HomeMy WebLinkAboutAQVST Lot 7 E101 REV05 7/15/20LOCATION
TO FP&L TIE-IN
ELECTRICAL RISER DIAGRAM
METER
(1) #2 CU TO 5/8" GROUNDING ROD
& TO FOOTER STEAL
(1) #2 CU. GND. WIRE TO H2O
150AMP
150AMP
150A
PANEL
B
40 CKTS
M.L.O.
A
B
ELECTRICAL
METER & MAIN
DISCONNECT
UNDERGROUND
A.I.C.
10,000
A.I.C.
10,000
POOL PANEL
60 AMP
M.L.O.
150A
PANEL
A
40 CKTS
M.L.O.
(2) #6, 1 #6 NEUTRAL,
(1) #10 GND IN 1" PVC
(3) #2/0 CU
& (1) #6
IN 2" PVC
SERVING
2 AHU #1650
1
3
SERVING
2
4
POLEWIRE AMPSCIR #POLEWIRE AMPSCIR #
120/240150A
VOLTAGEAMPSPNL
42
CKTS
3
WIRE
1
PHASE
2 ACCU #1650
KW
5.0
KW
-
5
7
2 OVENS650 5.4
1 COOKTOP HOOD20
9
1 GARAGE DR OPENER1220
11
1 GEN'L LIGHTING1415
13
1 GEN'L LIGHTING1415
15
17
19
21
23
25
27
31
33
29
35
37
39
41
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
1 BATH GFI'S #11220
38
1.5
SPACE
40
42
** GEN. L'TING (2,516 SF @ 3W/SF)
PANEL A TOTAL KW =39.6
7.5
PANEL 'A' LOAD CALCULATIONS
25,700 W.
240 V.
= 107.1 Amps
1st 10.0 KW @ 100%
LARGEST OF:
HEATING @ 65%
COOLING @ 100%
REMAINING KW @ 40%
TOTAL KW
10.0
9.8
5.9
25.7
SERVING
2 ELEVATOR1030
1
3
SERVING
2
4
POLEWIRE AMPSCIR #POLEWIRE AMPSCIR #
120/240150B
VOLTAGEAMPSPNL
42
CKTS
3
WIRE
1
PHASE
2 AHU #2660
KW
3.0
KW
10.0
5
7
6
8
9
11
13
15
1 KIT REF122017 1.5
1 SMALL APPLIANCE #21220
19
1.5
21
23
25
1.5 1.5
**
**
27
29
31
33
35
37
39
41
10
12
14
16
1 WASHER1220
18
1.2
20
22
24
26
28
30
32
34
36
38
40
42
** GEN. L'TING (2,517 SF @ 3W/SF)
PANEL B TOTAL KW =39.1
7.4
PANEL 'B' LOAD CALCULATIONS
24,200 W.
240 V.
= 100.8 Amps
1st 10.0 KW @ 100%
LARGEST OF:
HEATING @ 65%
COOLING @ 100%
REMAINING KW @ 40%
TOTAL KW
10.0
6.5
7.7
24.2
SERVING SERVINGPOLEWIREAMPSCIR #POLEWIRE AMPSCIR #
120/24060P (POOL)
VOLTAGEAMPSPNL
12
CKTS
3
WIRE
1
PHASE
KW KW
2 POOL PUMP840
1
1.5
3
5
7
1 POOL LIGHTS12202 0.8
4
6
8
10
12
1 POOL CONTROLLER
9
SPACE
11
SPACE
12 20 0.5
1 POOL HEATER IGNITER1220 0.5
PANEL P TOTAL KW =3.3
PANEL 'P' LOAD CALCULATIONS
1st 10.0 KW @ 100%
LARGEST OF:
HEATING @ 65% (6.5 KW)
COOLING @ 100% (KW)
REMAINING KW @ 40%
TOTAL KW
3.3
0.0
3.3
3,300 W.
240 V.
= 13.8 Amps
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 SMALL APPLIANCE #120 1.5
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415 **1 GEN'L LIGHTING1415 **
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415
1 GEN'L LIGHTING1415
**
**
1 GEN'L LIGHTING1415 **1 GEN'L LIGHTING1415 **
SPACESPACE
1 GEN'L LIGHTING1415 **1 GEN'L LIGHTING1415 **1 GEN'L LIGHTING1415 **1 GEN'L LIGHTING1415 **
2 DW & DISP #11220 2.2
SPACE
SPACE
12
1 CEN VAC1220 1.2
1 RECIRCULATING PUMP1220 1.2
1 BATH GFI'S #21220 1.5
SPACE
2 ACCU #2660 -
2 AHU #3660 10.02ACCU #3650 -
2 WATER HEATER1030 4.5
2 COOKTOP650 5.0 2 DRYER1030 4.5
UTILITY ROOM 5
5
ELEVATOR NOTES:
1. ELEVATOR SHALL MEET NEC 620 22-23; VERIFY LOCATION AND
ELECTRICAL REQUIREMENTS OF ELEVATOR EQUIPMENT WITH MFG SPECS
PRIOR TO CONSTRUCTION.
2. IF THERE IS AN ELEVATOR PIT LOCATED BELOW, PROVIDE WITH FLOAT
SWITCH SENSOR; LIGHT FIXTURE SHALL NOT BE INSTALLED IN ELEVATOR PIT.
3. PROVIDE A LIGHTING FIXTURE WITH RECEPTACLE OUTLET, CONTROLLED
BY A SWITCH LOCATED AT THE PASSAGEWAY OPENING PER FMC 306.3.1.
ELECTRICAL NOTES
GENERAL:
1) CONTRACTOR SHALL VERIFY THE LOCATION OF SERVICE AND SHALL
LOCATE THE METER & PANELS AS REQUIRED.
2) ALL WIRE SHALL BE THHN COPPER, UNLESS NOTED OTHERWISE.
3) WHERE REQUIRED BY OTHER CODES, SERVICE AND FEEDER
CONDUCTORS SHALL BE COPPER OF EQUAL AMPACITY.
4) ALL BRANCH CIRCUITS IN RACEWAY OR NON METALLIC SHEATHED CABLE.
5) COORDINATE RACEWAY INSTALLATIONS WITH OTHER TRADES PRIOR TO
CONSTRUCTION.
6) ROMEX MAY BE USED WHERE CONDUIT IS NOT REQUIRED.
7) BX CABLE MAY BE USED IN LIEU OF RIGID CONDUIT.
8) VERIFY ALL CONDUCTORS AND BREAKERS WITH EQUIPMENT
MANUFACTURER SPECIFICATIONS.
9) PROVIDE DISCONNECT SWITCHES OF SIZE AS REQUIRED BY LOADS.
10) PROVIDE NON-FUSIBLE GENERAL DUTY SAFETY SWITCHES AT A/C EQUIP.
AND AT PUMPS NOT VISIBLE FROM CIRCUIT BREAKER PANEL AND AS PER
MANUFACTURER RECOMMENDATIONS.
11) PROVIDE DISCONNECTS FOR POOL PUMP PER N.E.C. 680. POOL
CONTRACTOR SHALL PROVIDE ELECTRICAL CONTRACTOR WITH ALL LOADS
PRIOR TO INSTALLATION. ELECTRICAL CONTRACTOR TO MAKE ALL
CONNECTIONS PER POOL COMPANY DRAWINGS. VERIFY LOCATION OF ALL
POOL/SPA EQIUPMENT.
12) ALL 120 VOLT 15 AND 20 AMP CIRCUITS THAT SERVE FAMILY ROOMS,
DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
SUNROOMS, REC ROOMS, CLOSETS, HALLWAYS, OR SIMILIAR ROOMS TO BE
ARC FAULT CIRCUIT PROTECTED PER FBCR E3902.12.
13) WIRES SMALLER THAN #6 SHALL HAVE THHN INSULATION, #6 & LARGER
SHALL HAVE THWN INSULATION.
FIXTURES:
1) PROVIDE GREEN WIRE GROUND TO ALL EXTERIOR FIXTURES AND "J"
BOXES.
2) ELECTRICAL FIXTURES, TRIM AND APPLIANCES SHALL BE UL APPROVED
AND AS SELECTED BY OWNER.
3) ALL LIGHTING FIXTURES AND FANS TO BE SELECTED & LOCATED BY
OWNER/ARCHITECT/INTERIOR DESIGNER, UNLESS OTHERWISE NOTED.
4) ARCHITECT TO SET MOUNTING HEIGHTS FOR ALL FIXTURES WHERE
APPLICABLE, UNLESS OTHERWISE NOTED.
5) FLUORESCENT CLOSET LIGHT FIXTURES SHALL HAVE A MINIMUM
CLEARANCE OF 6" AWAY FROM CLOTHING.
6) PREWIRE FOR GARAGE DOOR OPENER SENSOR.
7) HIHATS TO BE 4" ROUND
OUTLETS:
1) ALL COUNTERTOP RECEPTACLES SHALL BE GFCI OUTLETS.
2) PROVIDE GFCI BREAKERS FOR ALL BATHROOMS, GARAGE AND EXTERIOR
OUTLETS AS SHOWN ON PLANS.
3) ALL 125 VOLT 15 AND 20 AMP RECEPTACLES TO BE TAMPER RESISTANT
PER FBCR E3902.12.
4) PROVIDE PRE-WIRED TELEPHONE & CABLE T.V. OUTLETS AS SHOWN ON
PLAN. PROVIDE OPTIONAL PRE-WIRED HIGHSPEED DATA OUTLETS AS SHOWN
ON PLANS. (IF APPLICABLE)
5) FOR FLOOR RECEPTACLES, PROVIDE A COVER PLATE AND FLUSH WITH
FLOOR. VERIFY EXACT LOCATION WITH GC/OWNER. PROVIDE 1/2" CONDUIT
UNDER SLAB FROM WALL.
SMOKE DETECTORS:
1) ALL SMOKE DETECTORS TO HAVE BATTERY BACK UP AND SIGNAL
SIMULTANEOUSLY W/ TEMPORAL SOUND.
2) SMOKE DETECTORS TO BE LOCATED MIN 3'-0" FROM: R/A & SUPPLY GRILLS,
KITCHENS, BATH ROOMS.
3) SMOKE DETECTORS TO BE COMBINATION TYPE CARBON MONOXIDE ALARM
& SMOKE DETECTOR.
WPGF
GF
4-WAY WALL SWITCH
DIMMER WALL SWITCH
PUSH BUTTON SWITCH
WEATHER PROOF GFCI OUTLET
G.F.C.I. PROTECTED OUTLET
DUPLEX OUTLET - HALF SWITCHED
DUPLEX FLOOR OUTLET
3-WAY WALL SWITCH
WALL SWITCH
D
ELECTRIC METER
ELECTRIC PANEL
220 VOLT RECEPTACLE
DUPLEX OUTLET
DISCONNECT
CENTRAL VAC. HOSE OUTLET
PULL CORD FIXTUREPC
KEYPAD
THERMOSTAT
INTERCOM
SPRINKLER TIMER
MOTION DETECTOR
kp
ST
i
T
ELECTRICAL LEGEND
DOUBLE CAT 5e CABLE
tv
CV
C5
RECESSED ADJUSTABLE FIXTURE
VAPOR PROOF RECESSED FIXTUREVP
UNDER CABINET FIXTURE
FLOOD/SECURITY LIGHTS
FLOURESCENT LIGHT FIXTURE
CEILING MOUNTED J-BOX
RECESSED LIGHT FIXTURE
CJ
CEILING FAN
WALL MOUNTED J-BOX
CEILING MOUNTED FIXTURE
WALL MOUNTED FIXTUREWF
WJ
CF
EXHAUST FAN
SMOKE DETECTOR
SINGLE OUTLET
PHONE JACKPH
VIDEO OUTLET
ACQUAVISTA LOT #7VENETIAN ADMINISTRATION LLC7.10.2020ob No. 1802011
permit sets GS 10.5.2018
1 1st Building Comments GS 2.18.2019
2 2nd Building Comments GS 3.7.2019
3 As built roofing GS 6.24.2020
4 flood resistant materials GS 6.24.2020
5 elec meter/panel loc's GS 7.10.2020
E101