HomeMy WebLinkAboutProject InformationRECEIVED Project Summary APR 2 3 2020 Job: wrightsoft° Date: Feb 17, 2020 Entire House Permitting Department Air Conditioning Unlimited LLC St. Lucie County 5536 NW Burgin, Port St Lucie, FI Proiect Information For: 5806 Sunset Blvd., Adams Homes 751 Port St Lucie Blvd., Port St Lucie, FI Notes: Design Information Weather: Winter Design Conditions Outside db 42 'F Inside db 68 °F Design TD 26 °F Heating Summary Structure 17288 Btuh Ducts 6720 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 24008 Btuh Infiltration Method Construction quality Fireplaces Fort Pierce, FL, US Simplified Average 0 Heating Cooling Area (ft2) 2116 2116 Volume (ft3) 17607 17607 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 94 47 Heating Equipment Summary Make Carrier Trade CARRIER Model 25HBC537AO030 AHRI ref 10487322 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacitybalance point= 33 °F Summer Design Conditions Outside db 90 'F Inside db 75 'F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 18133 Btuh Ducts 10232 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 1707 Btuh Use manufacturer's data n Rate/swing multiplier Equipment sensible load 0.95 28568 Btuh Latent Cooling Equipment Load Sizing Structure 2961 Btuh Ducts 2824 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 5785 Btuh Equipment Total Load (Sen+Lat) 34353 Btuh Req. total capacity at 0.70 SHR 3.4 ton Cooling Equipment Summary - Make Carrier Trade CARRIER Cond 26HBC537AO030 Coil FX4DNB037L AHRI ref 10487322 8.5 HSPF Efficiency 12.5 EER, Sensible cooling 34600 Btuh @ 47°F Latent cooling 27 'F Total cooling 1167 cfm Actual air flow 0.049 cfm/Btuh Air flow factor 0 in.H2O Static pressure Load sensible heat ratio Backup: Input = 7 kW, Output = 23025 Btuh, 100 AFUE 15.5 SEER 24500 Btuh 10500 Btuh 35000 Btuh 1167 cfm 0.041 cfm/Btuh 0 in H2O 0.84 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrrgl�`sotC 2020-Feb-1707:42A3 •—•� Right -Build Universat Cao= 18 Fro R oor fac0 FI■ p COPY Pagel ... ents\Wnghtsofl HVAC15806 Sunset Blvd-Atlams.nup Calc = MJ8 Front Door faces: E FILE COPY + wrightsoft 5536 NW Burgin, Port St Lucie, Ft Right-J® Worksheet Entire House Air Conditioning Unlimited LLC Job: Date: Feb 17, 2020 By: 1 Room name Entire House mstrsuite 2 3 Exposed wall Room height 211.9 ft 8.3 ft 31.0 ft 8.0 ft heal/cool 4 5 Room dimensions Room area 2116.0 ft2 14.0 x 17.0 ft 238.0 ft2 Ty Construction U-value IOr HTM Area (ft2) I Load Area (ft2) I Load number (Btuh/ft'-'F]I (BtuhM1W) or perimeter (ft) I (Btuh) or perimeter (ft) I (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A flocs 0.143 n 3.72 2.55 -,to 8 388 1434 982 ' 136 TN 447 ' 306 �G Vy 2glazing,cUautr,_ _ 12C-0sw _ ___0.330 0,091 _ n_ a ._.8.58 2.37 ..__ _9.77, 2.18 _ __.22 168 �._._._.0 148 ...___. 192 351 ____219 324 _ ____16 0 _. 0 0 ___ _136 0 _ _ 155 0 11 11P0 43A-40m �"��- 0.290 -R-0.143 _e a _ 7.54 ~372 8.41 -��2.55 _ _ 20 _ 279 __ 20 199 150 ---- 740 167 _ 507 0 -----0 0 --- -0 0 0 0 -----p __�D w l--G Vy 2 glazing, clr outr, .11P0 ________ 13A4ocs 0.330 ___,0290 0.143 a -_.e. s 858 __ _7.54 3.72 27.05 __.:8.41 2.55 59 __. __ _21 408 0 ,_.._,21 - 1506 __.._._158 1437 1596 _ __.177 M 0 _ __ _. 0 0 0 ___,__ 0 0 0 _.__._0 0 0 . _ _ .0 0 387 -G Vy 2 olazina. clroutr 13A4ocs _0330 0143 a__._, w 858 372 _ 10.72 2.55 22 q 466 0 m 361 184 --1342 _ _231 919 0 112 0 62 _ 0 - 305 0 l209 �G C-_ F _ 29tazirig:cluoutr,�_____-0.330 i8B-30ad 22A-fp1__-0.989 0,032 .w_._..858.._.27.05 _ - _ _ _ 0.83 _ 25.7,1 1.68 __ ;0.00 ___105 _2116 _ .211fi __.__0 _ 2116 _...._212 ..__._901._.._2840 __ _ 1761 __,_..5449 3555 __._0 ._-.30 _ -,238 -_..238 0 ._238 __ _31 _..._257. 198. _ _._._797.._ ,_-812 _ 400 .._ _.0 61 c)AED excursion 311 166 Envelope loss/gain 14605 12809 2140 2047 12 a) Infiltration b) Room ventilation 2683 0 774 0 385 0 111 0 13 Internal gains: Occupants Q 230 5 1150 2 460 Appliancestother 3400 0 Subtotal (lines 6 to 13) 17288 18133 2525 2618 14 15 Less external load Less transfer Redistribution Subtotal Duct leads 39% 56% 0 0 0 17288 6720 0 0 0 18133 10232 39% 56% 0 0 0 2525 982 0 0 0 2618 1477 Total room load Air requiretl (ctm) I I 24118 11671 21165 11671 I I 3507 170I 40 1619 Calculations approved by ACCA to meet all repuirements of Manual J 8th Ed t "�'rlgf•r^orr 2020-Feb-1707:42:43 Sunset Bl d-AdleS marupUniveCale=al 19.0.0o Door face Pagel ...entslWdghlsoR HVAC65806 Sunset BlvdAdams.rop CaIc=MJB Front Door faces: E wrightsoftRight-J® Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 Room name wic total 2 Exposed wall 0 It 4.0 It 3 Room height 8.0 ft heao'cool 8.0 Itheaticool 4 Room dimensions Room area 1.0 x 44.5 It 44.5 W x 8.0 It5 32.0 ft- Ty Construction U-value Or HTM Area (fP) Load I Area (W) Load number (Bluhffu-T (Bfuh/fP) or perimeter (ft) (Bluh) or perimeter (%) I (Btuh) Heat Cool Grass N/P!S Hea[ Cool Gross N/P/S Heat Cool 6 ...__ _ W �G _ _.___-.-_ _.. _ 13A3ocs 2glazing, elrouti,_..._ 12C-Osw .__.._ 0143 _ _ 0.330 0.091 ...__ - n n_. a 372 _-.858 2.37 2.55 -9.77 2.18 0� __0 0 �_ 0 --.---0 0 ..._._._.. 0 ._�._0 0 �`�0 0.-----,0 0 '0 32 ----0 -0 32 __ _ . 0 -----0 76 0 ___0 70 IW 11 11 PO _ 73A-0acs _ 0.290 0.143 _e_ a _ _ 754 372 ___8.41 - 2.55 __ 0 i0 0 ^.� 0 0 _��0 0 ._�.__0 _0 -_ _ 0 0 __ ___.0 0 _ _ _ ._0 0 _.__ _ _0 =c w I--G 2 glazing, dr outr, 11P0_ - _.._ 13A4ocs 0.330 ,.. __0.290 0.143 e'. _a_ s 858 __7.54. 3.72 27.05 .-_-8A1 2.55 0 _,._. _0 0 0 _0__.�0 0 '0 0 0 __ ___ 0._. 0 '0 _.__0 0 0 ._._._.0 0 0 _ ____ 0 0 0 0 _t _--DDD Vy t_ 2 alazina. clroutr __,_, 73A-0ocs ___ _0.330 0.143 ,_s , w ___8.58 372 �'� 10.72 2.55 ,_„_ �,_0 0 0 0 0 0 0 0 0 0 _ __0 0 ___-_ _0 0 _ _ 0 ��� �0 -.(' C_ __ E_-_ 2Blazing,clroutr, _... 16B30ad_,-_-__-._„ 22A-101. _ �.__ _._ ___0.330..w_ ,__ 0,032 ___0.989 -__ . __ ___.8.58 _--0.83 .. 25.7,1 ..-.27.05 _ 1.68 �.0.00 _ _,1_0 - _45 _. _ 45 _____:0 ___ ,_45 ..-0. _...----- 0 _._-_0 __, _, -:0 -_ _ ___32 .__ _ . 32 _____0,_.. _ 32 ._ _4 _--- .0 27 _ __103 .. _..__D _ 54 . __..0 37 � .0 _ 75 _._ _ _0 61 c)AED excursion _5 _g Envelope loss/gain 37 70 1 205 115 12 a) Infiltration b) Room ventilation 0 0 0 0 50 0 14 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 37 70 255 129 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 3 40 16 0 0 6 76 43 39% 56% 0 0 0 255 99 0 0 0 129 73 Total mom load Air required (cfm) I I I 53I 115I I I 3571 208I Calculations aggroved by ACCA to meet all requirements of Manual J 8th Ed #�!91xlso. TC RigUniversal 2B1919.D.68 R 0 2020-Feb-1707:42:43 '�._enlsWdghtsoft HVACL065unset Blvd-Adams.rup CaIc=MJB FronlOoorfaces: E Page wrightsoft' Right-.lM Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 Room name I in 2 3 Exposed wall Room height 8.0 ft 8.0 it heat/cool 16.9 R 8.0 it heat/cool 4 5 Room dimensions Room area 4.0 x 4.0 it 16.0 it' 1.0 x 117.5 ft 117.5 ft' Ty Construction number I U-value (Btuh/ft'--F Or HTM I (Btuh/ft') Area (ft') I or perimeter (R) Load (BNh) Area (it') I or perimeter (R) Load I (Btuh) Heal Cool Gross N/P/S Heat Cool Grass N/P/S Heat Cool 6 11 T W L--G Vy �D 13A-flocs 2 glaring. clroutr. _ 12C-Osw ,11P0_ 13A-0ocs � 0.143 __.0.330 0.091 0.290 .0.143 n _n_ a a a 3.72 - 858. 2.37 7.54 $.7Y2.55 2 55 __9.77 2.18 _ _ 8.41 32 _ -----0 32 0 -0 32 _.._ . 0 32 0 -'0 119 _._ __,0 76 -___ _0 0 81 _.._ _0 70 0 --_--0 88 . _ ,_ 7 48 0 -^---0 -� -- 82 ___0 48 0 --�-0 303 __ 56 114 D --0 4 - 207 _ -.-64 105 0 _��---0 _ VIA--G 2glazing clr outr, 13A-4ocs 0.330 -,0.290 0.143 a _e_ s 8.58 __ 7.54..._.8.41.0--- 3.72 27.05 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 _. 0 0 0 -..0 0 ._�-D.:11Po Vy t-13A-0ocs 2 alazina ;dr outr _,�0330 0,743 a__._,858-__10.72. w 3:72 2.55 -___0 0 00 "0 0 0 _.,- 0 0 __..,�_0 - 0 0 0 „_. _.__0. 0 _. G C_-_-_ F 2 glazing, Nr our,....- 16B7308d.._.__ 22A-fpl ,._ --_0.330 ,._..-,0.032 _ 0.989 _w_ - _..---_ =_ __.8.58 0.83. _. _.25.T.1 -27.05 _-_ 1.68 _._ 0.00 ---- --0. 16. ___ __ 16 __ __.:0 r..___ i6 __.,__..8 .___ -_-0 ._.� _73 �._-206 `- ^0 0.__-o _ _ 27 _ _._ .,--0 --„--178 __. __118._ _-.-0 - 118 17 _-__._0 _.__- 98 -._._435 _.. ___0 _ __197 6 c) AED excursion _13 -01 Envelope lossigain 4141 1651 i 1005 532 12 a) Infiltration b) Room ventilation 99 0 29 0 211 0 61 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 - 0 0 Subtotal (lines 6 to 13) 513 193 1216 593 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 -513 0 0 0 0 .193 0 0 39% 56% 0 0 513 1729 672 0 0 193 787 444 Airrel9uir load I I I 0d(cm) OI OI I I 211 I 1251 Calculations anDroved by ACCA to meet all requirements of Manual J 8th Ed Rig2020-Feb-1707:42:43 Sunset BSuiAd Universal Cal2019 19.D.0o R Door faces: Page3 ...ents\Wrightsofl HVACL58065unset BlvbAdams.rup CaIc=MJB Front Door faces: E + wrightsoft2 5536 NW Burgin, Port St Lucie, FI Right -A) Worksheet Entire House Air Conditioning Unlimited LLC Job: Date: Feb 17, 2020 By: 1 2 3 Room name Exposed wall Room height laundry 7.0 8 8.0 it heat/cool p 0 it 8.0 it heal/cool 4 5 Room dimensions Roam area 7.0 x 9.0 it2.0 63.0 u2 x 5.0 ft 10.0 H2 Ty Construction J-value IOr HTM/ft2) Area (w) I Load I Area (u2) I Load number (Stuh/ft2-°Ft (Bluh or perimeter (it) (Btuh) or perimeter (ft) I (Btuh) Heat I Cool Gross NIP/S Heat Cool Gross NIP/S Heal Cool 6 Yy _. G Vy 13Adacs 2glazin9; dr ouu _..._,. 12C-0sw ---6:f43330 -.0091 0.091 'n w.n__._;837 a 3 72 2.37 2.55 _N.2.18 2.18 0 '._., ,. _6 56 0 _,,..., _36 36 0' _. �.__0_.. 86 0 —,..-0 79 0 '. ...0 0 - 0' ___0 0 —' 0 ,._ _ 0 0 0 _._ __...0 0 11 11P0 _ __— 13A-4ocs __.— 0.290 0.143 , e_ e __754 3 72 _ 8.41. 2.55 ____20 0 ,�__20 0 �_150 0 ___ 167 , 0 0 --` 0 �__-_0____ 0 0 0 0 _ 0 _�-_ --._ 4y 2 glazing clr outr, II PO __._-____. 13A.4ocs 0.330 ___.._0290 0.143 a _e.—_.7.54._ s 858 3.72 27.05 _8.41-.___0._-__.__0 2.55 0 0 0 0 0 _-.__._0 0 - 0 __0 0 0 _0 0 0 .. -----0 0 0 __. _.__:0 0 0 _.. _. 0 0 .__. 4y 2alazina. Or outr..—.0.330_.s8.58_._.10.72,,____,_0-000 13A4ccs 0.143 w 3.72� - 2.55 0 0 0 0 0 0 0 0 0, 0 ._. _. _0 -0 .--G 2.glazing, dr outr,.__. —_._.0330._w_..__8.58 —27.05 _».,.0-_._.___0_. _._...0 __.___._0 ___-__0 ____0___—_.0 --___.0 p-___, F_ ___. 168-30atl __...___.. 22A-Ipl.-.__ _._... __..__-__ ._. _. 0.032 0.989 ._.:._... _c_ _0.83 ._ .25.7.1. 1.68 _._._0.00 "'..--.-___63 L.___.__63 _....... _63 _ _.. 7 -. »_.52. .__'.180 __-'106 __ ____0 10 ____._ 10 10 ...._ _-_ _0 _. _8 _ _.0 ...__. 17. _ _ .. .0 61 c)AED excursion 571 1q Envelope losstgain 4681 295 1 i 8 161 12 a) Infiltration b) Room ventilation 87 0 25 0 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13) 554 820 8 i6 14 15 Less external lead Less transfer Redistribute. Subtotal Duct loads 39% 56% 0 0 1 556 216 0 0 2 822 464 39% 56% 0 0 -8 0 0 0 0 -16 0 0 Airtreyuved (cfmj I I 73e1 125361 I I OI OI Calculations aooroved by ACCA to meet all reauirements of Manual J 8th Ed 2020-Feb-17 07.42:43 Sunset Blvd -Ad ms.rupUniveCole=al J8 Front R Door faces: Page ...ents\Wnghtsoft HVAC15806 Sunset Blvd-Atlams.mp CaIc=MJB Front Door faces: E + wrightsoft* 5536 NW Burgin, Port St Lucie, Ft Right-J® Worksheet Entire House Air Conditioning Unlimited LLC Job: Dale: Feb 17, 2020 By: 1 2 3 Room name Exposed wall Room height kiUbrkst 10.0 ft 9.0 ft heatfcool dining 23.0 0 8.0 ft heaVcml 4 5 Room dimensions Room area 1.0 x 220.0 ft 220.0 ft' 11.0 x 17.0 ft 187.0 ft' Ty Construction number I U-value (BtuhIftMF19 Or HTM I (Btuh/ft') Area (ft.) I or perimeter (ft) Load I (Btuh) Area (ft') I or perimeter (ft) Load I (Btuh) Heat Cool Gross N/P/S Heat I Cool Gross NIP/S Heat Cool 6 T—G 13A4ocs 11III 0d43 n 372 2.55 0 0 0 - 0 - 64 163 B4 -- 238 291azin9, clLouU.-.. 12C-Om _—.0.091 0.290 ._a a ._..858 2.64 ,_.2.18 T. ... ;0 0 �._-0._�.....-0 0 0 ___.. .0 0 ._..__�0 0 ..�_._,.0 0 _._ .__.0 0 .__ _'..0 0 Vy 11 11 PDa 13A-0ocs 0290 0143 �e e � _754_ 372 8.41 8.47. �2.55 0 ---�-0 __ 0 0 0 �_'�0 0 0 ___0 ' S8 0 0 -�-- 148 _'�-0 �88 —'���• 216 � Vy 2 glazing, clr outr, 11Po._.___.._.-.._..__0.290 73A4ocs 0.330 0.143 e ,_e_-__7.54.___.8.41__.__0 s 8.58 3.72 27.05 2.55 . 0 0 0 _0 0 0 —._-_.-0 0 0 ____.0_ 0 '30 0__._. 32 0 32 257 __0 119 812 _ 0 - 81 Vy 2 glazinq, clr outr, 73A4ocs „ _y 0.330 0.143 s_ —w 8.58 3.72 10.72 2.55 0 90 _... 0 60 _.--__.a22, 0 223 v. _.--_0 153 0 0 0 ~� 0 _ 0 ' -0 _ _ _ 0 0 �G C__. .. F_ ___ 2gla:ing,droutr, _ 16830ad-_-, `-_ . 22A-Ipl_�____-__ _ __0.330 _�0.032 _0.989 _w_ --,-„-, ____8.58 0.83 25.7.1, _ 27.05 1168 _ _ 0.00 __-__30 ,_ 220 . _.._ ----220 _._ _,_.0 -_ _.220 ._. _- 10 ._. _257 183 .._. .._... ._._ _ 257 ___ _812 -.«-370 _- .__0 _ ___0 ._... _ 187 _-___ 187 _. _. 0 _....._ 187 ___ ___23 _____ _ 0 _ ,_LL 156 ___591 ___--- -0 - ..__ 314 v_._.... 0 6 c) AED excursion 142 1 Envelope loss/gain 921 1476 1577 1519 12 a) Infiltraticm b) Room ventilation 140 0 40 0 286 0 82 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 2000 0 Subtotal (lines 6 to 13) 10fi0 35161 18631 1601 14 15 Less external load 1 Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 4 1064 414 0 0 8 3524 1988 39% 56% 0 0 399 2261 B79 0 0 436 2037 1149 load1472I Aotaequved(c(m) I I 18 5 227 I I t5 331 3131 —_ Calculations aooroved by ACCA to meet all recuirements of Manual J 8th Ed =lgtiis'an � 2020-Feb-1 7 07:42:43 Right3uite® Universal 2019 19.0.08 RSU06570 Page 5 ...ents\Wrightsoft HVACZ806 Sunset Blvd-Adams.rup CaIc=MJ8 Front Door faces: E wrightsoft Right-M Worksheet Job: Entire House Dale: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area great an 16.0 ft 9.0 ft heaycool 16.0 x 23.0 ft 368.0 fP foyer 7.0 it 9.0 it heat/coot 7.0 x 13.0 ft 91.0 fP Ty Construction number U-value (Bluh/ftIMF Or I HTM M uldfP) I Area (fN) or perimeter (ft) I Load (Btuh) Area (fN or perimeter (it) I Load (Btuh) Heat Cool Gross N/P/S Heat I Coal Gross N/P/S Heat Cool I_ 6 11 W ' _ G Vjy �_ 13A-0ocs 291azin9. or outr.._ _ 11po 11P0 _ _ , M-flocs 2 glazing, Gr outr, �Y 11P0.____..__ ___ 13A-4ocs 2 alazina. clr,outr. 13Addis 2 glazing, clr outr... -.._ 16B_30atl,-„__,_ 22A-�- __ 0330 ._. _0091 0.290 0.290 ---0.143 0.330 _ _0.29D 0.143 ..__.._ 0,330 0.143 --_._0330 .,_V,_0.032 __._.D.989 �_ n 'n.. a _ e_ a a _e_ s ,_s__ w w. __-, ._�. _ 372 .__..837 2.37 7.54 -3.72 8.58 _. 7.54 3.72 _.__8.58. 3.72 -___8.58._.27.65___-30 -__0.83 25.7.1. 2.55 .... 2.18 2.18 __ 8.41 _2.55 27.05 __,8.41 2.55 �. 10.72 2.55 _- J.68 _ _.0.00' 0 _ .- _0 0 0 --_0 0' _ __0 0 _..__.__0 144 - 368 ._.,�368 0 ......-. A 0 0 ��- 63 14 _.____21 0 - 0 _-_ ,- 0 _ _ _ 91 ._ -- 91 0 _. ...:0 0 0 28' 0 -_ _21 0 _.__ _, 0 0 _.____0 _ 91 .__ ._7 0 _. ___.. D 0 0 �104 120 _. _158 0 0 - ��_0 _...___0 76 .._ _�180 0 ... 0 0 _ _ 0 71 379 _.. _177. D _. _._ 0 0 _.__ 0 153 _..._ _..0 0 _... A 0 0 �---0 D ._._-._0 0 _. __0 - ' 114 ---0___-257-__._812_.._.__0 „_,368 �_-___ 16 0 _. :._.0 0 0 �---0 0 _... _ _0 0 ...,_'0 424 _ _308 _ __411 __ 0 _ ,.._ 0 0 0 - ^0 0 0 0 __0 ' 290 .�,_ 618 T �:_ _0 `D V f•-�-G II -DD Vy _�...._ Vy C _ - F_ ... 6 c)AED excursion 186 -3 Envelope loss/gain 1399 1906 638 776 12 a) Infiltration223 b) Room ventilation 0 64 0 98 0 28 0 13 Internal gains: Occupants @ 230 Appliancestother 0 0 900 0 0 0 Subtotal (lines 6 to 13) 1622 2671 736 804 14 15 Less external loatl Less hansfer Retlistribution Subtotal Ducl loatls 39% 56% 0 0 357 1980 770 0 0 345 3216 1815 39% 56% 0 0 -736 0 01 0 0 -804 0 0 Toeroom load I lraquiretl (cfm) I I 27 149I 5200371 I I I O I O34 Calculations approved by ACCA to'meet all reauirements of Manual J 8th Ed Rig2020-Feb-1707:42:43 .ICCA Sunset BhuiAd UniversC 201919.0.0o Doar face Page ...enlslWdghLsoft HVACL5806 Sunset BlvdAdams.rup Cale=MJB From Ooor hates: E A,_ wrightsoft• Right-M Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area bedml4 21.0 it 8.0 itheat/ccol 10.0 x 15.0 it 150.0 ft2 c2 3.0 it 8.0 itheallcool 3.0 x 7.0 ft 21.0 fP Ty Construction number U-value (Btutdit'- °F Or HTM I (Btuh/fP) I Area (W) or perimeter (it) I Load (Btuh) I Area (w) or perimeter (fl) I Load Heat I Cool Gross I NIP/S Heat Cool Gross N/P/S Heat Cool T— 11 _ _ Vy � W F---G I--D W --G 4y — _ C_, _.._ E_,_ 2 glazing. clr,outr:__ 12GOsw 11P0 73A-flocs ---- 2glazin0 cir outr, 11P0__-__.___ 13A4ocs 2olazino. clr outr,-_-__,____0,330 13A4ocs 2glazing,.ciroutr,_ _. 16B;30ad___,__ 22A-1p1._, ___0.330 0.091 __-0.290 0.143 0330 __._0.290_e_ 0.143 0.143 ._.._0.330 _,_,_0.032 ._ __.0.989 _n- a _a__ a a s ...s w _w,__8.58 __ _ ___ ___ 8,58....__9.77. 2.37 __754 372 8.58 _.7.54.. 3.72 8.58 3.72 _ 0.83, .__25.Z7 — 2.18 __ 8.41 �2.55 27.05 --8.41 2.55 10.72 2.55 ... 27.05 _168 _._ _0.00 ----88 _..__,_0 0 0 86 _...-_ -_0 0 0 327 _._,_—.0 0 0 242 129 _.. 0 _ - 0_0 0 --__.-_-125. __.__540 224 _____0 0 0 165�—�-0 406 0 0 _..,._ 252 _____,.0 0 ___. .. __0 0 0 .0 _0 0 0 Y' 24 _____.0 __,_._21 _ . _...__21 �� '0 ... _.0 0 0 0 0 0 0 - 24 _0 _-___,_21 .__. _ _3 ._ _._ _0 0 0 —� -'-0 0 0 0 --�— 80 _,0 ._,__ _17 __ 77 .�._ 0 0 0 ---'� '0 0 0 -_0 61 __. _-.a __,..__ 35 ._ .._0 80 15 _, ___0 0 0 �, 65 0 0 0 —i y-�0 0 _�_... 150 ____�21 0 _._,.__0—,_0.____G_____0 -____150 __ _.-:150 6 c)AED excursion J5 7 Envelope loss/gain 1362 1012 1 194 89 12 a) Infiltration b) Room ventilation 261 0 75 0 37 0 11 0 13 Internal gains: Occupants@ 230 Appliances/other 1 230 0 0 0 0 Subtotal (lines 6 to 13) 1623 1317 221 100 14 15 Less external load Less externtransfer Redistribution Subtotal Duct loads 39% 56% 0 0 765 1765 686 0 0 1488 48 940 3995 56% 0 0 -221 0 0 0 0 -100 p 0 Total room load I Alr required (cfm) I I 245111 119 P396I I I 0I O Calculations approved by ACCA to meet all requirements of Manual J Sth Ed .&A Right-Suite®Universal Colo= 1 Fro Door face 2020-Feb-1707:42:43 ...enlslWdghSofl HVAC15806 Sunset Blvd-Adams.rup CaIc=MJB Front Door faces: E Page 7 wrightsoftRight-J® Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, R 1 2 3 4 5 Room name Exposed wall Roam height Room dimensions Room area c2/2 0 If 8.0 It heat/cool 3.0 x 6.0 a 18.0 fl' bednn 2 25.0 it 8.0 It hea0cool 12.0 x 13.0 ft 156.0 ft' Ty Construction number U-value (fit Wit or HTM (Btut ) I Area (fP) or perimeter (ft) I Load (BNh) I Area (ft' or perimeter (ft) I Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W�- _ --C W --- W �G fly `G C. ._,__ F_. _ 13A-4ocs 2 gluing, drouir. 12C-Osw 11P0 134-46cs 2 glazing, or outs, 11P0_.____, 13A4ocs 2 olazinp. clr outs, _ ._ 13A-0ocs 2 glazing, NrouS;._.__ 168-30ad.,-,_,___ __. _ 22A-tpl _____._'_.�. 0743 .,_ _0,330 0.091 0.290 0.143 0.330 -_-_-0.290-_e___7.54..__8.41 0.143 __ v0,330 - 0.143 _ _..0.330 - _ w0,032 0.989_.a____25.7.1..___0.00....... n n _.._ a a e- a s s _ w_ _w_ ;_. �___ '372 _..858 237 754 -�-372 .8 58 3.72 �8.58 _ 3.72. -__8.58 _.___0.83. __-1__ -1-T-_ 0 .,„,., ...-,0 0 0 0 0 0 0 .._,-.._._.0 _.. ,_15 0 __ . _.. -0 0 0 --' 0 0 _.0 387 0 -_.._301 _-_129 _ _-- _130. 0 ._.:0 0 0 __-__-a 0 _-_ _.0 265 0 2.55 .9,77 2.18 8.41, 2.55 27.05 2.55 _ 10,72 _ 2.55 _.-27.05 _„_1.68 -0 . ____0 0 _ 0 0 - 0 ._00.__.__._.0__.�_.0._-_-_.0 0 0 _.-"'"--0 ___._0 _. .._18__, _.._78 0 _____0 0 0 0. 0 0 0 ..._A._.,.0 __0._-__,0 . „__, 18 _._,__0 0 ._.. _,__._0 0 0 0 0 0 0 ..,..._ _0 .______0 _ 30 .._.__. 0-._._._156 0 ,.�„0 0 0 0 0 104 0 .._..- -.._96 __.__15. -_.__- 156 _ 0. .__ .__.0 0 0 �.-0 0 __0 104 _ 0 �.__ 81 --0._ -,,,_.- 156 .�-..__ 25____643_.____0 _�_206 _ _ -406 __ _- 262 __ 6 c) AED excursion -2 86 Envelope losstgain 15 28 1589 1224 12 a) Infiltration b) Room ventilation 0 0 0 0 310 0 90 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 1 230 0 Subtotal (lines 6 to 13) 15 28 1900 1544 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% L15-208 39% 56% 0 0 124 2124 787 0 0 7614 1819 914 oad Alrtre9ual uedl(cfm) I I I DI OI I I 2837I 10 21�I Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed w:L nh efC- Right-Suite®anlversa1201919.0.98 R 2020-Feb-1707:42A3 0 Page8 ...entslWdghLsofl HVAC15806 sunset Blvd-Atlamsjup CaIc=MJB Front Door oorfacfaces: E wrightsoft, Right-J® Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 Room name bath3 bedrm3 2 Exposed wall 6o it 11.0 It 3 Room height 8.0 it heat(cool 8.0 It heat(cool 4 5 Room dimensions Room area 9.0 z 6.0 it 54.0 fP 1.0 x 119.0 ft 119.0 it - Ty Construction U-value Or HTM Area (fN) I Load I Area (ft') Load number (,,uIVu .F (Btuh/ft-) or perimeter (fi) (Btuh) or perimeter (ft) I (Btuh) Heat Ceol Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-0oa 2 glazing, cIr outr.. _. �0143 _ __0330__n.___8.58 n. - 3 72 2.55 -9.77.__ 0 __0_ 0 _. __0 '0 ._...___0 - 0 -.. ____o 0 -- ---0 0 __. _--0 '- 0 ___ __0 D ___.___0 vy 12C-0sw 0.091 a 2.37 2.18 0 0 0 0 0 0 0 0 11 13A-0acs 0290 -0 143 _ a_ a _754 3 72 _ _8.41, 2.58 0 0 0 0 „__�,_ 0 0 0 0- 0 0 _ __.0 0 '-0 0 2 glazing or outr, 11P0._ _---._._ 13A4ocs 0330 __ __0290 0.143 a _e.- s 8.58 __ 7.54..-;8.41 3.72 27.05 2.55 0 __-...0 48 0 -._-0 48 0 ___,-. 0 178 0 0.,-__0 122 0- 88 ,0 _0 73 0 .. .. _.__0 271 0 _ _.0 186 Vy __-. i 4y 2 plazinq.clr,outr 13A4ocs ___0.330 0.143 -- s_ w -„�858 372 -„10.72 2.55 _0 0 _0 �~ 0 _,_-„ _0 0 -__-..0 0 _-., 15 0 _ _,_ 0 0 _.- __ 129 0 -_- 161 0 .__ C F,___ 2 glazing, clroutr, 16B_30ad_________„__,- 22A-tpl ------..__.0.989 . _..._. ___ _ _.__0330 0.032 w -_„ __ 858 _._0.83, -_:2571 __27.05 -_"� 1.68 _-_0.00 _ _,0 __. ,54_-_54 �..-------- 54-___..„-_6 ----.0 _.--- _0 _ ___.45 --_--:154 _.__ 0 _-_91 ,,.--_..__0 _ __-_0 119 ,_...^„.11S __.-__0 119 _.. 11 _ :.. -0 _ _-_99 .283... -_-0 -._200 ..-.... 0 6 c)AED excursion -15 -30 Envelope loss/gain 3781, 78 198 782 517 12 a) Infiltration b) Room ventilation 74 0 21 0 137 0 39 0 13 Internal gains: Occupants Qa 230 0 0 1 Appliances/other 0 jo Subtotal (lines 6 to 13) 452 219 919 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 12 464 180 0 0 23 242 136 39% 56% 0 0 27 946 368 0 0 51 838 473 'T alroomload Air required (cfm) I I I 645 31I 378 16I I I 1313 64I 1310 541 Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed 2020-Fah-1707:42:43 Right -Suite® Universal 201919.0.08 RSU06570 ...entslWrightsoft HVACX5806 Sunset Blvd-Adams.rup Cale =MJ8 Front Door faces: E Page wrightsoft, Right-J® Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, R c4 c3 =dimensfons 11.0 ft 8.0 ft heat/cool 0 ft 8.0 ft heat/cool s 6.0 x 5.0 ft 30.0 fP 5.0 x 2.0 ft 10.0 ft' Ty Construction number U-value (Btuh/ft;°F Or HTM (Blob/(!') Area (ft') I or perimeter (ft) Load I (Blob) Area (ft') or pedmeter (ft) Load I (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 . 11 4y - - W �D W - � - Vy lum s 2 gluing, 12GOsw 12C-0s9, clroutr, m..____0.091 11PQ cs 13A-0oas �� 2'glazing clr outr, _ 11P0___ ,__ _' 13A-4ocs .__.__.__- 0.143 0.290 0.143 _� 0.143 0.330 _ ____.0.290 0.143 _._.. n ...:n_ a _e - a a _e_ s __--___.w-___ 3.72 __..e2.37 2,37 __754 372" 858 754 3.72 .._.,9.77....._...-.0D,__,...,.,0 %7Z 8,41 _-_8,41 2.55 27.05 _ _8,41 2.55 0, 0 0 48 - 0 ----0 --_0 40 -` 0 0 0 0 0 0 � 178 0 _ _.a0 149 __,__,. _ 0 _-.�_._ 0.____., 0 0 "-122 0 _ _.0 102 _ _�___ 0 0 0 0 �-�-0 •0 �..._0 0 _ __-- ._.__0 0^^ 0 0 -'�_'�0 0 _ _ _._.0 0 �_ .0 - A 0 0 � -�-'0 0 _ _ _.. 0 0 _�_ 0 0 0 ���--'0 0 ._-..__A 0 48 b ._ -__0 40 - Yy 2plazina, clr outr.-_,_,Y___0.330 13A-4ads 0.143 _s_ w 8.58 3.72 ,._„10.72 2.55 _„�_-_,_0 0 ._._.__...0 0 0 0 ___,_„_ 0 0 .__.._0 0 __ __,_,� 0 0 __0 0 _0 0 _�- A..__ _ F 2 glazing, dr cutr,._.__ 16B30atl .._,._ 22A.tpl.,,,,_�._..._� ____0.330 ____0.032 _,___.0.989 .w _.; _ ._-._ ___.8.58 __.0.83 ._. 25.7L _.27.05 - -1.68 _ -0.00 __._. __.0 ,_ 30 _._. �.. 30 0 30 _..__ _ �.__ 11 -0 .. .. _._ 25 —_-283 --- __0 ._..._..... 50 ___0 _---o , _JO _ 10 __-0 .. 10 _.._� _0 _0 .._. .8 .. --_0 .._ _. _0 _. _17 D 6 c) AED excursion -20 -1 Envelope loss/galn 635 251 8 16 12 a) Infiltration b) Room ventilation 137 0 39 0 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 772 293 8 16 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 0 772 300 0 0 0 293 166 39% 56% 0 0 -8 0 0 0 0 -16 0 0 m load AlrtaeQuoired (cfm) I I I 1052I 419 I 01 001 Calculations aooroved by ACCA to meet all requirements of Manual J 8th Ed Rig,C, 2020-FelA707:42:43 Sunset Bluite®ms.rup sCale=al 19. Fro R Door faces: Page 10 ...enLslWd9htsaft HVAC15806 Sunset Blv0.Adams.rup CaIc=MJB Front Door (aces: E wrightsoft, Right -JCS Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC ey: 5536 NW Burgin, Port St Lucie, FI 1 2 3 Room name Exposed wall Room height bath2 12.0 ft 8.0 it heat/cool ec 0 It 8.0 It heaUcool 4 5 Room dimensions Room area 6.0 x 12.0 ft 72.0 fN 2.0 x 6.0 It 12.0 fP Ty Construction number I U-value (Btuh/ftLT Of I HTM (Btuh/fe) I Area (ft')I or perimeter (ft) Load (Btuh) Area (fN) or perimeter (ft) I Load (Btuh) Heal Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool 6 T W .`G Vy 13A4acs 2 glazing, clr.outr, 12C-0sw 0.143 --_.0,330 0.091 _ __-0. 0 _.. ..,0 0 _--. __ 0 0 _ - 0 0 n _n:.—.858 a 372 2.37 2.55 - 9.77 2.18 -----0 ..,_0 0 _ 'T 0 -- _-0._-..,_'_..:0 0 0 0 11 71P0 _ _.. 13A-0ocs0.743 0,290 _ e_. a _,- 754 372 _8.41 2.55 0 - 0 _____0 0 _0__,___ 0 _0 0 _0 0 _0 0' _ 0 '-0 0 �0 _ - i 2 glazing'clr outr, 11P0_______..- 13A-40M 0.330 __,..0.290 0.143 a _a.-.__7.54. a 8.58 3.72 27.05 _-8.41 2.55 '0 96 ' 0 __._. _0 90 0 __—__0 - 333 0 _ -_0._- 228 0 _._._-0 0 0 _ ____0 0 0 __..._0 0 0 __..._ 0 0 Yy VG W 2 olazino.clroutr.._._ 13A-0ocs _ 0,330 0.743 s -w _ _. _858 372 _ 10.72 � 2.55 __7 __,_, —0 O _ 58 _.r � 0 _ 70 V0 0 0 ._0 ,. 0 _ _ 0 _ 0 _. U 0 - 0 . _G F__._ 2 glazing, clroutr,_ _ _..� 22A-b1 _0,330 _._0.032 0.989 w. - _ -. -._858 0.83 ,__257Y _._27.05 - 1.68 ___.0.00 —0 ...,_.72 ..., _.. _...72__ ----___0 72 12 _ __0 ...._,__ 60 -.__.309 _-___0 - _� _ _._,� _0 0 _,-..__0 , ... 12 12 __ _,0 _ 12 :_D ..-... ------0 __._ 10 __ 0 _ _ __0 , , . 20 _.. _0 61 c) AED excursion -20 -1 Envelope loss/gain i 757 399 10 19 12 a) Infiltration b) Room ventilation 149 0 43 0 0 0 0 0 13 Internal gains: Occupants nQ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 906 442 10 19 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 1 907 353 0 0 3 444 251 39% 56% 0 0 -10 0 0 0 0 -19 0 a Airtl room loadrequired (c m) I I 12695 1I 829 I I 01 0I Calculations aooroved by ACCA to meet all reauirements of Manual J 8th Ed .0 #' rrL91x!>=nfC 2020-Feb-1707:42:43 Right-SulteO U niversal 201919.0.08 RSU06570 ...entslWrightsoft HVACZ806 Sunset Blvd-Adams.rup Cuts =MJ8 Front Door faces: E Pag a 11 i ! wrightsofr Right-J® Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 Roam name 12 alh 2 3 5 Exposed wall Room height Room area O ft ( 8.0 ft heat/cool 6.0 fP O ft 8.0 ft heat/cool 16.5 ft2 Ty Construction number U-value (Btuh/ft'-'F Or I I HTM (Bluh/ft2) I Area (fP) or perimeter (8) I Load (Btuh) Area (ft2 or perimeter (ft) I Load (Btuh) I Heat I Coal Gross NIP/S Heat I Cool Gross I N/P/S Heat Cool Imo- 11 . I---G Vy ___.. 2 glazing, cicoutr.... 12C-Osw 11PD_. 13A-0ocs .0330 0.091 0.290 0.143 . h _o.. a —e_ a iT- 372 _._..8.58 2.37 ,_7.54 3.72 25T' ..-_9.77, 2.18 8.41 —21ii _.-_..0__O 0 __— U 0 0 0 -��_ 01- _. _ _-_0.-_..__.0 0 . ____O 0 - 0 ._.__._.D 0 _. _'0 0 _•__ _0 0 �— 06 .,_. -0 0 0 0 �0 0 0 ____ _0. 0 0 __. __A 0 �__ 0 0 --""0 0 t--G Vy _-,�-_G, W 2 glazing, Gr ouV; 11P. — 13A-4ocs 2 alazino. clr out_r.__--„ 13A-0ocs ", 0.330 0.290 0.143 r _� 0330 0143 e- _e_ s s w 8.58 _-_.,-7.54 3.72 858 3.72 27.05 _,-;:8AI 2.55 -. .10.72 2.55 0 — 0 0 0 0 0 _A,.--_:0 0 0 0 0 ---__-_0 0 _._.0 0 0 __-,,._.0 0 0 0" 0 _-__.__.. 0 0 ---_, 0.-, 0 0 _._._-0 0 0 0 0 _--�,.,0 0 ,- 0. 0 0 _._ .�.:0 0 __..__. _D 0 LL:7] �--r' C_ _ _- F._� 2glazing. dr outr __. 15B-30ad _-_ , a-_ . 22A-1PI _-.___. _ ._.. __0.330 __ _ _oO32 ____0.989 _w_ y_ __ 8.58 _- 0,83. 25.7.1. __27.05 1.68 __._. _._.0.00 _0 __ __..6 -.__.6 __ _....0 -__._.-6__-._.-.5___... _-__..:0 __. 0 _- ___..0 —___. 0 10 -----0 _ _ _- 0 .. __..,J7_ _- _.- 17 —._..0 _�.17 _,___0 _____0 _14 _____._.0 28 .__.___0 ._.. 61 c)AED excursion _7 -2 Envelope losstgain 5 9 14 26 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants Q 230 0 0 0 0 Appliances/other' 0 0 Subtotal (lines 6 to 13) 1 51 9 14 26 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 39% 56% 0 0 -5 0 0 0 0 -9 0 0 39% 56% 0 0 -14 0 0 0 0 .26 0 0 Airtre9uueal(a ) I I 1 DI DI 1 1 DI DI Calculations anoroved by ACCA to meet all requirements of Manual J 8th Ed wNgti - 2020-Feb-1707:42:43 RightSuite® Universal 201919.0.08 RSU06570 Page 12 ...entsMrightsoft HVAC\5806 Sunset Blvd-Adams.mp Calc=MJ8 Front Doorfaces: E wrightsoft, Right -A) Worksheet Job: Entire House Date: Feb 17, 2020 Air Conditioning Unlimited LLC By: 5536 NW Burgin, Port St Lucie, FI 1 Room name It 2 Exposed wall 0 It 3 Room height 8.0 it heat/cool 4 Room dimensions 1.0 x 64.5 ft 5 Room area 64.5 fix Ty Construction U-value Or HTM I Area (ft') I Load I Area Load number (BtuNfle � (Btul✓fl°) or perimeter (ft) (Btuh) I or perimeter Heal Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 fly'13A-0ois V"glazing, 0.143 n 372 2.55 6 '0 0 _ 26 clr cub ____0330 _.n_ ___858, .: .__9.77 __-_,0._..__..,_.0 _ —0 "- Yy 12C-Osw 0,091 a 2.37 2.18 0 0 0 0 _LO 11P0 —'—�� 0.290 --_-�0.143 _ e _ 0 0 0 0 17 W 13A-flocs a _7.54, 3.72 _ __8.41 2.55 "0 p -�- -- p `—' -0 F--G 2 glazing, clr outr, 0.330 a 8.58 27.05 0 0 0 0 __ _0290 _e_ —754. _r8.41. _ _„0 _ 0 W 13Adocs 0143 s 372 2.55 0 0 0 0 __,_, 2 alazina, dr ouV _ _ 0.330 ,s _ ,-„8 58. 10.72 _ ___0 , „,. 0 , 0 W 13A-4om 0143 w 3.72 �2 .55 0 0 ..,_ _'_0 0 0 2.glazing, clr oub, _-..__0330 _w.. _.,..8.58 __27.05 -----0 -------0 ___01_`0 Q 16B-30aA------- ___0.032 7.68 65 F_— 22A-1DI__ _..... L. __0.989 �___ ----0.83. .._.25.7.1. .___ ___0.00 ___—. ._ _� 65 -____ -65-____.54___108 _.0 A __..__,0 _ _ ___.___ _.._-_,.___..",...______ 6 c)AED excursion _7 Envelope losstgain 54 101 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants aQ 230 0 0 Appliancestother 0 Subtotal (lines 6 to 13) 54 101 Less external load 0 0 Less bansfer 0 0 Redistribution F56% -54 -101 14 Subtotal 0 0 15 Duct loads 39% 0 0 Air relquved (c m) I I gl OI Calculations aooroved by ACCA to meet all requirements of Manual J 8th Ed 'I+ wSL "M!a L � RlghtSuite® Universal 201919.0.08 RSU06570 2020-Feb-170Pa e 13 ...ents\Wdghlsoft HVAV5806 Sunset Blvd-Adams.rup Calc=MJ8 Front Door faces: E g 13 Job M Performed for: 5806 Sunset Blvd. 751 Port St Lucie BINd. Port St Lude, FI Sheet 1 Air Conditioning Unlimited LLC 5536 NW Burgin Port St Lucie, FI Scale: 1 : 92 Page 1 Right -Suite® Universal 2019 19.0.08 RSU06570 2020-Feb-17 07:43:12 ... HVAC15806 Sunset Blvd-Adan wri htsoft Manual S Compliance Report Job: 9 Entire House Byte: Fenn, zozo Air Conditioning Unlimited LLC 5536 NW Burgin, Part St Lucie, FI Project• • For: 5806 Sunset Blvd., Adams Homes 751 Port St Lucie Blvd., Port St Lucie, FI Cooling Equipment Design Conditions Outdoor design DB: 90.0'F Sensible gain: 30072 Stuh Outdoor design WB: 78.0'F Latent gain: 5785 Btuh Indoor design DB: 75.0°F Total gain: 35857 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Actual airflow: 1167 cfm Sensible capacity: 24500 Btuh Latent capacity: 10500 Btuh Total capacity: 35000 Btuh Design Conditions Outdoor design DB: 42.0°F Indoor design IDS: 68.0°F Model: 25HBC537A0030+FX4DNB037L 81% of load 182% of load 98% of load SHR: 70% NEMMIZEM Heat loss: 24008 Btuh Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC537A0030+FX4DNB037L Actual airflow: 1167 cfm Output capacity: 34600 Btuh 144% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 6.7 kW 96% of load Temp. rise: 50 OF Meets all requirements of ACCA Manual S. Entering coil DB: 79.5'F Entering coil WB: 64.6°F Entering coil DB: 67.1°F Capacity balance: 33 OF Economic balance: -99 OF C " WrightcsofC - 2020-Feb-1707:42:44 ....�..._,._.., RightSuite®Universal 201919.0.08 RSU06570 Page 1 ...entMWdghtsoO HVAC15806 Sunset Blvd-Adams.rup Cale =MJB Front Door faces: E wri htsoft Duct System Summary Job: 9 Date: Feb 17, 2020 Entire House By: Air Conditioning Unlimited LLC 5536 NW Burgin, Port St Lucie, n Project• • For: 5806 Sunset Blvd., Adams Homes 751 Port St Lucie Blvd., Port St Lucie, FI External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0 in H2O 0 in H2O 0 in H2O 0.000 / 0.000 in H2O 0 in/100ft 1167 cfm 181 ft Cooling 0 in H2O 0 in H2O 0 in H2O 0.000 / 0.000 in H2O 0 in/100ft 1167 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (ft) Trunk bathe h 695 61 29 0 4.0 Ox 0 VIFx 24.0 115.0 stl bath3 h 378 31 16 0 4.0 Ox 0 VIFx 6.0 100.0 bed=2 h 2533 137 104 0 6.0 Ox0 VIFx 9.2 100.0 bednn 4 h 2328 119 96 0 6.0 Ox 0 VIFx 24.2 115.0 stl bedrm3 h 1310 64 54 0 6.0 Ox 0 VIFx 20.9 120.0 sill 04 h 459 52 19 0 4.0 Ox 0 VIFx 30.2 115.0 stl dining h 3186 153 131 0 7.0 Ox 0 VIFx 21.0 120.0 st2 great rm c 5031 134 207 0 8.0 Ox0 VIFx 21.0 120.0 st2 kit(brkst c 5512 72 227 0 8.0 OX 0 VIFx 29.7 120.0 st2 laundry c 1286 38 53 0 4.0 Ox 0 VIFx 25.1 120.0 st2 m bath h 1230 117 51 0 6.0 Ox 0 VIFx 41.1 140.0 st3 mstrsuite h 4096 170 169 0 8.0 Ox0 VIFx 41.1 140.0 st3 tolet h 202 17 8 0 4.0 Ox 0 VIFX 38.1 135.0 st3 ""0 c 118 3 5 0 4.0 Ox 0 VIFx 35.1 135.0 st3 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1 Peak AVF 296 197 0 277 14.0 0 x 0 VinlFlx st2 Peak AVF 703 850 0 795 14.0 0 x 0 VinlFlx SO Peak AVF 307 232 0 695 9.0 0 x 0 VinlFlx st2 BolaVitalie values have been manually overridden -*- wrightsoft- 2020-Feb-1 7 07.42:44 •...., ..�.�.., Right-Suite(s) Universal 2019 19.. 008 RSU06570 Page 1 ...entslWdghtsoft HVAC15866 Sunset Blvd-Adams.rup Calc=MJ8 Front Doorfaces: E Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1167 1167 0 0 0 0 Ox 0 VIFx wrightsoft' 2020-Feb-1707:42:44 Rig htSuiter�l Universal 201919.0.08 RSUO6870 Paget ...entslWrightsoft HVAC1880B Sunset Blvd-Adams.rup Calc=MIA Front Door faces: E