HomeMy WebLinkAboutREG SPECS - 7-14-20Bulletin LP -T R122H
Type R122H First -Stage Regulator
Introduction
The Type R122H is an Underwriters Laboratories listed
regulator designed for T.vo-Stage LP -Gas systems.
The unit is designed to reduce the tank pressure to an
outlet pressure of 10 psig. The compact size makes it
ideal for small domestic applications and underground
tanks. The outlet pressure setting is nonadjustable
and is factory set at a nominal 10 psig. Screened drip -
lip vents are oriented over the outlet as standard.
Features
• 20 Year Recommended Replacement Life - The
R122H is designed using rugged time proven
design concepts and constructed of corrosion
resistant materials, both intemally and externally.
With proper installation and periodic inspection and
maintenance the R122H regulator will meet a 20
Year Recommended Replacement Life.
• Dual Gauge Taps - Built-in 118 inch NPT gauge
taps orificed to a number 54 drill size on both
the inlet and outlet side of the regulator allow for
easy testing.
• Durability - A fluorocarbon valve disc is utilized
to improve lockup performance in systems with
contaminated gas.
• Improved Regulation - A large fabric -reinforced
diaphragm and stabilizer clip deliver accurate and
stable regulation.
• Easy Installation - The units compact size and
easily accessible inlet and outlet wrench flats make
installation easy even in the tightest installations.
March 2010
Figure t. Type R122H Frsr-Stage Regulator
Superior Overpressure Protection - The
combination of a high rapacity relief valve and large
vent provide overpressure protection that exceeds
IJL standards. When used in conjunction with a
R622 or R652, the two-stage system will limit the
downstream pressure from the second -stage to 2
psig even in a double failure situation.
• Corrosion -Resistant - Added corrosion resistance
from an internal and external coating process for all
castings prior to painting, stainless steel relief valve
spring and retainer and a corrosion resistant relief
valve seat.
Positive Draining Spring Case - When installed
properly with the spring case vent pointed down,
the design allows moisture formed in the spring
case to drain out limiting the problems with
corrosion and freezing water in the spring case.
www.FISHERregulators.com/lp
4r
EMERSON.
Process Management
Bulletin LP -7: R122H
Table 1. Ordering Informalron
TYPE NUMBER CAPACITY BTUMR CONNECTIONS
PROPANEM INLET x OUTLET NOMINAL OUTLET SETTING
R122H-AA,! 1,100,000 t1 -mm x 1 4nM NPT 10 pscg (0.69 Bar)
1 Catty to OZf00 an 30 PS* R07 ban rife! amsmm =w 20% arota
1/14.1810
FW.A
Figure 2. Type R 122 Dimensions atmos
IMM)
LP -Gas Equipamt
Emerton Process Management
Regulator Technologies. In&
USA - Headquarters
MdCf:nteq, Texas 75069.1872 USA
Tctephw e: l (800) 558,%%
Telephone:1(972) 5483574
For further information visit www. fisherreplators.corMp
The Fstt 4 A C bpm is a Lr4srs=tk aro weft marls at Em&-mn t:WW Co An Dater tusks aro tae txWM ad taen Wa%ncbvp awrters Flatter MSM a mask owrte0 Qy Frslttr Co ttrara tM.. a
bustsm ar Eators % Plot= Ktardoerrertt
The IrsI M , at tab pttboCIbon are presented qtr bs0 Mwanw OarPosos oily, arc waft every eRbrt stat bamt meas tb mum mw ss Awy. u" are row b be ean*ue0 sss wmw as or
duress artsttpom n ft amemb or =VMS eDasotbed txreat or afar use or wombaaywt nsSerna tat no co foully or mmm" tnt dtstpsts 0r qwCMCw1*M atsuch
pwWM at asty cane Mcm n n400t.
Peoasss kCfrtapnsetmzl predudp [adsrd n q sole r wm► tae for tde setec!>on. wa or MW4VW= or arty Pro"& P4SPWMaK4ty qtr PMPW aeteaoan. u3e aitd MRMft M of" r-r+orSon
EMERSON..
°E'ttom IN ' or Te&J*b9ft ft- M. 2010: Ao RVO Received Process Management
Bulletin 71.1:R622
Type R622 Pressure Reducing Regulator
• Compart Desinn
• Prote
Scree
. uinh rrnnn;ity
• Inlet and Outlet Pressure Gauge Taps
Figure i. iypr 8622 Prex:ma Raducmg Raqulnrw
Introduction
Type R622 direct -operated. spring-loaded regulators
provide economical pressure reducing control in
a variety of residential. commercial. and industrial
FISHER -
Relief
Veight
applications. These regulators can be used :ith
natural. manufactured. or propane gases and have the
same inlet and outlet pressure capabilities.
C.
EMERSON.
Bulletin 71.1:R622
Specifications
Body Size and End Connection Stylet) Pressure Registration
112 NPT inlet and outlet Internal
Maximum Allowable Inlet Pressurett)
Operating: 125 psig (8,6 bar)
Emergency: 125 psig (8,6 bar)
Except 1.8 to 2.2 -inches w.c. (4 to 5 mbar) spring
range which has operating and emergency
pressures of 60 psig (4,1 bar)
Maximum Allowable Outlet (Casing) Pressure0)
Operating to Avoid Internal Part Damage:
3 psid (0,21 bar d) above outlet pressure setting
Emergency: 20 psi (1,4 bar)
Outlet Pressure Ranges
See Table 1
Orifice Size
118 -inch (3,2 mm) orifice
Flow Coefficients
Wide -Open Cs for Relief Sizing: 12.5
Weide-Open C. for Relief Sizing: 0.36
Cl: 35
IEC Sizing Coefficients
XT 0.78
Fp: 0.82
FL: 0.89
Flow Capacities
See Table 2
Relief Performance
See Figure 4
Internal Relief Performance
Start -to -Discharge is 8 to 22 -inches w.c.
(20 to 55 mbar) for setpoints from
1.8 to 20 -inches w.c. (4 to 50 mbar)
Start -to -Discharge is 140 to 200°% over setpoint
from 20 -inches w.c. to 2.2 psig (50 to 152 mbar)
Spring Case Vent Connections
314 NPT with removable screen
Temperature Capabilities(')
-20° to 160`F (-29' to 71 °C)
Approximate Weight
2.35 pounds (1 kg)
Construction Materials
Body, Spring Case, Diaphragm Plate. and
Orifice: Aluminum
Diaphragm, Disk, and O-ring: Nitrite (NBR)
Adjusting Screw and Pushpost: Delrin®
Closing Cap: ASA Thermoplastic (UV -Ray Resistant)
Control Spring: Zinc- plated steel
Machine Screw, Spring Seat,
and Lever. Zinc -plated steel
Valve Stem: Zinc
Relief Valve Spring, Relief Spring Retainer,
Lever Pin, and Vent Screen: Stainless steel
1 7be Wma in Oft Suft fn or wW qWkcaW slaw" Mr4ow stmW not no wmeeaed.
0=6 a a MXk Owned by E I. dy Pw de marokas and Co.
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start -to -discharge point
of the non-adjustable relief valve spring moves the
diaphragm off of the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
Table 1. Outlet Pressure Ranges
Specifications
The Spedfcations section lists specifications forType R622
Pressure Reducing Regulators. As it originally comes
from the factory, specifications for a given regulator
are stamped on the spring case nameplate.
OUTLET PRESSURE RANGE
CONTROL SPRING PART
NUMBER
CONTROL SPRING
COLOR CODE
SPRING WIRE DIAMETER
INCHES (nun)
SPRING FREE LENGTH.
INCHES (MM)
18 to 2.2-Mchm w.c. (4 to 5 mbar)
T 14453TUO 12
Pulpae
0051(1.30)
3.40 (86.4)
5 to 7 -Indus w.c. (12 to 17 mbar)
T 14398TOO 12
Orange
0.062 (1,58)
3.40 (86.4)
6.5 to 94ncnes w.c. (16 to 22 Inbar)
T 1439970012
Yellow
0.067 (1.70)
3.61 (91,7)
9 to 134nC n w.c. (22 to 32 mbar)
T 1440070012
Saver
0.072 (1.83)
4.10 (104)
13 to 204 ndies w.c. (32 to 50 Inbar)
T 14401 T0012
Gray
0.080 (2.03)
3.60 (91.4)
16 to 35 -tram w.c. (40 to 87 mbar)
T 14402T0012
Pack
0093(2.36)
3.52 (89.4)
1 to 2.2 psig (69 to 152 mbar)
T14403T0012
LUPI Blue
0 105 (2.67)
3.66 (93.0)