HomeMy WebLinkAboutA-1 150 A THOMPSONBack-up generator system will be a
non-separately derived grounding system
Ground metallic gas line to
generator frame with MIN #6
Green DRAWN
CHECKED
DATE
SCALE
JOB NO.
SHEET
OF 2 SHEETS5818 Lyda laneOrlando Fl. 32839407-816-9000General ContractorQualifer: Mark CrossLicense #: CGC1514240Electrical ContractorQualifer: Mark CrossLicense #: EC13001174REVISIONS BY
ELECTRICALPLANINSTALL STANDBY GENERATORFORQUALIFER: MARK CROSS
LICENSE # EC13001174
MC
04-16-2020
A-1
CONSTRUCTION TYPE:
TYPE
OCCUPANCY:
SINGLE FAMILY RESIDENCE
JURISDICTION:
ST. LUCIE COUNTY
APPLICABLE BUILDING CODES:
•FLORIDA BUILDING CODE, SIXTH EDITION (2017)
•FLORIDA ENERGY CODE, SIXTH EDITION (2017)
•FLORIDA MECHANICAL CODE, SIXTH EDITION (2017)
•FLORIDA PLUMBING CODE, SIXTH EDITION (2017)
•EXISTING BLDG. FLORIDA BUILDING CODE, SIXTH EDITION (2017)
•FLORIDA ACCESSIBILITY CODE, SIXTH EDITION (2017)
•FLORIDA FIRE PREVENTION CODE, SIXTH EDITION
•2014 NATIONAL ELECTRIC CODE
•NFPA 101 LIFE SAFETY CODE, 2015 EDITION
•2013 NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS
NOTES:
IT IS THE CONTRACTOR'S RESPONSIBILITY TO FURNISH AND
INSTALL ALL NECESSARY COMPONENTS FOR THE PROPER
OPERATION OF ALL SPECIFIED SYSTEMS, REGARDLESS OF
WHITHER THOSE COMPONENTS ARE SHOWN ON THE DRAWINGS
OR NOT. CONTRACTOR SHALL ALSO VERIFY THAT SPECIFIED
COMPONENTS ARE COMPATIBLE WITH OTHERS WITHIN THE SAME
SYSTEM ANO WITH THE SYSTEM ITSELF.
LEGAL DESCRIPTION:
PORTOFINO SHORES-PHASE TWO- (PB 43-33) LOT 193
PARCEL ID #: 1312-502-0094-000-7
PROJECT NO.: G200108
DATE: 6-17-2020
GENERAL ELECIRICAL NOTES:
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE AND OTHER APPLICABLE CODES AND
STANDARDS.
2. THE CONTRACTOR SHALL SATISFACTORLIY REPAIR/REPLACE
EQUIPMENT OR PART OF STRUCTURE DAMAGED AS A RESULT OF
HIS WORK.
3. APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR
TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT MEMBER .
4. MINIMUM WIRE SIZE SHALL BE #12 THWN UNLESS OTHERWISE
NOTED ON PLANS .
5. ALL CONDUCTORS SMALLER THAN #8 SHALL BE COPPER
UNLESS OTHERWISE NOTED ON PLANS .
6. ALL EXPOSED CONDUCTORS SHALL BE RUN IN CONDUIT.
7. ALL MATERIALS SHALL BE U.L. APPROVED.
8. CONTRACTOR SHALL SEAL ALL FIRE RATED PENETRATIONS
WITH A FIRE SEALANT EQUAL TO THE RATINGS OF THE
PENETRATION.
9. RISERS ARE DIAGRAMATIC ONLY. THEY DO NOT SHOW EVERY
BEND REQUIRED FOR THE INSTALLATION
10. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF
ELECTRICAL SERVICE. THE ELECTRICAL CONTRACTOR IS
RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
11. ALL CABLES SHALL BE RUN WITHOUT SPLICES. EXCEPT AS
OTHERWISE INDICATED.
12. ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL
TIMES.
13. EXACT POINT AND METHODS OF CONNECTIONS TO
EQUIPMENT'S SHALL BE DETERMINED IN FIELD.
14. ALL WORK SHALL BE DONE IN A NEAT ANO WORKMANLIKE
MANNER.
GENERATOR PACKAGE UNIT
OUTLINE SPECIFICATIONS
THIS GENERATOR PACKAGE SHALL CONSIST OF
A 120/240V, 22 KW, SINGLE PHASE, SOUND
ATTENUATED, FULLY PACKAGED, GUARDIAN
AIR-COOLED GAS ENGINE GENERATOR SET
INCLUDE:
BATTERY CHARGING ALTERNATOR
MICROPROCESSOR CONTROL
FACTORY LOADBANK TESTED
100A MAINLINE CIRCUIT BREAKER
SOUND ATTENUATED, WEATHERPROOF ENCLOSURE, 59db
@ 23 FEET COMPOSITE MOUNTING PAD
UL 2200 LISTED
NATURAL GAS OR LP GAS FUEL
ELECTRONIC GOVERNOR
ENCLOSED CRITICAL GRADE MUFFLER
OUTLINE SPECIFICATIONS
AUTOMATIC TRANSFER SWITCH 150A, TWO (2) POLES,
120/240 VOLTS, SINGLE PHASE, 22 KAIC. IN A NEMA 3R
ENCLOSURE W/ 150A M.C.B, SERVICE ENTRANCE
EQUIPMENT RATED
one line diagram
EXISTING 150 AMP
SINGLE PHASE
120/240 VOLT
METER/ MAIN
COMBO
NEW 150 AMP SE
RATED TRANSFER
SWITCH WITH 150 AMP
120/240 VOLT 2 POLE
SERVICE RATED
BREAKER NEMA 3R
EXISTING INTERIOR
LOAD CENTER 150 AMP
120/240 VOLT SINGLE
PHASE NEMA 1
2
REUSE EXISTING
GROUNDING ELECTRODE
SYSTEM, CONFIRM
SEPERATION OF GROUNDS
AND NEUTRALS IN EXISTING
LOAD CENTER AND
TRANSFER SWITCH
WIND DESIGN REQUIREMENTS:
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH
EDITION
(2017))
AT-GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY= III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY
FACTOR Kd=
0.85
ENCLOSURE CATEGORY= N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR= 0.85 PRESSURE AT HEIGHT H qh
= 77.56
lb/ft2
FORCE COEFFICIENT Cf= 1.44
WIND PRESSURE:
P = qh G Cf= 56.80 lb/ft2 (ASD)
CONCRETE PAD
-----50" ---
4" APPROVED
PRECAST PAD
PRECAST PAD DETAIL DAVID THOMPSON5411 LAKE PLACE DRIVEFORT PIERCE, FL. 34951CONTRACTOR:
CODE INFORMATION
MARCOPE, LLC
5818 LYDA LANE
ORLANDO, FL. 32839
CGC1514240 EC13001174
1
BRAND & MODEL CAPACITY WIDTH LENGTH HEIGHT WEIGHT ALLOWABLE PRESSURE Generac 005871 & 005883 lOKW 25.00" 48.00" 29.00" 387 lbs 41.43 Psf Generac 005872 & 005884 14KW 25.00" 48.00" 29.00" 439Ibs 47.44 Psf Generac 6459, 6461, 6462 16KW 25.00" 48.00" 29.00" 513 lbs 47.44 Psf Generac 006721 16KW 25.00" 48.00" 29.00" 448 lbs 47.44 Psf Generac 005873 & 005885 17 KW 25.00" 48.00" 29.00" 455 lbs 47.44 Psf Generac 005874 & 005886 17 KW 25.00" 48.00" 29.00" 421 lbs 47.44 Psf Generac 005875 & 005887 20KW 25.00" 48.00" 29.00" 451 lbs 47.44 Psf Generac 006729 & 006730 20KW 25.00" 48.00" 29.00" 516 lbs 47.44 Psf Generac 006551 & 006552 22 KW 25.00" 48.00" 29.00" 526 lbs 47.44 Psf Kohler 14RES & 20RES 14-20 KW 26.00" 48.00" 29.00" 500 lbs 47.44 Psf GE 40323GE & 40324GE 13 KW 35.00" 39.40" 39.00" 540 lbs 39.09 Psf GE 040382 15KW 15 KW 33.00" 48.00" 30.50" 484 lbs 43.83 Psf GE 040378 17KW 17 KW 33.00" 48.00" 30.50" 484 lbs 43.83 Psf GE 40330GE & 40331GE 20KW 33.00" 48.00" 30.50" 600 lbs 43.83 Psf Briggs & Stratton 040243-0 lOKW 31.00" 32.00" 34.00" 430 lbs 43.83 Psf Briggs & Stratton 040302-2 12 KW 33.75" 50.00" 31.60" 507 lbs 41.43 Psf Briggs & Stratton 040303-1 15 KW 33.75" 49.00" 31.60" 562 lbs 43.83 Psf Briggs & Stratton 040304-1 18KW 33.75" 49.00" 31.60" 568 lbs 44.00 Psf Briggs & Stratton 040305-1 20KW 33.75" 49.00" 31.60" 570 lbs 44.00 Psf Generac 7035, 7036, 7037 16KW 25.00" 48.00" 29.00" 406 lbs 47.44 Psf Generac 007038 & 007039 20KW 25.00" 48.00" 29.00" 448 lbs 47.44 Psf Generac 007042 & 7043 22 KW 25.00" 48.00" 29.00" 466 lbs 47.44 Psf
COMMENTS EXP C 175 MPH & D 156 MPH
EXP C 186 MPH & D 156 MPH
EXP C 170 MPH & D 156 MPH
EXP C 180 MPH & D 156 MPH
EXP C 175 MPH & D 156 MPH
EXP C 180 MPH & D 156 MPH
EXP C 186 MPH & D 156 MPH
NEW EXTERIOR LOAD
CENTER 150 AMP
120/240 VOLT SINGLE
PHASE NEMA 3R
MOVE EXISTING LOADS
FROM METER/MAIN COMBO
TO NEW LOAD CENTER
4
4
FEEDER
1
2
FEEDER SCHEDULE
FEEDER SIZE
Existing 3-#2/0 AL IN 2" PVC or 3-#1 CU IN 1 1/2" PVC
NEW 3 #1 AL + 1 #6 GD IN 1 1/4" PVC
NEW 3-#2/0 AL IN 2" PVC or 3-#2/0 CU IN 1 1/2" PVC
NEW 3-#2/0 & 1-#4 AL IN 2" PVC or 3-#1 & 1-#6 CU IN 1 1/2" PVC
FEEDER AS PER NEC TABLE 310.15(B)(6)
3
4
NEC 702.7(A) STANDBY POWER SOURCES. A SIGN THAT
INDICATES THE TYPE AND LKOCATION OF ON-SITE OPTIONAL
STANDBY POWER SOURCES MUST BE PLACED AT THE
SERVICE-ENTRANCE EQUIPMENT.
FUEL PIPE SHALL BE BONDED AS PER NEC 250.104(B)
GENERATOR FRAME TO GAS PIPE ONLY.
TRANSFER SWITCH IS NON-SEPARATELY DERIVED SYSTEM.
ALL ELECTRICAL / PLUMBING / MECHANICAL EQUIPMENT SHALL BE
ABOVE REQUIRED ELEVATION AS PER CHAPTER 11C-5(F)(4)
SOIL STATEMENT:
THE EXISTING SOIL INSPECTED IS SUITABLE FOR SUPPORT OF THE
PROPOSED CONSTRUCTION AND THE BEARING CAPACITY OF THE
SOILS FOUND MEET OR EXCEED 2000 PSF.
(3)-3/8"0 TITEN HD OR EQUIVALENT,
2-3/4" FULL EMBED TO CONCRETE, 3" MIN EDGE DISTANCE, 6" MIN.
SPACING TO ANY ADJACENT ANCHOR.
NFPA 37, Section 4.1.4, Engines Located Outdoors: Engines, and their
weatherproof housings if provided, that are installed outdoors shall be
located at least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52
m) from structures having combustible walls.
Based on this testing and the requirements of NFPA 37
Sec 4.1.4, the guidelines for installation of the generators listed are
changed to 18 in (457 mm) from the back side of the generator to a
stationary wall or building. For adequate maintenance and airflow
clearance, the area above the generator should be at least 5 ft (1.52 m)
with a minimum of 3 ft (0.91 m) at the front and ends of the enclosure.
This includes trees, shrubs, and bushes. Vegetation not in compliance
with these clearance parameters could obstruct air flow. In addition,
exhaust fumes from the generator could inhibit plant growth