HomeMy WebLinkAboutSpecificationsPossible Issues with Electronic Governing See Table 7 (Common faults and
their remedial actions) inside the
online "Operation InsWctions GC1031 GENSET
Controller' manual (part number 80086364).
Specifications
Generator Specifications: 17kW and
20KW
' 17k Watt.
Rated Maximum Load Current' (at
25'C777'F, LP)': at 240 Volts
70.8 Amps
Rated AC Voltage
120/240 Volts
Phase
Single phase
Rated Frequency
60 Hertz
Generator Breaker
80 Amp
Normal Operating Range
-20'F (-28.8'C) to 104-F (40'C)
Output Sound Level
69.1 dB(A) at 23IL (7 m) at normal
load
Shipping Weight
1610 lb (278 kg)
20k Watt
Rated Maximum Load Current' (at
25'C/77'F, LP)': at 240 Volts
83.3 Amps
Rated AC Voltage
1201240 Volts
Phase
Single phase
Rated Frequency
60 Hertz
Generator Breaker
100 Amp
Normal Operating Range
-20-F (-28.8-C) to 104-F (40-C)
Output Sound Level
69.1 dB(A) at 23 ft. (7 m) at normal
load
Shipping Weight
1626 lb (278 kg)
' Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Engine Specifications
. 17k Watt.
Displacement
60.60 ci. (993 cc)
Bore
3.405 In. (86.5 mm)
Stroke
3.366 In. (85.5 mm)
Spark Plug Gap
0.020 in. (0.51 mm)
Spark Plug Torque
180 lb -in. (20 Nm)
Armature Air Gap
0.005 - 0.008 in. (0.13 - 0.20 mm)
Intake Valve Clearance
0.004.0.006 in. (0.10 - 0.15 mm)
Exhaust Valve Clearance
0.007 - 0.008 in. (0.15 - 0.20 mm)
Oil Type
SW30 Synthetic
Oil Capacity (vdih filter)
78 - 80 oz. (2.3 - 2.4 L)
Engine End Cover Boll
220 lb -In (25Nm)
' 2Ok Watt.
Displacement
60.60 ci. (993 cc)
Bore
3.4051n. (86.5 mm)
Stroke
3.366 In. (85.5 mm)
Spark Plug Gap
0.020 in. (0.51 mm)
Spark Plug Torque
180 lb -in. (20 Nm)
Armature Air Gap
0.005 - 0.008 in. (0.13 - 0.20 mm)
Intake Valve Clearance
0.004 - 0.006 in. (0.10 - 0.15 mm)
Exhaust Valve Clearance
0.007 - 0.008 in. (0.15 - 0.20 mm)
Oil Type
5W30 Synthetic
Oil Capacity (with filter)
78 - 80 oz. (2.3 - 2.4 L)
Engine End Cover Bolt
220 lb,4n (25Nm)
BId
system setup
You must perform the following before operating the system:
• If generator is installed in an area regularly subjected to
temperatures below 40•F (4•C), select a 50 second warm up
time by moving jumper JP2 (C) installed on transfer switch
control board from '20' position to '50' position.
Set the DPSW1 (A) and DPSW2 (B) dipswitches on the
transfer switch control board to match the kW rating of the
home standby generator, as described In Setting Dipswitches.
/0/0
C7 M1
oa000uo
CQ
=:Je
.,,s 1 °
Setting Dipswitches
Dipswitches are used to adjust control board operation based
on generator capacity. DPSW1 and DPSW2 switches are, set to
correspond to total system kW rating. Dipswitch DPSWT..(A) has
units of 1,000 watts; Dipswitch DPSW2 (B) has unit of
10,000 watts.
Set dipswitches with power removed from the transfer switch to
ensure proper control system operation. If dipswitches are set
when power is present at transfer switch, a power reset needs to be
performed before the new dipswitch settings will take effect. Power
reset is when all power is removed from the transfer switch and
then reintroduced after 30 seconds.
NOTICE A transfer switch fault message will occur on standby
generator control board if dipswitches are not properly established
as noted above.
To properly establish the dipswitches, make sure that only one
dipswitch is set to "ON" position for DPSW1 and one dipswitch for
DPSW2. For example a 20kW generator, set DPSW2 dipswitch 20
to "ON" position and DPSW1 dipswitch 0 to "ON" position.
20,000 plus 0 equal 20,000 watts.
NONCE Use extreme caution when setting dipswitches or
damage to control board will result.
Use a pencil or small piece of plastic to set the dipswitch.
NEVER use a screwdriver or any type of metal object to set
dipswitches.
The "On" position for the dipswitches 1s the switch number ON
THE TRANSFER SWITCH CONTROL BOARD, not on the switch. For
example, for an 18,000 watt generator, set DPSW2 dipswitch 10 to
"On" position. Set DPSW1 dipswitch 8 to "On" position.10,000 plus
$000 equals 18,000 watts. Set only one switch to "On" position
on DPSW1 and DPSW2.
Refer to following chart for proper switch selection(s).
kW Rating
of
Generator
® OPSW
81 "ON"
Position
g OPSW
#2 "ON"
Position
M
7
0
8kW
s
0
90
9
0
10kW*
0
10
MW'
:1
10
1M..
2
10
13Wt ,, '=
3
10
14kW
4
10
16M
5
10
16kW
6
10
MIN
7
10
18kW
8
10
19kW
9
10
200
0
20
MIN
0
30
45kW
5
40
MW
8
40
MW
0
50
60M
0
60
• For genarat= sith a oft tW Includes 500 watts, =nd dw to
next tomt rating
(mmpk IM M eet to 13M
NOTICE Air density is less at high altitudes, resulting in less
available engine power. Specifically, engine power will decrease 3.5%
for each 1.000 feet (300 meters) above sea level and 1% for each 10°
F (5.6°C) above 77°F (250C). Generators located in these conditions
must have the transfer switch programmed appropriately for this
power decrease.
14 BRIGGSandSTRATTON.COM
Automatic Transfer Switch
Product Specfications
Model 071US
Series 100$ED
Rated Maximum load Current
a 25°C (770F)"..............................................................100 Amps
Rated AC Voltage...............................................................250 Volts
Poles............................................................................................... 2
Frequency................................................................................60 Hz
Fault Current Rating ..........22,000 RMS symmetrical Amperes on ucny side
.................................10,000 RMS Symmetrical Amperes on Generator side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight........................................................................13 kg (29 lbs)
Model 071049
Series 200SED
Rated Maximum Load Current
a25°C (77°F)•..............................................................2(W ps
Rated AC Voltage...............................................................250 Volts
Poles........................................................................ «.:........... 2
Frequency..................................................... ............. ...GO Hz
Fault Current Rating ..........25,000 RMS Symmetr[W'Ampem on utility Skle
.................................10,000 RMS Symmetrio Amperes on Generator Sid$
Normal Operating Range ............. !,.-28.8T 209to 40°C �04°
Weight .......................................... 4............................... 27 kg (59 ibs�
Model 071068 `
Series 200SED
Rated Maximum Load Current
a25°C (77°F)'..............................................................200 Amps
Rated AC Voltage...............................................................250 Volts
Poles............................................................................................... 2
Frequency................................................................................60 Hz
Fault Current Rating ..........25,000 RMS Symmetrical Amperes on Utility side
...............................10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight........................................................................27 kg (59 lbs)
This transter switch is a UL Listed device.
Model 071054
Series 200SED
Rated Maximum Load Current
a 25°C (770F)'..............................................................200 Amps
Rated AC Voltage...............................................................250 Volts
Poles............................................................................................... 2
Frequency................................................................................60 Hz
Fault Current Rating ..........25,000 RMS symmetrtcal Amperes on My side
.................................10,000 RMS Symmetrical Amperes on Gere3rator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight........................................................................27 kg (59 lbs)
Model 071070
Series 200SED
Rated Maximum Log, Current
a25°C (77AE)'.:.0..........................................................150 Amps
Rated AC Voltage...............................................................250 Volts
Poles:...:.:....................................................................................... 2
Eraquepcy................................................................................60 Hz
r
Fault Current Rating ..........25,000 RMS Symmetrical Amperes on utlydy Side
................................... 10,000 RMS Symmetrical Amperes on Generator side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (1040F)
Weight........................................................................27 kg (59 lbs)
Model 071071
Series 100SED
Rated Maximum Load Current
a25°C (77°F)'..............................................................100 Amps
Rated AC Voltage...............................................................250 Volts
Poles............................................................................................... 2
Frequency................................................................................60 Hz
Fault Current Rating ..........22.000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight........................................................................13 kg (29 lbs)