Loading...
HomeMy WebLinkAboutField Density ReportANDERSEN ANDRE CONSULTING ENGINEERS, INC. 834 SW Swan Avenue Port St. Lucie, Florida 34983 Phone: 772-807-9191 Fax: 772-807-9192 www.aaceinc.com FIELD DENSITY TEST REPORT PROJECT: FPL Solar Interstate Education/Operation Center FILE NO: 20-148 St. Lucie County, FL % REPORT NO: 20 REPORTED TO: Curington Contracting CC: DATE OF TESTS): 07/0212020 PAGE NO.: 1 OF 1 TEST NO, Dumpster Pad Subgrade MDR MOISTURE DENSITY PERCENT DEPTH NO. CONTENT(/o) (PCF) COMPACTION LOCATION 1 NEC of Pad 3065 10.3 106.5 95 0 to -12" FS 2 NWC of Pad 3065 9.9 107.0 96 0 to -12" FS 3 SWC of Pad ' 3065 10.6 106.7 96 0 to -12" FS 4 SEC of Pad 3065 10.2 108.0 97 0 to -12" FS DENOTES IN -PLACE DENSITY TEST DOES NOT MEET MINIMUM COMPACTION REQUIREMENT OF 95 PERCENT. ** RETEST INDICATED DENSITY MEETS OR EXCEEDS MIN. DENSITY REQUIREMENTS PER SPECIFICATIONS FIELD TE81' ASTM D 2937 jv ASTMM D-2922 I- ASTM D-2167 F ASTM D-1555 TECHNICIAN: SM REMARKS: LABORATORY MOISTURE -DENSITY RELATIONSHIP F= SOIL DIRECTLY BELOW FOOTING FS = FLOOR SLAB SUBGRADE OPTIMUM GA = SOIL IN GENERAL COMPACTED AREA PAV = SOIL BELOW STABILIZED SECTION MDR NO. ASTM MAX. MOISTURE PSSG = STABILIZBD SUBGRADE PB z PAVEMENT BASE TEST METHOD DENSITY CONTENT RS = ROADWAY NSSG = NON STABILIZED SUBGRADE 3065 D1557 111.7 PCF 10.1 % SBP = SOIL BELOW PAVEMENT TOP = TOP OF PPE BOP = BOTTOM OF PIPE BOS = BOTTOM OF STRUCTURE OTHER: 617 L i F417ep'G. ANcFsqD7%6 *Ia'. Reg. ND. 57956 AS A MUTUAL PROTECTION TO CLIENTS, THE PUBLIC AND OURSELVES, ALL REPORTS ARE SUBMITTED AS THE CONF[ kl'I5'7� RROPERT I AIJ0 AUTP FOR PUBLICATION OF STATEMENTS, CONCLUSIONS OR EXTRACTS FROM OR REGARDING OUR REPORTS IS R�RiLln�,9NDIN U Ij��{{��N APPRZ ��. �ZORIE77P.•►