HomeMy WebLinkAbout008 E000 ELECTRICAL COVER SHEETE000ELECTRICAL COVER SHEETProject Number:PROJECT ISSUE DATES:SHEET NUMBERDATE:architecture3021 Jupiter Park CircleSuite 102Jupiter, FL 33458t 561.203.7539sparcdesignplanninginteriorswww.sparcdesign.usJupiter Commerce ParkSEAN PATRICK SUKHU
AR97488
HARBOUR RIDGE YACHT
AND COUNTRY CLUB
LAKESIDE ACTIVITY CENTER
PALM CITY, FLORIDA
AA26003806SHEET NAME2019.1372020.03.272020.03.27ISSUED FOR BID/PERMITThis Document is an ins
trument ofservice and the property ofSun Patrick Architecture, INC. AA26003806and shall remain their property. This documen
t isnot suitable for use on other projec
ts or in o
therlocations. Publication is expressly limited to theoriginal site
for which i
t was prepared.2020 Sun Patrick Architec
ture, INC.CThis item has been electronically signedand sealed by Sean Sukhu, R.A. onthe da
te and/or time stamp shownusing a digital signaturePrinted copies of this document are notconsidered signed and sealed andthe signature mus
t be verified onany electronic copies.RGDConsulting Engineers2151 S. ALT A1A, SUITE 2000, JUPITER, FL 33477 (561) 743-0165MechanicalElectricalStructuralmade in the usawww.rgdengineers
.comPlumbingFire ProtectionDATE3.31.2020DAVIS A. FITZGERALD, P.E.FLORIDA P.E. NO. 82057ELECTRICAL ENGINEERCERT OF AUTH 5454PROJECT #: 19-1168These Drawings are NOT VALID for any purpose which requires the originalsignature and seal of the engineer unless the original signature and seal are affixed.Drawings not signed and sealed by the engineer shall not be submitted to anyauthority or used for any purpose where signed and sealed documents are required.DAV
I
S
A. FITZGERALDLI
CENSEL
I
CENSEPROFESSIONAL ENGI
NEERPROFESSIONALENGI
NEERFLORIDAFLORIDA No. 82057STATE OFELECTRICAL COVER SHEETE000A -AMPEREAC -ALTERNATING CURRENTAFF -ABOVE FINISHED FLOORAHJ-AUTHORITY HAVING JURISDICTIONAL -ALUMINUMATC,BMS,EMCS-HVAC CONTROLSATS -AUTOMATIC TRANSFER SWITCHAIC -AMPS INTERRUPTING CAPACITYBRKR -BREAKERC or COND -CONDUITCD-CANDELACKT -CIRCUITCT -CURRENT TRANSFORMERCU-COPPERDN-DOWNDWG-DRAWINGDC -DIRECT CURRENT(E) or EXIST-EXISTINGE.C.-ELECTRICAL CONTRACTORELEV-ELEVATOREMER-EMERGENCYEMT-ELECTRIC METALLIC TUBINGEUH-ELECTRIC UNIT HEATEREWC-ELECTRIC WATER COOLEREWH-ELECTRIC WATER HEATERF-FUSEFA-FIRE ALARMFCA-FAULT CURRENT AVAILABLEFCR-FAULT CURRENT RATINGFSS-FUSED SAFETY SWITCHFTL-FEED THRU LUGSG , GND -GROUNDGFI -GROUND FAULT INTERRUPTGFP-GROUND FAULT PROTECTIONHZ-HERTZHP -HORSEPOWERIBC -INTERNATIONAL BUILDING CODEIG-ISOLATED GROUNDJ-JUNCTION BOXKVA-KILOVOLT-AMPEREKW-KILOWATTLTG -LIGHTINGELECTRICAL ABBREVIATIONSM -METERMCA-MINIMUM CIRCUIT AMPACITYMCB-MAIN CIRCUIT BREAKERMCC -MOTOR CONTROL CENTERMFR -MANUFACTURER+, MH-MOUNTING HEIGHTMLO-MAIN LUGS ONLYMOP, MOCP-MAXIMUM OVERCURRENT PROTECTIONMS, MSB-MAIN SWITCHBOARDMTS-MANUAL TRANSFER SWITCHNEC -NATIONAL ELECTRICAL CODE(N) -NEWNA -NOT APPLICABLENC-NORMALLY CLOSEDNF-NON-FUSEDNFPA-NATIONAL FIRE PROTECTION ASSOCIATIONNFSS-NON-FUSED SAFETY SWITCHNIC-NOT IN CONTRACTNO-NORMALLY OPENOCPD-OVERCURRENT PROTECTION DEVICEP-POLEPH OR Ø-PHASENEMA -NATIONAL ELECTRIC MANUFACTURERS ASSOCIATIONPB -PULL BOXPC -PHOTOCELLPNL -PANELBOARD(R) -RELOCATEDRECEPT -RECEPTACLERM-ROOMTHD-TOTAL HARMONIC DISTORTIONTVSS -TRANSIENT VOLTAGE SURGE SUPPRESSIONTYP -TYPICALUL-UNDERWRITERS LABORATORIESUNO-UNLESS NOTED OTHERWISEUPS-UNINTERRUPTIBLE POWER SUPPLYV -VOLTVFD -VARIABLE FREQUENCY DRIVEW -WATTW/-WITHWP -WEATHERPROOFXFMR -TRANSFORMERELECTRICAL SYMBOL LEGEND3-WAY, 20 AMP, SWITCH.SINGLE POLE, 20 AMP, SWITCH.D320 AMP DUPLEX RECEPTACLE20 AMP QUADRUPLEX RECEPTACLE20 AMP DUPLEX RECEPTACLE, WITH SELF-TESTING GROUND FAULT CIRCUIT INTERRUPTER. WIREMOLD RFB4 20 AMP DUPLEX/QUADRUPLEX RECEPTACLE, RECESS FLOOR MOUNTED BOX.SPECIAL-PURPOSE RECEPTACLE; NEMA TYPE AS INDICATED.20 AMP DUPLEX RECEPTACLE, CEILING MOUNTED.GFIJUNCTION BOXJTELEPHONE/DATA OUTLET FLOOR RECESSED.TELEPHONE/DATA OUTLET WITH 1" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.DATA OUTLET WITH 1" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.FUSIBLE DISCONNECT SWITCH NFSS = NON FUSED, F30SS = FUSEDGROUNDING ELECTRODE & CONDUCTOR SYSTEM120/208V ELECTRICAL PANELBOARD; MANDATORY CLEARANCE INDICATED WITH DASHED LINES.TRANSFORMERTELEPHONE WOOD BACKBOARDSINGLE PHASE MOTOREMERGENCY LIGHTSINGLE POLE OCCUPANCY SWITCH; ONW-D-1001-MV-W 120/277VAC SINGLE RELAY DT WALL SWITCH SENSORMDIMMER SWITCH. PROVIDE WBSD-010SLD-W 0-10V SLIDE DIMMER WALL STATION.WIREMOLD RC4ATCAL 20 AMP QUADRUPLEX, DATA/TELEPHONE FLOOR POKE-THRU DEVICE20 AMP DUPLEX RECEPTACLE, WEATHERPROOF WHILE-IN-USE.WPTVCONFIRM COLOR SELECTION WITH ARCHITECT PRIOR TO ORDERING.TEXIT SIGN. SHADED SIDES INDICATE FACES. ARROWS INDICATE CHEVRONS.20 AMP, FAN SWITCH.FSWITCH WITH THERMAL OVERLOAD PROTECTION (MANUAL MOTOR STARTER)T277/480V ELECTRICAL PANELBOARD; MANDATORY CLEARANCE INDICATED WITH DASHED LINES.THREE PHASE MOTORINTEGRAL STARTER OR CONTROLLER AND DISCONNECT CABINET BY THE MECHANICAL CONTRACTORCIRCUIT BREAKERBMAGNETIC MOTOR STARTER AND DISCONNECT BY THE ELECTRICAL CONTRACTORMMAGNETIC MOTOR STARTER BY THE ELECTRICAL CONTRACTORMT-STAT BY MECHANICAL CONTRACTOR, WIRING BY ELECTRICAL CONTRACTORPOWER PACK; SP20-MV 120/277VAC SINGLE RELAY SWITCHPACKPP20 AMP SIMPLEX RECEPTACLE20 AMP DUPLEX RECEPTACLE WITH ISOLATED GROUND.IGMETERMAUTOMATIC TRANSFER SWITCHMOLDED CASE CIRCUIT BREAKERPLUG-IN FUSED DISCONNECTCEILING MOUNTED SENSOR; PROVIDE OAC-DT-1000 360 DEGREE 1000FT DT CEILING SENSORHATCHED LIGHT FIXTURE - PROVIDED WITH EMERGENCY BATTERY.G.P. RECEPTACLE CIRCUIT USING 2#12, 1#12 G. IN 1/2" CONDUIT.MOTORIZED DAMPER BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL WIRE TO NEARESTMVDELECTRICAL SHEET INDEXWIRE CONCEALED IN WALLS/CEILINGS. QUANTITY OF WIRES IN HOMERUN INDICATED ON PANEL SCHEDULES.GROUND WIRE IS IN ADDITION TO WIRES INDICATED. ADDITIONAL SWITCH WIRES SHALL BE DETERMINED BY E.C.WIREMOLD RFB4 20 AMP DUPLEX/QUADRUPLEX RECEPTACLE WITH DATA/TELEPHONE,RECESS FLOOR MOUNTED BOX.20 AMP DUPLEX RECEPTACLE, WEATHER-RESISTANTWR20 AMP DUPLEX RECEPTACLE, TAMPER-RESISTANTTRxRECEPTACLE SUBSCRIPT DEFINITIONS:a:GFI, WP, WRb:GFI, WP, WR, TRc:GFI, TR20 AMP DUPLEX RECEPTACLE, TOP HALF SWITCHED.LOW VOLTAGE WIRE CONCEALED IN WALLS/CEILINGS. QUANTITY OF WIRES SHALL BE DETERMINED BY E.C.ELECTRICAL SITE PLANE100SCENE SELECTOR SWITCH. PROVIDE LUTRON SO-4SN-WH-EGN OVERRIDE SWITCH/ SCENE STATION.S26.CONDUITS SHALL BE RIGIDLY SUPPORTED TO THE BUILDING STRUCTURE. AC AND MC CABLES SHALL BESUPPORTED WITHIN 12" OF EVERY BOX, FITTING, ETC. AND SUPPORT SPACINGS SHALL NOT EXCEED 6' INTERVALS.RIGID CONDUIT SUPPORT SPACINGS SHALL NOT EXCEED 10'-0” FOR VERTICAL RUNS AND 8'-0” FOR HORIZONTALRUNS, HOWEVER ALL SUPPORT SPACINGS FOR ALL CONDUIT TYPES SHALL BE IN ACCORDANCE WITH THE NECREGARDLESS OF WHAT IS STATED HERE. COUPLINGS AND FITTINGS SHALL BE STEEL WITH COMPRESSION OR SETSTEEL SCREW CONNECTIONS. THERE SHALL NOT BE MORE THAN THE EQUIVALENT OF FOUR QUARTER BENDS (360DEGREES TOTAL) BETWEEN PULL POINTS FOR POWER (120V OR HIGHER) CIRCUITS AND NOT MORE THAN THEEQUIVALENT OF TWO QUARTER BENDS (180 DEGREES TOTAL) BETWEEN PULL POINTS FOR LOW VOLTAGE(TELEPHONE, DATA, ETC) CIRCUITS. LOW VOLTAGE CONDUIT RUNS SHALL ALSO NOT EXCEED 100' BETWEEN PULLPOINTS. ALL CONDUITS SHALL BE TERMINATED WITH INSULATED THROAT CONNECTORS FOR CONDUITS 1” ANDSMALLER, AND WITH INSULATED BUSHINGS AND LOCKNUTS FOR CONDUITS OVER 1”. EMPTY CONDUIT RUNSEXCEEDING 10' SHALL BE PROVIDED WITH PULL WIRES SECURELY FASTENED AT BOTH ENDS. EXPANSION FITTINGSSHALL BE PROVIDED AT ALL BUILDING EXPANSION JOINTS OR WHERE NEEDED TO ALLOW FOR THERMALEXPANSION.27.CONDUIT SIZES INDICATED IN PANEL SCHEDULES AND ON THE SINGLE LINE ARE BASED ON TYPE THHN IN EMT. ASOTHER TYPES OF CONDUIT AND CONDUCTORS ARE PERMISSIBLE IN THIS PROJECT, THE CONTRACTOR SHALLADJUST THE DIMENSION OF THE CONDUIT TO COMPLY WITH CHAPTER 9, TABLE 1 IN THE NEC. ADJUSTMENTS TOTHE CONDUIT SIZE SHALL BE PART OF THE BID AND SHALL BE AT NO ADDITIONAL EXPENSE TO THE OWNER.28.WIRE SIZES INDICATED ARE BASED UPON DIRECT ORTHOGONAL PATHS TO THE PANELBOARD. FEEDERS ARE SIZEDFOR A MAXIMUM OF 2% VOLTAGE DROP, AND BRANCH CIRCUITS ARE DESIGNED FOR A MAXIMUM OF 3% VOLTAGEDROP. IF FIELD CONDITIONS DO NOT ALLOW THESE PATHS OR IF THE CONTRACTOR RUNS ADDITIONAL LENGTHS,THEY SHALL BE RESPONSIBLE FOR INCREASING WIRE SIZE TO ACCOUNT FOR VOLTAGE DROP AT NO ADDITIONALCOST. WIRING SMALLER THAN #12 AWG SHALL NOT BE USED FOR ANY INSTALLATIONS.29.THE CONTRACTOR SHALL CIRCUIT PANELBOARDS EXACTLY AS INDICATED IN THE PANEL SCHEDULES. IF ANYDEVIATIONS ARE NECESSARY, THE ENGINEER SHALL BE NOTIFIED. TYPED DIRECTORY CARDS SHALL BE PROVIDEDAT EACH PANELBOARD INDICATING LOAD SERVED AND FINAL ROOM NUMBERS PER THE NEC. WHEN EXISTINGDIRECTORIES ARE REPLACED FOR RENOVATION WORK, EXISTING LOAD INFORMATION SHALL BE DIRECTLYTRANSFERRED TO THE NEW DIRECTORY CARDS.30.NEUTRAL CONDUCTORS SHALL ONLY BE SHARED WHEN INDICATED ON THE DRAWINGS. WHERE NEUTRALS AREINDICATED TO BE SHARED, THE NEUTRAL SHALL BE A MINIMUM OF #10 AWG.31.THE CONTRACTOR SHALL REMOVE ALL UNUSED AND ABANDONED WIRING AND CABLING FROM THE CEILINGPLENUM THAT ISN'T LABELED FOR FUTURE USE, AS REQUIRED BY THE NEC. THIS SHALL INCLUDE BUT IS NOTLIMITED TO FIRE ALARM, POWER, SECURITY, CONTROLS, DATA, TELEPHONE, A/V, ETC.32.WHEN A RETURN AIR PLENUM IS UTILIZED, ALL CABLING AND CONDUIT SHALL BE PLENUM RATED OR IN PLENUMRATED CONDUIT. THIS INCLUDES TELEPHONE, DATA, CONTROL CABLES, ETC. AND RESTRICTS THE USE OF PVC.33.ALL BRANCH CIRCUIT CONDUCTORS AND FEEDER CIRCUITS 100A OR SMALLER SHALL BE COPPER. FEEDERCIRCUITS SERVING LOADS LARGER THAN 100A MAY BE EITHER COPPER OR ALUMINUM, HOWEVER THE DESIGN ISBASED AROUND COPPER AND THE CONTRACTOR WILL BE RESPONSIBLE FOR ACCOUNTING FOR INCREASED WIRESIZE, CONDUIT SIZE, AND SPACE TAKEN BY THE LARGER CONDUIT IF ALUMINUM IS USED. HOWEVER, BRANCHCIRCUITS FEEDING MOTORS SHALL ALWAYS BE COPPER REGARDLESS. CONDUCTORS #10 AWG AND SMALLERSHALL BE SOLID, AND CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED. CONDUCTORS SHALL BE CODETYPE THW, THHN, THWN, OR XHHW UNLESS OTHERWISE REQUIRED BY THE NEC. CONDUCTORS SHALL BE MARKEDWITH INSULATION CODE, VOLTAGE RATING, AWG SIZE, AND MANUFACTURER AND INCLUDE A CONTINUOUS COLORCODING FROM PANEL TO LOAD SERVED. WHERE CONTINUOUS MARKINGS ARE NOT AVAILABLE, USE COLOR CODEDTAPE AT EACH TERMINATION. #8 AWG AND SMALLER CONDUCTORS SHALL BE SPLICED WITH SPRINGCONNECTORS. #6 AWG AND LARGER SHALL BE SPLICED WITH BARREL CONNECTORS REQUIRING COMPRESSIONON EACH END.34.NEW LIGHTS AND LAMPS SHALL MATCH EXISTING BUILDING STANDARD, INCLUDING LAMP TEMPERATURE COLOR.THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFIRMING BUILDING STANDARDS PRIOR TO PURCHASE. THECONTRACTOR SHALL PROVIDE THE PROPER FIXTURE TYPE FOR THE CEILING OR WALL TYPE WHICH THE FIXTURE ISTO BE INSTALLED IN INCLUDING TRIM, MOUNTING ACCESSORIES ETC. REGARDLESS OF THE MODEL NUMBERS INTHE LIGHT FIXTURE SCHEDULE, THE CORRECT MOUNTING TYPE SHALL BE PROVIDED. THE CONTRACTOR SHALLREFER TO INTERIOR DESIGNER, ARCHITECTURAL, LANDSCAPE, OR OTHER CONSULTANT PLANS FOR ADDITIONALINFORMATION AND REQUIREMENTS; WHERE THERE IS A DISCREPANCY BETWEEN ELECTRICAL PLANS AND OTHERCONSULTANT PLANS, THE OTHER CONSULTANT PLANS SHALL TAKE PRIORITY EXCEPT FOR VOLTAGE AND WATTAGEOF FIXTURES. FIXTURE TYPES IN THE LIGHT FIXTURE SCHEDULE ARE TO ESTABLISH A TYPE, NOT A METHOD OFMOUNTING. FLUORESCENT FIXTURES THAT UTILIZE DOUBLE-ENDED LAMPS AND CONTAIN BALLASTS THAT CAN BESERVICED IN PLACE SHALL HAVE A DISCONNECTING MEANS, UNLESS THE FIXTURE IS USED FOR EMERGENCYLIGHTING. ALL BALLASTS SHALL BE ELECTRONIC, LESS THAN 20% THD, CREST FACTOR OF 1.7 FOR FLUORESCENTSAND 1.8 FOR METAL HALIDES, HIGH POWER FACTOR, AND RATED FOR THE TYPE OF LAMP IT OPERATES.MANUFACTURERS SHALL BE GE, ADVANCE, MAGNETEK, MOTOROLA, LUTRON, OR OTHER APPROVED EQUAL. LIGHTFIXTURES, BALLASTS, TRANSFORMERS, DRIVERS, ETC LOCATED IN A WET OR DAMP LOCATION SHALL BE LISTEDFOR SAID USE. LIGHT FIXTURES INSTALLED IN AREAS HAVING EXPOSED FOOD OR FOOD PREPARATION AREAS ORKITCHENS SHALL BE PROPERLY LENSED AND HAVE SHATTER PROOF LAMPS.35.ALL LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURAL SYSTEM BY SUPPORT WIRES,INDEPENDENT OF CEILING GRID SYSTEMS. TROFFER TYPE FIXTURES SHALL BE SUPPORTED BY WIRES AT ALLFOUR CORNERS. RECESSED DOWNLIGHTS SHALL BE SUPPORTED VIA HANGER BARS SUPPORTED BY WIRES AT ALLFOUR CORNERS. SUPPORT MEANS SHALL BE IN ACCORDANCE WITH LOCAL SEISMIC REQUIREMENTS.36.THE EQUIPMENT GROUNDING SYSTEM SHALL CONSIST OF AN ELECTRICALLY CONTINUOUS METALLIC CONDUITSYSTEM TOGETHER WITH INSULATED EQUIPMENT GROUNDING CONDUCTORS. EVERY ITEM SERVED BY THEELECTRICAL SYSTEM SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH NEC ARTICLE 250. THIS SHALLINCLUDE RACEWAYS, JUNCTION/OUTLET BOXES, MACHINE FRAMES, ETC. ALL BRANCH CIRCUITS AND FEEDERSSHALL HAVE A GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR OR GROUND ELECTRODE SIZED INACCORDANCE WITH THE NEC. PROVIDE BONDING JUMPERS FOR ALL NON-CURRENT CARRYING CONDUCTORS OFDIFFERENT SYSTEMS TO ENSURE NO VOLTAGE POTENTIAL. METAL GAS PIPING SHALL ONLY BE GROUNDED ATEQUIPMENT HOUSING BOTH ELECTRICAL CIRCUITS AND UTILIZING GAS VIA THE EQUIPMENT GROUND ROUTED WITHTHE CIRCUIT. ALL GROUND WIRES SHALL BE COPPER.37.A LIGHTNING PROTECTION SYSTEM SHALL BE PROVIDED. THE SYSTEM SHALL BE CLASS 1, WITH ALUMINUMCONDUCTORS. ELECTROCHEMICALLY DISSIMILAR MATERIALS SHALL NOT BE IN DIRECT CONTACT. DOWNCONDUCTORS, SYSTEM CONDUCTORS, INTERIOR CONDUCTORS, AND ANY OTHER CONDUCTORS WITHIN NORMALVIEW OF EXTERIOR LOCATIONS AT GRADE WITHIN 200' OF THE BUILDING SHALL BE CONCEALED. ALL TERMINALSAND EQUIPMENT SHALL BE SECURED TO THE ROOF MEMBRANE WITH AN ADHESIVE THAT IS COMPATIBLE WITH THEROOFING MATERIAL.38.SUBMITTALS SHALL BE SUBMITTED ELECTRONICALLY, IN PDF FORMAT. THE CONTRACTOR SHALL ALLOW FOR ATOTAL OF 10 BUSINESS DAYS FOR REVIEW BY THE ENGINEER. SUBMITTALS SHALL INCLUDE PANELBOARDS,TRANSFORMERS, DISCONNECTS, WIRING DEVICES, UPS'S, LIGHT FIXTURES, TVSS, AND FIRE ALARM SYSTEM.SUBMITTALS SHALL ONLY INCLUDE DATA RELEVANT TO THIS PROJECT; DATA SHEETS INDICATING SEVERALPRODUCTS SHALL HAVE THE RELEVANT PRODUCTS HIGH-LITED OR CLEARLY IDENTIFIED. SIMILAR EQUIPMENTSHALL BE SUBMITTED IN ONE COMPLETE SUBMITTAL PACKAGE (I.E. ALL PANELBOARDS, ALL LIGHTING FIXTURES,ETC.).39.PROVIDE PAD LOCKING HARDWARE ON CIRCUIT BREAKERS FOR EQUIPMENT WHICH IS HARDWIRED WITHOUT ALOCAL DISCONNECTING MEANS THAT ARE NOT WITHIN SIGHT OF THE PANELBOARD.40.PROVIDE RECEPTACLES SIMILAR TO PASS & SEYMOUR #26352 SERIES AND LIGHT SWITCHES SIMILAR TO PASS &SEYMOUR #2621 SERIES. COVER PLATES SHALL BE AS SPECIFIED BY THE ARCHITECT OR BRUSHED STAINLESSSTEEL. CONFIRM ALL DEVICE COLORS WITH THE ARCHITECT.41.DUPLEX OUTLETS SHALL BE NEMA 5-20R WHEN THEY ARE THE ONLY LOAD ON A CIRCUIT.42.PANELBOARDS SHALL HAVE COPPER FULL SIZE PHASE BUSSES, NEUTRAL BUSSES, AND BOLTED ON COPPERGROUNDING BUS WITH MAIN LUGS. BUS BAR CONNECTIONS SHALL BE COLUMN CONSECUTIVE PHASE-SEQUENCETYPE. BUS BARS SHALL BE DRILLED AND EQUIPPED FOR BOLT-ON MOLDED CASE CIRCUIT BREAKERS. SHORTCIRCUIT BRACING AND BREAKER INTERRUPTING CAPACITY SHALL BE AS INDICATED ON THE PANEL SCHEDULES,BUT SHALL NOT BE BELOW 10,000 A.I.C. FOR 120/208V PANELS AND 14,000 A.I.C. FOR 277/480V PANELS. PANELCONSTRUCTION SHALL BE HINGED DOOR IN DOOR COVERS WITH MASTER-KEYED DOOR LOCKS, GALVANIZEDSHEET STEEL CABINETS WITH MULTIPLE KNOCKOUTS, WIRING GUTTERS, AND SPACE FOR A TYPED CIRCUITDIRECTORY. MAIN BREAKERS OR MAIN LUGS ONLY SHALL BE PROVIDED AS INDICATED IN THE PANEL SCHEDULES.PANELS SHALL BE PROVIDED WITH FEED THRU LUGS UNLESS OTHERWISE NOTED.43.MOLDED CASE CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC AND AMBIENT COMPENSATED INVERSETIME-DELAY OVERLOAD AND INSTANTANEOUS SHORT CIRCUIT PROTECTED, FULL SIZE, BOLT-ON, WITH AQUICK-MAKE, QUICK-BREAK OVER-CENTER SWITCHING MECHANISM THAT IS MECHANICALLY TRIP-FREE FROM THEHANDLE SUCH THAT THE CONTACTS CAN NOT BE CLOSED AGAINST SHORT CIRCUITS. CONTACTS SHALL BENON-WELDING SILVER ALLOY. TRIPPING DUE TO OVERLOAD OR SHORT CIRCUIT SHALL BE INDICATED BY THEBREAKER RESTING AT A MID POINT BETWEEN THE ON AND OFF POSITIONS. AMPERE AND FAULT CURRENT RATINGSSHALL BE CLEARLY VISIBLE. BREAKERS SHALL BE LISTED FOR USE WITH 75°C AND 90°C CONDUCTORS.MULTI-POLE BREAKERS SHALL BE OF THE COMMON TRIP TYPE HAVING A SINGLE HANDLE. WHERE NEUTRALS ARESHARED AMONG CIRCUITS, THE CONTRACTOR SHALL PROVIDE MULTI-POLE BREAKERS TO SIMULTANEOUSLYDISCONNECT ALL CIRCUITS IN THE EVENT OF ONE TRIPPING; IN THIS CASE SINGLE POLE BREAKERS MAY BECONNECTED BY A COMMON TRIP HANDLE.44.MOLDED CASE CIRCUIT BREAKERS INDICATED FOR SHUNT TRIP SHALL BE 60 HERTZ, FACTORY INSTALLED, ANDHAVE A 120 VOLT COIL CIRCUITED FROM A 120/208V PANEL PROVIDED BY THE CONTRACTOR. SHUNT TRIPBREAKERS SHALL TAKE ONE POLE SPACE IN PANELBOARDS AND MAY BE EITHER LEFT OR RIGHT MOUNTED. THESHUNT TRIP ACTIVATION DEVICE SHALL BE A MOMENTARY CLOSE CONTACT TYPE.45.ALL FUSES SHALL BE DUAL-ELEMENT RK5 FOR MOTORS AND DUAL-ELEMENT RK1 FOR ALL OTHER CONNECTIONS ASMANUFACTURED BY BUSSMAN OR LITTLE FUSE. FUSE VOLTAGE RATING SHALL BE 250 VOLT FOR 120/208 VOLTSYSTEM AND 600 VOLT FOR 277/480 VOLT SYSTEM.46.DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, HIGH I2T RATED, APPROVED FOR SERVICE ENTRANCEAPPLICATIONS. DISCONNECT SWITCHES SPECIFIED FOR 208 VOLT CIRCUITS SHALL BE RATED AT 240 VOLT, ANDDISCONNECT SWITCHES SPECIFIED AT 480 VOLT SHALL BE RATED AT 600 VOLT. ALL DISCONNECTS SHALL BEQUICK-MAKE, QUICK-BREAK TYPE AND HAVE PROVISIONS FOR ACCOMMODATING R TYPE FUSES. SWITCHES INEXTERIOR LOCATIONS SHALL BE NEMA TYPE 4X, AND INDOOR SWITCHES EXPOSED TO WET OR DAMP CONDITIONSSHALL BE NEMA TYPE 3R. SWITCHES SHALL HAVE PROVISIONS FOR PADLOCKING. SWITCHES SHALL BEPREVENTED FROM OPENING WHILE SWITCH IS ON. FUSED DISCONNECTS SHALL BE PROVIDED WHEN REQUIRED BYTHE MANUFACTURER OR BY THE LOCAL INSPECTING AUTHORITY.47.THE CONTRACTOR SHALL PROVIDE THE NECESSARY JUNCTION BOXES AND CONNECTIONS FOR THE UNDERSIDE OFALL POKE-THRU DEVICES. CORE DRILLS, SLEEVES, ETC SHALL BE PROVIDED AS NECESSARY TO RETURN ALLPOKE-THRU HOMERUNS.ELECTRICAL NOTES1.THE CONTRACT DOCUMENTS CONSIST OF DRAWINGS, SPECIFICATIONS AND DESIGN INFORMATION PREPARED BYMULTIPLE DISCIPLINES AND MUST BE USED AS A WHOLE AND IN COORDINATION WITH EACH OTHER. THECONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY APPARENT DISCREPANCIES OR OMISSION OF INFORMATIONNOT SHOWN ON THE ELECTRICAL DRAWINGS. SHOP DRAWINGS SHALL BE PROVIDED WHERE NECESSARY FORCOORDINATION. THE CONTRACTOR IS RESPONSIBLE FOR CORRECTING ERRORS RESULTING FROM LACK OFCOORDINATION OF DOCUMENTS.2.REFER TO THE ARCHITECTURAL DOCUMENTS FOR ALL APPLICABLE CODES. THE WORK SHALL BE IN ACCORDANCEWITH THE 2014 NATIONAL ELECTRICAL CODE (NFPA 70), FLORIDA BUILDING CODE 6TH EDITION (2017), 2013 NFPA 72,FLORIDA FIRE PREVENTION CODE 6TH EDITION, FAC, AND ANY OTHER LOCAL JURISDICTIONAL REQUIREMENTS. INADDITION, ANY BASE BUILDING OR TENANT GENERAL CONDITIONS SHALL GOVERN ACCEPTABLE MATERIALS ANDWORK.3.THE CONTRACTOR SHALL BRING ANY CONFLICTS OR DISCREPANCIES TO THE ATTENTION OF THE ENGINEER INWRITING PRIOR TO PROCEEDING WITH WORK.4.THE CONTRACTOR SHALL FIELD VISIT THE SITE PRIOR TO BID TO FAMILIARIZE HIMSELF WITH THE SCOPE OF WORK.5.ALL WORK SHALL BE DONE IN A FIRST CLASS WORKMANLIKE MANNER BY A LICENSED ELECTRICAL CONTRACTOR.THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A SAFE, CLEANLY, AND UNDISRUPTIVE JOB SITE THATDOES NOT IMPEDE EGRESS PATHS OR OTHER TENANTS. DISRUPTIONS TO POWER AFFECTING OTHER TENANTS ORAREAS OUTSIDE THE SCOPE OF WORK SHALL BE COORDINATED WITH THE OWNER. THE CONTRACTOR SHALL BERESPONSIBLE FOR ALL CUTTING AND PATCHING OF HIS WORK. WHEN THE WORK IS COMPLETE, ALL ELECTRICALDEVICES SHALL BE VACUUMED CLEAN. THE FINAL PRODUCT SHALL BE A FULLY FUNCTIONAL SYSTEM MEETING THEINTENT OF THE DRAWINGS/DOCUMENTS. WORKMANSHIP AND ALL MATERIALS AND EQUIPMENT SHALL BEGUARANTEED FOR A MINIMUM OF ONE YEAR IN WRITING COMMENCING UPON ACCEPTANCE OF INSTALLATION BYOWNER.6.WITHIN 30 DAYS AFTER THE DATE OF THE SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUALINSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING A SINGLE-LINE DIAGRAM OF THEBUILDING ELECTRICAL DISTRIBUTION SYSTEM AND FLOOR PLANS INDICATING LOCATION AND AREA SERVED FORALL DISTRIBUTION. ADDITIONALLY, AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TOTHE BUILDING OWNER INCLUDING THE FOLLOWING: SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTEDOPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE, OPERATION MANUALS AND MAINTENANCEMANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE INCLUDING CLEARLY IDENTIFIED ROUTINEMAINTENANCE ACTIONS, AND NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.7.UNLESS PROVIDED WITH DIMENSIONS OR NOTED OTHERWISE, ELECTRICAL PLANS ARE STRICTLY DIAGRAMMATICONLY. REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, MOUNTING HEIGHTS, ETC. EFFORT HASBEEN MADE TO PROPERLY ACCOUNT FOR ALL SPACE REQUIREMENTS, CLEARANCES, ETC. BUT SITE CONDITIONSAND PRODUCTS SELECTED MAY VARY AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN PROPERARRANGEMENTS AND CLEARANCES. DRAWINGS SHALL NOT BE SCALED.8.THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PAYING ALL ASSOCIATED FEES, ANDDOCUMENTING AND FILING ALL PAPERWORK ASSOCIATED WITH THIS SCOPE OF WORK. WHEN THE WORK ISCOMPLETE, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED CERTIFICATES OFINSPECTION.9.UNLESS NOTED OTHERWISE ALL EXISTING ELECTRICAL DEVICES INSTALLED UNDER PREVIOUS CONTRACTS SHALLREMAIN. CONTRACTOR SHALL EXTEND AND RELOCATE EXISTING DEVICES INTO NEW TENANT SPACE AND MOUNTTO PARTITIONS, CEILINGS, OR FINISHES AS REQUIRED.10.THE CONTRACTOR IS EXPECTED TO HAVE A FULL FUNCTIONAL KNOWLEDGE OF ELECTRICAL SYSTEMS ANDWHETHER INDICATED ON THE DRAWINGS OR NOT SHALL PROVIDE THE CORRECT NUMBER OF WIRES, AT NOADDITIONAL CHARGE, TO FACILITATE PROPER OPERATION OF ALL EQUIPMENT. QUANTITY OF WIRES WILL ONLY BEINDICATED WHERE NECESSARY FOR CLARIFICATION.11.THE INSTALLATION SHALL BE IN COMPLIANCE WITH THE AMERICAN WITH DISABILITIES ACT (ADA), UNLESSINSTALLED FOR SPECIFIC USES EXEMPT FROM ADA OR IN AREAS NOT NORMALLY ACCESSED BY BUILDINGOCCUPANTS.12.THE ELECTRICAL CONTRACTOR SHALL REFER TO THE MECHANICAL AND PLUMBING DRAWINGS FOR EXACTLOCATIONS OF EQUIPMENT. PRIOR TO ORDERING ELECTRICAL EQUIPMENT SERVING MECHANICAL & PLUMBINGEQUIPMENT, THE ELECTRICAL CONTRACTOR SHALL CONFIRM THE EQUIPMENT BEING ORDERED BY THE HVAC ORPLUMBING CONTRACTORS AND PROVIDE WIRING, CONDUIT, AND OVERCURRENT PROTECTION MEETING THEREQUIREMENTS AT NO ADDITIONAL COST. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FORREVIEWING AND COORDINATING WITH THE HVAC CONTRACTOR FOR PROVIDING ANY NECESSARY LINE AND LOWVOLTAGE WIRING. FINAL TERMINATION TO BE MADE BY THE HVAC CONTRACTOR. ALL BREAKERS SUPPLYING HVACLOADS SHALL BE HACR TYPE.13.THE CONTRACTOR SHALL DETERMINE THE EXACT SCOPE OF WORK REQUIRED TO MODIFY THE EXISTING FIREALARM SYSTEM PRIOR TO PRICING AND BIDDING. THE BID SHALL INCLUDE ALL MODIFICATIONS NECESSARYINCLUDING DEVICES, WIRING, SOFTWARE, CALCULATIONS, ETC. WHETHER INDICATED ON THE DRAWINGS OR NOT.THIS SHALL INCLUDE WIRING REQUIRED TO INTERFACE WITH SECURITY LOCKS, WIRING REQUIRED FOR KITCHENANSUL SYSTEMS, ETC. FIRE ALARM STROBES SHALL BE INSTALLED 80” A.F.F. OR 6” BELOW THE CEILING,WHICHEVER IS LOWER. STROBES SHALL INCLUDE MULTIPLE CANDELA SETTINGS AND SHALL BE FULLYSYNCHRONIZED THROUGHOUT THE SPACE. MANUAL STATIONS SHALL BE INSTALLED AT BETWEEN 42” TO 54” A.F.F.AND WITHIN 5' OF EACH CODE REQUIRED EXIT. AUDIBLE ALARMS SHALL MEET AN OUTPUT OF AT LEAST 15 dBAABOVE THE AMBIENT NOISE LEVEL AND SHALL INCLUDE MULTIPLE VOLUME WATTAGE TAPS TO ACHIEVE HIGHERLEVELS IF NECESSARY. SMOKE DETECTORS (NEW AND EXISTING) SHALL BE COVERED AND PROTECTED DURINGCONSTRUCTION. IF EMERGENCY CIRCUITS ARE AVAILABLE, ANY FIRE ALARM EQUIPMENT REQUIRING POWERSHALL BE CONNECTED TO THE EMERGENCY STANDBY SYSTEM. BATTERY CALCULATIONS SHALL BE PROVIDED TODETERMINE IF EXTRA EQUIPMENT SHALL BE REQUIRED. THE CONTRACTOR SHALL SUBMIT A DETAILED SET OFSHOP DRAWINGS, WIRING DIAGRAMS, FLOORPLAN DRAWINGS WITH ALL DEVICE LOCATIONS, AND ALLCALCULATIONS AT THE TIME OF SUBMISSION FOR PERMIT. AN INSTALLATION AND USER MANUAL SHALL BEMAINTAINED AT THE MAIN FIRE ALARM CONTROL PANEL.14.ALL EXISTING CIRCUITS INDICATED AS SPARE SHALL BE TRACED AND VERIFIED BY THE CONTRACTOR. IF A CIRCUITIS LABELED AS SPARE OR INDICATED FOR RE-USE BUT UTILIZED BY AN ADJACENT TENANT OR OCCUPIED SPACE,THE ENGINEER SHALL BE NOTIFIED AND A NEW CIRCUIT SHALL BE ASSIGNED.15.ALL MATERIALS AND EQUIPMENT FURNISHED SHALL BE NEW (UNLESS NOTED OTHERWISE) AND BEAR THE U.L.LISTING FOR THEIR INTENDED USE. MATCH BUILDING STANDARDS FOR MANUFACTURER AND TYPE OF EQUIPMENTFOR LIGHTS, EXIT SIGNS, FIRE ALARM DEVICES, WIRING DEVICES, AND ELECTRICAL DISTRIBUTION EQUIPMENT.WHERE NO BUILDING STANDARD EXISTS FOR ELECTRICAL EQUIPMENT, EQUIPMENT SHALL BE MANUFACTURED BYG.E., SQUARE-D, EATON CUTLER-HAMMER OR SIEMENS. INSTALL A PLASTIC-LAMINATE SIGN ON EACH NEW UNIT OFELECTRICAL EQUIPMENT WITH 1/2" ENGRAVED LETTERING FOR IDENTIFICATION. IDENTIFICATION SHALL MATCHCONTRACT DOCUMENTS, SHALL INDICATE SOURCE FED PER NEC 408.4(B), AND SHALL INDICATE ARC-FLASHHAZARD PER NEC 110.16.16.THE FAULT CURRENT RATING OF ALL EQUIPMENT ADDED TO THE ELECTRICAL DISTRIBUTION SHALL MEET THEAVAILABLE FAULT CURRENT. EQUIPMENT ADDED TO THE EMERGENCY SYSTEM SHALL BE SELECTIVELYCOORDINATED. EQUIPMENT SHALL BE FULLY RATED UNLESS NOTED OTHERWISE.17.THE CONTRACTOR SHALL GIVE PERMISSION FOR THE AHJ, ENGINEER, ARCHITECT, INSPECTOR, ETC. TO PERFORMTESTS OF THE ELECTRICAL SYSTEM AS REQUIRED.18.JUNCTION AND PULL BOXES ARE ONLY INDICATED WHERE REQUIRED FOR LARGE SCALE COORDINATION. THECONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING JUNCTION AND PULL BOXES AS REQUIRED BY THE CODEAND PER A STANDARD INSTALLATION, AND SHALL INCLUDE THIS IN THEIR BID. BOXES SHALL BE STEEL ANDINCLUDE EARS INSIDE TO ATTACH COVERS. OUTLET BOXES SHALL BE FOUR INCH SQUARE DEEP TYPE. OUTLETBOXES FOR 120V OR HIGHER CIRCUITS SHALL INCLUDE A #12 AWG SOLID COPPER PIGTAIL. OUTLET BOXESLOCATED OUTDOOR OR EXPOSED TO WET CONDITIONS SHALL INCLUDE GASKETED COVERS. THE MAXIMUM GAPAROUND BOXES SHALL BE 1/8" OR SMALLER ON ALL EDGES. JUNCTION BOXES SHALL BE COLOR CODED WITH PAINTTO INDICATE THEIR USE AS FOLLOWS: NORMAL POWER - BLACK, STANDBY POWER - ORANGE, FIRE ALARM - RED,TELEPHONE/DATA - YELLOW, HVAC CONTROLS - BLUE.19.CONDUCTORS SHALL BE LOOPED AROUND SCREW POSTS SO THAT ROTATION OF THE SCREW TENDS TO FURTHERWRAP THE CONNECTION. SCREW TERMINALS SHALL BE WRAPPED IN ELECTRICAL TAPE. AT LEAST 6" OF FREECONDUCTOR SHALL BE LEFT AT EACH J-BOX, OUTLET AND SWITCH BACK-BOX, ETC FOR FUTURE SPLICING.20.THE CONTRACTOR SHALL MAINTAIN THE FIRE RATING OF ALL FIRE-RATED PARTITIONS, AS INDICATED IN IEEE REDBOOK. IF A DEVICE WILL VOID THE FIRE RATING OF A WALL, IT SHALL BE INSTALLED IN AN ALTERNATE LOCATIONPER THE ARCHITECT OR ENGINEER'S DIRECTION. ALL VOIDS AROUND CONDUITS AND/OR CORE DRILLSPENETRATING FIRE RATED PARTITIONS SHALL BE FILLED WITH FIRE-SAFING MATERIAL OR UL APPROVED FIRERATING DEVICE. THE FIRE RATING OF A PARTITION SHALL NEVER BE COMPROMISED.21.THE CONTRACTOR SHALL MAINTAIN THE INSULATION RATING AND VAPOR BARRIERS ON ALL PERIMETER WALLS. IFA DEVICE WILL DAMAGE OR COMPROMISE THE VAPOR BARRIER OR INSULATION, IT SHALL BE INSTALLED IN ANALTERNATE LOCATION PER THE ARCHITECT OR ENGINEER'S DIRECTION.22.PRIOR TO PENETRATING STRUCTURE, THE CONTRACTOR SHALL X-RAY THE SLABS. CONCRETE CUTTING, COREDRILLING, AND ANY OTHER ACTION THAT COULD AFFECT OTHER SPACES BY NOISE OR INTRUSION SHALL BE DONEAFTER HOURS. ALL SLAB/STRUCTURE PENETRATIONS SHALL BE COORDINATED WITH THE STRUCTURAL ENGINEERFOR APPROVAL.23.ALL EQUIPMENT REQUIRING ACCESS SUCH AS J-BOXES, PULL BOXES, TRANSFORMERS, DRIVERS, ETC. SHALL BEINSTALLED IN ACCESSIBLE LOCATIONS. EXISTING ELECTRICAL DEVICES WHICH ARE LOCATED BEHINDINACCESSIBLE LOCATIONS DUE TO THE RENOVATION SHALL BE REROUTED AND MADE ACCESSIBLE.24.CONDUITS AND/OR MATERIALS LOCATED IN ENVIRONMENTAL AIR PLENUMS SHALL BE PROPERLY LISTED FOR THEAPPLICATION. INTERIOR CONCEALED RACEWAYS MAY BE AC OR MC CABLE IF ALLOWED BY THE AHJ. EXPOSEDRACEWAYS, INCLUDING RACEWAYS EXPOSED IN THE BACK OF HOUSE SHALL BE GALVANIZED STEEL OR ALUMINUMEMT. MOTOR CONNECTIONS SHALL BE FLEXIBLE METAL CONDUIT FOR INTERIOR APPLICATIONS AND LIQUID TIGHTFLEX FOR EXTERIOR APPLICATIONS. ALL OTHER EXTERIOR CONDUITS SHALL BE GALVANIZED STEEL, ALUMINUMEMT OR RIGID STEEL IF EXPOSED TO STRIKING. EXTERIOR CONDUITS SHALL UTILIZE COMPRESSION CONNECTORS.AC/MC CABLE SHALL NOT TERMINATE AT PANELBOARDS. A GUTTER OUTSIDE THE ELECTRICAL CLOSET SHALL BEPROVIDED WITH CONDUIT FROM THE GUTTER TO THE PANELBOARD.25.CABLE AND CONDUIT ROUTING SHALL BE DONE IN A NEAT AND ORDERLY FASHION. LINES SHALL BE RUN PARALLELTO ALL BUILDING FEATURES, AND SHALL BE GROUPED TOGETHER TO CREATE AN AESTHETICALLY PLEASING ANDEASY TO FOLLOW ROUTE. CABLES SHALL BE PERMITTED TO BE BUNDLED BUT SHALL NOT EXCEED TEN INQUANTITY. ROUTING SHALL BE COORDINATED WITH OTHER TRADES TO AVOID CONFLICT.ELECTRICAL NOTESFLUSH TELEVISION OUTLET MOUNTED BEHIND TV. COORDINATE HEIGHT WITH ARCHITECT. FLUSH MOUNTTWO-GANG OUTLET BOX WITH BARRIER, ONE SIDE SHALL HAVE DUPLEX RECEPTACLE, OTHER SIDE SHALLHAVE TELEVISION SIGNAL CONNECTION. PROVIDE 3/4" CONDUIT STUBBED UP TO ACCESSIBLE CEILING.20 AMP DUPLEX RECEPTACLE, MOUNTED ABOVE COUNTER TOP, COORDINATE FINAL HEIGHT WITH ARCHITECT.SINGLE POLE OCCUPANCY/ DIMMER SWITCH; PROVIDE LUTRON MSCL-OP153M OR SIMILAR, CONFIRMMDCOLOR SELECTION AND FINAL MODEL WITH ARCHITECT PRIOR TO ORDERING. COORDINATE FINAL TYPE AND LOCATION WITH ARCHITECT/ OWNER.20 AMP CLOCK RECEPTACLE, COORDINATE FINAL HEIGHT WITH ARCHITECT.CLELECTRICAL RISER & SCHEDULESE200