HomeMy WebLinkAboutBuxton signed manual j and engergy calc.pdf 2007-0233FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: BUXTON GUEST HOUSE Builder Name: TREFELNER CONSTRUCTION
Street: 470 WOODCREST DRIVE Permit Office: ST LUCIE COUNTY
LI Y, State, Zip: FORT PIERCE , FL, Permit Number:
Owner: TIM AND LACEY BUXTON Jurisdiction: ST LUCIE COUNTY
Design Location: FL, For Pierce County: St. Lucie (Florida Climate Zone 2 j
1. New construction or existing New (From Plans) 9. Wall Types (1261.0 sgft.) Insulation Area
2. Single family or multiple family Single-family a. Concrete Block - Int Insul, Exterior R=4.1 1261.00 ft'
3. Number of units, if multiple family 1 b. NiA R= ft'c NIA
R= fit'
4. Number of Bedrooms 3 d. NIA R- ft'
5. Is this a worst case? No 10. Ceiling Types (I 183.0 sgft.) Insulation Area
a. Roof Deck (Unvented) R=20.0 1183.00 ft'
6. Conditioned floor area above grade (ft') 1183 b. NIA R- ft'
Conditioned floor area below grade (ft') 0 c• NIA R= ft'
11. Ducts R ft2
7. Windows(147.0 sqft.) Description Area a. Sup: Attic, Ret: Attic, AK LINENIAHU CLST 6 125
a. U-Factor: Sill, U-0.32 147.00 ft'
SHGC: SHGC-0.22
b. U-Factor: NIA ft2 12. Cooling systems kBtu/hr Efficiency
SHGC: a. Centra{ Unit 17.7 SEERA6.00
c. U-Factor: NIA ft'
SHGC. 13. Heating systems kBtulhr Efficiency
d. U-Factor: NIA ft' a. Electric Strip Heat 17.0 COPA.00
SHGC:
Area Weighted Average Overhang Depth: 2.000 ft.
Area Weighted Average SHGC. 0.220 14. Hot water systems
S. Floor Types (1183.0 sgft.) Insulation Area a. Electric Cap: 50 gallons
a. Siah-On-Grade Edge Insulation R=0.0 1163.00 ft' EF: 0.980
b. Conservation features
b. N/A R- ft' None
c. NIA R= ft, 15. Credits
None
GiassiFioor Area: 0.124 Total Proposed Modified Loads: 44.86 A
Total Baseline Loads: 47.27 A
SS
t hereby certify that the plans and specifications covered by Review of the plans and V -ViRE 5r
this calculation are in compliance with the Florida Energy specifications covered by this ~ 0,
Cade, calculation indicates compliance,, f
with the Florida Energy Cade.
PREPARED Y: Before construction is completed
DATE: x p
this building will be inspected for
compliance with Section 553.908
I hereby certify that this building, as desigtni d, is in COMPliance Florida Statutes.
with the Florida Energy Coda.wEzg�-
IOWNERIAG N ' 7 'BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402A.1.1 and this project requires
an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (111402.4.1.2).
b/22/2020 3:30 PM EnergyGaugeV USA 6.0,02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page i of s
FORM R405-217117 IIUDI IT CI IRARAADV r+uCr•Wl P#--,r nl mr%r%-r
9 I'LL—r WIN i
PROJECT
Title:
BUXTON GUEST HOUSE
Bedrooms: 3
Address Type;
Street Address
Building Type:
User
Conditioned Area: 1183
Lot
Owner Name:
TIM AND LACEYBUY.TON
Tutai Stories: t
Block/Subdivis; :
4 of Units:
1
Worst Case: No
PlatBook:
Builder Name:
TREFELNER CONSTRUCT!
Rotate Angle: 0
Street:
470 WOODCREST DRI
Permit Office:
ST LUCIE COUNTY
Crass Ventilation: No
County:
St. Lucie
Jurisdiction:
ST LUCIE COUNTY
Whole House Fan: No
City, State, Zip:
FORT PIERCE,
FamiiyType:
Single-family
FL
NewlExisting:
New (From Plans)
Comment:
CLIMATE
/
�/
Design Temp
Int Design Temp
Heating Design Daily Temp
Design
Location TMY Site
97.5 %
2.5 %
Winter
Summer
Degree Days
Moisture
Range
FL, Fort Pierce FL_VERO_BEACH _MUNI 39
90
70
75
299
62
Low
BLOCKS
Number
Name Area
Volume
1
Entire House 1183
9582.3
SPACES
Number
Name Area
Volume Kitchen Occupants
Bedrooms
InfilID
Finished Cooled
Heated
1
MASTER BECROO 182
1474.2 No
0
1
1
Yes
Yes
Yes
2
CLST 2 16
130 No
0
1
Yes
Yes
Yes
3
BEDROOM 2 149
1206.9 No
0
1
1
Yes
Yes
Yes
4
BEDROOM 3 120
972 No
0
1
1
Yes
Yes
Yes
5
M CLST 18
146 No
0
1
No
Yes
Yes
6
M BATH 68
551 No
0
1
Yes
Yes
Yes
7
BATH 2 70
567 No
0
1
No
Yes
Yes
8
HALL 36
292 No
0
1
No
Yes
Yes
9
LINEN/AHU CLST 4
32 No
0
1
No
Yes
Yes
10
CLST 3 20
162 No
0
1
Yes
Yes
Yes
11
LIVING ROOM 255
2066 No
0
1
Yes
Yes
Yes
12
KITCHEN 182
1474.2 Yes
0
1
Yes
Yes
Yes
13
LAUNDRY 63
510 No
0
1
Yes
Yes
Yes
FLOORS
#
Floor Type Space
Perimeter Perimeter R-Value
Area
Joist R-Value
Tile Wood
Carpet
1 Slab -On -Grade Edge Insulation MASTER
BEDRO 27 ft 0
182 ftz
_-__
1 0
0
2 Slab -On -Grade Edge Insulation CLST 2 2 ft 0
16 tv
----
1 0
0
3 Slab -On -Grade Edge insulation BEDROOM 2 24 ft 0
149 ftz
____
1 0
0
4 Slab -On -Grade Edge Insulation BEDROOM 3 loft 0
120 W
____
1 0
0
6122/2020 3:30 PM EnergyGaugeV USA 6.0.f12 (Rev. 1) - FlaRes2017 FBC 5th Edition (2017) Complianf Software Page 2 of 6
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
FLOORS
# Floor Type
Space Perimeter Perimeter R-Value
Area
Joist R-Value
Tile Wood Carpet
S Slab -On -Grade Edge Insulation
M CLST 1 ft
0
18 ft'
6 Slab -On -Grade Edge Insulation
M BATH 12 ft
0
68 W
7 Slab -On -Grade Edge Insulation
BATH 2 1 ft
0
70 ft2
0
0
8 Slab -On -Grade Edge Insulation
HALL i ft
0
36 ft'
_
1 0
0
9 Slab -On -Grade Edge Insulation
LINEN/AHU CLST 1 ft
0
4 f12
1 0
0
0Siab-On-Grade Edge Insulation
CLST 3 2 ft
0
20 ft'
_
1 0
0
11SIa6-On-Grade Edge Insulation
LIVING ROOM 32 ft
0
255 ft'
1 0
0
12Siab-On-Grade Edge Insulation
KITCHEN 21 f1
0
182 ft2
----
1 0
0
135Iab-On-Grade Edge Insulation
LAUNDRY 26 ft
0
63 ft2
1 0
0
ROOF
# Type Materials
Roof
Gable
Roof
Rad
Solar
SA Emitt
Emitt Deck
Pitch
Area
Area
Color
Barr
Absor.
Tested
Tested Insul.
(dea)
1 Hip Metal 1281 ft'
0 ft'
Light
N
0.3
No 0,9
No 20
22.6
ATTIC
# Type
Ventilation Vent Ratio (1 in)
Area
RBS
IRCC
1 Full attic
Unvented
0
1183ft'
N
N
CEILING
4 Ceiling Type
space
R-Value
Ins Type
Area
Framing Frac
Truss Type
1 Under Attic (Unvented)
MASTER BEDRO
0
Blown
1a2 ft'
0.1
Wood
2 Under Attic (Unvented)
CLST 2
0
Blown
16 W
0 1
Wood
3 Under Attic (Unvented)
BEDROOM 2
0
Blown
149 ft'
0.1
Wood
4 Under Attic (Unvented)
BEDROOM 3
0
Blown
120 ft'
0.1
Wood
5 Under Attic (Unvented)
M CLST
0
Blown
18 f?
0.1
Wood
6 Under Attic (Unvented)
M BATH
0
Blown
68 ft'
0.1
Wood
7 Under Attic (Unvented)
BATH 2
0
Blown
70 W
0.1
Wood
8 Under Attic (Unvented)
HALL
0
Blown
36 f?
0.1
Wood
9 Under Attic (Unvented)
LINEN/AHU CLST
0
Blown
4 W
0.1
Wood
10 Under Attic (Unvented)
CLST 3
0
Blown
20 fP
0.1
Wood
11 Under Attic (Unvented)
LIVING ROOM
0
Blown
255 ft'
0.1
Wood
12 Under Attic (Unvented)
KITCHEN
0
Blown
182 W
0.1
Wood
13 Under Attic (Unvented)
LAUNDRY
0
Blown
63 ft2
0.1
Woad
612212020 3:30 PM FnergyGau+ge® USA 5.0.02 (Rev. 1) - FlaRes2017 FRC 6th Editi-n (9017) Compliant Software Pang 3 of 6
FORM R405-2017
INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent S
11 TypeSpace
P
Cawty
Width
Height
Sheathing Framing
Solar Bslow
1
2
3
4
5
N
E
N
N
W
Exterior
Exterior
Exterior
Exterior
Exterior
Concrete Black - fnt InsuMASTER BE
Concrete Block - Int InFmMASTER BE
Concrete Block - Int Insul CLST 2
Concrete Block - Int InsuBEDROOM 2
Concrete Black - Int InsuBEDR00M 2
4.1
4.1
4.1
4.1
4.1
13
14
2
13
11
0
0
0
0
0
8 1
8 1
& 1
8 1
8 1
105.1 ft'
113.2 ft'
16.2 W
105,1 ft'
88.9 W
0
0
0
0
0
0
0
0
0
0
0.3
0.3
0.3
0.3
0.3
0
0
0
0
C
6
W
Exterior
Concrete Block - Int InsuBEDROOM 3
4,1
10
0
8 1
80.8 ft'
0
0
0.3
0
_ 7
E
Exterior
Concrete Block - Int Insul M BATH
4.1
12
0
8 1
97.0 ft'
0
0
0.3
0
8
9
W
S
Exterior
Exterior
Concrete Block - int Insul CLST 3
Concrete Block - Int InsuLIVING ROO
4.1
4.1
2
15
0
0
8 1
8 1
16.2 ft'
121.3 ft'
0
0
0
0
0.3
0,3
0
£}
i 0
W
Exterior
Concrete Block - Int InsuLIVINti ROO
4.1
17
0
8 1
137.4 ft'
0
0
D.3
D
11
F
Exterior
Concrete Block - Int Insul KITCHEN
4.1
14
0
8 1
113.2 ft'
0
0
0.3
0
12
8
Exterior
Concrete Block - Int Insul KITCHEN
4.1
7
0
8 1
56.6 ft'
0
0
0.3
D
_ 13
N
Exterior
Concrete Block - Int Insui LAUNDRY
4.1
3
0
8 1
24.3 ft'
0
0
0.3
0
_ 14
E
Exterior
Concrete Block - Int Insul LAUNDRY
4.1
7
0
8 1
56.6 ft'
0
0
0.3
0
_ 15
S
Exterior
Concrete Block - Int Insul LAUNDRY
4.1
9
0
8 1
72.8 ft'
0
0
0.3
0
16
W
Exterior
Concrete Block - Int Insul LAUNDRY
4.1
7
0
8 1
56.6 ft'
0
0
0.3
0
DOORS
#
Ornt
Door Type Space
Storms
U-Value
Ft
Width
In
Height
Ft In
Area
1
W
Insulated LIVING ROO
None
.39
3
6 8
20 ft'
2
S
Insulated KITCHEN
None
.39
3
6 8
20 ti'
WINDOWS
Orientatfon shown is the entered, Proposed
orientation.
1/
#
Wall
Ornt ID
Frame Panes NFRC U-Factor SHGC
Imp
Area
Overhang
[depth Separation
Int Shade
Screening
1
N
1
Vinyl Low-E Single Yes
0.32
0.22
N
15.0 ft'
2 ft 0 in
1 ft 4 in
None
None
2
E
2
Vinyf Low-E Sing€e Yes
0.32
0.22
N
15.0 ft'
2 ft 0 in
1 ft 4 in
None
None
3
N
4
Vinyl Low-P Single Yes
0.32
0.22
N
15.0 ft'
2 ft 0 in
1 ft 4 in
None
None
4
W
5
Vinyl Low-E Single Yes
0.32
0.22
N
15.0 ft'
2 ft 0 in
1 ft 4 in
None
None
5
W
6
Vinyl Low-E Single Yes
0.32
0.22
N
15.0 ft'
2 ft 0 in
1 ft 4 in
None
None
6
E
7
Vinyl Low-E Single Yes
0.32
0.22
N
4.0 ft'
2 ft 0 in
1 ft 4 in
None
None
7
W
10
Vinyl Low-E Single Yes
0.32
0.22
N
30.0 W
2 ft 0 in
1 ft 4 in
None
None
8
I=
11
Vinyl Low-F Single Yes
0.32
0.22
N
34.0 ft'
2 ft 0 in
1 ft 4 in
None
None
9
E
14
Vinyl Low-E Single Yes
0.32
0,22
N
4.0 ft'
2 ft 0 in
-1 ft 4 in
None
None
6/22/2020 3:30 PN4 EnergyGauge®R USA 6.0.02 (Rev. 1) - FlaRes2017 FBC_= 6th Edition 12,917) compliant Software Page 4 of 6
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
INFILTRATION
# Scope Method
SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50)
.00036 1118.1 61.38 115.43 .1255 7
HEATING SYSTEM
# System Type
Subtype Speed Efficiency Capacity
Block
Ducts
1 Electric Strip Heat/
Nene COPA 17 kBtu/hr
1
sys#1
COOLING SYSTEM
# System Type
Subtype Subtype Efficiency Capacity Air Flow SHR
Block
Ducts
1 Central Unit/
Split Single SEFR: 16 17.7 kBtulhr 531 cfm 0.8
1
sys#1
HOT WATER SYSTEM
# System Type SubType
Location FF Cap Use Setpnt Conservation
1 Electric None
LAUNDRY 0.98 50 gal 62.3 gal 120 deg
None
SOLAR HOT WATER SYSTEM
rSEt✓
Collector Storage
Cert # Company Name
System Made{ # Collector Model # Area Volume
FEF
None None
ft.
DUCTS
/ ----Supply----
---- Return ---- Air CFM 25 CFM25
HVAC #
�/ # Location R-Value Area
Location Area Leakage Type Handler TOT OUT QN
RLF
Heat Cool
1 Attic 6 125 W
Attic 13 ft' Default Leakage LINEN/AHU (Default) c(Default) c
1 1
TEMPERATURES
Programable Thermostat: N
Ceiling Fans:
Cooling Jan Feb Mar
Heating Jan Feb [X Mar
Venting Jan Feb
[ Apr j May riJun Jul X Aug Se Oct
t Apr ] May Jun Jul Au ] Sep Oct
Nov
x Nov
Dec
7Cf7ec
X Mar
[X] A r J Ma Jun Jui Aug [ ] Se Oct
X Nov
Dec
6l2212020 3:30 PM EnergyGaugeC USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Fdition (2017) Compliant Software Page 5 of 6
FORM R405-2017
INPUT SUMMARY CHECKLIST REPORT
Thermostat Schedule:
HERS 2006 Reference
Hours
Schedule Type
1
2
3
4
5
6
7
Cooling (WD)
AM
PM
78
80
78
80
78
80
78
78
78
78
80
78
78
78
Cooling (WEH)
AM
PM
78
80
78
80
78
80
78
78
78
78
80
78
78
78
Heating (WM
AM
PM
65
fib
65
68
65
68
65
65
65
65
68
68
68
68
Heating (WEH)
AM
PM
65
68
65
65
65
65
65
65
68
68
68
68
68
68
Mass Type
Default(8 lbslsq.ft.
Default(8 Ibslsq.ft.
Default(8 Ibslsq.ft.
Default(8 Ibs/sq.ft.
Default(8 Ibslsq.ft.
Default(8 Ibslsq.ft.
Default(8 Ibsila-0t,
Defautt(8 Ibslsq.ft.
Default(8 ibslsq.ft.
Default(8 Ibslsq.ft.
Default(8 Ibslsq,ft,
Default(8 Ibs/sq,ft.
MASS
Area
T`h1 ckness
0 ft2
0 ft
ft'
ft
ft2
ft
ft'
ft
ft'
ff
ft'
ft
ft'
ft
ft'
ft
Itzft
ft,
ft
ft'
ft
W
ft
ft2
ft
8 9 10 11 12
78
80
80
80
80
78
78
78
78
78
78
80
80
80
80
78
78
78
78
78
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
58
68
68
68
68
Furniture Fraction
0.3
0.3
0.3
0.3
0.3
0.3
0.8
0.3
0.3
0.3
0,3
0.3
0.3
MASTER BEDROO
CLST 2
BEDROOM 2
BEDROOM 3
M CLST
M BATH
BATH 2
HALL
LINENIAHU CLST
CLST 3
LIVING ROOM
KITCHEN
LAUNDRY
6/220-020 3-qn PM FnergyGaugr.C5 USA_ 6.0.02 (Rev, 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 6 of 6
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 95
The lower the Energy Performance Index, the more efficient the home
1. New home or, addition
1. New (From Plans)
12. Ducts, location & insulation level
a) Supply ducts R
6.0
2. Single-family or multiple -family
2. Single-family
b) Return ducts R
6,0
3. No. of units (if multiple -family)
3.
1
c) AHU location LINEN/AHU CLS T
4. Number of bedrooms
4.
3
13. Cooling system: Capacity
17.7
a) Split system SEER
16.0
5. Is this a worst case? (yes/no)
5.
No
b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area (sq. ft.)
6.
1183
d) Room unit/PTAC EER
e) Other
7. Windows, type and area
a) U-factor:(weighted average)
7a.
0.320
b) Solar Heat Gain Coefficient (SHGC)
7b.
0220
14, Heating system: Capacity
17.0
c) Area
7c.
147,0
a) Split system heat pump HSPF
b) Single package heat pump HSPF
8. Skylights
c) Electric resistance COP
1.0
a) U-factor:(weighted average)
8a.
NA
d) Gas furnace, natural gas AFUE
b) Solar Heat Gain Coefficient (SHGC)
8b.
NA
e) Gas furnace, LPG AFUE
f) Other
g_ Floor type, insulation level:
a) Slab -on -grade (R-value)
9a.
0.0
b) Wood, raised (R-value)
9b.
15. Water heating system
c) Concrete, raised (R-value)
9c.
a) Electric resistance EF
0.98
b) Gas fired, natural gas EF
10, Wall type and insulation:
c) Gas fired, LPG EF
A. Exterior:
d) Solar system with tank EF
1. Wood frame (Insulation R-value)
10A1.
e) Dedicated heat pump with tank EF
2. Masonry (insulation R-value)
10A2.
4.1
f) Heat recovery unit HeatRec%
B. Adjacent:
g) Other
1. Wood frame (Insulation R-value)
10B1.
2, Masonry (insulation R-value)
1DB2.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level
a) Ceiling fans
a) Under attic
1la,
0.0
b) Cross ventilation
No
b) Single assembly
11b.
c) Whole house fan
No
c) Knee walls/skylight walls
11c.
d) Multizone cooling credit
d) Radiant barrier installed
11d.
No
e) Multizone heating credit
f) Programmable thermostat
No
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT
I certify that this home has compiled with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature: I A ❑ate: Z14'14 O
Address of New Home: 471) WOODCREST DRIVE City/FL Zip: FORT PIERCE, FL
6/22/2020 3:30:44 PM EnergyGauge® USA 6.0.04 (Rev. 1) - RaRes2017 FBC Gth Edition (2017) Compiiarnt Software Page 1 of 1
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name:
BUXTON GUEST HOUSE Builder N2mp:
TREFELNER CONSTRUCTION
Street:
470 WOODCREST DRIVE Permit Office: ST LUCIE COUNTY
City, State, Zip:
FORT PIERCE, FL, Permit Number-
Owner:
TIM AND LACEY BUXTON Jurisdiction:
ST LUCIE COUNTY
Y
w
Design Location:
FL, Fort Pierce
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall he sealed.
not be used as a sealing material.
Ceilinglattic
The air barrier in any dropped ceilinglsoffit snail be aligned with the
The insulation in any dropped ceiling/soffit
Insulation and any gaps In the err barrier shall be sealed.
Access openings, drop down stairs or knee wail doors to
shall be aligned with the air barrier.
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the tap of exterior wafls steal[ be sealed,
shall be insulated by completely filling the cavity with a
Knee walls shall be sealed.
material having a thermal resistance of R-3 per inch
minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and continuous
alignment with the air barrier.
Windows, skylights
The space between windowidoor jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of insulation.
Floor framing cavity insulation shall he installed to
(including
above garage
maintain permanent contact with the underside of
and cani0evered floors)
subfloor decking, or floor framing cavity insulation shaft
be permitted to be in contact with the top side Of
sheathing, or continuous insulation installed on the
underside of floor framing and extends from the bottom
to the top of all perimeter floor framing members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with a
Where provided instead of floor insulation, insulation
Class I vapor retarder with overlapping joints taped,
shall be permanently attached to the crawlspace walls,
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to exterior
or unconditionad space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on installation
readily conforms to the available: cavity spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope shall
Recessed light fixtures installed in the building
be sealed to the drywal,.
thermal enveiope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring a
plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind ELiping and wiring.
Showeritub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall be
on exterior wall
tubs shall separate them from the showers and tubs.
insulated.
Electrical/phone box on
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boats
HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub -floor or drywall.
GunLedivu
When requireo to be scdidu, concealed Lire sprinklers snot€ only be Sealed
sprinklers
in a manner that is recommended by the manufacturer. Caulking or other
adhesive sealants shall not be used to fill voids between fire sprinkler
cover plates and walls or cei in s.
a rn a`Iflit:.,n fnc,ze.-ri.,., _T
i.... ,.,-. n.- .-4.-.n M..:.... __. _.�_ —--
....... ._._ , ..Wr_..-.�.... .„y ...��., ,���,..�� — UC1004-11— vnui uic NiUviaiuiia U1 Jk.%. °FUU.
6/22/2020 3:30 PRIG EnergyGaugcO USA 6.0.02 (Rev, 1) - FlaRes2017 FBC 6th Edition (20171 Compliant Software Page 1 of 1
wlri htsvft` Project Summary "ebb:
9 Entire House ByEe. Jun za, zoao
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PfLRCE. FL 34946 Phone: 772-466-5799 Far 772- 46"796 r; -qk QUICKCALCSc[rAOL.COM
Project Information
For: BUXTON GUEST HOUSE, TREFELNER CONSTRUCTION
470 WOODCREST DRIVE, FORT PIERCE, FL
Notes:
Design•
•
Weather: Fort Pierce, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db
Inside db
42
70
°F
°F
Outside db
Inside db
90
75
of
aF
Design TD
28
°F
Design TD
15
°F
Daily range
M
Relative humidity
50
%
Moisture difference
61
gr/lb
Heating
Summary
Sensible Cooling Equipment Load Sizing
Structure
16085
Btuh
Structure
13614
Stuh
Ducts
0
Btuh
Ducts
0
Btuh
Central vent (0 cfm)
0
Btuh
Central vent (0 cfm)
0
Btuh
(none)
(none;
Humidification
0
Btuh
Blower
0
Btuh
Piping
0
Btuh
Equipment load
16085
Btuh
Use manufacturer's data
In
Ratelswing multiplier
0,96
Infiltration
Fquipmenf sensible load
12933
Btuh
Method
Simplified
Latent Cooling Equipment Load Sizing
Construction quality
Average
Fireplaces
0
Structure
2934
Btuh
Ducts
0
Btuh
Central vent (0 cfm)
0
Btuh
Area
Heating
Coatingg
{none)
(fit=)
1183
1183
Equipment latent load
2934
Btuh
Volume (W)
9582
9582
Air changes/hour
0,45
0.23
Equipment Total Load (Sen+Lat)
15868
Btuh
Equiv. AVF (cfm)
72
37
Req, total capacity at 0.70 S H R
1.5
ton
Heating Equipment
Summary
Cooling Equipment Summary
Make
Make Carrier
Trade
Trade CARRIER
Model
Cond CA16NW01800GOAD
AHRI ref
Coil FX4DNF019L
Efficiency
100 EFF
AHRI ref 9200656
Efficiency 13.5 EER, 16
SEER
Heating input
5.3
kW
Sensible cooling
12390
Btuh
Heating output
18019
Btuh
Latent cooling
5310
Btuh
Temperature rise
28
°F
Total cooling
17700
Btuh
,actual air flmv
590
cfm
Actual a;r flow
590
cfm
Air flow factor
0.037
cQBtuh
Air flow factor
0.043
cfm/Btuh
Static pressure
1.00
in H2O
Static pressure
1.00
in H2O
Space thermostat
Load sensible heat ratio
0.82
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
vtirriir�h€Csoft- 2020-Jun-2215:38:19
r+ Ri htSr WID Universal2019 19,0,08 RSU08101 Page 1
' .,.ocumnetst4Veig€eisoR HVAC`..3UXTON GUEST HOUSE, rup Ca€c = M,l8 Fmnt Donrfaces: 1Y 9
v wrightsoft Right-J@ Worksheet Job:
Entire House Date: Jun 22, 2020
QUICK CALCS, INC. By:
317 ST LUCIE LANE, FORT PIERCE. FL 34946 Phone: 772-466-57R9 Fax 772-465-6725 FinaII- Dill r.kf',Al rcnani rune
1
Room name
y
MASTER BEDROOM
2
Exposed wall
Entire House
3
Room height
156.0 ft
27.0 ft
4
Roarrt dirnensians
8.1 ft
8.1 ft heatla001
5
Room area
1183.0 ftz
14.0x 13.0 ft
t'14.0
182.0 ft'
Ty Construction U-value or HTv1
number (Btuhlftr °F)
Arai ft'
( ) Load
Area (ftt) Load
(Btuhlftr)
or perimeter (ttj (Btuh)
or perimeter (ft) {Btuhj
Heat Cool
Gross
N1PIS
Heat
Cool
Gross
N1p/5
Heat
Cool
6
U+d
ILr
13A-4ocs
2 glazing. clr low-e
0.143
0.320
n
n
4.00
9.95
2,19
9.41
251
221
&85
484
105
9D
362
198
13A-4ocs
0.143
e
4.00
2A9
30
3,91
0
324
269
1296
282
708
15
113
0
134
141
2 glazing, clr low-e
0.320
e
8.96
22.97
8
1
72
194
0
98
0
394
215
11
2 glazing, clr low-e
0.320
e
8.96
24.75
15
1
1,,34
371
15
1
0
134
0
371
2 glazing, clr low-e
13A-4ocs
0.320
0.143
a
8.96
25.07
34
2
305
852
0
0
0
0
11D0
0.390
s
s
4.00
10.92
2.19
10.34
251
20
231
20
925
219
505
0
0
0
0
0.143
w
4.00
2.19
381
301
1204
208
658
0
0
0
0
0
0
0
Tif13A-4ocs
2 glazing, cir low-e
0.320
w
8.95
24.75
60
4
538
1485
0
0
0
0
0
D
C
1100
16X19-0md
0.390
0.408
w
10.92
1.59
10.34
1.37
20
11,93
20
1183
219
1876
208
0
0
0
0
F
22A-tph
1.358
3&.02
0.00
1183
156
5932
1619
0
182
182
182
27
289
1027
249
0
6
c)ALD excursion
45
130
Envelope Inss/gain
13673
7608
2340
1045
12
a) InfWation
2212
606
383
105
b) Room wntilaCo'.1
0
0
0
0
13
intemal gains: Occupants @ 230
0
0
0
Applianceslother
5400
0
1000
Subtotal (lines 6 to 13)
16085
13614
2722
2149
Less extemal load
0
0
0
Less transfer
D
D
0
0
3
Redistribution
0
0
106
43
14
15
Subtotal
Duct loads
16085
13614
2828
2193
D%
0%
0
0
0%
0
0
0
Totai room load
Air required (ofm)
16065
13614
2828
2i93
590
5901
104
95
Caicuiations approved byACCA to meet_all requirements of Manuai J 8th Ed
.:-,y - wrFgF�tsoft 2020-Jun-2115: 38: i9
. s:T';._:.^ .. .. .... RightSuite@ Universal 2019 19.0.08 RSU08101 Page 1
...ocumneWWdotitsott HVAC113UXTON GUEST HOUSE.rup Calc = M,i8 Front Deor €aces: W
wrightsoftmight-J& Worksheet
Job:
Entire House
Date: Jun 22, 2020
QUICK QNLCS, INC.
By:
317
ST LUCIE LANE, FORT PIERCE, FL 34946 Phone, 772-466-6799 Fax: 772-466-6796
Email: QUIGKCALCS@AOL.COM
1
2
Room name
Exposed wall
CLST 2
BEDROOM 2
3
Room height
2.0 ft
8.1 ft heat/cool
24.0 ft
8.1 ft beaticool
5
Room area dimensions
8.0 x 2,0 ft
1.0 x 149.0 ft
16.0 ft2
ft 149A 2
Ty Construction 1-1-value Or HTM
number (Btuhlft T) (Btuh1ft')
Area (fit') Load
Area (ft') Load
or perimeter (ft) (Btuh)
or perimeter (ft) (Btuh)
Gross
N1PJs
Heat
Cool
Gress
N1P1S
Heat
Cool
Heat Cool
5
V 13A-flocs 0.1-03 n 4.00 2.19
G 2 glazing, clr lower 0.320 n 8.96 9.41
16
16
65
35
105
90
352
198
13A-4ocs 0.143 e 4.00 2.19
0
0
0
0
0
0
0
0
15
0
0
134
141
2 glazing, clr ow-e 0.320 a 8.96 22.97
0
0
0
0
0
0
0
0
0
11
2 glazing, elr low-e 0.320 a 8.96 24.75
0
0
0!
0
0
0
0
2 glazinq, cir low-e 0.320 a 8.96 25.07
0
0
0
0
0
0
0
0
0
Val 13A-4ocs 0.143 s 4.00 2.19
0
0
0
0
0
0
0
---.p 11DO 0.390 s 10.92 10.34
0
0
0
0
0
U
0
p
0
p
13A4ocs 0,143 w 4.00 2.19
0
0
0
0
89
74
297
162
2 glazing, clr low-e 0.320 w 9.95 24.75
0
0
0
0
1s
1
134
371
11DO 0.390 w 10.92 10.34
0
0
0
a
0
0
0
0
C 16X19-0md 0.408 1.59 1.37
F 22Atph 1.358 38.02 0.00
16
16
25
22
149
149
236
204
16
2
76
0
149
24
913
0
6
c)AED excursion
-4
40
Envelope loss;gain
165
54
2076
1116
12
a) Infiltration
28
6
340
93
b) Roam v::nWanon
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Applianceslother
_
1000
Subtotal (lines 6 to 13)
195
61
2416
2209
Less external load
0
0
0
0
Less transfer
0
0
0
0
14
Redistribution
Subtotal
-195
-61
115
39
15
Duct loads
0%
0%
0
0
0
0
0%
0%
2531
0
2249
0
Total room load Ai
r required (cfm)
A
Q
2551
2249
0
93
97
Calculations approved b ACCA to meet all requirements of Manual J Sth Ed.
2020,!un•22 1 S: 38;18
rCGC;•A.. ,. Rig}si-SuiteL� Universal 2099 18.0.08 RSUDSIOl Page t
ocumnetslWrightson HVA0BUXTDN GUEST HOUSF.rup Calc = W8 Front Osorfaces: W
+
wrightsoft
might-J& Worksheet
Job:
Entire House
i}ate:
Jun 22,
2020
QUICK CALCS, INC.
By:
317
ST LUCIE LANE, FORT PIERCE. FL 34946 Phone: 772-466-6799 Fax 772-466-6736 Email:
QUICKCALCS@AOL.COM
1
Room name
2
Exposed wall
BEDROOM 3
M CLST
3
Room height
10.0
ft
0 ft
4
Room dimensions
8.1 ft
heaticool
6.1 ft
heaticoo!
5
boom area
a
10,0
x 12.0 ft
2.0 x
9.0 fit
120.0 ft �
18.0 ft :
Ty Construction
number
a -value Or HTM Area (ft`)
(13tuhift` °Fj
Load
Area (ft')
Load
or
perimeter
ft
l)
(8tuh)
or perimeter
(ft)
(I3tuhj
Heat Cool Gross NIPIS
Heat
Coal
Grass
MPS
Heat
Coo}
6
sal 13A4ocs
0.143 n 4.00 2.19
0
0 0
0
00
L-( 2 glazing, ch 3ow-e
0.320 n 6.96 9.41
0
0 0
0
0
0
0
13A4ocs
0.143 e 4.00 2.19
0
0 0
0
0
0
p
0
2 glazing, Or low-e
0.320 e 8.95 22.97
0
0
0
0
0
0
0
0
0
11
2 glazing, clr low-e
0.320 e 8.96 24.75
0
0
0
0
0
0
0
2 glazinu. clr 11
0.320 e 8.96 25.07
0
0
0
0
0
0
0
0
13A,4ocs
0.143 s 4.00 2.19
0
0
0
0
0
0
0
0
0
11D0
0.390 s %92 10.34
0
0
0
0
0
0
0
0
D
0
13A-4ocs
0.143 w 4.00 2.19
81
66
264
144
0
0
0
0
2 glazing, clr low-e
0.320 w 8.96 24.75
18
1
134
371
0
0
0
11DO
0.390 w 10.92 10.34
0
0
0
0
0
0
0
0
G 16X19-0md
F 22A-tpt'i
9.408 1.59 1.37
1,358
120
120
190
164
18
18
29
25
38.02 0.00
120
10
380
0
18
0
0
0
6
c)AED excursion
Envelope losslgain
969
744
1
29
23
12
a) Infiltration
142
39
0
0
b) ROOM 1A 9tl!atiDn
0
0
00
13
Irrternal gains:
Occupants @ 230
0
0
0
Appliances/other
1500
0
0
Subtotal (lines 6 to 13)
1111
2283
29
23
Less extemal load
0
0
0
Less transfer
0
0
0
0
14
Redistribution
Subtotal
126
54
29
0
-23
15
Duct loads
0%
0%
1237
0
2336
0
0%
0% 1
0
01
0
0
0
Total room lead
Air required (cfm)
1237
2336
u
>7
4S
101
0
g
Caiculatioros a roved i5 ACCA to meek a!i requirements of #llanual J 8th Ed
. r�,csft
wr�g�_ Ri htSuitei] Universal Z4'IS 1S.O.OS RSUpE3191
2D2fl-JU-221S:38:19
...ocumnetsWdri htsrott WACI6UXTON GUEST HOUSE.rup 084c = VJa gars€ floor faces: W Page 3
wrightsoft` night-J® Worksheet
Job:
Entire House
Date. Jun 22, 2020
QUICK CALCS, INC.
By:
317
ST LUCIE LANE; FORT PIERCE, FL 34046 Phone: 772-466-6799 Fax. 772-466-6796
Lrnail: QUICKCALCS@AOL.COM
1
2
Room name
Exposed wall
M B
BATH
BATH 2
3
Room height
ft
0 ft
4
Room dimensions
8.1 ft heaticeol
S.1 ft heaticool
5
Room area
1.0 x 68.0 ft
10.0 x 7.0 ft
68.0 ft z
70.0 fN
Ty Construction U-aafue Or HTM
number (8tuhlft1°I-) (etuhift')
Area (ft') Load
Area (ft') Load
or perimeter (ft) (Btuh)
or perimeter (f€) (Btuh)
Grass
N(PIS
Heat
Cool
Gross
N1PIS
Heat
Cool
Heat Cool
6
VI! 13A�ocs 0.143 n 4.00 2.19
L-(
0
0
0
fl
0
0
2 glazing, clr low-e 0.320 n 8.95 9.41
0
01
0
0
0
0
0
13A-4ocs 0.143 e 4. DO 2.19
97
93
373
204
0
0
0
0
0
0
2 glazing, cif bw-e 0.320 e 9.96 22.97
4
1
36
92
0
0
0
11
2 glazing, clr lew-e 0.320 e US 24.75
0
0
0
0
0
0
0
2 glazinq. clr low-e 0.320 a 8.96 25.07
0
0
0
0
D
0
0
0
0
W 13A-4ocs 0A43 s 4.00 2.19
0
0
0
0
0
0
0
D
11 D0 0.390 s 10.92 10.34
0
0
0
0
0
0
0
0
0
0
V�1 13A-4DCs D.143 w 4.00 2J9
0
0
0
0
0
I�--C{ij 2 glazing, clr low-e 0.320 w 9.96 24.75
0
0
0
00
0
0
0
11Dn 0.390 w 10.92 10.34
0
0
0
0
D
0
0
0
n
0
C 16X19-ornd 0.40E 1.59 1.37
F 22A-tph 1.358 38.02 0.00
68
68
108
93
70
70
111
0
96
Be
12
456
0
70
0
0
0
6
c)AFD excursion
23
Envelope loss/gain
973
366
111
90
12
a) Infiltration
17D
47
0
0
b) Room ventilation
0
0
0
n
13
Intetna# gains: Occupants @ 230
Cr
0
0
Applianceslother
n
0
0
Subtotal (lines 6 to 13)
1143
412
111
90
Less external load
0
0
Less transfer
0
0
0
0
Redistribution
5
0
25
0G
21
14
Subtotal
1149
417
136
111
15
Duct toads
0%
0%
0
0
0 %
0%
01
0
Total room load
Air rPnLllr. . (rfm)
1149
4i7
136
111
42
1S
5
5
CAiculations a2proved by ACCA to meet all__requirernents of Manual j girth Ed
tsoiFt•"- 2020Jun-22 15: 38:19
6.�. ..ocumnsts; �,.li�,.....� ....... Right�uitsJ Universal 2fl'Is 19.0.Da RSLJi38191
)!'7
ry g tsoft HVACIBUXTON GUEST HOUSE .rup Catc W M,tA Front Door faces: iU Page 4
wrightsof fight-J@ Worksheet Job:
Entire House Date: Jun 22, 2020
QUICK CALCS, INC,
317 ST LUCIE LANE; FORT PIERCE. FL 34946 Phone: 772-4ti6,6799 Fax 772-486-6798 Ema4: QUICKCALCSBAOLC.()M
1
Room name
V
2
Exposed wall
HALL
LINENIAHU CLST
3
Room height
0 ft
0 ft
4
Room dimensions
8.1 ft heaticool
8.1 ## heat/coot
5
Room area
36.0 ft212.0 x 3.0 ft
2.0 x 2.0 ft
4.0 ft
Ty Construction U-value Dr HTM
number (H-tuhlft' `r) (8fuhfft')
Area OF) Load
Area (ft') Load
or perimeter (ft) (Btuh)
or perimeter (ft) (gtuh)
Heat Cooi
Gross
NIP/S
Heat
Cool
Gross
N1P1S
Heat
Cool
6
13A-4ces
0,143
n
4.00
2.15
0
0i
0
0
0
0
0
2 glazing, clr law-e
0.320
n
R_9H
9.41
0
0
0
0
0
0
0
13A-4ocs
0.143
e
4,00
2A9
0
0
0
0
0
D
a
0
a
2 glazing, ctr iow-e
0.321)
e
8.96
22.97
0
0
0
0
0
O
0
0
11
2 glazing, clr tow-e.
9.320
0
8.96
24,75
0
0
0
0
0
0
0
0
0
2 plazinq, nlr low-e
0.320
a
8.95
25.07
0
0
0
0
0
0
0
0
0
13A-4ocs
0.143
s
4A0
2.19
0
0
0
O
0
0
0
11DO
0,390
s
10.92
10.34
0
0
0
0
0
0
0
0
0
13A-4ocs
0.143
w
4.00
2.19
0
0
0
0
0
0
0
2 glazing; clr luw-e
0,320
w
8.96
24.75
0
0
0
0
0
0
0
0
11 DO
0.390
w
10.92
10.34
0
0
0
O
0
0
0
0
0
C
MX19-0md
0,408
1.69
1.37
36
36
57
49
4
4
6
5
F
22A-tph
1.35E
38.02
0-00
36
0
0
0
4
0
0
0
61
c)ALD excursion
-3
0
Envelope loss/galr
57
46
12
a) infiltration
0
0
0
0
b) Room ventilation
0
0
0
01
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
57
45
6
5
Less external load
0
0
0
D
Less transfer
O
O
0
0
Radistnbiftn
-57
-46
-6
14
6ubtotai
0
0
0
0
15
Duct loads
0%
0%
0
D
0%a
0°%
0
0
ictal room load
0
0
0
0
Air required (cfm)
0
0
0
0
Calculations approved byACCA_EO €meet all reouirements of Manual J 8tn Ed.
" wrigl-stspft -.... 2020-Jun-2215:38:19
-.. Right-Suita® Universal 2019 19.0.08 RSU08141
' - ...ocumnets)Wrightsaft HVACIBUXTON GUEST Hp USE.rup Caic = MJB Front Doortaces: W
Page 5
+
wrightsoft Right-J@ Worksheet
Jnb:
Entire House
[late: Jun 22, 2020
QUICK CALCS, INC.
gy:
317
ST LUCIE LANE, FORT PIERCE, FL 34945 Phone: 772-466-6799 Fax: 772-469-6796
Email: QUICKCALCS@AOL.COM
1
2
Room name
1-)posed wall
CLST 3
LIVING ROOM
3
4
Room height
Roam dimensions
0 ft
8.1 ft 2 heaticaol
32.0 ft
8.1 ft heaticool
5
Roam area
2.0 x 10.0 ft
x 15.Q ft
20.f) ft2
255 0 ft217.0
Ty Construction U-value Or HTM
number (13tuhift'2F)
Area (f) Load
Area (ft') Load
(Btuhifr`)
or permeter (ft) (Btuh)
or perimeter (ft) (Btuh)
Gross
N!P!S
Heat
Cool
Gross
NIP/S
Heat
Cool
Heat C1301
6
Vd/ 13A-4ocs 0.143 n 4.00 2A9
Q
Q
0
0
0
G 2 glazing cfr low-e 0.320n 8.96 9.41
0
0
4
0
0
0
0
0
D
13A-flocs 0.143 e 4.00 2.19
0
0
0
Q
0
0
0
0
Q
Ti 2 glazing, clr low-e 0.320 a 8.96 22.97
0
0
0
0
0
0
0
a
11
2 glazing, clr low-e 0.320 a 8.96 24.75
0
0
0
0
0
D
0
2 dazinq, clr low-e 0.320 a 8.96 25.07
Q
0
0
0
0
0
0
0
Vj! 13A-4 of 0.143 s 4.00 2.19
�--O 11DO
0
0
0
0122
122
0
486
0
266
0.390 s 10.92 10.34
0
0
0
0
0
0
0
0
13A-40cs 0.143 w 4.00 2.19
2 glazing, cir Iovi-e 0.320 w 8.96 24.75
16
0
16
65
35
138
88
351
192
11D0 0.390 w 10.92 1D.34
0
0
0
0
Q
0
0
3o
20
2
20
269
219
743
2DB
C 16X19-Dmd 0.403 1.59 1.37
F 22A-tph 1.358
20
20
32
27
255
255
404
349
38.02 000
20
2
76
0
255
32
1217
0
6
c)AED excursion
4
205
Envelopelosslgair
173
59
2947
1962
12
a) lrJlltraticn
28
8
454
124
b) Rccm ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
D
12D0
Subtotal (lines 6 to 13)
201
67
3400
3286
Less a)dernal load
0
0
0
0
Less transfer
0
0
0
0
14
Redistribution
Subtotal
-201
-£7
110
41
15
Duct loads
0%
0%
0
0
0
0
0%
ft.
3510
0
3327
0
Total room load
Air requirAd (&m)
D
`01.
0
3-a10
3327
Q
129
"4
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed
w�.grscsort- --
�Y ..UGEltnnetStt/Jrl. Right-Guite@ Universal 2019 19.0.08 RSU061 Ot 2020h1un�22 15;38:19
t' F
ghtstift WAC:BUXTON GUEST HOUSE.rup Calc = Mja Front 600rfaces: W Paq e 6
+
wrightsof Right -AD Worksheet
Job.
Entire House
bate: Jun 22, 2020
QUICK CALLS, INC.
By:
317
ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796
Email: 4UICKCALCSgaAOL.COM
1
name
2
E)Room
lxflosed wall
KITCHEN LAUNDRY
3
Room height
21.0 ft 26-0 ft
&1 ft
4
Roam dimensions
.heat/cool B
hB. 1 ft heat/cool
5
Room area
14.0 x 13.0 fY 7.0 x 9.0 ft
isz.D ft2 63.D it,
Ty Construction U-value Or HTM
number Btuhfft' °F
( ) (Btuh/ft')
Area ftz
{ ) Load Area (ft') Load
or
perimeter {ft) (I3tuh) or perimeter (n) (Otuh)
Gross
WPIS
Heat
Cool Gross
NIP/5
Heat
Caul
Heat COD]
6
Vd! 13A4ccs 0.143 n 4.0D 2,19
I
o
D
o
-- ter 2 glazing, ctr low-e 0,320 n 8,9€'i 9.41
13A4ocs 0.143 e 4,00 2.19
D
113
0
79
a
0 ZO
24
90
50
2 giazfng, clr low-e 0.320 e 8,96 22.97
0
O
318
0
174 57
0
53
211
115
11
2 glazing, clr low-e 0.320 e 8,98 24.75
O
0
0
4
0
1
36
92
2 olazlra, clr low-e 0.320 e 8.96 25.07
34
2
305
0
852 0
0
0
0
0
V�! 13A-4ocs 0.143 s 4.00 2.19
L...❑
57
37
147
80 73
73
0
0
11DO 0.390 s 10.92 10.34
20
20
219
208 0
0
292
0
159
0
13A-4ocs 0.143 w 4.00 2.19
2 glazing, clr low-e 0.320
0
0
0
D 57
57
22
124
w 8.96 24.75
11DD a.390 w 1p.92 ia.3a
0
D
0
o
0
o
0 0
0
0
0
a
C 15X19-Omd 0.408 1,59 1,37
F 22Atph 1.358
182
182
289
o D
249 63
o
53
o
160
a
86
38,02 O.Do
182
21
799
0 63
26
989
0
6
c)AED excursion
-54
-40
Envelopeluss/gair
2076
1509
1952
590
12
a) Infiltration
b) P,00m ventilation
298
82
1369
101
0
0
0
0
13
Internal gains: Occupants @ 230
0
0 0
Appliancestother
700
0
0
Subtotal (lines 6 to 13)
2373
2290
2320
691
Less odemal load
0
0
0
Less transfer
0
0
D
O
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct IDa
2373
2290
2320
691
0%
C1%
0
0
Toiai room laacf
Air required {cfm j
2373
2290
Z32D
69 i
87
99
85
30
Calculations approved byACCA to meet all requirements of Manual J 8tn Ed
wri Fatsoft-- RighiSuiteQ Universal 2019 19.0.08 RSU08101 2020-Jun-2215:38:19
�`� . ghisk4i HVACI0UXTON GUEST HOUSE. rup Calc - MJS Front Door faces: W Page 7
Lust ste111�1 Summary Job.
n►rlgh soft Date: ,tun 22, 2020
Entire House By-,
QUICK CALCS, INC.
317 STLUCIE LANE, FORT PIERCE, FL 94946 Phone: 772-466-6799 Fax 772-466-6796 UP -Oil: QUiCKCAtCS d[ AOL.G0M
For; BUXTON GUEST HOUSE, TREFELNER CONSTRUCTION
470 WOODCREST DRIVE, FORT PIERCE, FL
Extemal static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
1.00
III H2O
0
in H2O
1.00
in H2O
0.50u i 0.500
in H2O
1.000
in/100ft
590
cfm
139 ft
Cooli ng
1.00
In H2O
0
in H2O
1.00
in H2O
0.500 i 0.500
in H 2O
1.000
in/ 100ft
590
cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
5ATH2
h 136
5
5
1.000
4.0
Ox0
VIFx
9.n
115.J
sY2
BEDROOMc
2249
93
I 97
1.000
7.0
Ox 0
VIFx
17.2
115.0
st2
BEDROOM 3
c 2336
45
! 101
1.000
7.0
Ox fl
VIFx
9.1
115.0
st2
KITCHEN
c 2290
87
99
1.000
7.0
Ox 0
VlFx
22.6
115.0
sti
LAUNDRY
h 2320
85
30
1.000
5.0
Ox0
VIFx
23.6
115.0
sti
LIVING ROOM
c 3327
129
144
1.000
8.0
Ox 0
VIFx
3.6
95.0
M BATH
h 1149
42
18
1.000
5.0
Ox0
VIFx
14.5
115.0
st2
MASTER BEDROOM
h 2828
104
95
1.000
TO
OX0
ViFx
15.4
115.0
sit
Supply Trunk Detall Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FR
(fpna)
(In)
(in)
Material
Trunk
sti
Peak AVF
172
129
1.000
493
8.0
0 x 0
VinlFlx
st2
Peak AVF
289
317
1.000
580
10.0
0 x 0
VinlFlx
-- Return Branch.Detail Table
Name
Grilte
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rb1
Ox 0
590
590
0
O
0
0
Ox 0
VIFx
-�'�- wrightsoft° 2020-gum-22 15:$i M
Rlghi-ault@�D Universal 2019 19,O,Oa 1151.1oa,.ai
Page 1
...pzumnatslWrightsott HVAOIBUXTt3N GUEST HOUSE. nip Caic = MJS Front [lnnrfates: Vj!