HomeMy WebLinkAboutProject Information�/� C A Manual S Compliance Report Job: Lot 24 Block Waterstone... , DEL -AIR Date: DECEMBER 13, 2010 KF Ma•AM C001110=11 Entire House By: DCs DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407,333.2665 Fax: 407-333-3853 Web: WWW.DrL-AIR.COM Project• For: ADAMS HOMES 8204Amalfi Circle, Fort Pierce, FL 34951 Cooling Equipment Design Conditions design DB: 90.4°F Sensible gain: 26756 Btuh Outdoor design WB: 77.4°F Latent gain: 4820 Btuh Indoor design DB: 75.0°F Total gain: 31576 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASH Manufacturer: Carrier Model: 25HBC537A0030+FX4DNF037L Actual airflow: 1167 cfm Sensible capacity: 28117 Btuh 105% of load Latent capacity: 5248 Btuh 109% of load Total capacity: 33366 Btuh 106% of load SHR: 840% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 29898 Btuh Indoor design DB: 70.0°F Entering coil DB: 76.5°F Entering coil WB: 63.3°F RECEIVED APR 3 0 2020 Permitting Department St. Lucie County Entering coil DB: 69.5°F Manufacturer's Performance Data at Actual Design Condite P� Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC537AO030+FX4DNF037L Actual airflow: 1167 cfm Output capacity: 31707 Btuh 106% of load Capacity balance: 37 IF Supplemental heat required: 0 Btuh Economic balance: -99 OF Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 8.8 kW 100% of load Temp. rise: 23 OF Meets all requirements of ACCA Manual S. ' Wrightsoft- 2020-Mar-1909:14:58 ••• •.. .�-.v.•..•, Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ACM ...aterstcne2330BGR\Lot24Blk2Waterstone2330BGR.rup Cate =MJ8 House faces: W Lot 24 1RDEL-AIR Component Constructions Job: DECE Block ER13, terstohe... Date: DECEMBER 13, 2010 HUMS GIB COIIDMBNMC Entire House By: DCs DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DrL.AIR.COM For: ADAMS HOMES 8204Amalfi Circle, Fort Pierce, FL34951 Design• Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain R• 81 Mt?-F W-'F/BNh BtuhfiF Btuh BtuhV Btuh Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav Ins, 1/2' gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud n 450 0.201 4.1 5.83 2623 4.06 1827 ne 21 0.201 4.1 5.83 125 4.06 87 e 380 0.201 4.1 5.83 2218 4.06 1545 s 400 0.201 4.1 5.83 2334 4.06 1625 w 228 0.201 4.1 5.83 1327 4.06 924 all 1480 0.201 4.1 5.83 8626 4.06 6009 213 0.091 13.0 2.64 561 1.31 279 Windows 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, n 1/8" thk; NFRC rated (SHGC=0.70); 50% drapes, medium; 23 ft s overhang (6.67 ft window ht, 0.67 It sep.); 6.67 It head ht all 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 114" gap, n 118" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 it overhang (3.17 ft window ht, 2 it sep.); 6.67 it head ht 2A-2ov:2 glazing, cir low-e outr, air gas, vnl frm mat, cir innr, 114" gap, n 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (5.25 ftwindow ht, 2 ft sep.); 6.67 it head ht 2A-2ov:2 glazing, cir low-e ouir, air gas, vnl frm mat, clr innr, 1/4" gap, ne 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.67 ft overhang (5 it window ht, 0.33 ft sep.); 6.67 it head ht 100-v: 2 glazing, cir low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, e 1/8" ink; NFRC rated (SHGC=0.70); 50% drapes, medium; 9.67 it overhang (6.67 ft window ht, 0.67 ft sep.); 6.67 it head ht 2A-2ov:2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, e 118" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 7 ft overhang (5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 16 0.550 0 16.0 248 12.6 197 18 0.550 0 15.9 284 12.6 225 33 0.550 0 15.9 532 12.6 421 10 0.330 0 9.57 93 8.52 83 16 0.330 0 9.57 155 8.52 138 13 0.330 0 9.57 120 17.7 221 18 0.550 0 15.9 284 12.6 225 17 0.330 0 9.57 160 8.52 142 wrightsoR' 2020-Mar-1909:14:58 "N,.-, •h•"• aft Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ...aterstone2330BGR\Lot24Blk2Waterstcne2330BGR.rup Colo =MJB House faces: W 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, air innr, 1/4" gap, a 30 0.330 0 9.57 287 8.52 256 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 9.67 it overhang (5 It window In, 0.33 It sep.); 6.67 It head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, a 49 0.330 0 9.57 465 22.9 1112 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 it s 32 0.330 0 9.57 310 8.52 276 overhang (5.25 it window ht, 1 it sep.); 6.67 It head ht all 81 0.330 0 9.57 775 17.2 1388 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, w 77 0.330 0 9.57 738 21.4 1649 1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 it overhang (6.25 ft window ht, 1 ft sep.); 6.67 It head ht 2B-21v: 2 glazing, clr low-e oun, air gas, vnl frm mat, clr innr, 1/4" gap, w 10 0.330 0 9.57 96 11.6 116 1/B" Ink; NFRC rated (SHGC=0.31); 10.33 ft overhang (2 ft window ht, 1.33 it sep.); 6.67 If head ht 28-2fv: 2 glazing, air low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, w 13 0.330 0 9.57 128 19.5 260 1/8" thk; NFRC rated (SHGC=0.31); 10.33 it overhang (6.67 it window ht, 4.17 it sep.); 6.67 It head It Doors 11JO: Door, mil fbrgl type w 20 0.600 6.3 17.4 348 17.6 352 11 DO: Door, wd so type n 18 0.390 0 11.3 201 11.4 203 Ceilings 16B-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 2536 0.032 30.0 0.93 2353 1.69 4285 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 211 0.989 0 28.7 6056 0 0 wrightsof - 2020-Mar-19 09:14:58 AWNr� Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2 ...aterstone2330BGR\Lot248lk2Waterstone2330BGR.rup Cale =MA House faces: W Lot 24 RDEL--AIR Project Summary Job: DECE Block ER13, terstone... 1 y Date: DECEMBER 13, 2010 HUM13• GIB CCtmm01MG Entire House By: DCS DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-33MEIM Web: W W W.DEL-AIR.com Pro"ect Information For: ADAMS HOMES 8204Amalfi Circle, Fort Pierce, FL 34951 Notes: RVSD 1-3-11 DCS RVSD 8-20-15 JA L. S. 3-19-20 VWK Design Weather: St Lucie Cc Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 Moisture difference 57 gr/lb Heating Summary Structure 25191 Btuh Ducts 4707 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 29898 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ft2) 2330 2330 Volume ft3) 21646 21646 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 115 58 Heating Equipment Summary Make Carrier Trade CARRIER Model 25HBC537AO030 AHRI ref 10487322 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacity balance point = 37 OF "":Wgo 34600 Btuh @ 470F 27 0 1167 cfm 0.039 cfm/Btuh 0.30 in H2O Backup: Input = 9 kW, Output = 29893 Btuh, 100 AFUE Sensible Cooling Equipment Load Sizing Structure 20305 Btuh Ducts 6451 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Equipment sensible load 26756 Btuh Latent Cooling Equipment Load Sizing Structure 3231 Btuh Ducts 1590 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 4820 Btuh Equipment Total Load (Sen+Lat) 31576 Btuh Req. total capacity at 0.75 SHR 3.0 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond 25HBC537AO030 Coil FX4DNF037L AHRI ref 10487322 Efficiency 12.5 EER, 15.5 SEER Sensible cooling 26250 Btuh Latent cooling 8750 Btuh Total cooling 35000 Btuh Actual air flow 1167 cfm Air flow factor 0.044 cfm/Btuh Static pressure 0.30 in H2O Load sensible heat ratio 0.85 Calculations approved by ACCA to meet all requirements of Manual J Sth Ed -rk- =Lqn> --ft- 2020-Mar-19 09:14:5B A ton ^ - Righemione Universal p Colo = 2 RS 2382BHouse Page 1 ...aterstone2330BGR\Le124BIk2Walerslone23308GR.rup Catc=MJB House faces: W '�QEL-AIR Right-J® Worksheet �°°""'m`°' Entire House DEL -AIR HEATING & AIR 531 CODISCO WAY, SANFORD, FL 32771 PPhhNDNIG 4D7IO3.2665 Fax: 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 Room name Entire House MASTER BDRM 2 3 Exposed wall Room height 211.2 (1 9.3 It 40.0 it 8.0 It heat/coal 4 5 Room dimensions Roam area 2339.3 ft' 14.5 x 16.5 It 239.3 ft2 Ty Construction number U-value (Btuh/fti-F) Or HTM (Btul✓ft2) Area (IF) or perimeter (ft) Load (Btuh) Area (fv) or perimeter (It) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Vy �C Blkwall stucc6& tO -v 2A 2ov 2A 2ov _ Blk wall stucco exl 2A 2ov __ Blk wall, stucco ezt tOGv 0201 0.550 0.330 0.330 0,201 0.330 0.201 0550 n n n . R. no ne -e _ a 583 15.95 9.57 _- 9.57 5.83 _9 57 _ . 5.83 15.95 4.06 12.64 8.52 8.52 4.06 17.70 - � 4.06 1264 492 16 10 16 34 13 �_ � 494 18 450 0 0 0 21 0 "`-380 18 2623 248 93 __._ 155 125 120 -- -2218 284 -- 1827 197 83 -_ _138 87 221 -_ 1545 225 132 0 0 _.._0 --- -- 132 0 0 __-___0 0 0 -- 769 0 0 __o 0 _ _ 0 `- `487 0 - 536 0 0 _ 0 0 _ 0 � - 340 0 �L-CG W, �--(' 0 _ µ,_ 0 116 0 __ _ -eb 0 ._..__ �C 2A 2ov 2A 2ov 2A 2ov ___._.__ _ Blk wall, stucco ext 10G-v 0.330 0.330 _-..0.330 0.201 0.550 a e ...e _ s 5 9.57 9.57 _..-9.57 5.83 15.95 8.52 8.52 . _ 22.90 4.06 12.64 17 30 __. _ _ _49 451 18 17 30 __._.._._7 4G0 18 160 287 ._.._ _.465._.__.1112 2334 284 142 256 1625 225 0 0 ____.. .32 72 18 0 0 ..,. _ ___l 54 18 0 0 __._...310 316 284 0 0 ..__741. 220 225 R �_ D - ' C _ F 2A 2ov Blk wall AWccdext 2A 2ov 2021v 28 2tv 11,10 _ . __ _ ... 12C-Osw 11DO _ 16B 30ad _ _ _, 22A-tpl , `. 0,330 0.201 0.330 0330 0.330 __.-0.600 0.091 _ ___ 0.390 __ 0,032 0.989 _ s W w w w __w_ - n .- - 9.S7 - 583 9.57 957 9.57 __77.40 2.64 11.31 '0.93 28.68 _ 8.52 4.06 21.40 11.58 19.46 .. _17.58._._._..20 1.31 11.43 -.... 1i69 _ 0.00 _ __ 32 348 77 '10 13 231 18 _ __ 2536 . , 2339 __ 32 -' 228 1 10 9 _..__._.20 213 _ _ 18 - _ 2536 --_ 211 _ 310 --1327 738 96 128 _. _...348._.__..352 561 201 _ 2353 6056 __ _276 924 1649 116 260 279 203 .. _.__4285 0 ___ _ 0 _ 0 0 0 0 ..._.__.0 0 _ 0 239 239 __ 0 0 0 0 0 __._... _0 0 _ 0 ..239 40 ____ 0 0 0 0 0 _-.._ ----0 0 0 ;� , .- 222 1147 _ 0 '0 0 0 0 _ ._. _0 0 _ _ 0 _ 404 0 6 c) AED excursion 353 _76 Envelope lass/gain 21512 16379 3536 2390 12 a) Infiltration b) Room ventilation 3679 0 ^ 977 0 648 0 172 0 13 Internal gains: Occupants @ 230 5 1150 1 230 Appliances/other 18W 0 Subtotal (lines 6 to 13) 25191 20305 4183 2792 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 19% 32% 0 0 0 25191 4707 0 0 0 20305 6451 19% 32% 0 0 0 4183 782 0 0 0 2792 887 Tat room load Air required (cfm) 29898 1167 26756 1167 4965 194 3679 160 Calculations approved by ACCA to meet all requirements of Manual J Sth Ed -- wrlghGsosft- 2020-Mar-19 09:14:58 c� RightSuileG Universal20l9 l9.0.12 RSU23828 Page 1 ...aterstone2330BGR\L0124Blk2Waterstcne2333BGR.rup Colo =MJ8 House faces: W '1 DEL -AIR Right-M Worksheet °°"°'MUNU MO Entire House DEL -AIR HEATING & AIR 531 CODISCO WAY, SANFORD, FL 3277CONDITIONING 1 Phone: 407-333-2665 Fax: 407.333-3653 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 Room name M. WIC M. WIC II 2 3 4 5 Exposed wall Room height Room dimensions Room area 6.5 R 8.0 It heat/cool 7.5 x 6.5 If 48.8 ftr 0 It 8.0 If heat/cool 7.0 x 6.5 If 45.5 ft2 Ty Construction number U-value (BtuhfftzcF) Or HTM (Btuh/ffj Area (W) or perimeter (ft) Load (Btuh) Area (f12) or perimeter (ft) Load (Brun) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W_.__. 1-.^- IL-_GG W I--G --.-'--4.06"-._ yyll (--G IL-�-GGG _ 11- D . _ C.-_ F Blk wallstucbb ezt __ '%v 2A-2ov 2A-2ov._._____.._.,..._ Blk wall, stucco exf 2A_2ov Blkwall stucco exf 2A-2o 2A 2ov 2A 2ov 2A2ov.._......_.___. Blk wall, stucco ext 10C-v 2A 2ov Blk wall stucco exf 2A 2ov 2B2fv 2B.2ty .11J0.___._..-_ _- 12C-0sw . 11DO __ 16B�Oad _._ 22A-tpl _ .__-6.201 0.550 0.330 ._0.330 0.201 0,330 - 0.201 0.330 0330 0.330 __.0.330 0.201 0.550 _ 0.330 -0.201 0.330 0.330 0.330 __ 0.600 0.091 0.390 0,989 0.989 �n n n _n......_ ne no e' a e e .a-. s s s _w.... w w w _.w_ - n_ _._ - __ -. 5.88 15.95 9.57 .9.57 5.83 9.57 _...583 1557 9.57 9.57 9.57...2290...__.__0____._0__ 5.83 15.95 9.57 583 9.57 957 9.57 ___17.40 2.64 11.31 .__ 8.68 28.68 ._..4.06_ 1264 8.52 --.8.52 4.06 17.70 18.52 8.52 8.52 4.06 1264 _ 8.52 �4.06 21.40 11.58 19.46 .,_-17.58 1.31 11.43 ._ _ 1.00 0.00 _____52 0 0 __.__0 0 0 .._.__0 0 0 0 0 0 0 _._._ .0. 0 0 0 -0 0 .. _ _- 0 49 49 ___--- .52 0 0 _,..._._._.0 0 ___ 0--.,,__0 0 0 0 0 0 0 0 _ -0 0 0 0 _ ____0 0 __-. __ 0 �.__4986 7 __._306 0 0 _,____0 0 _0-,.__.._.0._ 0 0 0 --- --- 0.____._0 0 0 0 __ __ 0 - 0 0 0 ._ __0 0 ___...._. 0 186 __.-211-_- 0 0 0 0 0 0 0 0 0 0 0 _,____0 0 0 0 ______0 0 .__ ._ 0 ^__._80 0 _0 0 0 _ _ 0 0 0 ___.0 0 0 0 ___... _.0 0 0 0 _._. _,0 0 0 0 __. _ ._0 0 _ .. 0 _.___. 46 46 .- _p 0 0 0 0 0 _- .0 0 0 0 :0 0 0 0 __ _ __ 0 '0 0 0 0 _ _._. 0 _. .___40 0 -___.d 0 0 __�.. 0 0 0 ,__...._.. 0 0 0 0 0 0 0 ___0 0 0 0 0 _ ._ _ 0 _ -_____42 _- _ 42 0 - _ - �. _.. _0 0 0 _.�-_ 0 0 __... 0 0 0 0 0 0 0 _ _0 0 0 0 0 _ _ . 0 77 0 _ _ 6 c)AED excursion -18 -4 Envelope loss/gain Sm 275 42 73 12 a) Infiltration b) Room ventilation 105 0 28 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6to 13) 640 303 42 73 14 15 Less external load Less transfer Redistribution Subtotal Duct loads I9r 32% 0 0 0 640 120 0 0 0 303 96 19% 32% 0 0 0 42 8 0 0 0 73 23 Total room load Air required (cfm) 760 30 400 17 50 2 96 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed 2020-Mar-19 09:14:59 _`..A Right -Suite® universal BOR.r p alc m 2 RS House Page 2 ...aterstone2330BGR\Lot24BIk2Waterstone2330BGR.rup CaIc=MJB House faces: W 'DEL --AIR Right-JO Worksheet °"°�'=11KNo"�0 Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAV, SANFORD, FL27 371 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 Room name M. BATH M. W/C 2 Exposed wall 10.0 it 0 it 3 Roam height 8.0 it heat/coal 8.0 it heat/cool 4 5 Roam dimensions Room area 1.0 x 129.0 it 129.0 f12 4.0 x 4.0 it 16.0 W Ty Construction U-value Or HTM Area (09 Load Area (ft') Load number (BtulVltLcF) (Btutvftg or perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Blk wall,`stuccoekl-, 10Gv 2A 2ov 2A-2ov-v __,. _... _ Blk wall, stucco ext -�-- 0201 0650 0 330 0.330 0.201 n n d _n_ ne 583 1595 9 57 __,..9.57 5.83 _...406 1264 8.52 ...__8.52 4.06 _....._ .80 0 10 _.-.-0 0 .._. .......70 0 0 -__-_ -0 0 409 0 93 _ _0 0 285 0 83 . - _ 0 0 "-...._ 0 0 0 ._ -__ _.0 0 .. ____ 0 .0 0 ._._0 0 _...._._.0 0 0 0 0 . ._._ ,_0 0 0 .- _ _ 0 0 W 2A 2ov Blk wall stucco ext 103-v .,, 0 330 0201 0.550 ne, a a 9 57 583 15.95 _17.70 4.08 1264 0 "`0 0 0 �� -0 0 0 "� �0 0 0 0 0_ 0 0 0 0_ 0 0 0 2A20v 2A 2ov 0330 0330 a a 957 957 8.52 8.52 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I-G 2A2ov___- ., Blk wall, stucco ext 10c-v ___0.330 0.201 0.550 e_. s s __9.57_ 5.83 15.95 .22.90.____0 4.06 1264 0 0 0___ 0 0 .0 0 0 _. __._0 0 0 __..0 0 0 _. :0__. 0 0 0 0 0 ...0 0 0 2A2ov Blk wall stucco ekl 0330 0.201 s w 957 -'-583 8.52 4.06 _0 � " 0 0 - � 0 ___ 0 ` � 0 _ _0 � �� 0 _ 0 - --0 0 0 0 0 0 - 0 2A2ov 26 2fv 28 2fv 0330 0.330 0.330 w w w 957 957 9.57 21.40 11.58 19.46 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 _ .11J0_- __. _.__ __.._0.600 w_.__17.40 _17.58 ^.0_., --- --0 ---0 __�-0_____0-___0 P LD 120-0sw 11D0 0.091 0.390 - n 2.64 11.31 1.31 11.43 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 G _.._. F 168-30ad_ _. _.. ??A-tpl ___0032 0.989 _---_098_ 28.68 I.69 0.00 .-'-129` 129 129. 10 _ - _ 120-.�_�_218. 287 0 _ 16 16 y ,18_ 0 -15 0 ... _27 0 6 c) AED excursion -35 '2 Envelope loss/gain 909 551 15 26 12 a) Infiltration 162 43 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1071 594 15 26 14 15 Less external load IJsastransfer Redistribution Subtotal Duct loads 19% 32% 0 0 0 1071 200 0 0 0 594 189 19% 3el 0 0 0 15 3 0 0 0 26 8 Total room load Air required (ofm) 1271 50 783 34 18 1 34 1 Calculations approved by ACCA to meet all reouirements of Manual J 8th Ed A-r�§- wrlgtiCsoAe- 2020-Mar-1909:14:58 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 3 ...atemlone2330BGR1Lot24Blk2Waterstone2330BGR.rup Calc=MJ8 House faces: W '1 DEL -AIR Right-JO Worksheet ramaia'.m mxomoimlc Entire House DEL -AIR HEATING &AIR 531 CODISCO WAY, SANFORD, FL CONDITIONING 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 Room name LIVING RM FAMILY RM 2 3 4 5 Exposed wall Room height Room dimensions Room area 37.5 fit 9.0 If heaUcool 1.0 x 228.0 It 228.0 fie 24.0 If 11.8 It heat/coal 1.0 x 456.0 If 456.0 W Ty Construction number U-value (BtuWft'-F) Or HTM (Btuh/ftj Area (Itq or perimeter (fl) Load (Btuh) Area or perimeter (ft) Load (Bth) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 . 11 Blk wall, -stucco ezl _ 10C.v 2A-2ov 2A-2av__.__�.__._..._. Blk wall, stucco ezt 2A 2ov Blkwall stucco ezt 10Gv 2A 2ov 2A2ov 2A2ov. ._.._..,___0.330_.a____.9.57_...22.90..._...._.._0 Blk wall, stucco ext 10Gv 2A 2ov Blk wall stuccb ezt 2A 2ov 262Iv 2B2fv _11J0 .....- _.. 12C-Osw 11DO - - .. 16B-30ad _ _. 22A-lpl `--0201 0.550 0.330 _0.330 0.201 0,330 0201 0.550 0.330 0.330 0.201 0.550 0.330 -0.201 0.330 0.330 0.330 - .0.600 0.091 ... ___ 0.390 ___._ 0.032 0.989 n n n ._n.. ne ne a a e a s s s -w_ w w w '._w - n _ _._ -___ - - 5.83 15.95 9.57 _ 9.57 5.83 --.-- 9 57 583 15.95 9.57 957 5.83 15.95 9.57 __..583 9,57 957 957 __:17.40.._17.58 2.64 11.31 __- _ .._0.98 28.68 4.08 1264 8.52 ._ _8.52 4.06 17.70 `4.06-"-'�"�0 12.64 8.52 8.52 4.06 1264 8.52 - 4:06 21.40 11.58 19.46 1.31 11.43 _-_ _- L69 0.00 � � ��731 0 0 �.._._16 0 0 0 0 0 59 0 0 "�'._ .149 39 0 0 ._____0 0 _ _ 0 ___. _228 228 - ---114 0 0 _._ _.-_-0 0 0 _� �_"`0 0 0 0 .._...._o_._..0.._...._.o__.-____0.__.._:.0 59 0 0 ._ __ 110 -1 0 0 _._____0 0 _ 0 _._ �..228 38 --_-666 0 0 _._.._ 155 0 ._._.._ 0 0 0 0 0 341 0 0 _ .641 369 0 0 ..._____.0 0 __. - 0 _. 212 1076 - �-'-464 0 0 ___.__138 0 ..__.-_ 0 Ov 0 '0 0 238 0 0 _-. _.� 825 0 0 __ __0_.-._._.20 0 _ _... 0 _. _ 385 0 �'_�---0 0 0 ._ __-_0 0 0 "_782 18 0 30 0 0 0 -__..� 0 10 13 0 0 .__`_ 573 456' �`_ p 0 0 ___...___0 0 0 - 134"--_--779 18 0 30 0 0 0 _ __39 0 10 9 ___ 20_.._... 0 0 _.___573 24 � ""0 0 0 __.�-.._0 0 0 284 0 287 0 0 0 _... _ _228 '0 96 128 348..__._352 0 0 __.-532 688 -. '0 0 0 ..__._.__ 0 0 0 _-543 225 0 256 0 0 0 _ . 159 0 116 260 0 ... __ 0 .__ 968 0 .,.__ Vjl �-_ _ WWW V�1 �--G L--D Cr_. F 6 c) AED excursion 263 204 Envelope loss/gain 3459 2758 3370 3082 12 a) Infiltration b) Room ventilation 683 0 181 0 534 0 142 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 3 690 0 Subtotal (lines 6 to 13) 4142 2940 3904 3914 14 1151 Less external load Less transfer Redistribution Subtotal Duct loads 19% 32% 0 0 0 4142 774 0 0 0 2940 934 19% 32o/ 0 0 0 3904 729 0 0 0 3914 1243 Total room load Air required (cfm) 4916 192 3874 169 4634 181 5157 225 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed 2020-Mar-19 09:14:58 A Right -Suite® Universal 2019 19.0.12 RSU23828 Page 4 ...aterstone2330BGR1L0124Blk2Waters10ne2330BGR.rup Cale = MJ8 House faces: W '1 DEL -AIR Right-M Worksheet Entire House DEL -AIR HEATING &AIR 531 CODISCO WAY, SANFORD, FL 3277CONDITIONING 1 Phone: 407-333-2665 Fax: 407-333.3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 Room name DINING RM BRKFST 2 3 4 5 Exposed wall Room height Room dimensions Room area 18.0 ft 9.0 it heat/cool 13.0 x 13.0 It 169.0 Its 8.7 ft 9.9 ft heat/cool 1.0 x 108.3 It 108.3 112 Ty Construction number U-value (Stuh/ftz°F) Or HTM (BtuldfR) Area (ftq or perimeter (ft) Load (Btuh) Area (ft.) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 U�/ _.. L�GG W _C VVyy (--G IL---- ._..GGG -_ 21013-v P. LD C.. F Blk walhatucco ext 10C-v - 2A2ov 2A 2ov_ l3 k wall, stucco ext 2A 2ov Blk wall stucco &t 10Gv 2A 2ov 2A 2ov 2A2ov...... _. _._ Blk wall, stucco ext 2A-2ov _ Silk wall, stucco 6t 2A-2qv 2B-2fv 2B-2fv 11J0__.._...__ 12C-Osw 11D0 __ _.. i6B-30ad _ _ _ 22A _tpl- � 0.201 0.550 0.330 __._0.330 0.201 0.330 0 201 0.550 0.33330 0.3300 ___0.330 0.201 0.550 0.330 `-`0.201 0.330 0.330 0.330 --0.600_w-__17.40=_..17.58.__...._0_-..___0.____._A___..._0,.0 0.091 ._ 0.390 . _ 0.032 0.989 - n` n n __n_ ne ne e a e - a e. s s s vi- w w w - n .___.. __ - - -583 1595 957 . __. 9.57 5.83 9.57 5 83 15 95 9.57 ,957 __.957....22.90,___..._0.._.:._._._0.__..__0 5.83 15.95 9.57 `-5.83 9.57 9.57 9.67 2.64 11.31 -_ _ 0.93 2868 � 4.00._.._ '12.64 8.52 _.__.8.52 4.06 __17.70 4.06 1.52 8.52 8 8.52' 4.06 12.64 __ 8.52 4.06 21.40 11.58 19,46 1.31 11.43 _ 0.00 0.00 _._� 0 0 -__ _.,_ 0 0 0 �` 0 0 0 0 0 0 0 --" 117 39 0 0 59 0 .... 169 169 _ _ __-� 0 0 _. __.__0 0 0 `-"' "' "0 0 0 0 0 0 0 - -- -78 1 0 0 59 0 _718 � 18 ...___Z� 0 0 ......... 0 0 --___._0 0 0 0 0 0 0 - --457 369 0 0 154 0 _ ... 516 516 -183 0 .0 _.-.._� 0 0 0 _ _._.0 0 0 0 _.._._._0 0 0 _ _ _ 0 319 825 0 0 77 _. 0 -__200 0 _____ 0 0 0 .__ __,.0 34 13 _-.__ -36 0 17 0 __.__0 0 0 0 _____0 0 .0 0 0 _._.. 0 -" _ _ 108 108 _. ____0 0 0 _..� _ 0 21 0 _ -.__ -19 0 17 0 _.._.__,0_�.__.0 0 0 0 "- _0 0 0 0 0 0 _ 0 _..__. 179 9 _. ___ _0 0 0 .___..,�,0 125 120 - 113 0 160 0 0 0 0 -- � -0 0 0 0 0 0 0 __249 249 -01-9 0 0 .. __.. 0 87 221 -- - 78 0 142 0 __ ..0 0 0 _ 0 0 0 0 0 __..__.0 0 .. 0 .___'_ 300 0 6 c) AED excursion 336 .49 Envelope loss/gain 1916 2025 930 780 12 a) Infiltration b) Room ventilation 328 0 87 0 142 0 38 0 13 Internal gains: Occupants @ 230 Appliances/other 1 230 0 0 0 0 Subtotal (lines 6to 13) 2244 2342 1072 817 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 1 19% 32% 1 0 0 0 2244 419 0 0 0 2342 744 19% 32% 0 0 0 1072 200 0 0 0 817 260 Toat room load Air required (cfm) 2663 104 3086 135 1272 50 1077 47 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed 'rl'r' wrrghtsoft- 2020-Mar-19 09:14:58 Rightrstone universal BGR.r p Cato = 2 RS House Page 5 ...aterstone2330BGR1Lo124BIk2Waterslone2330BGR.rup CaIc=MJB House laces: W 'DEL -AIR Right-JO Worksheet Entire House DEL -AIR HEATING &AIR 531 CODISCO WAY, SANFORD, FL 32771 Phone: COND907ION6NGac 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Black Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area KITCHEN 0 it 11.2 it heat/coal 1.0 x 189.0 It 189.0 ft' LAUNDRY 0 it 8.0 it heat/cool 7.0 x 8.0 it 56.0 IF Ty Construction number U-value (Btufdit--F) Or I HTM (BtulVftg Area (fig or perimeter (it) Load (Btuh) Area (fig or perimeter (it) Load (Btuh) Heat Cool Gross WP/S Heat I Cool Gross WP/S Heat Coot 6 . 11 ._...__ ly 44yy l--G ILA--GGG ._ IN I--t' R T-D . __.. C F Bik wall, stucco e# � 100-v 2A-2ov .2A-2ov_.,_..____.__ Blk wall, stucco ext 2A 2ov Blk wolf stucco ext 10Pv 2A 2ov ZA 2ov 2A2ov _..._ BIk wall, stucco ext 10C-v 2A2ov IlKwall stuccoexl 2A 2ov 2B 2fv 2B2fv .11J0 ___. ._.. 12C-0sw 11DO . _ .10B 30ad-"-__ 22A_tpl _ _ 0201 0,550 0.330 _._ _0.330 0.201 0 330 "�0201 0 330 0.330 0.330 __.._0.330 0.201 0.550 0330 0.201 0,330 0.330 0330 ._. __0.600 0.091 0.390 ..._._0:032 0.989 n n n __n._ ne ne e�� a e a e__-_.957 5 s s -w w w w: _.w. - n -- - 5,83 15.95 9.57 _... 19.57 5.83 9 57 � 583 15.95 9.57 957 5.83 15.95 957 ---883 9.57 957 957 _ 17.40 2.64 11.31 _.. ,0.93 28.68 � - 4.06 12.64 8.52 _ _8.52 4.06 17.70 -4:06 18.52 8.52 8.52 -2290 4.06 1264 8.52 �4.06 . 21.40 - 11.58 19.46 - _ 17.511 1.31 _ _11.43 _ 1.69, 0.00 0 0 0 -� _0 0 0 0 0 0 0 ._ __.0 0 0 0 __ ..0 0 0 0 ____0 0 0 __200 189 '0 0 0 __... ...._0 0 0 � "`-0 0 0 0 _..___0 0 0 0 0 0 0 0 ... _.0 0 0 200_ 0 0 0 0 ....__.__ 0 0 _-__ 0 0 0 0 0 ._._._.0 0 0 _ 0. '0 0 0 0 ------- _0 0 _ 0 _. 1&5. 0 .��- �0 0 0 ____0 0 ..._._.._. 0 0 0 0 0 _._.__0 0 0 _0 -, 0 0 0 0 _._ _ _,_0 0 .__.. 0 337 0 �� ' 0 0 0 __._. 0 0 ____-_ 0 0 0 0 0 ,..___.. 0....____. 0 0 _ _ 0_ - ---0 0 0 0 ____0 56 _ _ 18 _56 56 '� 0 '0 0 _. 0 0 0 ��-`� �0 0 0 0 0 0 0 0 -0' 0 0 0 _ 0 38 18 �._. 56 0 � _ -0 0 0 -. . 0 0 0 �- ��-0 0 0 0 .._.__. 0. 0 0 _ _ 0 - 0 0 0 0 _. __...0 101 201 �..__ .__._ 52 0 �0 0 0 _ A _._ 0 0 _.__,..__ 0 0 0 0 0 _.0 0 0 __ 0 0 0 0 0 .__ _.0 50 _ _ 203 .. __ 95 0 6 c)AED excursion .87 -53 Envelope loss/gain 185 251 354 294 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 1200 0 0 600 Subtotal (lines 6to 13) 185 1451 3.54 894 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 19% 32% 0 0 0 185 35 0 0 0 1 45 1 461 19% 32% 0 0 0 354 66 0 0 0 894 ' 294 Total roam load Air required (cfm) 220 9 1912 831 420 16 1179 51 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed -FP' wrr9F+esoit- 2020-Mar-19 09:14:58 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 6 ...aterstone23308GRtLot24Blk2Waterstone2330BGR.rup Colo =MJ8 House faces: W 43�DEL-AIR Right-JO Worksheet Q6"G ""`W0m0H°0 Entire House DEL -AIR HEATING & AIR 531 CODISCO WAY, SANFORD, FL 327711CP0hNDa071ON665 CONDITIONING 407-333.3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BDRM 2 12.0 It 8.0 It heat/cool 1.0 x 178.0 it 178.0 IF BDRM 3 13.5 It 8.0 It heat/cool 15.5 x 13.5 If 209.3 f12 Ty Construction number U-value (Stuh/ft2-OF) Or HTM (Btuwftg Area (W) of perimeter (ft) Load (Btuh) Area (ft2) or perimeter (It) Load (BWh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 IN �G _ W, �(% I--G ILA--GGG P L-D C_ __.12A-tpl F ___ Blkwall, stucco ext 10C-v 2A-2ov 2A-2ov-___.____._ elk wall, stucco ext 2A-20v -_.. Blk wall -stucco ezt 10Gv 2A 2ov 2A 2ov .2A 2ov _.__co.__ Blk wall, Stucco exl 10Gv 2A-20v __ BIk wall., studbo e# 2A-20v 20 -2Iv 2B-2(v 11J0.._.____.__..._..__._0.600:w..__17.40__17.58 12G0sw 11D0 -_..__. _.. 22A-ipl --_ 1 _. ____ 17.201 0.550 0.330 -_ _0.330 0.201 0.330 0201--e 0 330 0.330 0,330 .._ _ 0.201 0.550 0.550 _ _0.330 .. _ 0.201 0.330 0.3 30 0.330 0.091 0.390 __. 0.989 - _ - . 0:989 -n n n _n- ne ne_ a e e ._e..._-5.87. s s 5 ._zv w w w - n_ '_ _ - _ 5.83 15.95 9.57 .9.57 5.83 9.57 ..503' 15 95 9.57 9.57 5.95 15.95 9.57 ..5.83 9.57 9.57 9.57 2.64 11.31 __. .0.93 28.68 -_ 4.013 12.64 8.52 _..--8.52 4.06 17.70 4:06 18.52 8.52 8.52 '__ 2290 2.64 12.64 8.52 ' __4:06 21.40 11.58 19.46 1.31 11.43 __ 1.69-___178____778.-.,165. 0.00 ._ _._ _ 0 0 0 ..�_ .0 0 0 _._.__.0 0 0 0 _______6 96 0 _ 16 . __ -0 0 0 0 __-.__.,0 116 0 178 ..._.._...0 0 0 _.,�.__0 0 0 __...__0 0 0 0 ... ..._ 0 80 0 IS - _ _ . _0 0 0 0 __..._. 0_.__0___._0 116 0 12 _ _ 0 0 0 ._.__..__0 0 _ _____ 0 0:�__,_r0____ 0 0 0 _..__.__5 460 0 155 _ .._ .. 0 0 0 0 306 0 344 _-. ­0 0 0 _...�_ 0 0 0 0 0 0 _...__,,._4 320 0 138 _ __.. _ 0 0 0 0 152 0 ___301 0 _. - _ _0 0 0 _.. __ _ 0 0 0 _0..__.._ 0 0 0 _._____8 100 0 16 _ _ _ 0 0 0 0 _.__.0_0 0 0 ____209 209 0 0 -. __. _0 0 0 0....__ 0 0 0 _ __ _0_ 92 0 16 _ _ _ _ _0 0 0 0 0 0 __ _ 209 14 0 0 _-_-.._ 0 0 0 _0 0 0 0 _ __0 530 0 155 _. _. _ . 0 0 0 0 0 0 0 _- _194 387 0 0 _____ 0 0 0 _-. .. __It 0 0 0 __._ _ 3 373 0 138 __ .. 0 0 0 0 0 0 0 6 c) AED excursion -54 52 Envelope loss/gain 1436 860 1271 812 12 a) Infiltration b) Room ventilation 194 0 52 0 219 0 58 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1630 912 1490 870 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 1 19% 32% 0 0 0 1630 305 0 0 0 912 290 19% 32% 0 0 0 1490 278 0 0 0 870 277 Total room load Air required (cfm) 1935 75 1202 52 1769 69 1147 50 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed .- wrighesoTt- 2020-Mar-19 09:14:58 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 7 ...aterstcne2330BGR\Lot24Blk2Waterslone2330BGR.rup Calc=MJB House faces: W 2 DEL -AIR Right-JO Worksheet Entire House DEL -AIR HEATING & AIR 531 CODISCO WAY, SANFORD, FL CONDITIONING 32771 Phone: 407-333-2665 Fax: 407-333.3853 Web: WWW.DEL-AIR.COM Job: Lot 24 Block Waterstone 233... Date: DECEMBER 13, 2010 By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BDRM 4 26.5 If 8.0 It heat/cocl 120 x 14.5 It 174.0 ft- BATH 2 14.5 It 8.0 It heat/cool 1.0 x 93.3 If 93.3 IF Ty Construction number U-value (Btuh/ftz-F) Or HTM (Btuf✓ftr) Area (Its or perimeter (ft) Load (Btuh) Area (ftq or perimeter (ft) Load (Btuh Heat Cool Gross N/P/s Heat Cool Grass N/P/S Heat Cool 6 • 11 Blk wall, Stucco eM _ 10C-v 2A-2ov ,2A-20v _._.� Blk wail, stucco ezl 2A 2ov Blk wall stucco ext' 10Gv 2A 2ov 2A 2ov 2A20v.._.. _._____ Blk wall, stucco ext 10Gv 2A 2ov Blk wallstucco.ext 2A 2ov 2B 2fv 2B 2fv 12C-Osw 11DO 166-30ad_ _ 22A-tpl ,_ __�.O,pi 0.550 0.330 .0.330__n__-9.57-__8.52 0.201 0.330 " �-0.201 0.0 0.330 0.330 .._0.330 0.201 0.550 0 330 0201 0.330 0.330 0.330 ...._.0.600 0.091 0.390 0.989 0.989 __h_ n n ne no a a e e -.e_.-9.57 s s a_ w w w w .W _ - n __ - _-5.831- 15.95 9.57 5.83 9.57 -583 1595. 9.57 9,57 5.83 15.95 __ 9.57 . 583 9.57 957 957 __17.40 2.64 11.31 _._0.93 28.fi8 - b.06-`._._.0 1264 8.52 4.06 17.70 ---4.06 1264 8.52 8.52 _.._22.90 4.06 12.64 8.52 4.06 21.40 11.58 19.46 _._._17.58, 1.31 11.43 ____1.69 0.00 0 0 ._-_.___0 0 0 96 0 0 0 __ __.-16._-_..__0 116 0 0 ____0 ,. 0 0 0 _-_.__._0 0 _ 0 _._174 174 ._-__O 0 0 __._.._ 0_. 0 0 `-'-_`�- 80 0 0 0 116 0 0 ____.__0 0 0 0 _-_ -_0 0 _ 0 27 127 --_-0 0 0 _.�..0 0 0 465 0 0 0 _ ___.155 676 0 0 .-_._._0 0 0 0 ____ -0- 0 0 __�161 _ 760 __ _..0 0 0 .. 0._____0 0 0 -�- -`324 0 0 0 __ -371 471 0 0 _ _0 0 0 0 _-.0 0 0 290 _ 0 ._ ._.52.__ 16 0 0 0 ���_ �� '64 0 0 0 _._._.. _0 0 0 0 ______0 0 0 0 ___. 0 0 0 _-'.;�93 93 i ___38 0 0 __.___0 0 0 _��` --64 0 0 0 . __.. _:0 0 0 0 _0_ 0 0 0 ____ .._0 0 0 _..____15 15 -.. ... .212-.. 248 0 _0 0 0 373 0 0 0 _.._ . _.0 0 0 0 ._,0 0 0 0 0 0 0 _..87.-_ 416 148 197 0 _ 0 0 0 �- -260 0 0 0 __.._..0 0 0 0 _____0 0 0 0 _. _ _ 0 0 .---0 ._758 0 Vj/ WW D C_-__ F 6 c) AED excursion 26 -46 Envelope loss/gain 2218 1486 1336 716 12 a) Infiltration b) Room ventilation 429 0 114 0 235 0 62 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 2647 1600 1571 778 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 19% 32% 0 0 0 2647 495 0 0 0 1600 508 19% 32% 0 0 0 1571 293 0 0 0 778 247 Total room load Air required (cfm) 3142 123 2108 92 1 1864 73 1025 45 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed -/�- wrYghC�s--tn- 2020-Mar-19 09:14:58 Right -Suite® Universal 2019 19.0.12 RSU23828 page 8 ...aterstone23306GR\LOI246Ik2Waterstane2330BGR.rup Colo =Wit House faces: W '////_����` Job: Lot24BlockWalerstone. j.. DEL AIR Duct System Summary Date: DECEMBER 13, 2010 •••,�`eumBB•wB CBBBmOreliC Entire House By: DCS DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DEL-AIR.COM eLroject For: ADAMS HOMES 8204Amalfi Circle, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.159 in/100ft 1167 cfm Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.159 in/100ft 1167 cfm 151 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) CIg (cfm) Design FR Diam (in) H x W (in) Duct Mat] Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 1864 73 45 0.218 5.0 Ox0 VIFx 25.0 85.0 stl BDRM2 h 1935 75 52 0.307 6.0 Ox0 VIFx 8.1 70.0 BDRM3 h 1769 69 50 0.287 6.0 Ox0 VIFx 13.6 70.0 BDRM4 h 3142 123 92 0.209 6.0 Ox0 VIFx 30.1 85.0 stl BRKFST h 1272 50 47 0.216 6.0 NO VIFx 26.0 85.0 stl DINING RM C 3086 104 135 0.289 6.0 0x0 VIFX 12.9 70.0 FAMILY RM C 2579 90 112 0.208 6.0 OX0 VIFx 30.2 85.0 st2 FAMILYRM-A c 2579 90 112 0.208 6.0 Ox0 VIFx 30.6 85.0 st2 KITCHEN c 1912 9 83 0.300 6.0 Ox0 VIFx 10.1 70.0 LAUNDRY c 1179 16 51 0.326 4.0 Ox0 VIFx 3.5 70.0 LIVING RM h 4916 192 169 0.159 8.0 0x0 VIFx 50.9 100.0 st3 M. BATH h 1271 50 34 0.172 4.0 Ox0 VIFx 39.7 100.0 st3 M. WIC c 34 1 1 0.169 4.0 Ox0 VIFx 41.8 100.0 st3 M. WIG h 760 30 17 0.172 4.0 Ox0 VIFx 39.9 100.0 st3 M. WIC II C 96 2 4 0.175 4.0 Ox0 VIFx 37.0 100.0 st3 MASTER BDRM h 4965 194 160 1 0.162 8.0 UP VIFX 48.3 100.0 st3 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk SO Peak AVF 245 184 0.209 554 9.0 0 x 0 VIM% st2 Peak AVF 648 611 0.159 606 14.0 0 x 0 VinlFlx st3 Peak AVF 467 387 0.159 595 12.0 0 x 0 VinlAx st2 ' Wrlght502020-Mar4909:14:59 ,6, ••�+- .. ft ft Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ...aterstone2330BGR\Lot24Blk2Waterstone2330BGR.rup Cato. MJ8 House faces: W Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mall Trunk rbt Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx wrightsoft` 2020-Mar-19 09:14:59 XCK Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2 ...aterstone2330BGRtLot24Bik2Waterstone2330BGR.rup Calc = MJ8 Hause faces: W 2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 24 Block 2 Waterston 2330 BGR Builder Name: ADAMS HOMES Street: 8204 Amalfi Circle Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: U Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an dro ed ceilin /soffit Y dropped 9 the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls The junction of the top plate and the lop of exterior walls shall be shall be Insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterio} thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous Insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed In the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind pip'na an wrna Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exteriorwalls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids nrinkler cover nlates and walls or cellincis a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. 3/19/2020 9:30 AM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6lh Edition (2017) Compliant Software Page 1 of 1 FORM R405-2017 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the residential Simulated Performance Method shall include: ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page) and an input summary checklist that can be used for field verification (usually four pages/may be greater). ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method. ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report (usually one page) 3/19/2020 9:29:41 AM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition Jurisdiction: 661000 Permit #: Job Information Builder: ADAMS HOMES Community: Lot: NA Address: 8204 Amalfi Circle City: Fort Pierce State: FL Zip: 34951 Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method O PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour at a pressure of 0.2 inch w.g. (50 Pascals)in Climate Zones 1 and 2. O PERFORMANCE orERI METHOD -The building or dwellingunit shall be tested and verified ashaving an air leakage rate of not exceeding the selected ACH(50) value, as shown on Form R405-2017 (Performance) or R406-2017 (ERI), section labeled as infiltration, sub -section ACH50. ACH(50) specified on Form R405-2017-Energy Calc (Performance) or R406-2017 (ERI):. 7.000 x 60 - 21669 — Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans ❑ PASS Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 3/19/2020 9:30:42 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 6th Edition (2017) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 8204 Amalfi Circle Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD, R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal enveld-fta building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. El R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the lest and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdmft and flue dampers shall be closed, but not sealed beyond intended Infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. R402.4.3 Fenestration air IeakagdNindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 3/19/2020 9:30 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such moms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, Floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room Insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heal pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (1), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1, Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. EIR403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55"F (13"C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return ❑ pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 3/19/2020 9:30 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). Fi R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140'F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment Installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be Installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and Indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFMANATT) AIRFLOW RATE MAXIMU (CFM) Range hoods Any 2.8 dm/watt Any In -line fan Any 2.8 cm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916 3/19/2020 9:30 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than.1.15 limes greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity, is a nominal, rating -lest value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the.heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system Is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8'C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. ❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 3/19/2020 9:30 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heal pumps are not required to meet this standard. R403.11 Portable spas (Mandatory�e energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS ❑ R404.1 Lighting equipment (Mandatory), Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps. Exception: Low -voltage lighting. R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights. 3/19/2020 9:30 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5