2'-6"��
WINDOW
3'
2'-6..........
WINDOW
----------- -------------- ------------------------------
12"x12" REINFORCED FOOTER
NOTES:
SUB —GRADE SOILS:
—TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION
CONCRETE:
—MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
—ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
—MINIMUM GRADE 40 STEEL
—REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
—THE REBAR IS BENT COLD
—THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6—BAR DIAMETERS: AND
—REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
—COVER:
—2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF J" FOR FINE
GROUT, AND I" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER AND 1i" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATION:
—METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
3,-5y„ 2,-6
------------------------------------WINDOW
----------
4%54" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES —
AND EVERY OTHER END —WALL POST
2" MIN.—{ H- 'BASE RAIL
—�—I
2,500 PSI 4"
CONCRETE SLAB WITH
I
I-12"
W.W.F. OR FIBER MESH
MINIMUM SOIL BEARING
CONTINUOUS WITH MINIMUM
CAPACITY 2,000 PSF(TYP.)
12" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR
DETAIL
2 5" PLAN VIEW DOOR FRAMING
if J" RECESS
4"
DOOR WIDTH
ELEVATION VIEW
DOOR FRAMING
" RECESS
.75"T [ — —4„ DOOR WIDTH —
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
MIN. 2,500 PSI 4" CONCRETE SLAB WITH W.W.F. (OR FIBER
MESH) AND 12"02" REINFORCED FOOTER PERIMETER
------------------------------------------------------- SWIN NG-------------------------------------------------------------------ROu--UP------------------------------------------------------- RQLL=UP ----------------------
DOOR DOOR DOOR
12'-17" 3'-0" 10'-316" 10'-0" 3'-7" 10'-0"
2'-0"
i
'Z
i0
ILL -
CODE VERSION
r+o R P— � —
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,560 SQ. FT.
REVISIONS
REVI
DESCRIPTON
DATE
I BY
1
IREDESIGNED 52'L
6/29/20
IMTB
1 m, o,. MTB
DATE: 4/ 1 9/20
LOCATION: 5417 Cassia Dr., Ft. Pierce
SIZE: 521 X 30'W X 12'H
N
O
u
u
CD
W
6/30/20
z
MattheW T. BaldWin P.E.
Q
Florida License #64608
Sheet: CA-1 OF 4
12
3[::�—
FRONT/REAR END WALL
O.C. MAX.
10'-0"
0
10'-0"
0
0
ROLL —UP
DOOR
0
ROLL —UP
DOOR
sWiNciNc
DOOR
3'-7"
3'-0"
LEFT SIDE WALL
O.C. MAX.
E
2'-6"
WINDOW jo
N
2'-6"
WINDOW 1
N
2'-6"
WINDOW
N
Lj
RIGHT SIDE WALL
CODE VERSION
FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-165mph
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,560 SQ. FT.
REVISIONS
REV I DESCRIPTON DATE I BY
1 IREDESIGNED 52'L 1 6/29/20 1 MTB
MTB
4/19/20
5417 Cassia Dr., Ft. Pierce
52'L X 30'W X 12'H
W_
i
z
Q
LL-
Z
W
'd
6/30/20
Matthew T. Baldwin P.E.
IW
Florida License #64608
ci
Cn
Sheet:
CA-2 OF 4
N
WINDOW
sWINGING
DOOR
FRONT/REAR END WALL
LEFT SIDE WALL
RIGHT SIDE WALL
WINDOW
WINDOW
........ ..i ► l 1►fr�� l
CODE VERSION
FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-165mph
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,560 SQ. FT.
REVISIONS
REV I DESCRIPTON DATE BY
1 IREDESIGNED 52'L 1 6/29/20 1 MTB
MTB
4/19/20
5417 Cassia Dr., Ft. Pierce
52'L X 30'W X 12'H
W_
Z
W
6/30/20
Matthew T. Baldwin P.E.
IW Florida License #64608
Cn Sheet:
CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SC) 12 14xi" SELF —DRILLING
NIPPLE TO
V \ BASE RAIL NIPPLE
BASE I
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
I'
It
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
SINGLE OR DOUBLETS
HEADER
PPLE
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
12-14xi" SELF —DRILLING
_Ws
SINGLE OR DOUBLETS
HEADER
INTERMEDIATE POST TO
POST TO BASE RAIL END POST TO BASE RAIL HEADER/BASE RAIL/OR HEADER CONNECTION HEADER CONNECTION DETAIL
CONNECTION CONNECTION WINDOW RAIL DETAIL DETAIL OPTION 1 OPTION 2
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
NON—STRUCTURAL HEADER OR
WINDOW RAIL TO POST DETAIL
INTERIOR
#12-14xi" SELF —DRILLING
SCREWS ® 10" O.C. MAX.,
3" MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS VERTICALLI
EXTERIOR
DOOR FRAME TO POST
CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP SECURED
J I U. VAX. JF fAl INIi
[ziU' VARIES
ry
SIDE WALL ROLL —UP
DOOR/FRAME OUT
HEADER DETAIL
INSTALL PER MANUFACTURERS INSTRUCTIONS
#14x1" SELF —DRILLING
SCREWS ® 6" O.C. MAX.
& 6" MAX. FROM CORNERS
ROLL —UP DOOR TO
POST CONNECTION
DESIGN PRESSURES
— 165 Mph
ROOF
+23.3/-51.6
WALLS
+25.4/-28.6
DOORS
+25.4/-28.6
WINDOWS
+25.4/-28.6
1
2
3
4
5
ZONE
+12.0
—26.8
+14.9
—40.7
+23.3
—51.6
+24.2
—25.9
+25.4
—28.6
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xi" SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-140" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
LE TO
16 GA. U—CHANNEL
BRACE, MIN. 24" UP TO
m 7' POST, MIN. 48" OVEF
6„ 7' POST. MIN. 45' TO
MAX. 60' FROM HORIZ.
(EXCLUDE END —WALLS)
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xj" SELF —DRILLING
SCREWS
BOX EAVE RAFTER TO
NIPPLE
TRUSSED RAFTER
NIP
TO TR
POST CONNECTION DETAIL I CONNECTION DETAIL
MINIMUM 6" TS NIPPLE.
NIPPLE SECURED TO WALL
POST WITH (4)#12-14xi"
SELF —DRILLING SCREWS
POST TO TRUSS
CONNECTION
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 — R 1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL12765.3—R5
SERIES 3100
WINDOW
POCOHONTAS ALUMINUM COMPANY, INC.
FL12940—R5
MODEL 100VS
CODE VERSION
FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 30C
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,560 SQ. FT.
REVISIONS
REV
DESCRIPTON
DATE
1
IREDESIGNED 52'L
1 6/29/2l
BY: MTB
4/19/20
5417 Cassia Dr., Ft. Pierce
52'L X 30'W X 12'H
(„ 6/30/20
J
Q MattheW T. BaldWin P.E.
Florida License #64608
Sheet:
CA-4 OF 4