HomeMy WebLinkAboutBuxton signed manual j and engergy calc.pdf 2007-0233FORM R405-2017 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: BUXTON GUEST HOUSE Builder Name: TREFELNER CONSTRUCTION Street: 470 WOODCREST DRIVE Permit Office: ST LUCIE COUNTY LI Y, State, Zip: FORT PIERCE , FL, Permit Number: Owner: TIM AND LACEY BUXTON Jurisdiction: ST LUCIE COUNTY Design Location: FL, For Pierce County: St. Lucie (Florida Climate Zone 2 j 1. New construction or existing New (From Plans) 9. Wall Types (1261.0 sgft.) Insulation Area 2. Single family or multiple family Single-family a. Concrete Block - Int Insul, Exterior R=4.1 1261.00 ft' 3. Number of units, if multiple family 1 b. NiA R= ft'c NIA R= fit' 4. Number of Bedrooms 3 d. NIA R- ft' 5. Is this a worst case? No 10. Ceiling Types (I 183.0 sgft.) Insulation Area a. Roof Deck (Unvented) R=20.0 1183.00 ft' 6. Conditioned floor area above grade (ft') 1183 b. NIA R- ft' Conditioned floor area below grade (ft') 0 c• NIA R= ft' 11. Ducts R ft2 7. Windows(147.0 sqft.) Description Area a. Sup: Attic, Ret: Attic, AK LINENIAHU CLST 6 125 a. U-Factor: Sill, U-0.32 147.00 ft' SHGC: SHGC-0.22 b. U-Factor: NIA ft2 12. Cooling systems kBtu/hr Efficiency SHGC: a. Centra{ Unit 17.7 SEERA6.00 c. U-Factor: NIA ft' SHGC. 13. Heating systems kBtulhr Efficiency d. U-Factor: NIA ft' a. Electric Strip Heat 17.0 COPA.00 SHGC: Area Weighted Average Overhang Depth: 2.000 ft. Area Weighted Average SHGC. 0.220 14. Hot water systems S. Floor Types (1183.0 sgft.) Insulation Area a. Electric Cap: 50 gallons a. Siah-On-Grade Edge Insulation R=0.0 1163.00 ft' EF: 0.980 b. Conservation features b. N/A R- ft' None c. NIA R= ft, 15. Credits None GiassiFioor Area: 0.124 Total Proposed Modified Loads: 44.86 A Total Baseline Loads: 47.27 A SS t hereby certify that the plans and specifications covered by Review of the plans and V -ViRE 5r this calculation are in compliance with the Florida Energy specifications covered by this ~ 0, Cade, calculation indicates compliance,, f with the Florida Energy Cade. PREPARED Y: Before construction is completed DATE: x p this building will be inspected for compliance with Section 553.908 I hereby certify that this building, as desigtni d, is in COMPliance Florida Statutes. with the Florida Energy Coda.wEzg�- IOWNERIAG N ' 7 'BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402A.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (111402.4.1.2). b/22/2020 3:30 PM EnergyGaugeV USA 6.0,02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page i of s FORM R405-217117 IIUDI IT CI IRARAADV r+uCr•Wl P#--,r nl mr%r%-r 9 I'LL—r WIN i PROJECT Title: BUXTON GUEST HOUSE Bedrooms: 3 Address Type; Street Address Building Type: User Conditioned Area: 1183 Lot Owner Name: TIM AND LACEYBUY.TON Tutai Stories: t Block/Subdivis; : 4 of Units: 1 Worst Case: No PlatBook: Builder Name: TREFELNER CONSTRUCT! Rotate Angle: 0 Street: 470 WOODCREST DRI Permit Office: ST LUCIE COUNTY Crass Ventilation: No County: St. Lucie Jurisdiction: ST LUCIE COUNTY Whole House Fan: No City, State, Zip: FORT PIERCE, FamiiyType: Single-family FL NewlExisting: New (From Plans) Comment: CLIMATE / �/ Design Temp Int Design Temp Heating Design Daily Temp Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, Fort Pierce FL_VERO_BEACH _MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1183 9582.3 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 MASTER BECROO 182 1474.2 No 0 1 1 Yes Yes Yes 2 CLST 2 16 130 No 0 1 Yes Yes Yes 3 BEDROOM 2 149 1206.9 No 0 1 1 Yes Yes Yes 4 BEDROOM 3 120 972 No 0 1 1 Yes Yes Yes 5 M CLST 18 146 No 0 1 No Yes Yes 6 M BATH 68 551 No 0 1 Yes Yes Yes 7 BATH 2 70 567 No 0 1 No Yes Yes 8 HALL 36 292 No 0 1 No Yes Yes 9 LINEN/AHU CLST 4 32 No 0 1 No Yes Yes 10 CLST 3 20 162 No 0 1 Yes Yes Yes 11 LIVING ROOM 255 2066 No 0 1 Yes Yes Yes 12 KITCHEN 182 1474.2 Yes 0 1 Yes Yes Yes 13 LAUNDRY 63 510 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulation MASTER BEDRO 27 ft 0 182 ftz _-__ 1 0 0 2 Slab -On -Grade Edge Insulation CLST 2 2 ft 0 16 tv ---- 1 0 0 3 Slab -On -Grade Edge insulation BEDROOM 2 24 ft 0 149 ftz ____ 1 0 0 4 Slab -On -Grade Edge Insulation BEDROOM 3 loft 0 120 W ____ 1 0 0 6122/2020 3:30 PM EnergyGaugeV USA 6.0.f12 (Rev. 1) - FlaRes2017 FBC 5th Edition (2017) Complianf Software Page 2 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet S Slab -On -Grade Edge Insulation M CLST 1 ft 0 18 ft' 6 Slab -On -Grade Edge Insulation M BATH 12 ft 0 68 W 7 Slab -On -Grade Edge Insulation BATH 2 1 ft 0 70 ft2 0 0 8 Slab -On -Grade Edge Insulation HALL i ft 0 36 ft' _ 1 0 0 9 Slab -On -Grade Edge Insulation LINEN/AHU CLST 1 ft 0 4 f12 1 0 0 0Siab-On-Grade Edge Insulation CLST 3 2 ft 0 20 ft' _ 1 0 0 11SIa6-On-Grade Edge Insulation LIVING ROOM 32 ft 0 255 ft' 1 0 0 12Siab-On-Grade Edge Insulation KITCHEN 21 f1 0 182 ft2 ---- 1 0 0 135Iab-On-Grade Edge Insulation LAUNDRY 26 ft 0 63 ft2 1 0 0 ROOF # Type Materials Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch Area Area Color Barr Absor. Tested Tested Insul. (dea) 1 Hip Metal 1281 ft' 0 ft' Light N 0.3 No 0,9 No 20 22.6 ATTIC # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Unvented 0 1183ft' N N CEILING 4 Ceiling Type space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Unvented) MASTER BEDRO 0 Blown 1a2 ft' 0.1 Wood 2 Under Attic (Unvented) CLST 2 0 Blown 16 W 0 1 Wood 3 Under Attic (Unvented) BEDROOM 2 0 Blown 149 ft' 0.1 Wood 4 Under Attic (Unvented) BEDROOM 3 0 Blown 120 ft' 0.1 Wood 5 Under Attic (Unvented) M CLST 0 Blown 18 f? 0.1 Wood 6 Under Attic (Unvented) M BATH 0 Blown 68 ft' 0.1 Wood 7 Under Attic (Unvented) BATH 2 0 Blown 70 W 0.1 Wood 8 Under Attic (Unvented) HALL 0 Blown 36 f? 0.1 Wood 9 Under Attic (Unvented) LINEN/AHU CLST 0 Blown 4 W 0.1 Wood 10 Under Attic (Unvented) CLST 3 0 Blown 20 fP 0.1 Wood 11 Under Attic (Unvented) LIVING ROOM 0 Blown 255 ft' 0.1 Wood 12 Under Attic (Unvented) KITCHEN 0 Blown 182 W 0.1 Wood 13 Under Attic (Unvented) LAUNDRY 0 Blown 63 ft2 0.1 Woad 612212020 3:30 PM FnergyGau+ge® USA 5.0.02 (Rev. 1) - FlaRes2017 FRC 6th Editi-n (9017) Compliant Software Pang 3 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT WALLS Adjacent S 11 TypeSpace P Cawty Width Height Sheathing Framing Solar Bslow 1 2 3 4 5 N E N N W Exterior Exterior Exterior Exterior Exterior Concrete Black - fnt InsuMASTER BE Concrete Block - Int InFmMASTER BE Concrete Block - Int Insul CLST 2 Concrete Block - Int InsuBEDROOM 2 Concrete Black - Int InsuBEDR00M 2 4.1 4.1 4.1 4.1 4.1 13 14 2 13 11 0 0 0 0 0 8 1 8 1 & 1 8 1 8 1 105.1 ft' 113.2 ft' 16.2 W 105,1 ft' 88.9 W 0 0 0 0 0 0 0 0 0 0 0.3 0.3 0.3 0.3 0.3 0 0 0 0 C 6 W Exterior Concrete Block - Int InsuBEDROOM 3 4,1 10 0 8 1 80.8 ft' 0 0 0.3 0 _ 7 E Exterior Concrete Block - Int Insul M BATH 4.1 12 0 8 1 97.0 ft' 0 0 0.3 0 8 9 W S Exterior Exterior Concrete Block - int Insul CLST 3 Concrete Block - Int InsuLIVING ROO 4.1 4.1 2 15 0 0 8 1 8 1 16.2 ft' 121.3 ft' 0 0 0 0 0.3 0,3 0 £} i 0 W Exterior Concrete Block - Int InsuLIVINti ROO 4.1 17 0 8 1 137.4 ft' 0 0 D.3 D 11 F Exterior Concrete Block - Int Insul KITCHEN 4.1 14 0 8 1 113.2 ft' 0 0 0.3 0 12 8 Exterior Concrete Block - Int Insul KITCHEN 4.1 7 0 8 1 56.6 ft' 0 0 0.3 D _ 13 N Exterior Concrete Block - Int Insui LAUNDRY 4.1 3 0 8 1 24.3 ft' 0 0 0.3 0 _ 14 E Exterior Concrete Block - Int Insul LAUNDRY 4.1 7 0 8 1 56.6 ft' 0 0 0.3 0 _ 15 S Exterior Concrete Block - Int Insul LAUNDRY 4.1 9 0 8 1 72.8 ft' 0 0 0.3 0 16 W Exterior Concrete Block - Int Insul LAUNDRY 4.1 7 0 8 1 56.6 ft' 0 0 0.3 0 DOORS # Ornt Door Type Space Storms U-Value Ft Width In Height Ft In Area 1 W Insulated LIVING ROO None .39 3 6 8 20 ft' 2 S Insulated KITCHEN None .39 3 6 8 20 ti' WINDOWS Orientatfon shown is the entered, Proposed orientation. 1/ # Wall Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Overhang [depth Separation Int Shade Screening 1 N 1 Vinyl Low-E Single Yes 0.32 0.22 N 15.0 ft' 2 ft 0 in 1 ft 4 in None None 2 E 2 Vinyf Low-E Sing€e Yes 0.32 0.22 N 15.0 ft' 2 ft 0 in 1 ft 4 in None None 3 N 4 Vinyl Low-P Single Yes 0.32 0.22 N 15.0 ft' 2 ft 0 in 1 ft 4 in None None 4 W 5 Vinyl Low-E Single Yes 0.32 0.22 N 15.0 ft' 2 ft 0 in 1 ft 4 in None None 5 W 6 Vinyl Low-E Single Yes 0.32 0.22 N 15.0 ft' 2 ft 0 in 1 ft 4 in None None 6 E 7 Vinyl Low-E Single Yes 0.32 0.22 N 4.0 ft' 2 ft 0 in 1 ft 4 in None None 7 W 10 Vinyl Low-E Single Yes 0.32 0.22 N 30.0 W 2 ft 0 in 1 ft 4 in None None 8 I= 11 Vinyl Low-F Single Yes 0.32 0.22 N 34.0 ft' 2 ft 0 in 1 ft 4 in None None 9 E 14 Vinyl Low-E Single Yes 0.32 0,22 N 4.0 ft' 2 ft 0 in -1 ft 4 in None None 6/22/2020 3:30 PN4 EnergyGauge®R USA 6.0.02 (Rev. 1) - FlaRes2017 FBC_= 6th Edition 12,917) compliant Software Page 4 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .00036 1118.1 61.38 115.43 .1255 7 HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Strip Heat/ Nene COPA 17 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split Single SEFR: 16 17.7 kBtulhr 531 cfm 0.8 1 sys#1 HOT WATER SYSTEM # System Type SubType Location FF Cap Use Setpnt Conservation 1 Electric None LAUNDRY 0.98 50 gal 62.3 gal 120 deg None SOLAR HOT WATER SYSTEM rSEt✓ Collector Storage Cert # Company Name System Made{ # Collector Model # Area Volume FEF None None ft. DUCTS / ----Supply---- ---- Return ---- Air CFM 25 CFM25 HVAC # �/ # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 125 W Attic 13 ft' Default Leakage LINEN/AHU (Default) c(Default) c 1 1 TEMPERATURES Programable Thermostat: N Ceiling Fans: Cooling Jan Feb Mar Heating Jan Feb [X Mar Venting Jan Feb [ Apr j May riJun Jul X Aug Se Oct t Apr ] May Jun Jul Au ] Sep Oct Nov x Nov Dec 7Cf7ec X Mar [X] A r J Ma Jun Jui Aug [ ] Se Oct X Nov Dec 6l2212020 3:30 PM EnergyGaugeC USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Fdition (2017) Compliant Software Page 5 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 Cooling (WD) AM PM 78 80 78 80 78 80 78 78 78 78 80 78 78 78 Cooling (WEH) AM PM 78 80 78 80 78 80 78 78 78 78 80 78 78 78 Heating (WM AM PM 65 fib 65 68 65 68 65 65 65 65 68 68 68 68 Heating (WEH) AM PM 65 68 65 65 65 65 65 65 68 68 68 68 68 68 Mass Type Default(8 lbslsq.ft. Default(8 Ibslsq.ft. Default(8 Ibslsq.ft. Default(8 Ibs/sq.ft. Default(8 Ibslsq.ft. Default(8 Ibslsq.ft. Default(8 Ibsila-0t, Defautt(8 Ibslsq.ft. Default(8 ibslsq.ft. Default(8 Ibslsq.ft. Default(8 Ibslsq,ft, Default(8 Ibs/sq,ft. MASS Area T`h1 ckness 0 ft2 0 ft ft' ft ft2 ft ft' ft ft' ff ft' ft ft' ft ft' ft Itzft ft, ft ft' ft W ft ft2 ft 8 9 10 11 12 78 80 80 80 80 78 78 78 78 78 78 80 80 80 80 78 78 78 78 78 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 58 68 68 68 68 Furniture Fraction 0.3 0.3 0.3 0.3 0.3 0.3 0.8 0.3 0.3 0.3 0,3 0.3 0.3 MASTER BEDROO CLST 2 BEDROOM 2 BEDROOM 3 M CLST M BATH BATH 2 HALL LINENIAHU CLST CLST 3 LIVING ROOM KITCHEN LAUNDRY 6/220-020 3-qn PM FnergyGaugr.C5 USA_ 6.0.02 (Rev, 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 6 of 6 2017 EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 95 The lower the Energy Performance Index, the more efficient the home 1. New home or, addition 1. New (From Plans) 12. Ducts, location & insulation level a) Supply ducts R 6.0 2. Single-family or multiple -family 2. Single-family b) Return ducts R 6,0 3. No. of units (if multiple -family) 3. 1 c) AHU location LINEN/AHU CLS T 4. Number of bedrooms 4. 3 13. Cooling system: Capacity 17.7 a) Split system SEER 16.0 5. Is this a worst case? (yes/no) 5. No b) Single package SEER c) Ground/water source SEER/COP 6. Conditioned floor area (sq. ft.) 6. 1183 d) Room unit/PTAC EER e) Other 7. Windows, type and area a) U-factor:(weighted average) 7a. 0.320 b) Solar Heat Gain Coefficient (SHGC) 7b. 0220 14, Heating system: Capacity 17.0 c) Area 7c. 147,0 a) Split system heat pump HSPF b) Single package heat pump HSPF 8. Skylights c) Electric resistance COP 1.0 a) U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE b) Solar Heat Gain Coefficient (SHGC) 8b. NA e) Gas furnace, LPG AFUE f) Other g_ Floor type, insulation level: a) Slab -on -grade (R-value) 9a. 0.0 b) Wood, raised (R-value) 9b. 15. Water heating system c) Concrete, raised (R-value) 9c. a) Electric resistance EF 0.98 b) Gas fired, natural gas EF 10, Wall type and insulation: c) Gas fired, LPG EF A. Exterior: d) Solar system with tank EF 1. Wood frame (Insulation R-value) 10A1. e) Dedicated heat pump with tank EF 2. Masonry (insulation R-value) 10A2. 4.1 f) Heat recovery unit HeatRec% B. Adjacent: g) Other 1. Wood frame (Insulation R-value) 10B1. 2, Masonry (insulation R-value) 1DB2. 16. HVAC credits claimed (Performance Method) 11. Ceiling type and insulation level a) Ceiling fans a) Under attic 1la, 0.0 b) Cross ventilation No b) Single assembly 11b. c) Whole house fan No c) Knee walls/skylight walls 11c. d) Multizone cooling credit d) Radiant barrier installed 11d. No e) Multizone heating credit f) Programmable thermostat No *Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT I certify that this home has compiled with the Florida Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be completed based on installed code compliant features. Builder Signature: I A ❑ate: Z14'14 O Address of New Home: 471) WOODCREST DRIVE City/FL Zip: FORT PIERCE, FL 6/22/2020 3:30:44 PM EnergyGauge® USA 6.0.04 (Rev. 1) - RaRes2017 FBC Gth Edition (2017) Compiiarnt Software Page 1 of 1 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: BUXTON GUEST HOUSE Builder N2mp: TREFELNER CONSTRUCTION Street: 470 WOODCREST DRIVE Permit Office: ST LUCIE COUNTY City, State, Zip: FORT PIERCE, FL, Permit Number- Owner: TIM AND LACEY BUXTON Jurisdiction: ST LUCIE COUNTY Y w Design Location: FL, Fort Pierce COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. Breaks or joints in the air barrier shall he sealed. not be used as a sealing material. Ceilinglattic The air barrier in any dropped ceilinglsoffit snail be aligned with the The insulation in any dropped ceiling/soffit Insulation and any gaps In the err barrier shall be sealed. Access openings, drop down stairs or knee wail doors to shall be aligned with the air barrier. unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the tap of exterior wafls steal[ be sealed, shall be insulated by completely filling the cavity with a Knee walls shall be sealed. material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between windowidoor jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall he installed to (including above garage maintain permanent contact with the underside of and cani0evered floors) subfloor decking, or floor framing cavity insulation shaft be permitted to be in contact with the top side Of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with a Where provided instead of floor insulation, insulation Class I vapor retarder with overlapping joints taped, shall be permanently attached to the crawlspace walls, Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditionad space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available: cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall Recessed light fixtures installed in the building be sealed to the drywal,. thermal enveiope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring a plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind ELiping and wiring. Showeritub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall be on exterior wall tubs shall separate them from the showers and tubs. insulated. Electrical/phone box on The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boats HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. GunLedivu When requireo to be scdidu, concealed Lire sprinklers snot€ only be Sealed sprinklers in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or cei in s. a rn a`Iflit:.,n fnc,ze.-ri.,., _T i.... ,.,-. n.- .-4.-.n M..:.... __. _.�_ —-- ....... ._._ , ..Wr_..-.�.... .„y ...��., ,���,..�� — UC1004-11— vnui uic NiUviaiuiia U1 Jk.%. °FUU. 6/22/2020 3:30 PRIG EnergyGaugcO USA 6.0.02 (Rev, 1) - FlaRes2017 FBC 6th Edition (20171 Compliant Software Page 1 of 1 wlri htsvft` Project Summary "ebb: 9 Entire House ByEe. Jun za, zoao QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PfLRCE. FL 34946 Phone: 772-466-5799 Far 772- 46"796 r; -qk QUICKCALCSc[rAOL.COM Project Information For: BUXTON GUEST HOUSE, TREFELNER CONSTRUCTION 470 WOODCREST DRIVE, FORT PIERCE, FL Notes: Design• • Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db Inside db 42 70 °F °F Outside db Inside db 90 75 of aF Design TD 28 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 16085 Btuh Structure 13614 Stuh Ducts 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none; Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 16085 Btuh Use manufacturer's data In Ratelswing multiplier 0,96 Infiltration Fquipmenf sensible load 12933 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2934 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Area Heating Coatingg {none) (fit=) 1183 1183 Equipment latent load 2934 Btuh Volume (W) 9582 9582 Air changes/hour 0,45 0.23 Equipment Total Load (Sen+Lat) 15868 Btuh Equiv. AVF (cfm) 72 37 Req, total capacity at 0.70 S H R 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIER Model Cond CA16NW01800GOAD AHRI ref Coil FX4DNF019L Efficiency 100 EFF AHRI ref 9200656 Efficiency 13.5 EER, 16 SEER Heating input 5.3 kW Sensible cooling 12390 Btuh Heating output 18019 Btuh Latent cooling 5310 Btuh Temperature rise 28 °F Total cooling 17700 Btuh ,actual air flmv 590 cfm Actual a;r flow 590 cfm Air flow factor 0.037 cQBtuh Air flow factor 0.043 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed vtirriir�h€Csoft- 2020-Jun-2215:38:19 r+ Ri htSr WID Universal2019 19,0,08 RSU08101 Page 1 ' .,.ocumnetst4Veig€eisoR HVAC`..3UXTON GUEST HOUSE, rup Ca€c = M,l8 Fmnt Donrfaces: 1Y 9 v wrightsoft Right-J@ Worksheet Job: Entire House Date: Jun 22, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE. FL 34946 Phone: 772-466-57R9 Fax 772-465-6725 FinaII- Dill r.kf',Al rcnani rune 1 Room name y MASTER BEDROOM 2 Exposed wall Entire House 3 Room height 156.0 ft 27.0 ft 4 Roarrt dirnensians 8.1 ft 8.1 ft heatla001 5 Room area 1183.0 ftz 14.0x 13.0 ft t'14.0 182.0 ft' Ty Construction U-value or HTv1 number (Btuhlftr °F) Arai ft' ( ) Load Area (ftt) Load (Btuhlftr) or perimeter (ttj (Btuh) or perimeter (ft) {Btuhj Heat Cool Gross N1PIS Heat Cool Gross N1p/5 Heat Cool 6 U+d ILr 13A-4ocs 2 glazing. clr low-e 0.143 0.320 n n 4.00 9.95 2,19 9.41 251 221 &85 484 105 9D 362 198 13A-4ocs 0.143 e 4.00 2A9 30 3,91 0 324 269 1296 282 708 15 113 0 134 141 2 glazing, clr low-e 0.320 e 8.96 22.97 8 1 72 194 0 98 0 394 215 11 2 glazing, clr low-e 0.320 e 8.96 24.75 15 1 1,,34 371 15 1 0 134 0 371 2 glazing, clr low-e 13A-4ocs 0.320 0.143 a 8.96 25.07 34 2 305 852 0 0 0 0 11D0 0.390 s s 4.00 10.92 2.19 10.34 251 20 231 20 925 219 505 0 0 0 0 0.143 w 4.00 2.19 381 301 1204 208 658 0 0 0 0 0 0 0 Tif13A-4ocs 2 glazing, cir low-e 0.320 w 8.95 24.75 60 4 538 1485 0 0 0 0 0 D C 1100 16X19-0md 0.390 0.408 w 10.92 1.59 10.34 1.37 20 11,93 20 1183 219 1876 208 0 0 0 0 F 22A-tph 1.358 3&.02 0.00 1183 156 5932 1619 0 182 182 182 27 289 1027 249 0 6 c)ALD excursion 45 130 Envelope Inss/gain 13673 7608 2340 1045 12 a) InfWation 2212 606 383 105 b) Room wntilaCo'.1 0 0 0 0 13 intemal gains: Occupants @ 230 0 0 0 Applianceslother 5400 0 1000 Subtotal (lines 6 to 13) 16085 13614 2722 2149 Less extemal load 0 0 0 Less transfer D D 0 0 3 Redistribution 0 0 106 43 14 15 Subtotal Duct loads 16085 13614 2828 2193 D% 0% 0 0 0% 0 0 0 Totai room load Air required (ofm) 16065 13614 2828 2i93 590 5901 104 95 Caicuiations approved byACCA to meet_all requirements of Manuai J 8th Ed .:-,y - wrFgF�tsoft 2020-Jun-2115: 38: i9 . s:T';._:.^ .. .. .... RightSuite@ Universal 2019 19.0.08 RSU08101 Page 1 ...ocumneWWdotitsott HVAC113UXTON GUEST HOUSE.rup Calc = M,i8 Front Deor €aces: W wrightsoftmight-J& Worksheet Job: Entire House Date: Jun 22, 2020 QUICK QNLCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone, 772-466-6799 Fax: 772-466-6796 Email: QUIGKCALCS@AOL.COM 1 2 Room name Exposed wall CLST 2 BEDROOM 2 3 Room height 2.0 ft 8.1 ft heat/cool 24.0 ft 8.1 ft beaticool 5 Room area dimensions 8.0 x 2,0 ft 1.0 x 149.0 ft 16.0 ft2 ft 149A 2 Ty Construction 1-1-value Or HTM number (Btuhlft T) (Btuh1ft') Area (fit') Load Area (ft') Load or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Gross N1PJs Heat Cool Gress N1P1S Heat Cool Heat Cool 5 V 13A-flocs 0.1-03 n 4.00 2.19 G 2 glazing, clr lower 0.320 n 8.96 9.41 16 16 65 35 105 90 352 198 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 15 0 0 134 141 2 glazing, clr ow-e 0.320 a 8.96 22.97 0 0 0 0 0 0 0 0 0 11 2 glazing, elr low-e 0.320 a 8.96 24.75 0 0 0! 0 0 0 0 2 glazinq, cir low-e 0.320 a 8.96 25.07 0 0 0 0 0 0 0 0 0 Val 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 ---.p 11DO 0.390 s 10.92 10.34 0 0 0 0 0 U 0 p 0 p 13A4ocs 0,143 w 4.00 2.19 0 0 0 0 89 74 297 162 2 glazing, clr low-e 0.320 w 9.95 24.75 0 0 0 0 1s 1 134 371 11DO 0.390 w 10.92 10.34 0 0 0 a 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 F 22Atph 1.358 38.02 0.00 16 16 25 22 149 149 236 204 16 2 76 0 149 24 913 0 6 c)AED excursion -4 40 Envelope loss;gain 165 54 2076 1116 12 a) Infiltration 28 6 340 93 b) Roam v::nWanon 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother _ 1000 Subtotal (lines 6 to 13) 195 61 2416 2209 Less external load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal -195 -61 115 39 15 Duct loads 0% 0% 0 0 0 0 0% 0% 2531 0 2249 0 Total room load Ai r required (cfm) A Q 2551 2249 0 93 97 Calculations approved b ACCA to meet all requirements of Manual J Sth Ed. 2020,!un•22 1 S: 38;18 rCGC;•A.. ,. Rig}si-SuiteL� Universal 2099 18.0.08 RSUDSIOl Page t ocumnetslWrightson HVA0BUXTDN GUEST HOUSF.rup Calc = W8 Front Osorfaces: W + wrightsoft might-J& Worksheet Job: Entire House i}ate: Jun 22, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE. FL 34946 Phone: 772-466-6799 Fax 772-466-6736 Email: QUICKCALCS@AOL.COM 1 Room name 2 Exposed wall BEDROOM 3 M CLST 3 Room height 10.0 ft 0 ft 4 Room dimensions 8.1 ft heaticool 6.1 ft heaticoo! 5 boom area a 10,0 x 12.0 ft 2.0 x 9.0 fit 120.0 ft � 18.0 ft : Ty Construction number a -value Or HTM Area (ft`) (13tuhift` °Fj Load Area (ft') Load or perimeter ft l) (8tuh) or perimeter (ft) (I3tuhj Heat Cool Gross NIPIS Heat Coal Grass MPS Heat Coo} 6 sal 13A4ocs 0.143 n 4.00 2.19 0 0 0 0 00 L-( 2 glazing, ch 3ow-e 0.320 n 6.96 9.41 0 0 0 0 0 0 0 13A4ocs 0.143 e 4.00 2.19 0 0 0 0 0 0 p 0 2 glazing, Or low-e 0.320 e 8.95 22.97 0 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.320 e 8.96 24.75 0 0 0 0 0 0 0 2 glazinu. clr 11 0.320 e 8.96 25.07 0 0 0 0 0 0 0 0 13A,4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 0 11D0 0.390 s %92 10.34 0 0 0 0 0 0 0 0 D 0 13A-4ocs 0.143 w 4.00 2.19 81 66 264 144 0 0 0 0 2 glazing, clr low-e 0.320 w 8.96 24.75 18 1 134 371 0 0 0 11DO 0.390 w 10.92 10.34 0 0 0 0 0 0 0 0 G 16X19-0md F 22A-tpt'i 9.408 1.59 1.37 1,358 120 120 190 164 18 18 29 25 38.02 0.00 120 10 380 0 18 0 0 0 6 c)AED excursion Envelope losslgain 969 744 1 29 23 12 a) Infiltration 142 39 0 0 b) ROOM 1A 9tl!atiDn 0 0 00 13 Irrternal gains: Occupants @ 230 0 0 0 Appliances/other 1500 0 0 Subtotal (lines 6 to 13) 1111 2283 29 23 Less extemal load 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal 126 54 29 0 -23 15 Duct loads 0% 0% 1237 0 2336 0 0% 0% 1 0 01 0 0 0 Total room lead Air required (cfm) 1237 2336 u >7 4S 101 0 g Caiculatioros a roved i5 ACCA to meek a!i requirements of #llanual J 8th Ed . r�,csft wr�g�_ Ri htSuitei] Universal Z4'IS 1S.O.OS RSUpE3191 2D2fl-JU-221S:38:19 ...ocumnetsWdri htsrott WACI6UXTON GUEST HOUSE.rup 084c = VJa gars€ floor faces: W Page 3 wrightsoft` night-J® Worksheet Job: Entire House Date. Jun 22, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE; FORT PIERCE, FL 34046 Phone: 772-466-6799 Fax. 772-466-6796 Lrnail: QUICKCALCS@AOL.COM 1 2 Room name Exposed wall M B BATH BATH 2 3 Room height ft 0 ft 4 Room dimensions 8.1 ft heaticeol S.1 ft heaticool 5 Room area 1.0 x 68.0 ft 10.0 x 7.0 ft 68.0 ft z 70.0 fN Ty Construction U-aafue Or HTM number (8tuhlft1°I-) (etuhift') Area (ft') Load Area (ft') Load or perimeter (ft) (Btuh) or perimeter (f€) (Btuh) Grass N(PIS Heat Cool Gross N1PIS Heat Cool Heat Cool 6 VI! 13A�ocs 0.143 n 4.00 2.19 L-( 0 0 0 fl 0 0 2 glazing, clr low-e 0.320 n 8.95 9.41 0 01 0 0 0 0 0 13A-4ocs 0.143 e 4. DO 2.19 97 93 373 204 0 0 0 0 0 0 2 glazing, cif bw-e 0.320 e 9.96 22.97 4 1 36 92 0 0 0 11 2 glazing, clr lew-e 0.320 e US 24.75 0 0 0 0 0 0 0 2 glazinq. clr low-e 0.320 a 8.96 25.07 0 0 0 0 D 0 0 0 0 W 13A-4ocs 0A43 s 4.00 2.19 0 0 0 0 0 0 0 D 11 D0 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 0 0 V�1 13A-4DCs D.143 w 4.00 2J9 0 0 0 0 0 I�--C{ij 2 glazing, clr low-e 0.320 w 9.96 24.75 0 0 0 00 0 0 0 11Dn 0.390 w 10.92 10.34 0 0 0 0 D 0 0 0 n 0 C 16X19-ornd 0.40E 1.59 1.37 F 22A-tph 1.358 38.02 0.00 68 68 108 93 70 70 111 0 96 Be 12 456 0 70 0 0 0 6 c)AFD excursion 23 Envelope loss/gain 973 366 111 90 12 a) Infiltration 17D 47 0 0 b) Room ventilation 0 0 0 n 13 Intetna# gains: Occupants @ 230 Cr 0 0 Applianceslother n 0 0 Subtotal (lines 6 to 13) 1143 412 111 90 Less external load 0 0 Less transfer 0 0 0 0 Redistribution 5 0 25 0G 21 14 Subtotal 1149 417 136 111 15 Duct toads 0% 0% 0 0 0 % 0% 01 0 Total room load Air rPnLllr. . (rfm) 1149 4i7 136 111 42 1S 5 5 CAiculations a2proved by ACCA to meet all__requirernents of Manual j girth Ed tsoiFt•"- 2020Jun-22 15: 38:19 6.�. ..ocumnsts; �,.li�,.....� ....... Right�uitsJ Universal 2fl'Is 19.0.Da RSLJi38191 )!'7 ry g tsoft HVACIBUXTON GUEST HOUSE .rup Catc W M,tA Front Door faces: iU Page 4 wrightsof fight-J@ Worksheet Job: Entire House Date: Jun 22, 2020 QUICK CALCS, INC, 317 ST LUCIE LANE; FORT PIERCE. FL 34946 Phone: 772-4ti6,6799 Fax 772-486-6798 Ema4: QUICKCALCSBAOLC.()M 1 Room name V 2 Exposed wall HALL LINENIAHU CLST 3 Room height 0 ft 0 ft 4 Room dimensions 8.1 ft heaticool 8.1 ## heat/coot 5 Room area 36.0 ft212.0 x 3.0 ft 2.0 x 2.0 ft 4.0 ft Ty Construction U-value Dr HTM number (H-tuhlft' `r) (8fuhfft') Area OF) Load Area (ft') Load or perimeter (ft) (Btuh) or perimeter (ft) (gtuh) Heat Cooi Gross NIP/S Heat Cool Gross N1P1S Heat Cool 6 13A-4ces 0,143 n 4.00 2.15 0 0i 0 0 0 0 0 2 glazing, clr law-e 0.320 n R_9H 9.41 0 0 0 0 0 0 0 13A-4ocs 0.143 e 4,00 2A9 0 0 0 0 0 D a 0 a 2 glazing, ctr iow-e 0.321) e 8.96 22.97 0 0 0 0 0 O 0 0 11 2 glazing, clr tow-e. 9.320 0 8.96 24,75 0 0 0 0 0 0 0 0 0 2 plazinq, nlr low-e 0.320 a 8.95 25.07 0 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4A0 2.19 0 0 0 O 0 0 0 11DO 0,390 s 10.92 10.34 0 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 2 glazing; clr luw-e 0,320 w 8.96 24.75 0 0 0 0 0 0 0 0 11 DO 0.390 w 10.92 10.34 0 0 0 O 0 0 0 0 0 C MX19-0md 0,408 1.69 1.37 36 36 57 49 4 4 6 5 F 22A-tph 1.35E 38.02 0-00 36 0 0 0 4 0 0 0 61 c)ALD excursion -3 0 Envelope loss/galr 57 46 12 a) infiltration 0 0 0 0 b) Room ventilation 0 0 0 01 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 57 45 6 5 Less external load 0 0 0 D Less transfer O O 0 0 Radistnbiftn -57 -46 -6 14 6ubtotai 0 0 0 0 15 Duct loads 0% 0% 0 D 0%a 0°% 0 0 ictal room load 0 0 0 0 Air required (cfm) 0 0 0 0 Calculations approved byACCA_EO €meet all reouirements of Manual J 8tn Ed. " wrigl-stspft -.... 2020-Jun-2215:38:19 -.. Right-Suita® Universal 2019 19.0.08 RSU08141 ' - ...ocumnets)Wrightsaft HVACIBUXTON GUEST Hp USE.rup Caic = MJB Front Doortaces: W Page 5 + wrightsoft Right-J@ Worksheet Jnb: Entire House [late: Jun 22, 2020 QUICK CALCS, INC. gy: 317 ST LUCIE LANE, FORT PIERCE, FL 34945 Phone: 772-466-6799 Fax: 772-469-6796 Email: QUICKCALCS@AOL.COM 1 2 Room name 1-)posed wall CLST 3 LIVING ROOM 3 4 Room height Roam dimensions 0 ft 8.1 ft 2 heaticaol 32.0 ft 8.1 ft heaticool 5 Roam area 2.0 x 10.0 ft x 15.Q ft 20.f) ft2 255 0 ft217.0 Ty Construction U-value Or HTM number (13tuhift'2F) Area (f) Load Area (ft') Load (Btuhifr`) or permeter (ft) (Btuh) or perimeter (ft) (Btuh) Gross N!P!S Heat Cool Gross NIP/S Heat Cool Heat C1301 6 Vd/ 13A-4ocs 0.143 n 4.00 2A9 Q Q 0 0 0 G 2 glazing cfr low-e 0.320n 8.96 9.41 0 0 4 0 0 0 0 0 D 13A-flocs 0.143 e 4.00 2.19 0 0 0 Q 0 0 0 0 Q Ti 2 glazing, clr low-e 0.320 a 8.96 22.97 0 0 0 0 0 0 0 a 11 2 glazing, clr low-e 0.320 a 8.96 24.75 0 0 0 0 0 D 0 2 dazinq, clr low-e 0.320 a 8.96 25.07 Q 0 0 0 0 0 0 0 Vj! 13A-4 of 0.143 s 4.00 2.19 �--O 11DO 0 0 0 0122 122 0 486 0 266 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-40cs 0.143 w 4.00 2.19 2 glazing, cir Iovi-e 0.320 w 8.96 24.75 16 0 16 65 35 138 88 351 192 11D0 0.390 w 10.92 1D.34 0 0 0 0 Q 0 0 3o 20 2 20 269 219 743 2DB C 16X19-Dmd 0.403 1.59 1.37 F 22A-tph 1.358 20 20 32 27 255 255 404 349 38.02 000 20 2 76 0 255 32 1217 0 6 c)AED excursion 4 205 Envelopelosslgair 173 59 2947 1962 12 a) lrJlltraticn 28 8 454 124 b) Rccm ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other D 12D0 Subtotal (lines 6 to 13) 201 67 3400 3286 Less a)dernal load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal -201 -£7 110 41 15 Duct loads 0% 0% 0 0 0 0 0% ft. 3510 0 3327 0 Total room load Air requirAd (&m) D `01. 0 3-a10 3327 Q 129 "4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed w�.grscsort- -- �Y ..UGEltnnetStt/Jrl. Right-Guite@ Universal 2019 19.0.08 RSU061 Ot 2020h1un�22 15;38:19 t' F ghtstift WAC:BUXTON GUEST HOUSE.rup Calc = Mja Front 600rfaces: W Paq e 6 + wrightsof Right -AD Worksheet Job. Entire House bate: Jun 22, 2020 QUICK CALLS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: 4UICKCALCSgaAOL.COM 1 name 2 E)Room lxflosed wall KITCHEN LAUNDRY 3 Room height 21.0 ft 26-0 ft &1 ft 4 Roam dimensions .heat/cool B hB. 1 ft heat/cool 5 Room area 14.0 x 13.0 fY 7.0 x 9.0 ft isz.D ft2 63.D it, Ty Construction U-value Or HTM number Btuhfft' °F ( ) (Btuh/ft') Area ftz { ) Load Area (ft') Load or perimeter {ft) (I3tuh) or perimeter (n) (Otuh) Gross WPIS Heat Cool Gross NIP/5 Heat Caul Heat COD] 6 Vd! 13A4ccs 0.143 n 4.0D 2,19 I o D o -- ter 2 glazing, ctr low-e 0,320 n 8,9€'i 9.41 13A4ocs 0.143 e 4,00 2.19 D 113 0 79 a 0 ZO 24 90 50 2 giazfng, clr low-e 0.320 e 8,96 22.97 0 O 318 0 174 57 0 53 211 115 11 2 glazing, clr low-e 0.320 e 8,98 24.75 O 0 0 4 0 1 36 92 2 olazlra, clr low-e 0.320 e 8.96 25.07 34 2 305 0 852 0 0 0 0 0 V�! 13A-4ocs 0.143 s 4.00 2.19 L...❑ 57 37 147 80 73 73 0 0 11DO 0.390 s 10.92 10.34 20 20 219 208 0 0 292 0 159 0 13A-4ocs 0.143 w 4.00 2.19 2 glazing, clr low-e 0.320 0 0 0 D 57 57 22 124 w 8.96 24.75 11DD a.390 w 1p.92 ia.3a 0 D 0 o 0 o 0 0 0 0 0 a C 15X19-Omd 0.408 1,59 1,37 F 22Atph 1.358 182 182 289 o D 249 63 o 53 o 160 a 86 38,02 O.Do 182 21 799 0 63 26 989 0 6 c)AED excursion -54 -40 Envelopeluss/gair 2076 1509 1952 590 12 a) Infiltration b) P,00m ventilation 298 82 1369 101 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 Appliancestother 700 0 0 Subtotal (lines 6 to 13) 2373 2290 2320 691 Less odemal load 0 0 0 Less transfer 0 0 D O 0 Redistribution 0 0 0 0 14 15 Subtotal Duct IDa 2373 2290 2320 691 0% C1% 0 0 Toiai room laacf Air required {cfm j 2373 2290 Z32D 69 i 87 99 85 30 Calculations approved byACCA to meet all requirements of Manual J 8tn Ed wri Fatsoft-- RighiSuiteQ Universal 2019 19.0.08 RSU08101 2020-Jun-2215:38:19 �`� . ghisk4i HVACI0UXTON GUEST HOUSE. rup Calc - MJS Front Door faces: W Page 7 Lust ste111�1 Summary Job. n►rlgh soft Date: ,tun 22, 2020 Entire House By-, QUICK CALCS, INC. 317 STLUCIE LANE, FORT PIERCE, FL 94946 Phone: 772-466-6799 Fax 772-466-6796 UP -Oil: QUiCKCAtCS d[ AOL.G0M For; BUXTON GUEST HOUSE, TREFELNER CONSTRUCTION 470 WOODCREST DRIVE, FORT PIERCE, FL Extemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 III H2O 0 in H2O 1.00 in H2O 0.50u i 0.500 in H2O 1.000 in/100ft 590 cfm 139 ft Cooli ng 1.00 In H2O 0 in H2O 1.00 in H2O 0.500 i 0.500 in H 2O 1.000 in/ 100ft 590 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk 5ATH2 h 136 5 5 1.000 4.0 Ox0 VIFx 9.n 115.J sY2 BEDROOMc 2249 93 I 97 1.000 7.0 Ox 0 VIFx 17.2 115.0 st2 BEDROOM 3 c 2336 45 ! 101 1.000 7.0 Ox fl VIFx 9.1 115.0 st2 KITCHEN c 2290 87 99 1.000 7.0 Ox 0 VlFx 22.6 115.0 sti LAUNDRY h 2320 85 30 1.000 5.0 Ox0 VIFx 23.6 115.0 sti LIVING ROOM c 3327 129 144 1.000 8.0 Ox 0 VIFx 3.6 95.0 M BATH h 1149 42 18 1.000 5.0 Ox0 VIFx 14.5 115.0 st2 MASTER BEDROOM h 2828 104 95 1.000 TO OX0 ViFx 15.4 115.0 sit Supply Trunk Detall Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpna) (In) (in) Material Trunk sti Peak AVF 172 129 1.000 493 8.0 0 x 0 VinlFlx st2 Peak AVF 289 317 1.000 580 10.0 0 x 0 VinlFlx -- Return Branch.Detail Table Name Grilte Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 590 590 0 O 0 0 Ox 0 VIFx -�'�- wrightsoft° 2020-gum-22 15:$i M Rlghi-ault@�D Universal 2019 19,O,Oa 1151.1oa,.ai Page 1 ...pzumnatslWrightsott HVAOIBUXTt3N GUEST HOUSE. nip Caic = MJS Front [lnnrfates: Vj!