swartzel 911812017
COMPLETE Lashahna Ingram 916/2017
INCOMPLETE William Durden 11/8/2017
Email: Mikemiranda3074@AoI.Co
m
Date Completed Date Released
912512017 9/2512017
911812017 9/18/2017
91612017 91612017
• PLEASE CLARIFY THE DESCRIPTION OF MULTIPLE HOUSES SPECIFIED IN THE ENERGY CALC'S.
STRUCTURE IS A SINGLE-FAMILY RESIDENCE.
• LINE SEVEN ON THE ENERGY CALC'S ARE INCORRECT, MULTIPLE TYPES OF WINDOWS ON PLANS
PLEASE CORRECT ENERGY CALC'S AS PER SECTION R401.3 OF THE 2014 FLORIDA BUILDING CODE
ENERGY CONSERVATION 5TH EDITION.
SUBMITTED WALL DETAIL SHOWS R-13 WALL INSULATION, ENERGY CALC'S DO NOT SHOW THE
INSULATION OF THE SEPARATION WALL. PLEASE CORRECT.
6. SHOW INTERIOR WALL DETAIL FOR THE SEPARATION OF THE GARAGE TO HOUSE INCLUDING
INSULATION AND R VALUE. SEE SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Planning& Development Services REVIEW COMMENTS
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Fax:(772)462.6443
r. m .nl• PA(:F 3 OF 5 wwnr)WR CHOC AND THE I I-FAr1TOR ARF THE RAMF FOR At I FFNFRTRATION AND THE
NFRC IS MARKED YES. PLEASE SUBMIT THE ENERGY PERFORMANCE SHEETS FROM THE MANUFACTURE.
PAGE 3 OF 5 WILL NEED TO BE CORRECTED.
10/212017
• PLEASE SUBMIT THE ENERGY PERFOMANCE SHEETS OR SUBMIT A THE NFRC FENSTRATION
MANUFACTURE CERTIFICATE FOR THE U-FACTOR AND THE SHGC FOR EACH GLAZED OPENING SHOWING
COMPLIANCE WITH CHAPTER 4 SECTION 402.1.1 OF THE 2014 ENERGY CODE FIFTH EDITION.
101212017 Comment: ENERGY CALC'S ONLY CALL OUT ONE WATER HEATER, PLANS SHOW 3. PLEASE CLARIFY. SEE SECTION
107 OF THE 2014 FLORIDA BUILDING CODE.
Comment: THE PRODUCT APPROVALS THAT WERE SUBMITTED IS FOR THE METAL ROOF, PLEASE SUBMIT THE
ROOF UNDERLAYMENT.
10/2/2017 • PLEASE SUBMIT THE ROOF UNDERLAYMENT PRODUCT APPROVALS IN DUPLICATE. MEETING THE
REQUIREMENTS OF CHAPTER 9 SECTION R905.10.5 SUBSECTION R105.10.5.2 OF THE 2014 FLORIDA
BUIDING CODE.
10/212017 Comment: • THE ENERGY CALULATIONS MUST HAVE THE PREPARERS ORIGINAL SIGNATURE PLEASE FURNISH NEW
ENERGY CALULATIONS WITH ORIGINAL SIGNATURE PER 107.1 OF THE 2010 FLORIDA BUILDING CODE
PLANS EXAMINER ELECTRIC INCOMPLETE Joe Cielo 10/412017
101412017 Comment: PLS ADD THE QUANTITY OF APPLIANCES ITEMIZED WITHIN THE ELECTRICAL LOAD CALCULATIONS: EX: [
2 ] DISHWASHERS [ 31 MECHANICAL SYSTEMS ETC
10/4/2017 Comment: CHECK LOADS FOR APPLIANCES • NOT CONSISTENT WITH THE NEC' APPLIANCES ARE MISSING FROM
THE LIST PER THE PLANS
PLANS EXAMINER MECHANICAL
INCOMPLETE Joe Cicio 10/312017
Comment:
HOUSE 1, 2 AND MAIN HOUSE SQUARE FOOTAGES ON SUMMARY SHEETS MUST MATCH THE
10/3/2017
WORKSHEETS
10/3/2017
Comment:
SHOW THE OPENING SIZE AND CFM'S FOR FAMILY ROOM DROP IN HOUSE #1
Comment:
SHOW THE LOCATIONS OF ALL MECHANICAL EQUIPMENT ON PLANS' SHOW THE REQUIRED TIE DOWN
DETAILS FOR THE EXTERIOR EQUIPMENT PER FBCM 301.15 TO MEET THE DESIGN WIND SPEED AND
EXPOSURE'•• UNIT #1 AND UNIT #2 WILL NOT FIT IN THE ATTIC LOCATIONS AS SHOWN ON THE MECH
10/3/2017
PLANS' PLEASE CO-ORDINATE THESE LOCATIONS WITH THE TRUSS MANUFACTURERS ENGINEER AND
THE ENGINEER OF RECORD • SHOW ALL DETAILS ON PLANS PER FBCR M 1305.1.3 W/ PAN DETAILS AND
DRAINS
Comment:
PLEASE MAKE REFERENCE TO ALL MECHANICAL SYSTEMS ON ALL DOCUMENTS AS SYSTEM 1, SYSTEM 2
10/3/2017
AND SYSTEM 3 • THIS IS A SINGLE FAMILY DWELLING' PLEASE LABEL THESE SYSTEMS ON THE
MECHANICALPLANS
Comment:
MANUALS AND ENERGY CALCS SPEC R-4 OPEN CORE FOR EXTERIOR WALLS' PLANS SPEC R-9 CORE
10/3/2017
FILLED • PLS CORRECT ONE OR THE OTHER
Comment:
IF ANY MECHANICAL UNITS ARE IN THE ATTIC TRUSS COMPANY TO SHOW ON LAYOUTS WITH APPROVAL
10/3/2017
OF LOADING' ENERGY CALC IS SPECIFYING ALL [ 3 ] UNITS IN ATTIC
10/312017
Comment:
ENGINEER TO STATE THE CORRECT ADDRESS ON ALL PLANS, ENERGY CALCS AND MANUALS
10/4/2017
Comment:
ENERGY CALCS ARE SIGNED INCORRECTLY AND MUST ALL BE ORIGINAL SIGNATURES
PLANS EXAMINER PLUMBING
INCOMPLETE Joe Ciclo 10/412017
10/4/2017
Comment:
SHOW THE WATER HEATER SIZES ON PLANS AND ADD ADDITIONAL HEATERS TO ENERGY CALCS
10/412017
Comment:
SHOW THE REQUIRED PAN AND DRAIN SIZES ON PLANS FBCR P 2801.5
Comment:
ENGINEER TO NOTE THE TESTING STANDARDS FOR THE DRAINAGE AND VENT PIPING ON PLANS • SEE
10/412017
FBCR P 3002.1
PLANS EXAMINER REVIEW
COMPLETE William Durden 101212017 11/812017 111812017
Comment:
ZONING REVIEW
INCOMPLETE Lydia Galbraith 9/2212017
Comment:
PLEASE PROVIDE 2 UPDATED SIGNED AND SEALED SURVEYS WITH PROPOSED CONSTRUCTION,
9/22/2017
SETBACK, PROPOSED FFE, ELEVATION OF CENTER LINE ROAD, SEPTIC AND WELL.
9/22/2017
Comment:
PLEASE PROVIDE 2 FLOOR PLANS AND 2 SURVEYS STAMPED FOR APPROVAL BY HEALTH DER
-Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462-2172 Fax:(772)462.6443
REVIEW COMMENTS
9/22/2017 Comment:
PLEASE PROVIDE HEALTH DEP PERMIT FOR SEPTIC AND WELL
Comment:
SUBMITTED WARRANTY DEED IS NOT THE LATEST DEED. PROPERTY IS OWNED BY 3 PERSONS THAT
9/22/2017
ARE JOINT TENANTS.
Comment:
BUILDING PLANS GIVE THE IMPRESSION THE BUILDING TO BE A MULTI FAMILY BLD WITH 3 UNITS. AG 5
ZONING DISTRICT DOESN'T ALLOW MULTI FAMILY. TO BE ABLE TO PROCEED AS SFR THE PLANS SHOULD
9/2212017
NOT REFER TO MAIN, HOUSE 1 AND HOUSE 2. THE SAME FOR THE MANUAL J'S THEY SHOULD NOT REFER
TO MULTIPLE HOUSES. ALL INDICATION TO MULTIPLE UNITS SHOULD BE REMOVED FROM THE PLANS.
Comment:
PLEASE BE AWARE THAT WE WERE NOT ABLE TO COMPLETE THE ZONING REVIEW DUE TO MISSING
INFORMATION. THE PLANS WILL PROCEED THROUGH THE REVIEW PROCESS, HOWEVER, THE PERMIT
912212017
WILL NOT BE ISSUED UNTIL ZONING HAS BEEN ABLE TO FINALIZE THE REVIEW. PLEASE BE AWARE THAT
ADDITIONAL COMMENTS FROM DIFFERENT DEPARTMENTS MIGHT BE APPLICABLE.